1 STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi Bars, ASTM A615 Gr. 60, Fy = 60 ksi Fabric, ASTM A185 Gr. 65, Fy = 65 ksi f 'c = compressive strength in 28 days 3,000 psi for masonry corefill & conc. floor deck f 'm = net area compressive strength of masonry 1,500 psi unless noted All dimensional lumber - #2 SPF or equal Laminated Veneer Lumber (LVL) E = 1,900,000 psi Fb = 2600 psi Treated lumber - #2 S. Pine or equal DESIGN LOADS Roof Floors Dead load 15 psf Snow load Roof snow load = 35 psf Dead load 15 psf (5 psf top chord, 10 psf bottom chord) Wind Live loads Typical 90 mph (3 second gust) Exposure B, I = psf TEMPORARY BRACING Contractor is responsible for bracing, without overstressing, all structural elements as required at all stages of construction until completion of this project. Provide temporary lateral support for all walls until walls are adequately braced by floor or roof structure. Shore foundation walls retaining earth until floor framing and basement slab are in place. Use caution when operating equipment adjacent to foundation walls. GENERAL SOIL NOTES

2 The structure has been designed using a presumptive load-bearing value of 2000 psf in accordance with Table R of the IRC on virgin soil or compacted granular fill for footings. Remove all top soil, uncompacted fill or other poor soil from the construction area. Slope the site to drain away from the building. FOOTINGS/FOUNDATIONS All footings are to be formed. All stumps, roots and debris must be removed from the soil to a depth of at least 12 below the surface of the ground in the area occupied by the building. Footings shall be placed on undisturbed soil. All forms shall be removed from cast concrete. Wall footings are cast-in-place concrete with continuous reinforcing placed 3" clear of bottom and 2 clear at top and sides. Wall footings shall be minimum 10 thick with a 4 projection each side of wall. Reinforce with 2-#4 bars. Column footings shall be minimum 12 thick, plan dimension as shown on drawing. Reinforce with #4 bars at 8 on center each way. Provide 30 bar dia. lap at splices and full crossing lap at corners and intersections. Tie all reinforcing in place. Set footing reinforcing on chairs or masonry brick to obtain 3 clearance from bottom of footing. Unless otherwise noted, wall footings are centered under walls and column footings under columns. Maintain minimum frost depth of 42 for all exterior footings. Footing elevations if shown on the plan, are shown to top of footing. When not indicated, top of footing shall be placed 8 below top of slab on grade or the bottom of the footing shall be placed a minimum 42 below exterior grade whichever is deeper. Step footings in a uniform manner using a 2:1 horizontal to vertical slope. Refer to typical detail on structural drawings. Cast dowels in footing for foundation walls above. Dowels to be the same quantity, size and spacing as the vertical wall reinforcing. Dowels to be 30" long, extend 9" into footings unless noted otherwise. Shore all foundation walls appropriately before backfilling and compacting. SLABS ON GRADE All slabs on grade to be reinforced with either WWF 6x6-W1.4 x W1.4 in center of slab or 1.5 pounds per cubic yard polypropylene fiber reinforcement at contractor s option. Control joints shall be saw cut into strip pours as soon as concrete can accept it without raveling. Construction and/or control joints will occur at a maximum of 10'-0" o.c. at exterior slabs, maximum of 16-0 o.c. at interior slabs and shall be cleaned and sealed for curing purposes as soon as possible. Verify floor finishes and control/construction joint locations with architect. All control/construction joints shall be continuous and not staggered or offset. REINFORCED CONCRETE BLOCK WALLS Masonry shall not be laid when the temperatures of the outside air is below 40 0 F, unless approved methods are used during construction to prevent damage to the masonry. All materials used and surfaces built upon shall be free of snow and ice. Foundations supporting wood shall extend at least 6 above the adjacent finished grade. Wood beams pocketed into masonry shall be provided with a 1/2 air space on top, end and sides unless treated wood is used. Solid grout the masonry voids below beam bearing a minimum of 16. Masonry shall not bear permanently on wood members. Refer to dimension lumber notes for anchor bolt requirements.

