SECTION DOOR HARDWARE. A. Section includes hardware for wood, hollow metal, and aluminum doors.

Size: px
Start display at page:

Download "SECTION DOOR HARDWARE. A. Section includes hardware for wood, hollow metal, and aluminum doors."

Transcription

1 PHONE: FAX: P.O. BOX 1745, ALAMOGORDO, NM LIC Addendum #4 August 18, 2016 Roswell McGaffey Plaza Renovations Roswell, NM Project still bids Tuesday August 23 before 2:00 p.m. Questions & Answers: Add specification section Door Hardware in its entirety, attached. Sheet S-302 Detail D4 Reefers to Sheet S311 there is no sheet S311. Correction made. See Addendum 002. Sheet AD101 Existing Elevation E1 0 States to remove Little Caesars Storefront is this correct? Existing Storefront for Little Caesars to remain. No Detail for Metal Coping per Key Note #7 Sheet A-102 Metal Coping similar detail B2/A-302 without cornice. No Hardware Schedules? Hardware schedules will be issued as Addendum. Fixture type H is described to be a recessed fixture but drawn in as a linear. If we're to order a linear fixture there is no corresponding description to refer to. at the ross there is a neon linear. There are supposed to be two (2) Type "K" (Winona LED) fixtures at either end of the Ross store (the ones with no fixture types), and there are two (2) Type "L" fixtures (Plaque down lights) inside the soffit at either end. Change the Type "K" to Type "L" as shown on Sheet E-101. Fixture type L is listed on the schedule but does not appear in the drawing, However there are outlet symbols within the clouded area that have no types associated to them. There are supposed to be two (2) Type "K" (Winona LED) fixtures at either end of the Ross store (the ones with no fixture types), and there are two (2) Type "L" fixtures (Plaque down lights) inside the soffit at either end. Change the Type "K" to Type "L" as shown on Sheet E-101. Section where is this applicable to the plans? This section relates to existing foam roof over Ross, Burkes and Melrose. Section Don t see these on the drawings - I would imagine they relate to the new loading dock? That is correct. See NOTE on loading dock detail C4/S-002.

2 SECTION DOOR HARDWARE PART 1 GENERAL 1.1 SUMMARY A. Section includes hardware for wood, hollow metal, and aluminum doors. 1. Provide door gaskets, including weather stripping and seals, and thresholds. B. Related Sections: 1.2 REFERENCES 1. Section Metal Doors and Frames: Silencers integral with steel frames. 2. Section Flush Wood Doors. 3. Section Overhead Service Doors and Roll up grille. 4. Section Aluminum Entrances and Storefronts. A. American National Standards Institute: 1. ANSI A Butts and Hinges. 2. ANSI A Bored and Preassembled Locks and Latches. 3. ANSI A Exit Devices. 4. ANSI A Door Controls - Closures. 5. ANSI A Auxiliary Locks and Associated Products. 6. ANSI A Architectural Door Trim. 7. ANSI A Template Hinge Dimensions. 8. ANSI A Door Controls - Overhead Holders. 9. ANSI A Interconnected Locks and Latches. 10. ANSI A Mortise Locks and Latches. 11. ANSI A Sliding and Folding Door Hardware. 12. ANSI A Closer Holder Release Devices. 13. ANSI A Auxiliary Hardware. 14. ANSI A Materials and Finishes 15. ANSI A Power Assist and Low Energy Power Operated Doors. 16. ANSI A Electromagnetic Locks. 17. ANSI A Delayed Egress Locks. 18. ANSI A156 - Complete Set of 24 BHMA Standards (A156 Series) with Binder. B. Builders Hardware Manufacturers Association: 1. BHMA Directory of Certified Products DOOR HARDWAR - 1

