1 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract including general and supplementary conditions and specifications section apply to this section. B. Related Sections: The following sections contain requirements that relate to this section: 1. Section Hydronic Piping. 2. Section Hydronic Pumps. 3. Section HVAC Water Treatment. 4. Section Domestic Water Piping. 5. Section Domestic Water Piping Specialties. 6. Section Sanitary Waste and Vent Piping. 7. Section HVAC Insulation. 8. Section Mechanical Identification. 9. Section Motors and Variable Frequency Drives. 1.2 SUMMARY A. Cooling tower fill, distribution piping, drift eliminators and fan motor (concrete cooling tower structure). 1.3 REFERENCES A. ASME PTC 23 Atmospheric Water Cooling Equipment B. Cooling Tower Institute (CTI) ATC 105 Acceptance Test Code for Water Cooling Towers. C. Cooling Tower Institute (CTI) - Certification Standard STD SUBMITTALS A. Submit product data indicating rated capacities, dimensions, weights and point loadings, accessories, required clearances, electrical requirements and wiring diagrams, and location and size of field connections. B. Submit manufacturer s installation instructions. 1.5 OPERATION AND MAINTENANCE DATA A. Include start-up instructions, maintenance data, parts lists, controls, and accessories. 1.6 DELIVERY, STORAGE AND HANDLING A. Field assemble entire unit. Contractor shall field verify access to new tower enclosure prior to bid. Page 1 of 5
2 B. Comply with manufacturer s installation for rigging, unloading and transporting material. 1.7 WARRANTY A. Warranty: Include coverage for cooling tower package for one year from Date of Substantial Completion. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Any of the following manufacturers may be used in the base bid. 1. Marley Cooling Technologies. 2. Tower Engineering, Inc. 2.2 GENERAL A. Provide material equipment and appurtenances required for a complete counter-flow, induced draft cooling tower assembly as detailed and scheduled on the drawings. The cooling tower shall include fill, fill support lintels, drift eliminators, fan assemblies, speed reducers, fan drives, water distribution system and all other materials and parts required to make the cooling tower complete. B. It is the intention of this specification to cover the basin construction requirements for the following type of cooling tower and provide a fireproof, permanent type cooling tower having aesthetics and life expectancy in keeping with the total project concept, one with full thermal efficiency throughout its life to afford minimum operating costs and minimum maintenance expense. C. The cooling tower furnished shall be a regularly cataloged product of a Cooling Tower Manufacturer who has produced towers which have seen at least ten (10) years of satisfactory service using the manufacturer and type of fill material and other components proposed for this project. Under no circumstances will wood, plastic, metal, cement asbestos or asbestos fill material be considered. D. Cooling tower cell shall cool 6,000 GPM of water from 95 F HWT to 85 F CWT when operating at the design inlet wet bulb temperature of 77.6 F. E. Upon completion, the Tower Manufacturer shall issue a written guarantee, duly signed, covering the following components. Should any of these components fail during the specified time, they will be replaced F.O.B. Shipping Point. 1. The fill and fill support lintels shall be guaranteed against un-serviceability for a period of twenty-five (25) years. 2. The remaining internal components shall carry the Manufacturer s standard warranty of one (1) year of service or eighteen (18) months from the date of shipment, whichever is first. All warranties are predicated on installation, maintenance and operation in accordance with Page 2 of 5
3 the Tower Manufacturer s published instructions. The Tower Manufacturer s obligation under the warranty is limited to replacing or repairing all items F.O.B. Shipping Point. F. The cooling tower shall be constructed where indicated on the Drawings. The Cooling Tower Manufacturer shall take these space limitations into consideration for the various designs required, including water cooling capacity and performance, fan air handling and the motor brake horsepower requirements. 