3 See plans for location and spacing of reinforcement in walls. When one bar is in a single core place in center, unless noted otherwise. When two bars are in a single core, place one near each face. Vertical steel shall be lapped 48 dia. at all splices. Fill block core at vertical columns with 3,000 psi grout, rodded or vibrated in place. Grout shall be per ASTM C-476. Wall construction shall not exceed heights of 4'-0" before placement of core grout unless cleanout holes are provided at the bottom of each grout lift, then a maximum height of 8'-0" before placement of core grout. Provide 9 ga. horizontal joint reinforcing placed every 2nd course. Hollow unit concrete masonry shall be ASTM C90 grade N. Mortar shall be per ASTM C-270: Type M or S for Below grade and exterior masonry; Type N for all interior above grade masonry. MASONRY LINTELS All openings in concrete block walls not specifically indicated to have other types of lintels shall have reinforced block lintels as follows: 1. 8" deep for spans up to 8'-0" " deep for spans from 8'-0" to 12'-0". a. 4" and 6" wide units to be reinforced with 1-#5 BTM. b. 8", 10" and 12" wide units to have 2-#5 BTM. Where one lintel beam is continuous over two openings, with intermediate support, use 2-#5 top and 2-#5 bottom. Extend all lintels a minimum of 8" beyond opening and fill (2) block courses below lintel bearing with grout. All openings in brick faced or brick walls not specifically indicated to have other types of lintels shall have: L 3 1/2 x 3 1/2 x 5/16 for each nominal 4" of masonry to a maximum span of 5'-0". L 6 x 3 1/2 x 3/8 LLV for each nominal 4" of masonry to a maximum span of 8'-0". Bear 8" each end unless noted otherwise. DIMENSION LUMBER All foundation sills or plates that rest on masonry or concrete and all wood that is within 6 of finished grade shall be pressure treated wood. Treated sill plates to be bolted to foundation wall with 5/8" anchor 4'-0" o.c. max. to extend 13" minimum into solidly grouted foundation wall. Each sill plate to have a minimum of 2 bolts with one bolt located within 12" of each end of each piece, but not less than 4 from each end. Minimum nailing to be in accordance with Table R602.3(1) of the IRC unless noted otherwise. Exterior walls to have 2 x 6 16" o.c. unless noted otherwise. Interior bearing walls to have 2 x 4 16 o.c. unless noted otherwise. Interior non-load bearing walls to have 2 x 4 16" o.c. unless noted otherwise Typical openings to have a minimum of 2 jack (shoulder) studs and 1 king stud, typical, unless noted otherwise. Wood lintels and headers shall have a minimum 3" length of bearing at each end and bear the entire length of the jack (shoulder) studs. Openings not noted to have headers comprised of 2-2x6 long side vertical and a stud plate top and bottom long side horizontal. Wood joists shall bear the full width of supporting members (stud wall, beams, etc.) unless otherwise noted. All beams and joists not bearing on supporting members shall be framed with "USP" joist hangers or equal. Wood beams made of 2 or more 2x's shall be thru-bolted together with 3/8" round M.B. at 2'-0" o.c. or equivalent spikes. Spacing of bridging for joists shall not exceed 8'-0".

