ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT
|
|
- William Ferguson
- 6 years ago
- Views:
Transcription
1 ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT Specification for Acoustical Insulation (Lagging) for Piping and Equipment 1 of 5
2 TABLE OF CONTENTS 1.0SCOPE REFERENCED PUBLICATIONS GENERAL MATERIALS ABSORPTIVE LAYER APPLICATION (INSULATION) BARRIER LAYER APPLICATION FINISH APPLICATION IRREGULAR SURFACES FLASHING... 5 Specification for Acoustical Insulation (Lagging) for Piping and Equipment 2 of 5
3 1.0 SCOPE 1.1 This specification describes the materials for and the application of acoustical insulation (lagging) for piping and equipment in hot and cold services. 2.0 REFERENCED PUBLICATIONS The following publications (latest editions) form part of this specification: COMPANY Engineering Specifications Cold Piping and Equipment Insulation Hot Piping and Equipment Insulation 3.0 GENERAL 3.1 This specification requires compliance with all applicable federal, state, and local laws and regulations. 3.2 Piping and equipment that is specified to receive acoustical insulation shall be insulated in accordance with this specification and any additional project requirements. 3.3 All equipment that is to be insulated will be listed on the equipment insulation schedule along with the insulation type, material, and thickness. 3.4 All piping that is to be insulated will be listed on the line schedule along with the insulation type, material, and thickness. 3.5 General insulation requirements are covered in COMPANY Engineering Specification IC for cold service ( 225 F to +70 F) ( 143 C to +21C) installations and IH for hot service (+70 F to F) (+21 C to +649 C) installations. All requirements of COMPANY Engineering Specifications shall apply except any exceptions or variations stated in this specification shall take precedence where acoustical insulation is specified. 3.6 Reusable pad type insulation covers may be used for the services specified in COMPANY Engineering Specification, provided they are supplied with a noise barrier layer. 3.7 Only lead free materials shall be used. 4.0 MATERIALS 4.1 All materials shall conform to the requirements of COMPANY Engineering Specifications except as modified by this specification. 4.2 Absorptive layer materials shall be one of the following: a. Glass fiber with a minimum density of 3 lb/ft 3 (48 kg/m 3 ) of specified thickness. b. Mineral fiber with a minimum density of 8 lb/ft 3 (128 kg/m 3 ) of specified thickness. 4.3 Barrier layer materials shall be one of the following: a. Loaded vinyl sheeting, such as Soundmat PB by Soundcoat Co. or equal, of specified surface weight. b. Loaded mastic, such as Acousti Lag by RPR Products Inc. or equal, of specified surface weight. c. Loaded vinyl metal laminated sheeting of specified surface weight. 4.4 Laminates providing combinations of absorptive, barrier, or finish layers shall be one of the following: a. Loaded vinyl sheeting laminated to aluminum or stainless steel jacketing, such as Acousti Jac Aluminum or Acousti Jac SS by RPR Products Inc. or equal, of specified surface weight. 4.5 All materials shall be asbestos free. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 3 of 5
4 5.0 ABSORPTIVE LAYER APPLICATION (Insulation) 5.1 For cold service ( 225 F to +70 F) ( 143 C to +21 C) installations, the complete thermal system (basic insulation material, coverings and coatings, and sealers) shall be applied before any acoustical absorptive material is applied. A vapor barrier shall be installed between the acoustical insulation and the outer jacketing. 5.2 For hot service (+70 F to F) (+21 C to +649 C) installations, the acoustic absorptive material shall be applied directly to the piping or equipment. 5.3 For installations where thermal insulation already exists, the acoustic absorptive layer shall be applied directly over the existing insulation without modification to the thermal system. 5.4 All surfaces (including valve bodies, flanges, fittings, etc.) on the equipment or length of duct or piping that is to be acoustically insulated shall be covered with the absorptive material. Hangers and other supports shall also be covered. 5.5 Absorptive insulation shall be applied with a snug, tight fit at all joints, longitudinal and circumferential. If a thickness of more than 2 inches (50mm) is specified, the insulation shall be applied in multiple layers, staggering all joints. All openings shall be packed with loose insulation using elastomeric adhesives. Insulating cements shall not be used. 5.6 Insulation shall be secured on piping and equipment with wire or bands as required by COMPANY Engineering Specification IC or IH Pins and clips shall not be used to secure the insulation. 