3 D. National Fire Protection Association: 1. NFPA 80 - Standard for Fire Doors, Fire Windows. 2. NFPA Standard Methods of Fire Tests of Door Assemblies. E. Underwriters Laboratories Inc.: 1. UL 10B - Fire Tests of Door Assemblies. 2. UL Panic Hardware. 3. UL - Building Materials Directory. F. Intertek Testing Services (Warnock Hersey Listed): 1. WH - Certification Listings. 1.3 PERFORMANCE REQUIREMENTS A. Fire Rated Openings: Provide door hardware listed by UL or Intertek Testing Services (Warnock Hersey Listed), or other testing laboratory approved by applicable authorities. 1.4 SUBMITTALS 1. Hardware: Tested in accordance with NFPA 252. A. Section Submittals: Submittal procedures. B. Shop Drawings: 1. Indicate locations and mounting heights of each type of hardware, schedules, catalog cuts, electrical characteristics and connection requirements. 2. Submit manufacturer's parts lists, and templates. C. Samples: 1. Upon request submit one sample of typical hinge, latchset, lockset, and closer, illustrating style, color, and finish. 2. Approved samples may be incorporated into Work. 3. Manufacturer's Installation Instructions: Submit special procedures, and perimeter conditions requiring special attention. 1.5 CLOSEOUT SUBMITTALS A. Section Contract Closeout: Closeout procedures. B. Project Record Documents: Record actual locations of installed cylinders and their master key code. C. Operation and Maintenance Data: Submit data on operating hardware, lubrication requirements, and inspection procedures related to preventative maintenance DOOR HARDWAR - 2

4 D. Keys: Deliver with identifying tags to Owner by security shipment direct from hardware supplier. 1.6 QUALITY ASSURANCE A. Perform Work in accordance with the following requirements: 1.7 QUALIFICATIONS 1. ANSI A156 series. 2. NFPA UL 305. A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. B. Hardware Supplier: The hardware supplier must have in his/her employment an Architectural Hardware Consultant (AHC), as recognized by the Door And Hardware Institute, with a minimum of 10 years of Architectural Hardware experience or an equivalent person with 20 years of Architectural Hardware experience, who shall be responsible for the detailing, scheduling, and ordering of the finish hardware for this Contract. C. Products Requiring Electrical Connection: Listed and classified by Underwriters' Laboratories, Inc., or testing firm acceptable to authority having jurisdiction as suitable for purpose specified and indicated. 1.8 DELIVERY, STORAGE, AND HANDLING A. Package hardware items individually with necessary fasteners, instructions, and installation templates, when necessary; label and identify each package with door opening code to match hardware schedule. 1.9 COORDINATION A. Coordinate Work with other directly affected sections involving manufacture or fabrication of internal reinforcement for door hardware and recessed items. 1. Provide templates or actual hardware as required to ensure proper preparation of doors and frames. C. Sequence installation to accommodate required utility connections. D. Coordinate Owner's keying requirements during course of Work WARRANTY A. Section Contract Closeout: Product warranties and product bonds DOOR HARDWAR - 3

5 B. Furnish 3 copies of the following written warranty to be included in the Maintenance Manual: 1. Warranty against mechanical failure of exit devices for a 3 year period. 2. Warranty against mechanical failure of locksets and cores for a 7 year period. 3. Warranty against mechanical failure of door closers for a 10 year period. 4. Warranty door operators and supporting equipment for a 2 year period. 5. Warranty against failure of parts of all hardware except exit devices, locksets, and door closers for a 1 year period MAINTENANCE MATERIALS A. Section Contract Closeout: Maintenance materials. B. Furnish special wrenches and tools applicable for each different and for each special hardware component. C. Furnish maintenance tools and accessories supplied by hardware component manufacturer. PART 2 PRODUCTS 2.1 DOOR HARDWARE A. Hinge Manufacturers: 1. Ives Model 5BB1 / 5BB1HW 2. Bommer Model BB500 / BB Stanley Model FBB179 / FBB Substitutions: Section Substitutions. B. Lockset and Latch Set Manufacturers: 1. Falcon K Series 2. Best 93K Series Owner s Standard at Shell A - Ross 3. Schlage ND Series 4. Substitutions: Section Substitutions. C. Exit Device Manufacturers: 1. Von Duprin Model 99 Series Owner s Standard at Shell A - Ross 2. Falcon 25 Series 3. Sargent 80 Series 4. Substitutions: Section Substitutions. D. Cylinder Manufacturers: 1. Schlage 2. Best - Owner s Standard at Shell A Ross 3. Falcon 4. Substitutions: Section Substitutions DOOR HARDWAR - 4