4 Double all joists under parallel partitions unless shown otherwise. All plywood and OSB shall be installed per American Plywood Association standards, including using construction adhesive for fastening to floor joists. All fasteners and hangers in contact with treated lumber shall be G185 hot dipped galvanized or equal. All lumber shall be of good quality and not have large splits and checks and shall be visually inspected by the contractor at the time of construction. All beams shall bear on a minimum of 3 along their length and full along their width. WALL SHEATHING Wall sheathing shall be 1/2 APA rated panels. Provide Exterior or Exposure 1 grade. Panels shall be continuous over two or more spans and long dimension of panel shall be either perpendicular or parallel to supports. Fasten wall sheathing with 8d nails spaced at 6 on center at supported edges and 12 on center at intermediate supports. Leave a 1/8 gap at all end and edge joints to allow for expansion. Stagger end joints of panels. Refer to plan and notes for any special shear wall nailing and bolting conditions. Gypsum sheathing to be min. 1/2" fastened with 6d cooler or wallboard nails at 7" o.c. to all framing members unless noted. ROOF SHEATHING Roof sheathing shall be 5/8 APA rated panels. Rated for spacing of supporting members. A minimum of 32/16 span rating is recommended. Provide panel clips, one between each support, for supports spaced greater than 16 on center. Provide Exterior or Exposure 1 grade. Panels shall be continuous over two or more spans and long dimension of panel shall be perpendicular to supports. Fasten roof sheathing with 8d nails spaced at 6 on center at supported edges and 12 on center at intermediate supports. Leave a 1/8 gap at all end and edge joints to allow for expansion. ENGINEERED LUMBER I-JOISTS I-joist members noted on drawings are engineered laminated veneer lumber with webs and flanges, as manufactured by the Trus-Joist MacMillan Corporation. Alternate at contractors option of equal design properties. Sizes shown on plan are actual. Install web stiffeners, blocking between members, and nail to supporting members as per manufacturers recommendations. LVL WOOD MEMBERS LVL members noted on drawings are engineered laminated veneer lumber as manufactured by the Trus-Joist MacMillan Corporation. Alternate at contractors option of equal member design properties. Sizes shown on plan are actual. WOOD TRUSSES Truss supplier shall notify structural engineer on any proposed revisions made to the layout indicated on this plan. Truss manufacturer shall provide a truss layout and certified truss drawings prior to beginning construction. Live load deflection of roof trusses shall be limited to 1/360 of the span. Live load deflection of floor trusses shall be limited to 1/480 of the span. Truss configuration, pitch, overhang, etc. shall be indicated on the architectural

5 drawings. Spacing of roof and/or floor trusses shall not exceed 24" o.c. Lumber for wood trusses shall be in accordance with manufacturers recommendations. Truss manufacturer to specify if roof sheathing need be applied before placing over-framing. Provide metal framing anchors at truss bearing to mechanically fasten truss to bearing wall or supporting member. Truss manufacturer shall provide truss to truss connection hangers. Bridging, and bracing of truss compression and tension members, shall be installed in accordance with the truss manufacturer's design and directions. Temporarily brace trusses in accordance with manufacturer s recommendations and / or Truss Plate Institute HIB-91. No cutting, notching, or modifications of trusses will be allowed without the manufacturer's written approval. STRUCTURAL STEEL All structural steel shall be designed, fabricated, and erected according to the specifications of the American Institute of Steel Construction (A.I.S.C.) Latest Adoption. Structural steel supplier shall supply all cap plates, bearing assemblies, base plates, stiffeners, splices and connections, and shall design same unless noted on drawings. All welding shall be done by the shielded arc process using E70 electrodes in accordance with the rules of the American Welding Society (A.W.S.) Structural Welding Code, Latest Adoption. All welders shall be certified by the rules of the American Welding Society. OPENINGS Verify size and location of all openings with architectural and mechanical drawings. Openings in floor and roof not shown on structural drawings must be placed between structural members. Cutting and notching which exceeds the limits of the diagram provided on the structural drawings must be approved by the structural engineer.

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. SHED TO BE BUILT AS PER IRC, UBC OR CURRENT LOCAL CODE To the best of my knowledge

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06110 WOOD FRAMING PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But Not Supplied

More information

HOLDOWN & STRAP SCHEDULE

HOLDOWN & STRAP SCHEDULE SHEAR WALL SCHEDULE STRUCTURAL DESIGN CRITERIA GOVERNING CODE SOIL BEARING PRESSURE HOLDOWN & STRAP SCHEDULE MARK SHEATHING SHEATH BOTH SIDES NAILS EDGE SPACING NOTES MARK SW 7/" OSB NO 8d " OC - A SW

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN 30 year dimensional shingles and Metal Verticle siding over structural sheathing. Nailing schedule is " on ends 12" on centers d nails. Trusses are engineered on 24" and framing is 2" x " on 1" centers.

More information

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures Attachment A USG Minimum Design and Construction Requirements for Wood Framed Structures 1. General Design Criteria 1.1. Per Adopted Georgia State Minimum Standard Building Code 1.2. Minimum Live Loads

More information

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION Section R614 Add new section to read as shown: (RB34-06/07) SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION R614.1 General. Structural insulated panel (SIP) walls shall be designed in accordance

More information

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06 1100 WOOD FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

TP: 89'-0" BP: 86'-6 1/4" 2'-0" Typ TP: 89'-0" BP: 86'-6 1/4" 2'-0" Typ S201 TW: 89'-0" TF: 86'-0" S201 TW: 87'-11 1/4" S201 TF: 86'-10 1/4" S201