2.3 COMPONENTS A. Lintels The tile support lintels shall be fabricated from cast iron or corrugated fiberglass reinforced vinyl ester resin and shall be capable of withstanding a load of 400 lbs. per linear foot based on a 6 foot span with a safety factor of 3. The lintels shall be cut and installed to fit snug against the tower walls to minimize any shifting of tile during a seismic event. B. Tile Fill The fill shall be of multi-cell design set without mortar in a pattern and shall be of sufficient height to meet the performance specifications. The tile fill shall be hard burned clay with an average of 3% with no sample exceeding 4% water absorption such that it will pass a freeze-thaw conducted in accordance with ASTM C-67. Further, the tile fill shall have a minimum crushing strength of 2,000 psi over the gross area of the tile when the load is applied parallel to the cell(s) as tested in accordance with ASTM C-67. C. Drift Eliminators Cellular 3-pass PVC type, 10 mil minimum sheet thickness with 25 mil minimum PVC stiffeners, UV protected PVC type, capable of supporting weight of maintenance workers without damage to the top surface. Supports shall be of corrugated FRP structural shapes sufficiently sized and spaced to permit a loading of 50 lbs/ft 2 and shall be suspended from 5/16 inch diameter (minimum) brass or stainless steel rods connected to stainless steel embeds in the underside of the roof deck (see Section 3.1) Drift eliminators supported on the hot water distribution piping will not be permitted. Allowable drift shall be limited to 0.001% of circulating water flow. Mist eliminators shall have a flame spread rating of 15 or less when tested in accordance with ASTM E84. Provide a framed stainless steel access door for passage through eliminators to fill. Provide a 24-inch wide FRP grating maintenance walkway form access opening to the center of each cell and an HDG maintenance access form walkway to gearbox. D. Speed Reducers Shall match existing Amarillo units with speed reducer gears rated in accordance with practices of the American Gear Manufacturers Association using a Service Factor of 2.0 minimum for cooling tower services. These shall be in accordance with CTI STD-111. The gear reducers shall be of the spiral bevel type, double-reduction type. The gear reducer shall be bolted on a galvanized steel base plate and bolted and grouted to the structure. A vibration switch shall be supplied to protect the mechanical equipment against excessive damage due to a malfunction of the rotating members. The vibration switch shall be mounted near the gear reducer. The vibration switch shall automatically provide a 15 second time delay upon fan start-up to prevent false shutdown. The switch shall be a PMC Beta Model 440S. An oil level switch shall be provided by the Cooling Tower Manufacturer to provide protection against sudden loss of oil or low oil level in the gear reducer. Electrical connection and wiring of the vibration switch, and oil level switch in series with the control Page 3 of 5
4 circuit of the cooling tower motor magnetic starter shall be provided under Division 16. A stainless steel oil level sight glass, fill/drain line and vent line shall be installed terminating outside the fan stack. Drive shall be suitable for continuous operation at one-third maximum speed. E. Fan Assembly Shall match existing Hudson, 7-bladed fans. The complete fan assembly (the fan and mounting) shall be designed to give maximum fan efficiency and long life when handling saturated air at high velocities. The fan shall be of a multi-blade design. The fan blades shall be fiberglass reinforced resin system. F. Drive Connection The drive shaft shall be the full floating type with flexible couplings at both ends. The drive shaft shall be of composite design and shall eliminate the need for an intermediate pillow block bearing and shall be fitted on each end with flexible stainless steel plate type couplings. Each drive shaft coupling shall be provided with a galvanized steel guard to prevent damage to the surrounding equipment in case of shaft failure. G. Motor The motor shall be Premium efficiency, NEMA rated and shall be of the TEFC type with a Service Factor of 1.0 and with Class B insulation. The motor horsepower shall be of the next larger standard motor size than that calculated as required for the individual fan brake horsepower and shall be 3-phase, 60 Hertz, 460 Volt continuous duty type with normal starting torque. This motor shall be 100 horsepower, single-speed. Motor shall be Reliance brand XEX type. The fan drive motor and base plate shall be supplied and installed by the Cooling Tower Manufacturer, bolted and grouted to the structure after final adjustments. H. Distribution System Piping shall be schedule 40 PVC. The fittings and nozzles are PVC or ABS. The distribution system shall match the systems in the existing operational ceramic cooling tower cells, in design, layout, number of nozzles, type of nozzles, and required pump head, in order to allow for balancing of the five tower cells with the use of a common inlet header. The pump head, including static lift and dynamic head, shall not exceed 22-0 when measured from the interface flange located 6 below the top of the fill support beam up and through the nozzles. The distribution piping, including spray nozzles, pipe and fittings, shall