SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

Size: px
Start display at page:

Download "SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes."

Transcription

1 SECTION CONDUITS AND BOXES 1.01 DESCRIPTION PART 1- GENERAL A. Work covered by this section includes the furnishing and installation of conduits and boxes SUBMITTALS A. The Contractor shall submit shop drawings, in accordance with Section Shop Drawing submittals shall clearly show the following: 1. Materials 2. Ratings (voltage, phase, current) 3. Manufacturer s name, address and telephone number 4. Product data including manufacturer s technical data 5. Applicable manufacturer specifications 6. Installation instructions 1.03 QUALITY ASSURANCE A. Set all conduits and boxes plumb and level. B. All conduits and boxes shall be straight, free from blisters and defects, and shall bear the Underwriter s label PENETRATIONS A. Except where necessary, do not penetrate roofs and waterproofed surfaces. Where required, make penetrations prior to the application of roofing and waterproofing materials. B. Seal all conduits and penetrations entering hazardous areas in accordance with the NEC. C. Seal all conduits and penetrations which enter an area which r may contain a corrosive atmosphere or a potentially hazardous atmosphere. Seals shall be gas and vapor

2 PART 2- PRODUCTS 2.01 CONDUITS A. Conduits may be installed exposed unless installed in earth, or specifically as concealed on plans. B. Conduits installed in hazardous areas and in poured concrete shall be PVC coated heavy wail rigid galvanized steel. Conduits in concrete slabs shall exit slab with a factory applied PVC coating rigid galvanized pipe of a minimum length of 12. C. Schedule 80 PVC shall not be utilized unless otherwise noted on the plans. D. Conduits shall be placed at right angles or parallel to walls and securely held by stainless steel straps. E. No conduit shall be smaller than 3/4. F. The ends of all conduits where entering outlet boxes shall be fitted with locknuts and bushings. Provide ground bushings per code and, with full capacity separate ground wires. G. For all sizes of conduit larger than 1, large radius elbows and offsets made for the purpose shall be. Conduit bends shall be made in accordance with Article No, 346 of the NEC. H. If PVC conduit is permitted, all buried PVC conduit shall be provide with a rigid galvanized PVC coated rise elbow extending up to 6 feet above grade for mechanical protection. I. Conduit shall be as manufactured by Carlon, Clerio Wire and Cable or specifically approved equal LIQUID-TIGHT FLEXIBLE CONDUITS A. Connections to motors and equipment shall be made with liquid tight, flexible conduit of the same size as the conduit run

3 B. Maximum length of liquid tight flexible conduit unless otherwise noted or approved shall be 18. C. Non-metallic, liquid-tight conduits shall be provided with a polyvinyl chloride reinforced core. Conduit must conform to NEC 351 B. Conduits shall be as manufactured by Electri-Flex Liquatite Type LNM-P, Seal-Tite type VA as manufactured by American Brass Co or specifically approved equal GENERAL A. Conduits shall be sized per NFPA 70 NEC; minimum size shall be ¾. B. Each length of conduit shall bear the UL label and the manufacturer s name or trademark. C. Provide No. 12 galvanized pulling wire in each empty conduit D. In hazardous areas, provide explosion proof construction in compliance with NEC Class I, Division I, Group D. E. Use locknuts and proper insulating type bushings, as required BOXES A. Boxes and covers shall be of dimensions sufficient for the specific use and location, kind of equipment to be served. Outlet boxes shall be galvanized steel. B. All boxes for exterior and interior surface mounted work shall be galvanized steel equipped with gaskets and shall be vapor proof and watertight PULLBOXES. JUNCTION BOXES AND WIREWAYS A. Pull or junction boxes shall be NEMA 12 cabinet type construction unless noted. B. All interior wire ways and troughs shall be NEMA 4X construction