TP: 89'-0 BP: 86'-6 1/4 2'-0 Typ TP: 89'-0 BP: 86'-6 1/4 2'-0 Typ S201 TW: 89'-0 TF: 86'-0 S201 TW: 87'-11 1/4 S201 TF: 86'-10 1/4 S201 Resource reginc.com 0.. '-" P: '-" 0'-0" " P: '- /" 0'-" '-" '-0" '-0" 0'-0" '-0" '-" '- /" TF: '-0" TW: '-0" TF: '-0" TW: '-0" TF: '-0" TW: '- /" TF: '-" " Typ Sim. P: '-" " TF: '-0" C '- /" '-" Varies

More information

Building Division Informational Handout

Building Division Informational Handout CITY OF SAN JOSÉ, CALIFORNIA Building Division Informational Handout Conventional Light Frame Construction Design Provisions 2007 CBC Handout No. 2-21 Published: 1/1/08 Page 1 of 3 This document summarizes

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05 40 00 COLD-FORMED METAL FRAMING SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the

More information

Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL

Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL Our Company At Murphy Company we take pride in providing our customers with premium quality products and services. Our LVL is manufactured to provide

More information

BUILDING CODES Presented by CORUM ENGINEERING

BUILDING CODES Presented by CORUM ENGINEERING BUILDING CODES Presented by CORUM ENGINEERING AGENDA I. The Basics of Foundations A. Footer Designs B. Foundation Walls 1. Non-Backfilled Walls 2. Backfilled Walls (Retaining Walls) C. Slabs vs. Crawl

More information

Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010)

Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010) 1307 West Lehigh Street Bethlehem, PA 18018 610-866-9663 Office info@keycodes.net www.keycodes.net Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010)

More information

THE FLORIDA BUILDING CODE

THE FLORIDA BUILDING CODE THE FLORIDA BUILDING CODE 1. According to the Florida Building Code, spiral stairway treads must all be identical and rise must be sufficient enough to provide a headroom of minimum. A. 6'- 4" B. 6'- 6"

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. SHED TO BE BUILT AS PER IRC, UBC OR CURRENT LOCAL CODE To the best of my knowledge

More information

Garage/Accessory Structures

Garage/Accessory Structures Garage/Accessory Structures City of New Prague Building Inspections Department 118 Central Ave N New Prague, MN 56071 (952) 758-4401 Fax (952) 758-1149 Requirements for submitted Building Plans Signed

More information

TYPICAL BEARING WALL FRAMING Joints in plates must be offset by 24 min.

TYPICAL BEARING WALL FRAMING Joints in plates must be offset by 24 min. FRAMING TIPS City of Grand Rapids Building Safety Division 218-326-7601 www.grandrapidsmn.org This handout is intended only as a guide and is based in part on the 2007 Minnesota State Building Code, Grand

More information

#G445 Plans, 48'x28' x 10' detached garage with bonus room By SDS-CAD Specialized Design Systems

#G445 Plans, 48'x28' x 10' detached garage with bonus room By SDS-CAD Specialized Design Systems Architectural asphalt shingles and horizontal True Wood 7" Reveal siding over structural panel. Nailing schedule is 6" on ends 12" on centers 6d nails. Trusses are engineered on Bonus attic trusses 24"

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

S001 Structural General Notes and Legend

S001 Structural General Notes and Legend General Notes A. PROJECT INFORMATION. Building Jurisdiction: Summit County, CO. Building Code: IRC 0 B. DESIGN INFORMATION. Load Table: Load e Dead Weight (psf) Dead Load (psf) Superimposed Loads Live

More information

10 EXTREME BASEMENT PANELS

10 EXTREME BASEMENT PANELS 10 EXTREME BASEMENT PANELS On Granular Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions. Soils are classified

More information

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL A. BOLT ANCHOR BOLT L ANGLE (AISC) ARCH. ARCHITECTURAL LBS. POUNDS B.O. BOTTOM OF LL DOUBLE ANGLE (AISC) BCI I-JOIST (BOISE CASCADE) LVL LAMINATED VENEER LUMBER BRG. BEARING MAX. MAXIMUM C CHANNEL (AISC)