be supplied complete to flange face located at a point 6 below the top of the fill support beam. I. Fan Deck The fan deck shall be constructed of poured-in-place monolithic concrete by the General Contractor, forming a rigid base for mounting the fan, speed reduction coupling/drive shaft and motor. Grout after final alignment. J. Exhaust Fan Stack The exhaust fan stack shall be constructed of poured-in-place monolithic concrete by the General Contractor. An aluminum fan screen shall be furnished by the tower manufacturer over the fan stack. K. Tower Access A hot dip galvanized steel access door hall be provided for roof deck access. Ladder rungs cast in concrete shall be provided by The General Contractor and coordinated with the Cooling Tower Manufacturer. PART 3 EXECUTION Page 4 of 5
5 3.1 INSTALLATION A. Install in accordance with manufacturer s instructions. B. Install tower on view structural supports. C. Connect condenser water piping with flanged connections to tower. 3.2 FIELD QUALITY CONTROL A. Test under actual operating conditions and verify specified performance. 3.3 MANUFACTURER S FIELD SERVICES A. Prepare and start systems under provisions of General Conditions. B. Inspect tower after installation after installation and submit written report prior to start-up, verifying installation is in accordance with specifications and manufacturer s recommendations. C. Train Owner s maintenance staff in tower operation and maintenance. Provide seven (7) days notice prior to schedule training. END OF SECTION Page 5 of 5
Lenntech. Tel Fax / Marley MS Cooling Tower /
Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 / Marley MS Cooling Tower / SPX COOLING TECHNOLOGIES SPX Cooling Technologies has worldwide recognition as the pacesetter
More informationCooling Tower Depot, Inc. 651 Corporate Circle, Suite 206 Golden, CO Phone (720) Fax: (720)
CTD Proposal : - Project: Project Location: Cooling Tower Design Conditions and Dimensions: Water Flow Rate (gpm) 0 CTD Model # Hot Water Temp (F) 0 Cell Dimensions (ft) L x W x H Cold Water Temp (F) 0
More informationCooling Tower Depot, Inc. 651 Corporate Circle, Suite 206 Golden, CO Phone (720) Fax: (720)
CTD Proposal : - Project: Project Location: Cooling Tower Design Conditions and Dimensions: Water Flow Rate (gpm) 0 CTD Model # Hot Water Temp (F) 0 Cell Dimensions (ft) L x W x H Cold Water Temp (F) 0
More informationSECTION COOLING TOWER
PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue
More informationThe following document can be provided to an Engineer, Contractor, or Owner to allow them to
MESAN series MXL Engineering Guide Specifications The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXL series Cooling Towers. 15XXX-
More information.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.
Issued 2005/05/16 Section 15641 Cooling Towers Induced Draft Crossflow Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationThe following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXR-KM series Cooling Towers.
MESAN MXR-KM Engineering Guide Specifications The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXR-KM series Cooling Towers. 15XXX-
More informationTM Series Induced Draft Cooling Tower Specifications
Delta Cooling Towers, Inc. 41 Pine Street P.O. Box 315 Rockaway, New Jersey 07866-0315 Telephone 973.586.2201 Fax 973.586.2243 www.deltacooling.com sales@deltacooling.com TM Series Induced Draft Cooling
More informationPREMIER Low Profile Induced Draft Cooling Tower Specifications
Fa Delta Cooling Towers, Inc. 185 US Highway 206 Roxbury Township, NJ 07836 973.586.2201 973.586.2243 fax www.deltacooling.com sales@deltacooling.com PREMIER Low Profile Induced Draft Cooling Tower Specifications
More informationFXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2
- C 1 Product Detail Engineering Data Models... C2 Structural Support Models... C6 Engineering Specifications... C8 - C 2 Engineering Data Models REMARK: Do not use for construction. Refer to factory certified
More informationA. Operation and Maintenance Data: For pumps and controls, to include in operation and maintenance manuals.
Page 221429-1 SECTION 221429 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationB. Wiring Diagrams: For power, signal, and control wiring.
Page 221429-1 SECTION 221429 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationFiberglass Cooling Towers
Fiberglass Cooling Towers Available in sizes from 100 to 240 tons. FC Series 700 Fiberglass Cooling Tower Available in sizes from 170 to 240 tons. No other fiberglass cooling tower comes with as many high-quality
More informationSECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT
SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationWater headers are made of reinforced plastic and the design of the spray tree ensures uniform water distribution.