4 2.06 UNDERGROUND CONDUIT A. Unless otherwise specified or shown on the drawings, all underground conduits shall rigid galvanized steel. B. Plastic warning tape shall be buried 6 above all underground conduits LOCATIONS PART 3- EXECUTION A. The locations of outlets. Fixtures, equipment, wiring and other electrical devices are shown on the drawings. B. Conduit locations shown on the plans are not necessarily indicative of the required location or routing INSTALLATION A. Conform to NEC requirements. B. Unless otherwise shown on the drawings, all conduits shall be run exposed. C. For exposed work, conduit shall be supported by straps, securely tightly with screws. Maximum separation between supports shall be as specified in the NEC, but in no case shall exceed 5 feet. D. All exposed conduits shall be neat and symmetrical and run Insulating bushings shall be provided as required by NEC. E. The minimum depth of cover over underground conduits shall be 24, except under paved areas where cover shall be at least 30 inches. F. Underground conduit runs shall be sloped to drain away from the level of entry to equipment. G. Avoid bends and offsets where possible

5 H. Maintain a 12 inch minimum separation between all conduits and water, drainage, sewer, gas or telephone lines BOXES A. Boxes shall be supported independently of all conduits and shall be rigidly secured. B. Secure boxes by means of clamp type supports and provide rigid vibration proof installation. C. Unless otherwise shown on the plans, the mounting height of all boxes from the floor to the centerline of box shall be: 1. Switches Above grade receptacles Below grade receptacles Safety and disconnect switches Panels to top breaker Telephone outlets FINAL AND CLEANING A. Clear conduits of all obstructions and dirt prior to pulling wires or cables. B. Clean empty conduits, as specified above. END OF SECTION

6 PAGE INTENTIONALLY LEFT BLANK

SECTION CONDUITS AND BOXES

SECTION CONDUITS AND BOXES PART 1 GENERAL 1.01 DESCRIPTION A. Work covered by this section includes the furnishing and installation of conduits and boxes and the testing of the completed electrical systems 1.02 SUBMITTALS A. The

More information

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.

More information

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved

SECTION A. Underwriters Laboratories, Inc., listed and NEC approved PART 1 GENERAL 1.01 DESCRIPTION A. Provide all raceways, fittings, and boxes of specified type required for complete project. Install all systems in raceways unless specifically noted otherwise. Provide

More information

Youngstown State University

Youngstown State University SECTION 260533 - RACEWAYS PART 1 - GENERAL SUMMARY A. This section includes raceways for electrical wiring. Types of raceways in this section include the following: 1. Flexible metal conduit 2. Liquid

More information

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC). SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION RACEWAYS

SECTION RACEWAYS SECTION 16110 RACEWAYS PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Provide a complete raceway system suitable for receiving wire and cable and continuous from outlet to outlet. System shall be complete with

More information

Raceway and Boxes for Electrical Systems Page 1 of 7

Raceway and Boxes for Electrical Systems Page 1 of 7 Last Update: May 12, 2017 A. Conduits: Page 1 of 7 1. All conductors for each and every electrical system shall be installed in a raceway except communications and A/V systems which shall have stubs to

More information

GLENWOOD PLACE 2 MAR 2015

GLENWOOD PLACE 2 MAR 2015 PART 1 - GENERAL 1.01 SUMMARY: SECTION 16110 RACEWAYS A. Description: 1. Provide continuous conduit systems - beginning at the service point, to all distribution equipment and to every outlet and piece

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SECTION 260533 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring. B. See Division

More information

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 280528 - PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Metal conduits, tubing, and fittings. 2. Nonmetallic conduits, tubing, and fittings. 3.

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 260533 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes raceways, fittings, boxes, enclosures, cabinets, and track busway for electrical wiring.

More information

Design Standard Conduit for Electrical Systems

Design Standard Conduit for Electrical Systems Design Standard Purpose: This design standard has the purpose of creating a consistent application for the installation of conduits throughout the East Side Union High School District, therefore achieving

More information

SECTION RACEWAYS AND BOXES

SECTION RACEWAYS AND BOXES PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 26 05 33 RACEWAYS AND BOXES A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SECTION 26 05 33 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes conduit and tubing, surface raceways, wireways, outlet boxes, pull and junction boxes, and handholes.