More information

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL A. BOLT ANCHOR BOLT L ANGLE (AISC) ARCH. ARCHITECTURAL LBS. POUNDS B.O. BOTTOM OF LL DOUBLE ANGLE (AISC) BCI I-JOIST (BOISE CASCADE) LVL LAMINATED VENEER LUMBER BRG. BEARING MAX. MAXIMUM C CHANNEL (AISC)

More information

MAIN FLOOR PLAN. #G x 14 x 8 Shed - Chicken Coop By SDS-CAD Specialized Design Systems 10'-0" 3'-0" 1'-0" 14'-0" 14'-0" 1'-0" 6'-0" 3'-0"

MAIN FLOOR PLAN. #G x 14 x 8 Shed - Chicken Coop By SDS-CAD Specialized Design Systems 10'-0 3'-0 1'-0 14'-0 14'-0 1'-0 6'-0 3'-0 10'-0" BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. BARN TO BE BUILT AS PER LOCAL CODE REQUIREMENTS 14'-0" BWP BWP BWP ABWP 101

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading CONSTRUCTION TIP SHEET 5 w/ 60 lb Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which update the

More information

Custom 22' x 40' - 16' Tall Garage Plan #g227 By SDS-CAD Specialized Design Systems

Custom 22' x 40' - 16' Tall Garage Plan #g227 By SDS-CAD Specialized Design Systems P O Box 34 Mendon, Utah Custom 22' x 40' - 16' Tall Garage Plan #g22 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical

More information

Abbreviations. Balanced Glue Laminated Beam. Custom Fabricated Saddle Construction Joint (Cold Joint)

Abbreviations. Balanced Glue Laminated Beam. Custom Fabricated Saddle Construction Joint (Cold Joint) General Notes A. PROJECT INFORMATION:. uilding Jurisdiction. uilding Code IRC 0. DESIGN INFORMATION:. Load Table: Load Type Dead Weight (psf) Superimposed Loads Snow Load (psf) Description Dead Load (psf)

More information

WOOD I-JOIST AWARENESS GUIDE

WOOD I-JOIST AWARENESS GUIDE WOOD I-JOIST AWARENESS GUIDE American Wood Council Flange Web Flange American Forest & Paper Association WOOD I-JOIST AWARENESS GUIDE The American Wood Council is part of the wood products group of the

More information

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm

More information

Jackson Crossing Located in Alexandria, VA. Technical Report 1 Michael Bologna

Jackson Crossing Located in Alexandria, VA. Technical Report 1 Michael Bologna Jackson Crossing Located in Alexandria, VA Technical Report 1 Michael Bologna Structural Option Advisor: Dr. Linda Hanagan September 11, 2015 Table of Contents Executive Summary.3 Introduction 4 Purpose..4

More information

The Structural Redesign of Boyds Bear Country and its Related Systems. Boyds Bear Country, Pigeon Forge, Tennessee

The Structural Redesign of Boyds Bear Country and its Related Systems. Boyds Bear Country, Pigeon Forge, Tennessee The Structural Redesign of Boyds Bear Country and its Related Systems Included in this Presentation: Background and Existing System Proposal Problem / Solution Structural System Redesigns Pre-cast Concrete

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN #G389 14' X 24' X 8', Custom detached garage By Page 1 Page 2 Page 3 Page 4 Page BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. GARAGE

More information

TYPICAL BEARING WALL FRAMING

TYPICAL BEARING WALL FRAMING BASIC WOOD FRAMING City of Grand Rapids Building Safety Division 218-326-7601 www.grandrapidsmn.org This handout is intended only as a guide and is based in part on the 2007 Minnesota State Building Code,

More information

Interior Hangers. Application

Interior Hangers. Application Application Interior bridge deck hangers are typically fabricated using two heavy duty sheet metal end clips that have been electrically resistance welded to an appropriate sized wire or formed metal connecting

More information

LPI 56 Technical Guide

LPI 56 Technical Guide LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform

More information

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed

More information

Custom 30 x 48-14' Tall Garage Plan #g226 By SDS-CAD Specialized Design Systems

Custom 30 x 48-14' Tall Garage Plan #g226 By SDS-CAD Specialized Design Systems P O Box 34 Mendon, Utah Custom 30 x 48-14' Tall Garage Plan #g226 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section