6 F. Closers Manufacturers: 1. LCN 4040XP Series - Owner s Standard at Shell A Ross 2. Sargent 351 Series. 3. LCN 4050 Series 4. Norton 7500 Series 5. Substitutions: Section Substitutions. G. Door Controls and Overhead Holders Manufacturers: 1. Glynn Johnson Model 900 Series 2. ABH Model 9000 Series 3. Rixson Model 9 Series 4. Substitutions: Section Substitutions. H. Push/Pulls, Manual and Automatic Bolts, Protection Plates, and Trim Manufacturers: 2.2 COMPONENTS 1. Ives 2. Don-Jo 3. Trimco 4. Substitutions: Section Substitutions. A. General Hardware Requirements: Where not specifically indicated, comply with applicable ANSI A156 standard for type of hardware required. Furnish each type of hardware with accessories as required for applications indicated and for complete, finished, operational doors. 1. Templates: Furnish templates or physical hardware items to door and frame manufacturers sufficiently in advance to avoid delay in Work. 2. Reinforcing Units: Furnished by door and frame manufacturers; coordinated by hardware supplier or hardware manufacturer. 3. Fasteners: Furnish as recommended by hardware manufacturer and as required to secure hardware. a. Finish: Match hardware item being fastened. 4. Fire Ratings: Provide hardware with UL or Intertek Testing Services (Warnock Hersey Listed) listings for type of application involved. 5. Electrical Devices: Make provisions and coordinate requirements for electrical devices and connections for hardware. B. Hinges: ANSI A156.1, full mortise type complying with following general requirements unless otherwise scheduled. 1. Widths: Sufficient to clear trim projection when door swings 180 degrees. 2. Number: Furnish minimum three hinges to 90 inches high, four hinges to 120 inches high for each door leaf. a. Fire Rated Doors to 86 inches High: Minimum three hinges DOOR HARDWAR - 5

7 4. Size and Weight: 4-1/2 inch standard weight typical for 1-3/4 inch doors. a. Doors Over 40 inches Wide: Extra heavy weight ball bearing hinges. b. Doors 2 inch Thick: 5 inch extra heavy weight ball bearing. c. Doors Over 48 inches Wide: 5 x 4.5 inch extra heavy weight ball bearing. 5. Pins: Furnish non-removable pins (NRP) at exterior and locked outswinging doors, non-rising pins at interior doors. 6. Tips: Flat button tips with matching plug. 7. Stainless Steel with stainless steel pins at all exterior doors. C. Heavy Duty Cylindrical Locks and Latches: Schlage "ND" Series. Fastened with throughbolts. 1. Chassis: Cylindrical design, corrosion - resistant plated cold-rolled steel. 2. Latch Retractors: Forged steel. Balance of inner parts: Corrosion-resistant plated steel, or stainless steel. 3. Lever Trim: Accessible design, independent operation, spring-cage supported, minimum 2" clearance from lever mid-point to door face. 4. Locks shall be of such construction that when locked, the door may be opened from within by using lever and without the use of a key or special knowledge. 5. Rosettes: Minimum 3-7/16" diameter for coverage of ANSI/DHI A115.18, 1994 door preparation, through-bolt lugs on both spring cages to fully engage this pattern. 6. Springs: Full compression type. 7. Strikes: 16 gage curved steel, bronze or brass with 1" deep box construction, lips of sufficient length to clear trim and protect clothing. D. Exit Devices: ANSI A156.3, Grade 1 type rim type, with push pad. 1. Exit devices: Von Duprin as scheduled with push-through pad design, no exposed touch bar fasteners, no exposed cavities when operated. 2. Provide certification by independent testing laboratory that specified devices have completed over 1,000,000 cycles and still perform in accordance to ANSI/BHMA A All internal parts shall be of cold-rolled steel with zinc dichromate coating. 4. Mechanism case shall have an average thickness of.140" 5. Compression spring engineering. 6. Non-handled basic device design with center case interchangeable with all functions. 7. All devices shall have quiet return fluid dampeners. 8. All latchbolts for wide stile devices shall be deadlocking with 3/4" throw and have a self-lubricating coating to reduce friction and wear. 9. Device push bar must release when a force of 32 pounds, or less, of pressure is applied when a force of 250 pounds is applied to the door. 10. Device shall bear UL label for fire and or panic as may be required. 11. All surface strikes shall be roller type and utilize a plate underneath to prevent movement DOOR HARDWAR - 6