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Update sections Materials and Special Requirements 3 F. 2. 4 H. 2.; 10. & 11(added) 6/15/16 Updated division

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

SECTION CONDUIT AND BOXES

SECTION CONDUIT AND BOXES PART 1 - GENERAL 1.01 SUMMARY SECTION 27 05 33 CONDUIT AND BOXES A. This Section includes specific requirements for conduits and boxes within the Communications Pathway System as defined in Division 27

More information

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION OUTLET, PULL, AND JUNCTION BOXES SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 41 UNDERGROUND ELECTRICAL CONSTRUCTION A. This section specifies the furnishing, installation, and connection of precast manholes and pullboxes with ducts

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

1510 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

1510 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SECTION 260533-RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section includes conduit raceways, and tubing, surface raceways, wireways, outlet boxes, pull and junction boxes, and

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CONDUIT, FITTINGS, AND BODIES

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CONDUIT, FITTINGS, AND BODIES Section 16111 PART 1 GENERAL 1.01 SUMMARY This Section covers the furnishing and installation of conduit, fittings and bodies. 1.02 MEASUREMENT AND PAYMENT Unless indicated in the Unit Price Schedule as

More information

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL 1.01 DESCRIPTION SECTION 16000 GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL A. This Section includes the general provisions applicable to electrical work and testing of the completed electrical systems.

More information

DIVISION 22 PLUMBING SECTION INTERIOR SANITARY WASTE AND VENT PIPING SYSTEM

DIVISION 22 PLUMBING SECTION INTERIOR SANITARY WASTE AND VENT PIPING SYSTEM DIVISION 22 PLUMBING PART 1 GENERAL 1.01 DESCRIPTION A. Provide a complete system of soil, waste, and vent piping to fixtures and equipment, including traps, floor drains and cleanouts, extending to a

More information

A. Coordinate arrangement, mounting, and support of electrical equipment:

A. Coordinate arrangement, mounting, and support of electrical equipment: SECTION 260500 -BASIC ELECTRICAL MATERIALS AND METHODS PART 1- GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Electrical equipment coordination and installation. 2. Sleeves for raceways

More information

SECTION ELECTRICAL MATERIALS AND METHODS

SECTION ELECTRICAL MATERIALS AND METHODS SECTION 26 00 20 ELECTRICAL MATERIALS AND METHODS PART 1: GENERAL 1.01 WORK INCLUDED A. Furnish and install all conduit, conduit fittings and boxes to complete the installation of all electrically operated

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 16450 - ELECTRICAL WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

SECTION CONDUI T

SECTION CONDUI T PART1 GENERA L 1.01 SECTION INCLUDE S SECTION 26 0534 CONDUI T A. Galvanized steel rigid metal conduit (RMC). B. Intermediate metal conduit (IMC). C. Flexible metal conduit (FMC). D. Liquidtight flexible

More information

Daytona Beach Pier Building Renovation Jun 2010

Daytona Beach Pier Building Renovation Jun 2010 SECTION 15150 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

SECTION RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS SECTION 26 05 33 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.01 WORK INCLUDED A. Raceways: 1. Wireways. B. Conduit: 1. Rigid metal conduit and fittings. (RGS) 2. Electrical metallic

More information

SANITARY WASTE AND VENT PIPING

SANITARY WASTE AND VENT PIPING SECTION 15420 - SANITARY WASTE AND VENT PIPING PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. A. ANSI C Electrical Rigid Steel Conduit, Zinc Coated.

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. A. ANSI C Electrical Rigid Steel Conduit, Zinc Coated. SECTION 26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 -GENERAL 1.1 SUMMARY A. Section includes conduit and tubing, surface raceways, wireways, outlet boxes, pull and junction boxes, and handholes.

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

BASIC ELECTRICAL MATERIALS AND METHODS

BASIC ELECTRICAL MATERIALS AND METHODS BASIC ELECTRICAL MATERIALS AND METHODS General Scope Provide raceways for all wiring. All exposed and concealed wiring (including low voltage control, telecommunications, and power limited wiring) shall

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

SECTION ELECTRICAL SITE UTILITIES

SECTION ELECTRICAL SITE UTILITIES SECTION 16402 ELECTRICAL SITE UTILITIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

More information

SECTION CONDUIT AND FITTINGS

SECTION CONDUIT AND FITTINGS SECTION 16111 CONDUIT AND FITTINGS PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes specific requirements, products, and methods of execution relating to conduit and conduit fittings approved

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call 811 Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES 4901 East Park 30 Drive P.O.