More information

O S I N S K I R E S I D E N C E

O S I N S K I R E S I D E N C E O S I N S K I R E S I D E N C E OSINSKI RESIDENCE Drawing Schedule IMPORTANT NOTE ABOUT PLAN LIABILITY: THERE HAS BEEN REASONABLE CARE AND PROFESSIONAL SKILL IN PREPARATION AND EXECUTION OF THESE DOCUMENTS

More information

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E. STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral

More information

THE ASHTON PERSPECTIVE VIEW

THE ASHTON PERSPECTIVE VIEW THE ASHTON PERSPECTIVE VIEW TYPICAL DETAILS GENERAL DESIGN NOTES: 1. THESE DRAWINGS ARE OF A GENERAL NATURE AND ARE NOT INTENDED TO CONVEY THE METHOD OR MEANS OF CONSTRUCTION. IT IS ASSUMED THAT ALL WORK

More information

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued) 2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1

More information

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS 2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS HECO-6 GENERAL Pre-construction conference Preconstruction meeting Scheduled by SI with the Contractor, UBO, A/E, and relevant subs prior to commencement

More information

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,

More information

STRUCTURAL STEEL FRAMING

STRUCTURAL STEEL FRAMING SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical

More information

POST FRAME BUILDING STANDARDS

POST FRAME BUILDING STANDARDS CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 POST FRAME BUILDING STANDARDS 201.3

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building

More information

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete

More information

REINFORCED CONCRETE MASONRY SECTION

REINFORCED CONCRETE MASONRY SECTION SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09 PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

STANDARD RESIDENTIAL DECK DETAILS

STANDARD RESIDENTIAL DECK DETAILS STANDARD RESIDENTIAL DECK DETAILS GUARD DECKING FLASHING OVER LEDGER BOARD EXISTING HOUSE FLOOR CONSTRUCTION GUARD POST ATTACHEMENT LEDGER BOARD ATTACHMENT TO HOUSE RIM JOIST JOIST BEAM FOOTING JOIST TO

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN 12'-0" 4'-6" 3'-0" 4'-6" 3040 14'-0" LADDER LT LINE BUNK CABIN 11'-4" x 13'-4" 14'-0" BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS.

More information

Pulaski County, Virginia Typical Carport Enclosure Details Based on the 2012 International Residential Code

Pulaski County, Virginia Typical Carport Enclosure Details Based on the 2012 International Residential Code Pulaski County, Virginia Typical Carport Enclosure Details Based on the 2012 International Residential Code Carports enclosed into one-story garages or living spaces must be constructed in conformance

More information

Residential Deck Guide

Residential Deck Guide Residential Deck Guide The text and illustrations included in this guide represent opinions of the Borough of Mechanicsburg Codes and Zoning Department. This guide is for educational and information purposes

More information

City of Republic Community Development Girder and Header Spans for Exterior Walls

City of Republic Community Development Girder and Header Spans for Exterior Walls City of Republic Community Development Girder and Header Spans for Exterior Walls Revision Date: January 2017 2012 IRC Table R502.5(1) Girder Spans a and Header Spans a for Exterior Bearing Walls (Maximum

More information

4 EXTREME FOUNDATION PANELS

4 EXTREME FOUNDATION PANELS 4 EXTREME FOUNDATION PANELS For House Crawl Space On Concrete Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions.

More information

SECTION COLD-FORMED METAL TRUSSES

SECTION COLD-FORMED METAL TRUSSES SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Framing Methods Structural Components

Framing Methods Structural Components Framing Methods Structural Components Balloon Framing *Balloon framing or Eastern framing the exterior studs run from the top of the foundation to the top of the highest level. Benefits of this type of

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

30 X 40 POLE BARN 12 HIGH SIDE WALLS 2-12 WIDE X 10 HIGH SECTIONAL GARAGE DOORS OPTIONAL WINDOWS DETAILS INCLUDED

30 X 40 POLE BARN 12 HIGH SIDE WALLS 2-12 WIDE X 10 HIGH SECTIONAL GARAGE DOORS OPTIONAL WINDOWS DETAILS INCLUDED 30 X 40 POLE BARN 12 HIGH SIDE WALLS 2-12 WIDE X 10 HIGH SECTIONAL GARAGE DOORS OPTIONAL WINDOWS DETAILS INCLUDED 3 ENTRY DOOR METAL ROOF METAL SIDING GABLE ROOF, 4/12 PITCH INDEX PAGE DESCRIPTION 1 FRONT