COOLING TOWERS Main features of CT series cooling towers Standard Modural design Towers are constructed of standardized panels fabricated from heavy gauge hot-dip galvanized steel. Final assembly is made
More informationPioneer Forced Draft Cooling Tower Specifications
Delta Cooling Towers, Inc. 41 Pine Street P.O. Box 315 Rockaway, New Jersey 07866-0315 Telephone 973.586.2201 Fax 973.586.2243 www.deltacooling.com sales@deltacooling.com Pioneer Forced Draft Cooling Tower
More informationACF SERIES COUNTER FLOW COOLING TOWER ENGINEERING DATA
ICAN AMER G COOLIN C. IN R E TOW ACF SERIES COUNTER FLOW COOLING TOWER ENGINEERING DATA ACF SERIES FEATURES OVERVIEW The ACF series induced draft counter flow cooling tower is American Cooling Tower's
More informationTM Series Cooling Tower Specification
1.0 Cooling Tower TM Series Cooling Tower Specification 1.1 General: Furnish and install factory-assembled, induced draft, counterflow cooling tower(s) with vertical air discharge conforming in all aspects
More informationPioneer Forced Draft Cooling Tower Specifications
Delta Cooling Towers, Inc. 185 US Highway 206 Roxbury Township, NJ 07836 973.586.2201 973.586.2243 fax www.deltacooling.com sales@deltacooling.com Pioneer Forced Draft Cooling Tower Specifications Pioneer
More informationSECTION PLUMBING PIPING SYSTEM
SECTION 15410 - PLUMBING PIPING SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, are a part of this Section. 1.02 SUMMARY
More informationAMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL
AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER 1. Preface OPERATIONS AND MAINTAINENCE MANUAL 1-800-444-8693 Operation and Maintenance Manual For Amcot LRC-H Cooling Tower & LRC-LNS
More informationSECTION PACKAGE BOOSTER PUMP STATIONS
SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to
More informationQuadraFlow cooling tower
QuadraFlow cooling tower A Truly Unique Cooling Tower Design The QuadraFlow is a unique cooling tower. Unique in its design unique in its appearance unique in its performance reliability in all seasons
More informationCentral Station Air Handler Specification
Central Station Air Handler Specification PART 1: GENERAL 1.01 WORK INCLUDED (Model CS 3 ) Mechanical Specification A. Provide complete air handling unit(s) suitable for indoor installation. Contractor
More information2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps.
PART 1: GENERAL 1.01 Purpose: A. The design guidelines contained herein includes the requirements for pumps utilized for plumbing systems at Texas State University. It is the intention of this document
More informationSUGGESTED SPECIFICATIONS Pump Frames through 64132
TYPE HBB - HORIZONTAL SOLIDS-HANDLING WASTEWATER PUMPS Pump Frames 44081 through 64132 GENERAL Furnish and install Horizontal Flexible Coupled Dry Pit Pumping Units complete with all accessories and appurtenances
More informationSECTION AIR TERMINAL UNITS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationACX Series Cross Flow Induced Draft Cooling Towers
ACX Series Cross Flow Induced Draft Cooling Towers Engineering Data. AMERICAN COOLING TOWER INC. Components & Features Overview The ACX series induced draft cross flow cooling tower, manufactured by American
More informationA. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems:
SECTION 221429 - SUMP PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationIMT Open Cooling Towers... B78. Benefits... B80. Construction Details... B82. Custom Features and Options... B83. Accessories...
- B 77 Product Detail... B78 Benefits... B80 Construction Details... B82 Custom Features and Options... B83 Accessories... B85 Engineering Data... B86 Structural Support... B89 Engineering Specifications...
More informationB. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationSECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED
SECTION 08350 ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationRAOUL WALLENBERG HIGH SCHOOL SECURITY COILING GRILLE SFUSD PROJECT NO SAN FRANCISCO UNIFIED SCHOOL DISTRICT SECTION 08330
SECTION 08330 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Provide all labor, materials, necessary equipment, services and included but limited to all related work to complete security coiling grille
More informationSECTION FUEL-FIRED UNIT HEATERS
SECTION 23 55 33 PART 1 - GENERAL 1.1 DESCRIPTION A. This Section includes gas-fired unit heaters. SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable
More informationSECTION SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM
SECTION 13 1100 SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as
More information/ Marley Series 10 Series 15 Cooling Tower /
/ Marley Series 10 Series 15 Cooling Tower / / The Marley Difference / Series 10 and Series 15 cooling towers are field constructed, splash fill, crossflow wood cooling towers, designed to serve all normal
More informationSERIES COOLING TOWER 300, 400, 500 & 600 CLASS DIRTY WATER HIGH TEMPERATURE DURABILITY. Heavy Duty Crossflow Splash Filled Type
TWI SERIES COOLING TOWER 300, 00, 00 & 00 CLASS Heavy Duty Crossflow Splash Filled Type DIRTY WATER HIGH TEMPERATURE DURABILITY TWI SERIES FEATURES TWI Series Industrial Cooling Towers are specifically
More informationSERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS
SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,
More informationSECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT
SECTION 11322 MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT PART 1 GENERAL 1.01 SCOPE There shall be furnished ( ) Grit Separator Mechanism(s) suitable for installation in (a) concrete tank(s) -ft.