More information

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft. SECTION 260000 ELECTRICAL PART 1- GENERAL 2.1 SUMMARY : Provide complete distribution systems for electrical power as shown on the drawings or required by other sections of these specifications. A. Work

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

SECTION RACEWAYS AND BOXES

SECTION RACEWAYS AND BOXES SECTION 16110 RACEWAYS AND BOXES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications.

A. Section Includes: Electrical site utilities and coordination of requirements with the utility company and service specifications. 16402 ELECTRICAL SITE UTILITIES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 33 50 00. *************************************************************************************************************

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES CONTENTS Page # 100-200 OR 400 AMP

More information

SECTION ELECTRICAL SYSTEM RACEWAY and BOXES

SECTION ELECTRICAL SYSTEM RACEWAY and BOXES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal conduit B. Flexible metal conduit C. Liquid tight flexible metal conduit D. Electrical metallic tubing E. Non-metallic conduit F. Fittings and conduit bodies

More information

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SPEC WRITER NOTE: Delete between //---//if not applicable to project. Also, delete any other item or paragraph

More information

SECTION FACILITY LIGHTNING PROTECTION

SECTION FACILITY LIGHTNING PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable

More information

ELECTRICAL SECTION 2

ELECTRICAL SECTION 2 ELECTRICAL SECTION 2 COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. This Section includes raceways, conductors and cables, grounding materials, boxes, electrical identification

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

DIVISION 26 - ELECTRICAL Section Conduit for Electrical Systems 1. GENERAL 1.1 WORK INCLUDES

DIVISION 26 - ELECTRICAL Section Conduit for Electrical Systems 1. GENERAL 1.1 WORK INCLUDES DIVISION 26 - ELECTRICAL Section 26 05 33 - Conduit for Electrical Systems 1. GENERAL 1.1 WORK INCLUDES A. Base Bid: 1. Electrical Contractor provide: a. Rigid metallic conduit and fittings b. Flexible

More information

SECTION ELECTRICAL UTILITY SERVICES

SECTION ELECTRICAL UTILITY SERVICES SECTION 33 71 73 ELECTRICAL UTILITY SERVICES PART 1 GENERAL 1.1 REFERENCES A. American Association of State Highway Officials (AASHO): 1. Standard Specifications B. California Administrative Code (CAC):

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows:

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows: SECTION 16050 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: General requirements for providing basic electrical materials and methods. B. Related Work Specified in Other Sections Includes: 1. Certain

More information

Specifications Electrical Metallic Tubing (EMT)

Specifications Electrical Metallic Tubing (EMT) T& Fittings Specifications Electrical Metallic Tubing (EMT) Ref. CEC Rule 12-000 not exceeding 750 Volts Electrical Metallic Tubing (EMT) is similar to rigid steel conduit but is much lighter, weighing

More information

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual [Type text] Heber Light & Power Developers & Excavators Electrical Service Requirements Manual May 2017 E.1.1 - GENERAL REQUIREMENTS PURPOSE This section was prepared to aid developers, contractors, engineers

More information

New Conduit Specification

New Conduit Specification New Conduit Specification Combines Portions of Sections 715, 783 & 992 into New Section 630. Coordinated Effort Between Traffic Operations, ITS, Lighting, Construction, and Industry New Conduit Specification

More information

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

Procurement Services SVC East Fowler Avenue Tampa, Florida (813) Procurement Services SVC 1073 4202 East Fowler Avenue Tampa, Florida 33620 (813) 974-2481 Web Address: https://www.usf.edu/business-finance/purchasing/public-bids/rfi.aspx October 12, 2018 Invitation to

More information

SECTION C RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

SECTION C RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS SECTION C-2 26 0533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Provide all labor, materials, and equipment necessary for the installation of raceways and boxes for electrical

More information

2. Fittings shall be threaded and finished similar to conduit. Threadless fittings shall not be used.

2. Fittings shall be threaded and finished similar to conduit. Threadless fittings shall not be used. SECTION 16110 RACEWAYS AND FITTINGS 1.00 RACEWAYS: All wiring shall be in raceways. Raceways shall be run in slabs, walls, above ceilings or exposed as indicated on drawings. Acceptable raceway and their