8 12. Lever Trim: "Breakaway" design, forged brass or bronze escutcheon with a minimum of.130" thickness, match lockset lever design. 13. Removable Mullions: Removable with single turn of building key, securely reinstalled without need for key. 14. Furnish glass bead kits for vision lites where required. Devices for flush doors must fit flat on the door. 15. Exit devices shall be able to have latch-bolt monitoring switches, request to exit switches, electric latch-retraction, alarm kits, electric outside trim, or cylinder dogging added to the existing unit as the need arises for future electrified openings without replacing the original exit device. E. Cylinders: ANSI A156.5, Grade 1, 1. Keying: Keyed as directed by Owner. Master keyed, Grand master keyed, Great grand master keyed as directed. 2. Permanent cores shall be keyed/combinated in sets or subsets, master keyed or great grand master keyed, as directed by Owner. Permanent keys and cylinders/cores shall be marked with the applicable blind code for identification. 3. These visual key control marks or codes will not include the actual key cuts. Permanent keys will also be stamped Do Not Duplicate - Patented. Keys and cylinder identification stamping to be approved by Architect and Owner. Failure to properly comply with these requirements may be cause to require replacement of all or any part of the cylinders and keys involved as deemed necessary at no additional cost to the Owner. 4. Equip locks and cylinders with patent protected, full size cores with nickel silver blocking pin to check for patented feature on keys. Provide a minimum of six pins with nickel silver bottom pins. Cylinders must allow for multiplex master keying, combinated to Owner s instructions. 5. Supply all locks and cylinders with metal construction cylinders/cores. 6. It is the material supplier's responsibility to de-activate the construction keying and to deliver all permanent key blanks and other security keys direct to Owner s representative. Failure to properly comply with these requirements may be cause to require replacement of all or any part of the cylinders and keys involved as deemed necessary at no additional cost to the Owner. 7. Keys Required: Furnish quantity of keys as follows: Five (5) Master Keys Two (2) keys per lock or cylinder. Two (2) core keys. Fifteen (15) construction keys. 8. All keys shall be made of nickel silver. 9. Include construction keying. 10. Keys: Nickel silver. Stamp keys with DO NOT DUPLICATE. F. Closers: ANSI A156.4 modern type with cover, surface mounted ; full rack and pinion type with steel spring and non-freezing hydraulic fluid; closers required for fire rated doors unless otherwise indicated. 1. Surface type door closers shall be fully hydraulic, full rack and pinion action with a one piece forged steel piston 1-1/2 diameter minimum and have a ten year warranty DOOR HARDWAR - 7

9 2. Closers at fire rated doors shall be in compliance with UL 10 C and UBC 7.2 certified for positive pressure. 3. Hydraulic fluid shall be of a type requiring no seasonal adjustments for temperatures from 120 degrees F. to -30 degrees F.. 4. Pinion shaft shall be minimum of 5/8 diameter. 5. Barrier-free at all interior doors. 6. Separate adjusting valves shall be provided for closing speed, latching speed and backcheck. 7. Adjusting valves shall be of a metal material, concealed, adjustable only with special wrench, and shall be seated with O type rings. 8. Closers shall have forged steel main arms at high traffic doors. 9. Closers shall NOT be supplied with Pressure Relief Valves. G. Door Controls and Overhead Holders: Furnish with accessories as required for complete operational installation. 2.3 ACCESSORIES A. Lock Trim: Furnish levers with design as indicated in Schedule. B. Push/Pulls, Manual and Automatic Bolts, Protection Plates, Gaskets, Thresholds, and Trim: Furnish as indicated in Schedule, with accessories as required for complete operational door installations. 2.4 FINISHING 1. Push Plates and Pulls Plates: ANSI A156.6; push plates 4 x 16. Furnish straight pull on 4 x 16 plate with bolts to secure from opposite door face; furnish with minimum inch pull plates unless otherwise indicated. 2. Manual and Automatic Bolts: ANSI A Grade 1 top and bottom flush bolts, with dust-proof floor strike, unless otherwise indicated. 1. Kickplates : ANSI A156.6, metal; height indicated in Schedule by 2 inch less than door width; minimum inch thick stainless steel. 2. Weatherstripping: Furnish continuous weatherstripping at top and sides of exterior doors. 3. Fire Rated Gaskets: Furnish continuous fire rated gaskets at top and sides of fire rated doors. 4. Thresholds: Maximum 1/2 inch height. 5. Wall Stops: ANSI A156.1, Grade Electrical Power Transfer (EPT) units shall be fully concealed when the door is closed. EPT shall contain either 2 each 18 gauge stranded or 10 each 24 gauge stranded wires as determined in the hardware sets. The transfer tube shall be made of stainless steel. Spring Tubes are NOT acceptable. Electric hinges are NOT an approved substitution. C. Finishes: ANSI A156.18; furnish following finishes except where otherwise indicated in Schedule at end of section. 1. Hinges: a. BHMA 652 at exterior doors, 652 at interior doors, satin finish DOOR HARDWAR - 8