More informationSUGGESTED SPECIFICATIONS
SUGGESTED SPECIFICATIONS SERIES 3000 SUSPENDED, SCREENED WET-PIT PUMPS PART 1 GENERAL 1.1 DESCRIPTION Work Included: Under this section, the contractor shall provide all labor, equipment and material necessary
More informationSECTION ROTARY SCREW WATER CHILLERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING
SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationDIVISION 33 UTILITIES SECTION PACKAGED SEWAGE GRINDER PUMPING UNITS
DIVISION 33 UTILITIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: The work specified in this Section consists of providing an Environmental One grinder pump(s) unit with tank, internal piping and
More informationSECTION FENCING. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.
SECTION 323100 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting
More informationThe motor shall be high-starting torque, ball bearing, rated at 460 V, 3 phase
MODEL 41 ELECTRIC FOUR FOLD DOORS Guide Specification Template INSTRUCTIONS FOR USE EPD has provided this PDF guide template to assist in your development of an accurate document for use in specifying
More informationCOOLING TECHNOLOGY INSTITUTE
PAPER NO: TP08-16 CATEGORY: DRY COOLING COOLING TECHNOLOGY INSTITUTE THE COST OF NOISE ROBERT GIAMMARUTI HUDSON PRODUCTS CORPORATION JESS SEAWELL COMPOSITE COOLING SOLUTIONS, LLC The studies and conclusions
More informationJAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION
JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION PART 1 - GENERAL 1.1 APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification
More informationPrice Fan Powered Terminal Units
Price Fan Powered Terminal Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 3600 Air Terminal Units The following specification is for a defined application. Price would be pleased
More informationSECTION ALUMINUM GATES
P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,
More informationSECTION VIBRATION ISOLATION
SECTION 15240 VIBRATION ISOLATION PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15450 - Plumbing Equipment. 2. 15510 - Piping (HVAC). 3. 15515 Valves, Hangers, and Specialties. 4. 15540 - Pumping
More informationSECTION ROOF ACCESSORIES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 72 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter
More informationVSS S U B M E R S I B L E S E W A G E P U M P S
7 2 9 8 / 2 3 HP % % 64% 7 5 HP HP 5 HP % % C u r v e P a g e V S S - 4 5 R P M M O D E L : V S S - 4 E I M P E L L E R : V S A - 4 C - 2-5 A l s o a p p l i e s t o V S S - 5 E & V S S - 6 E 7 7 65 55
More informationSUPPORT AND ANCHORS SECTION 15090
SUPPORT AND ANCHORS SECTION 15090 PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. Work included in this Section: Materials, equipment, fabrication, installation and tests in conformity with applicable codes
More informationFXT Open Cooling Towers... B46. Benefits... B48. Construction Details... B49. Custom Features and Options... B50. Accessories...
B 45 Product Detail... B46 Benefits... B48 Construction Details... B49 Custom Features and Options... B Accessories... B51 Engineering Data... B52 Structural Support... B54 Engineering Specifications...
More informationASSE International Product (Seal) Listing Program. ASSE Outdoor Enclosures for Fluid Conveying Components
ASSE International Product (Seal) Listing Program ASSE 1060-2017 Outdoor Enclosures for Fluid Conveying Components Manufacturer: Contact Person: E-mail: Address: Laboratory: Laboratory File Number: Model
More informationC. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationOAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COOLING TOWERS
SECTION 23 65 00 PART 1 GENERAL 1.1 SUMMARY A. Section includes packaged, induced-draft, crossflow cooling tower, including but not limited to: 1. Structure, casing, walls, and fan deck. 2. Fan shroud.