More information

FIGURE R502.2 FLOOR CONSTRUCTION

FIGURE R502.2 FLOOR CONSTRUCTION CHAPTER 5 FLOORS 11 I SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces

More information

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS Code Reference: Chapter 97, Code of Public Local Laws and Ordinances of Carroll County and The International

More information

Elevation "L" ASTOR II DESIGN CRITERIA: 2012 International Residential Code with Georgia Amendments

Elevation L ASTOR II DESIGN CRITERIA: 2012 International Residential Code with Georgia Amendments REVISION CHANGES: REV. NO. REV. DATE C COPYRIGHT 2014 TAYLOR MORRISON --- THESE DRAWINGS AND ITS REPRODUCTIONS ARE THE PROPERTY OF taylor morrison AND MAY NOT BE REPRODUCED, PUBLISHED OR USED IN ANY WAY

More information

CHAPTER 5 FLOORS SECTION R501

CHAPTER 5 FLOORS SECTION R501 CHAPTER 5 FLOORS SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces used

More information

Thesis Proposal Structural Redesign / Cost, Schedule and Coordination Analysis / Architectural Impact

Thesis Proposal Structural Redesign / Cost, Schedule and Coordination Analysis / Architectural Impact Thesis Proposal Structural Redesign / Cost, Schedule and Coordination Analysis / Architectural Impact Executive Summary:, located in Pigeon Forge, Tennessee, is designed as a multifunctional space and

More information

Elevation "L" CHELSEA II DESIGN CRITERIA: 2012 International Residential Code with Georgia Amendments

Elevation L CHELSEA II DESIGN CRITERIA: 2012 International Residential Code with Georgia Amendments REVISION CHANGES: REV. NO. REV. DATE C COPYRIGHT 2014 TAYLOR MORRISON --- THESE DRAWINGS AND ITS REPRODUCTIONS ARE THE PROPERTY OF taylor morrison AND MAY NOT BE REPRODUCED, PUBLISHED OR USED IN ANY WAY

More information

PROJECT: 4/30/14 DATE: REVISIONS: 6/10/14 7/28/14 11/3/14 11/12/14 11/14/14 OF 6

PROJECT: 4/30/14 DATE: REVISIONS: 6/10/14 7/28/14 11/3/14 11/12/14 11/14/14 OF 6 4/30/14 C 7/31/2014 4'-6" RAMP TO EXISTING GRADE DRAWN: JW 11/12/2014 AS REQ'D 7'-10 1/2" 7'-10 1/2" 7'-10 1/2" 7'-10 1/2" 2'-0 1/2" 4'-10 1/2" 6" 3'-10" 3'-8" L2X2X1/8 @ 16" OC (TYP) L2X2X1/8 @ 16"

More information

PRESENTATION PLAN A MODEL COMPARISON FLOOR CONSTRUCTION

PRESENTATION PLAN A MODEL COMPARISON FLOOR CONSTRUCTION PRESENTATION PLAN A MODEL COMPARISON FLOOR CONSTRUCTION An overview of costing strategies for wood framed construction elements CREATING A PROJECT ENDLESS POSSIBILITIES COMPATORS LIST A FLOOR Cast in Place

More information

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647.

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647. 4 12 Pitch Cement board siding 7" Lap 4" Corner boards Vertical Cedar T&G Siding 4" Window and Door Trim (Street facing facade) P.T. 6x6 : Wrapped & collared with cement board Trim. Stone Veneer on Garage

More information

DECK PERMIT APPLICATION

DECK PERMIT APPLICATION DECK PERMIT APPLICATION APPLICANT S INFORMATION Name: Company Name: Current address: City: State: ZIP Code: Phone: Email: PROPERTY OWNER S INFORMATION Name: Property Address: Phone: E-mail: City: State:

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

2.2E Parallam PSL Deep Beam

2.2E Parallam PSL Deep Beam #TJ-7001 SPECIFIER S GUIDE 2.2E Parallam PSL Deep Beam Featuring 20" 24" Deep Trus Joist Parallam PSL Beams Ideal for multi-family and light commercial applications Offers high strength and consistent