10 2. Typical Exterior Exposed and High Use Interior Door Hardware: a. BHMA 630, satin finished stainless steel. b. BHMA 626, satin chromium plated brass or bronze. 3. Typical Interior Door Hardware: a. BHMA 626, satin chromium plated brass or bronze. b. BHMA 630, satin finished stainless steel. 4. Closers: a. BHMA 689, satin aluminum, powder coated. 5. Thresholds: a. BHMA 628, satin aluminum, clear anodized. 6. Other Items: Furnish manufacturer s standard finishes to match similar hardware types on same door, and maintain acceptable finish considering anticipated use and BHMA category of finish. PART 3 EXECUTION 3.1 EXAMINATION A. Verify doors and frames are ready to receive door hardware and dimensions are as indicated on shop drawings or instructed by manufacturer. B. Verify electric power is available to power operated devices and is of correct characteristics. 3.2 INSTALLATION A. Coordinate mounting heights with door and frame manufacturers. Use templates provided by hardware item manufacturer. 3.3 FIELD QUALITY CONTROL A. The Architectural Hardware Consultant (A.H.C.) or equivalent (as stated above), as employed by the material supplier of this section, in conjunction with the manufacturer s factory representative for locks, closers, and exit devices, along with the lead finish hardware installer shall inspect complete installation and certify that the hardware, installation, and adjustment of the hardware items has been furnished and installed in accordance with manufacturer s instructions and as specified herein. 3.4 ADJUSTING A. Section Execution and Closeout Requirements: Testing, adjusting, and balancing. B. Adjust hardware for smooth operation. 3.5 PROTECTION OF INSTALLED CONSTRUCTION A. Section Execution and Closeout Requirements: Protecting installed construction. B. Do not permit adjacent work to damage hardware or hardware finish DOOR HARDWAR - 9

11 3.6 SCHEDULES A. The following hardware sets are intended to establish type and standard of quality when used together with this section requirements. Examine Drawings and Specifications and furnish proper hardware for door openings. = Hardware Item Requiring Electrical Coordination SHELL A - ROSS HARDWARE GROUP NO. 01 DOOR NUMBER: A-101, A-102, A-103, A EA CYLINDER 1E74 OR 1E72 AS REQ 626 BES BALANCE OF HARDWARE BY DOOR MANUFACTURER HARDWARE GROUP NO. 02 DOOR NUMBER: A-105, A EA HW HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE 1 EA POWER TRANSFER EPT10 CON 689 VON 1 EA DELAYED PANIC HDW CX-9957-EO-CON 626 VON 1 EA MORTISE CYLINDER 1E BES 1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA GASKETING SET 8303AA X D.S. AA ZER 1 EA DOOR SWEEP 39A X D.W. A ZER 1 EA THRESHOLD 8655A X D.W. A ZER 1 EA RAIN DRIP 142A X D.W. +4" AS REQ A ZER 1 EA DOOR CONTACT HM BLK SCE 1 EA POWER SUPPLY PS914 LGR VON 1 EA WIRING DIAGRAM POINT TO POINT / RISER SCE DELAYED EGRESS EXIT DEVICE SYSTEM - DEPRESSING PUSHBAR FOR DESIGNATED AMOUNT OF TIME BEGINS IRREVERSIBLE ALARM CYCLE. UPON COMPLETION OF ALARM CYCLE FREE EGRESS IS ALLOWED. DEVICE CAN BE ARMED, RESET OR DISARMED BY KEY OR ACCESS CONTROL. (DELAYED EGRESS RESTRICTIONS PER LOCAL CODE REQUIREMENTS). DELAY 15 SECONDS DOOR HARDWAR - 10

12 HARDWARE GROUP NO. 03 DOOR NUMBER: A EA HW HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE 1 EA PANIC HARDWARE 99-EO 626 VON 1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA GASKETING SET 8303AA X D.S. AA ZER 1 EA DOOR SWEEP 39A X D.W. A ZER 1 EA THRESHOLD 8655A X D.W. A ZER 1 EA RAIN DRIP 142A X D.W. +4" AS REQ A ZER 1 EA DOOR VIEWER IVE HARDWARE GROUP NO. 04 DOOR NUMBER: A-107 ALL HARDWARE BY DOOR MANUFACTURER DOOR HARDWAR - 11