More informationThis guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.
SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial
More informationSECTION SUBMERSIBLE GRINDER PUMPS FOR WASTEWATER (LESS THAN 10 HORSEPOWER)
SECTION SUBMERSIBLE GRINDER PUMPS FOR WASTEWATER (LESS THAN 10 HORSEPOWER) 1. DESCRIPTION This specification shall govern all work necessary for furnishing, installing, and placing into operation, heavy
More informationSECTION HEAT TRACING FOR PLUMBING PIPING
SECTION 22 05 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB #
SECTION 26 0529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationDIVISION 15- MECHANICAL Section Fire Pumps
DIVISION 15- MECHANICAL Section 15320 Fire Pumps 1.00 PART 1 -GENERAL 1.01 DESCRIPTION OF WORK: A. Provide pumps for fire suppression. 1.02 SECTION INCLUDES: A. Vertical Turbine Fire Pump RELATED DOCUMENTS:
More informationC. Concrete Inertia Bases: Drawings showing required concrete steel reinforcing, construction details, and dimensions.
15240 VIBRATION ISOLATION ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 230548 An optional keynote
More informationPolycrete Big Block Standard Specification
Polycrete Big Block Standard Specification SECTION 03 11 19 INSULATED CONCRETE FORMING 10/13 PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent
More informationSECTION HEAT TRACING FOR PLUMBING PIPING
SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not
More informationFiberglass Crossflow Field-Erected Cooling Towers
Composite Cooling Solutions (CCS) is a custom cooling tower solutions provider specializing in the design and build of field-erected fiberglass and concrete cooling towers. Our exclusive tower structure
More informationCompass Series Open Cooling Towers BAC AUSTRALIA
Compass Series Open Cooling Towers BAC AUSTRALIA Compass Series Benefits Baltimore Aircoil Company (BAC) is the world s largest and leading supplier of evaporative heat transfer and thermal energy management
More informationINDUCED-DRAFT TWIN CROSSED-FLOW COOLING TOWER
Capacity: 2 to 1,393 tons (5 to 4,179 GPM @ 95 F/ 85 F / 78 F) Available in galvanized, epoxy-coated galvanized for marine environment, and stainless steel Low-cost installation and operation Low sound
More informationSECTION HVAC PUMPS. A. Provide centrifugal HVAC pumps, called for in drawing schedule, and as needed for a complete and proper installation.
PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 15540 HVAC PUMPS A. Provide centrifugal HVAC pumps, called for in drawing schedule, and as needed for a complete and proper installation. B. Provide variable
More informationA. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.
SECTION 10530 - EXTRUDED ALUMINUM WALKWAY COVERS PART I - GENERAL.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division
More informationFRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Architectural Decking panels and Fabrications REVISED 11.
FRP Specifications Section 06 73 13 Fiberglass Reinforced Polymer (FRP) Architectural Decking panels and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA
More informationOXF-30K INDUCED DRAUGHT CROSSFLOW FRP COOLING TOWER
SERIES OXF-30K INDUCED DRAUGHT CROSSFLOW FRP COOLING TOWER www.paharpur.com FEATURES OF OXF-30K 5 1 2 3 4 UNIQUE OCTAGONAL CROSSFLOW DESIGN The Paharpur Series OXF-30K is certified for thermal performance
More informationFXV Closed Circuit Cooling Tower Specification
FXV Closed Circuit Cooling Tower Specification 1.0 Closed Circuit Cooling Tower 1.1 General: Furnish and install, as shown on the plans, factory-assembled closed circuit cooling tower(s) of induced draft
More informationFranklin Hall Renovation TABLE OF Document Indiana University Bloomington
VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...