More information

Product Guide Specification

Product Guide Specification Norplex-Micarta October 2007 665 Lybrand Street Postville, Iowa 52162 Toll Free (800) 568-8108 Phone (817) 329-6191 Fax (817) 421-4208 Website www.stormblocker.com E-mail support@stormblocker.com Product

More information

FACT SHEET #2 DECK INFORMATION

FACT SHEET #2 DECK INFORMATION Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 FACT SHEET #2 DECK INFORMATION BACKGROUND The provisions of the PAUCC. ICC Property Maintenance

More information

Custom 24 x 26 Garage Plan Roy Hartmann Plan #g218 By SDS-CAD Specialized Design Systems CLIENT

Custom 24 x 26 Garage Plan Roy Hartmann Plan #g218 By SDS-CAD Specialized Design Systems CLIENT P O Box 34 Mendon, Utah Custom 24 x 26 Garage Plan Plan #g218 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section

More information

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016 Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016 SBCA has been the voice of the structural building components industry since 1983,

More information

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA Structural Analysis Overview: During the structural analysis of the in Lancaster, Pa, a redesign of the lateral and gravity system from masonry bearing and shear walls to a staggered truss system was performed.

More information

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647.

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647. 10" Belly Band Cement board shake siding Cement board siding 7" Lap Decorative Corbels Cement board siding 7" Lap 4" Corner boards Stone Veneer on Garage wings 48" high 4" Window and Door Trim (Street

More information

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831)

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831) County of Santa Cruz PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA 95060 (831) 4542580 FA: (831) 4542131 STATEMENT OF SPECIAL INSPECTIONS California Building Code 1704.3 Prior to issuance,

More information

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:

1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated: SECTION 04220 CONCRETE UNIT MASONRY PART 1 - GENERAL 1.01 SCOPE: A. The CONTRACTOR shall furnish all labor, materials and equipment necessary for the masonry construction as shown on the drawings or as

More information

SECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES

SECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES SECTION 05440- PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section includes pre-engineered, pre-fabricated cold formed steel framing elements. Work includes:

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code LEGACY REPORT ER-4203 Reissued June 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office #

More information

CHAPTER 5 FLOORS SECTION R501

CHAPTER 5 FLOORS SECTION R501 CHAPTER 5 FLOORS SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces used

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05.40.00 COLD-FORMED METAL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cold-formed metal framing for: B. Exterior load-bearing steel stud walls. 1. Interior load-bearing steel stud walls. 2.

More information

Left Elevation. Front Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,842. Scale : 1/4" = 1'

Left Elevation. Front Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,842. Scale : 1/4 = 1' Plan Name 4 4" Window and door trim. (Street facing facades) 4" Corner Boards 4" Vertical Cedar Siding Left Elevation Lap siding over approved building wrap over 1 2" OSB sheathing. Front Elevation Stone

More information

SECTION (formerly 05425) PRE-ENGINEERED, PRE-FABRICATED COLD-FORMED STEEL ROOF & FLOOR TRUSSES

SECTION (formerly 05425) PRE-ENGINEERED, PRE-FABRICATED COLD-FORMED STEEL ROOF & FLOOR TRUSSES SECTION 05 44 00 (formerly 05425) PRE-ENGINEERED, PRE-FABRICATED COLD-FORMED STEEL ROOF & FLOOR TRUSSES PART 1 GENERAL 1.1 SUMMARY A. Section includes pre-engineered, pre-fabricated cold-formed steel framing

More information

A. Product Data: For each type of cold-formed steel framing product and accessory.

A. Product Data: For each type of cold-formed steel framing product and accessory. SECTION 05400 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior non-load-bearing wall framing. 1.2 ACTION SUBMITTALS A. Product Data: For each type of cold-formed

More information

R Code and Commentary for 2012 NC Residential Code final 03/06/13

R Code and Commentary for 2012 NC Residential Code final 03/06/13 R602.10 Code and Commentary for 2012 NC Residential Code final 03/06/13 Commentary italicized and printed in red 1. Section R602.10 -- provides charging language for two simplified bracing approaches (isolated

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY 2009 prepared by N. A. JACOBSEN, P.Eng. CIVIL ENGINEERING CONSULTANT Whitehorse, Yukon ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY

More information