13 HARDWARE GROUP NO. 05 DOOR NUMBER: A EA HINGE 5BB1 4.5 X IVE 1 EA STOREROOM 9K37D 14D 626 BES 1 EA ELECTRIC STRIKE 6211 FSE 630 VON 1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA WALL STOP WS407CVX 630 IVE 1 EA GASKETING SET 8303AA X D.S. AA ZER 1 EA DOOR BOTTOM 111A X D.W. AL ZER 1 EA THRESHOLD 548A X D.W. A ZER 1 EA DOOR VIEWER IVE 1 EA CARD READER BY ACCESS CONTROL INTEGRATOR BLK SCE 1 EA DOOR CONTACT HM BLK SCE 1 EA MOTION SENSOR SCANII BLK SCE 1 EA POWER SUPPLY PS902 LGR SCE 1 EA WIRING DIAGRAM POINT TO POINT / RISER SCE DOORS NORMALLY CLOSED AND LOCKED. ENTRY BY VALID CREDENTIAL AT CARD READER OR BY KEY AT LOCK. RX MOTION SENSOR SHUNTS DOOR FORCED OPEN ALARM IN ACCESS CONTROL SYSTEM. FREE EGRESS AT ALL TIMES. SHELL B - G HARDWARE GROUP NO. 01 DOOR NUMBER: B-101, B EA CYLINDER 951 SCH C OR 986 SCH C AS REQ 626 FAL BALANCE OF HARDWARE BY DOOR MANUFACTURER HARDWARE GROUP NO. 02 NOT USED HARDWARE GROUP NO. 03 NOT USED DOOR HARDWAR - 12

14 HARDWARE GROUP NO. 04 DOOR NUMBER: E-102 ALL HARDWARE BY DOOR MANUFACTURER HARDWARE GROUP NO. 05 NOT USED HARDWARE GROUP NO. 06 DOOR NUMBER: C-101, D EA CONT. HINGE 112HD 628 IVE 1 EA PANIC HARDWARE 1691-DT-RL 628 FAL 1 EA PANIC HARDWARE 1694-NL-P 628 FAL 1 EA RIM CYLINDER SCH "C" 626 FAL 2 EA SURFACE CLOSER 4050 SCUSH 689 LCN 2 EA PA MOUNTING PLATE PA 689 LCN 2 EA DOOR SWEEP 39A X D.W. A ZER 1 EA THRESHOLD 8655A X D.W. A ZER 1 SET SEALS BY ALUMINUM FRAME SUPPLIER HARDWARE GROUP NO. 07 DOOR NUMBER: C EA HINGE 5BB1 4.5 X 4.5 NRP 652 IVE 1 EA STOREROOM K581CP6 QUA 626 FAL 1 EA SURFACE CLOSER 4050 RW/PA 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA WALL STOP WS407CVX 630 IVE 1 SET SEALS 188S X D.S. BLK ZER DOOR HARDWAR - 13

15 HARDWARE GROUP NO. 08 DOOR NUMBER: C-103, D EA HW HINGE 5BB1HW 4.5 X IVE 1 EA FIRE EXIT HARDWARE F-25-R-L-BE-QUA 626 FAL 1 EA SURFACE CLOSER 4050 RW/PA 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA WALL STOP WS407CVX 630 IVE SET SEALS 188S X D.S. BLK ZER HARDWARE GROUP NO. 09 DOOR NUMBER: C-104, D-103, E EA HW HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE 1 EA PANIC HARDWARE 25-R-L-511-QUA 626 FAL 1 EA MORTISE CYLINDER SCH "C" 626 FAL 1 EA SURFACE CLOSER 4050 SCUSH 689 LCN 1 EA KICK PLATE " X 2" LDW B-CS 630 IVE 1 EA GASKETING SET 8303AA X D.S. AA ZER 1 EA DOOR SWEEP 39A X D.W. A ZER 1 EA THRESHOLD 8655A X D.W. A ZER 1 EA RAIN DRIP 142A X D.W. +4" AS REQ A ZER 1 EA DOOR VIEWER IVE END OF SECTION DOOR HARDWAR - 14