More informationt y p e V S A S E W A G E P U M P
Pe r fo r m a n ce C h a r t 65 6 55 45 4 35 3 25 2 12 11 1 / 2 11 1 1 / 2 1 9 1 / 2 6% 7% 76% 7 1 HP 1/2 HP HP 76% 7% 6% C u r v e P a g e V S A - 5 1 1 5 R P M M O D E L : V S A - 6 H D I S C H A R G
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationNORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS
PART 1 GENERAL 1.01 SUMMARY Section 15140 PIPE HANGERS, This Section includes the furnishing and subsequent installation of: A. Pipe and equipment hangers, supports, and associated anchors B. Equipment
More informationVSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING
Flows to 200 GPM. TDH to 95 Feet at 1750 RPM Free Standing or Guide Rail Design. Available in Standard Submersible or Explosion Proof Design. Provided with 25 feet of submersible motor power cable. Cast
More informationWilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps. Engineering Specification
Wilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps Engineering Specification PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install horizontal multi-stage, high pressure, self priming pressure
More informationDELTA. Cooling Towers, Inc. Delta Cooling Towers. Leader in Non-Corrosive Cooling Tower Technology
DELTA Delta Cooling Towers Leader in Non-Corrosive Cooling Tower Technology PIONEER DELTA Forced Draft, Counter Flow Design 10-100 Ton Single Modules Pioneer cooling towers are forced draft counter flow
More informationVANGUARD Packed Column Air Stripping Tower Specifications
. 185 US Highway 206 Roxbury Township, NJ 07866-0315 Telephone 973.586.2201 Fax 973.586.2243 www.deltacooling.com sales@deltacooling.com VANGUARD Packed Column Air Stripping Tower Specifications VANGUARD
More informationIncinerator Systems NFPA 82 Inspection Form
Incinerator Systems NFPA 82 Inspection Form PART 1 INCINERATORS DESIGN AND AUXILIARY FUEL ELECTRICAL SUPPLY AIR FOR COMBUSTION AND VENTILATION SPARK ARRESTERS 1. Are gas-burning installations designed
More information1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.
PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More information1. Revision: The bid date has been postponed to July 18, 2012 at 1:30 PM.
East Energy Chiller 1 Cooling Tower Addition State Project Number H27-1969 Addendum Three July 12, 2012 NOTE: The following amendments, additions, and deletions shall be made to the Construction Documents
More informationPRODUCT SPECIFICATIONS PULTRUDED GRATING AND TREADS SECTION PART 1 GENERAL
PRODUCT SPECIFICATIONS PULTRUDED GRATING AND TREADS SECTION 06600 PART 1 GENERAL 1.1 Related Documents A. Drawings and general provisions of Contract, including General and Supplementary Conditions and
More informationSection BUILDINGS, SHELTERS, ENCLOSURES
Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices
More informationSECTION MECHANICALLY ASSISTED MOBILE STORAGE SHELVING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 10560 MECHANICALLY ASSISTED MOBILE STORAGE SHELVING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Chlorination System (On-site Sodium Hypochlorite Generation System) C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 11241 - Chlorination System (On-site Sodium Hypochlorite Generation System) C O N T E N T S PART 1 - GENERAL... 1 1.01 Scope... 1 1.02 Scope of Work... 1 1.03
More informationEssex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationStructural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)
Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction
More informationSECTION INFLUENT EQUALIZATION TANK PUMPS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Influent Equalization Pumps in accordance with the Contract Drawings
More informationA. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.
SECTION 230713 DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information.1 ANSI/ASME B31.1, Power Piping, (SI Edition)..2 American Society for Testing and Materials (ASTM)
Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 03300 - Cast-in-Place Concrete.2 Section 05121 - Structural Steel for Buildings.3 Section 05500 - Metal Fabrications 1.2 REFERENCES.1
More informationFRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.
FRP Specifications Section 06 70 00 Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA 24203-0580
More informationREINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS
SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of
More informationSECTION The specification section is organized by placing information in three standard parts:
SECTION 14244 LIMITED USE HYDRAULIC ELEVATOR ***** Since 1982 Liftavator, Inc. has provided limited use/limited application (LU/LA) elevators, residential elevators, hydraulic vertical platform wheelchair
More information1. Hangers and supports for electrical equipment and systems.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 PERFORMANCE REQUIREMENTS... 1 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 COORDINATION... 2 PART 2 - PRODUCTS...
More information1DIVISION 15- MECHANICAL Section Fire Pumps. A. Single Stage, Double Suction, 9100 Series Horizontal Splitcase Fire Pump (Base Mounted)
1DIVISION 15- MECHANICAL Section 15320 Fire Pumps 1.00 PART 1 -GENERAL 1.01 DESCRIPTION OF WORK: A. Provide pumps for fire suppression. 1.02 SECTION INCLUDES: A. Single Stage, Double Suction, 9100 Series
More information