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping inside the building.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping inside the building. SECTION 221413 - FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following storm drainage piping inside the building. 1. Pipe, tube, and fittings. 2. Special pipe

More information

SECTION RACEWAYS AND BOXES

SECTION RACEWAYS AND BOXES SECTION 16130 RACEWAYS AND BOXES PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Raceways and Boxes which includes fittings, bushings, hubs, identification tags, clamp supports,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

A. This Section includes sanitary waste and vent piping inside the building and to locations indicated.

A. This Section includes sanitary waste and vent piping inside the building and to locations indicated. SECTION 221316 SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION PLUMBING PIPING SYSTEMS

SECTION PLUMBING PIPING SYSTEMS SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Greenbook Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 08-15-17 Rev. #06:

More information

SECTION RACEWAYS AND BOXES FOR ELECTRONIC SAFETY AND SECURITY

SECTION RACEWAYS AND BOXES FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 33 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies the furnishing, installation, and connection of conduit, fittings, and boxes to form complete, coordinated, raceway systems.

More information

DIVISION 16. Electrical Specifications

DIVISION 16. Electrical Specifications DIVISION 16 Electrical Specifications 16.1 General - Provide all electrical materials and methods as shown on the Drawings, as specified herein, and as needed for a complete and proper installation, including

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 22 14 00 _STORM WATER PIPING SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Storm water piping 2. Roof drains. 3. Area

More information

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 41 SPEC WRITER NOTE: 1. Use this section only for NCA projects. Delete // // if not applicable to project. Also, delete any other item or paragraph not applicable

More information

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING 809-1(a-e) 09 OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING These special provisions amend and where in conflict, supersede applicable sections of the 2009 Standard

More information

NOVADYNE 365 Lansdowne St. E., Unit 1, Peterborough, ON K9L 2A3

NOVADYNE 365 Lansdowne St. E., Unit 1, Peterborough, ON K9L 2A3 SYMBOL MODEL NUMBER LIGHTING CONTROLS SCHEDULE MANUFACTURER DESCRIPTION EMERGENCY LIGHTING & EXIT SCHEDULE SYMBOL MODEL NUMBER MANUFACTURER DESCRIPTION RECEPTACLE LEGEND LIGHTING LEGEND 15 Lansdowne Street

More information

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION Page 210500-1 SECTION 210500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION RACEWAYS AND CONDUIT

SECTION RACEWAYS AND CONDUIT SECTION 16112 RACEWAYS AND CONDUIT PART 1 GENERAL 1.01 SUMMARY. A. Related Sections: 1. 02221 - Excavating, Backfilling, and Compaction for Utilities. 2. 07270 - Firestopping and Fire and Smoke Barrier

More information

SECTION PART 1 GENERAL

SECTION PART 1 GENERAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.

More information

SECTION RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS. B. PVC coated or Bituminous coated rigid metal conduit

SECTION RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS. B. PVC coated or Bituminous coated rigid metal conduit SECTION 260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Rigid metal conduit (RMC) B. PVC coated or Bituminous coated rigid metal conduit C. Flexible metal conduit

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

Specifications Rigid Metal Conduit / PVC Coated Rigid Metal Conduit

Specifications Rigid Metal Conduit / PVC Coated Rigid Metal Conduit Specifications Rigid Metal Conduit / PVC Coated Rigid Metal Conduit Ref. CEC Rule 12-1000 Rigid Metal Conduit affords maximum mechanical protection to conductors within the raceway. Rigid metal conduit

More information

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,

More information

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 2004 Specifications Houston District SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 1. Description. Furnish and place a Multi-Duct Conduit (MDC) system that is suitable for installation in an outdoor

More information

B. All materials provided under this section shall be listed by an OSHA-approved, Nationally Recognized Testing Laboratory (NRTL).

B. All materials provided under this section shall be listed by an OSHA-approved, Nationally Recognized Testing Laboratory (NRTL). 16112 RACEWAYS AND CONDUIT ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 33 An optional keynote

More information

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 33 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between //--//if not applicable to project. Also, delete any other item or paragraph

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: SECTION 27 05 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. Delete text between // // not applicable to project. Edit remaining text

More information