5.7 Elbows shall be covered with either preformed or field cut insulation of the same material and thickness as the pipe insulation. For other items like flanges in the system, the same treatment shall be applied in the most efficient manner. 6.0 BARRIER LAYER APPLICATION 6.1 Sheet barrier materials shall be applied in a watershed fashion, and all joints of barrier material and absorptive material shall be staggered. Circumferential and longitudinal joints of sheet barrier material shall be overlapped a minimum of 3 inches (76mm). On horizontal joints of sheet barrier material and loaded mastics, the sheet material shall be extended a minimum of 3 inches (76mm) over the mastic. On vertical joints, the mastic shall extend 3 inches (76mm) over the sheet material to provide proper watershed. All sheet barrier materials shall be applied in an airtight, gapless fashion. 6.2 The continuity of the barrier layer shall not be broken. Where it is impossible to fit the entire specified thickness of absorptive and barrier layers, the thickness of the absorptive layer shall be decreased to allow clearance. 6.3 On loaded vinyl sheet barrier materials where an additional finish is to be applied, bands, wire, tape, or adhesive bonding are all acceptable means of attachment. On vinyl sheet barrier material applications, when these materials will act as the finish surface, wire or tape shall not be used for attachment. To ensure gapless joints on vinyl sheet applications, all joints shall be adhesively bonded. Sheet metal screws shall not be used on plain vinyl sheet barrier layer materials. VENDORS should be consulted for specific instructions and limitations for their products. 7.0 FINISH APPLICATION 7.1 The final finish jacketing shall be secured with bands only. Screws or rivets shall not be used. 7.2 Prefabricated metal elbows and other fittings shall be used whenever possible. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 4 of 5
5 7.3 All longitudinal and circumferential seams shall be caulked. Cuts and openings for projections shall be made as tight as possible. All openings and seams shall be caulked with a nonhardening, nonshrinking type caulking compound. 7.4 There shall be no direct or indirect metalto metal contact of equipment or pipe walls with outer jacketing materials. The use of weld studs, weld pins, peg rivets, or similar devices which could couple the jacketing material to the equipment or piping walls is prohibited. The use of the insulation system shown in COMPANY Engineering Specification IH 1.0.0, Figure 6, is prohibited for acoustical insulation systems since it couples the jacketing to the vessel. 7.5 The outer jacketing material shall form a total enclosure around the piping and equipment. There shall be no leaks, voids, or openings in the jacketing material. 8.0 IRREGULAR SURFACES 8.1 All irregular surfaces receiving acoustical insulation shall be completely covered with absorptive insulation. The insulation shall be cut and fitted together to avoid gaps. All openings shall be packed with loose insulation using elastomeric adhesives. Insulating cements shall not be used. 8.3 A tack coat of mastic (approximately half of the desired film thickness) shall be applied with sufficient pressure to assure impregnation of the absorptive layer. Reinforcing fabric shall be embedded in the wet tack coat, and then the final coat shall be applied to the specified wet film thickness. Adjacent pieces of reinforcement shall be lapped a minimum of 3 inches (76mm). The installed reinforcing shall be free of wrinkles and protruding edges. In multiple coat applications, the reinforcing fabric shall be applied to the middle coating. 8.4 If the acoustical coating is used in conjunction with metal jacketing, the coating shall be overlapped at least 3 inches (76mm) by the jacketing and banded and caulked at the extreme end of the overlapping jacketing. 9.0 FLASHING 9.1 A 1/4 inch (6mm) bead of flashing compound shall be applied to all possible points of acoustic leakage or moisture penetration. These shall include any interruptions of the finish or barrier layer at joints or between finish or barrier layers and protrusions such as valve bonnets, hangers, and instrument connections. All joints that are to be broken in removing a removable cover shall also be flashed. 8.2 Trowelable acoustical coatings, such as loaded mastic, shall be applied directly to the absorptive insulation and reinforced with glass cloth. The coating shall have a minimum dry film thickness of 0.07 inch (1.8mm) and a minimum surface weight of 0.72 lb/ft 2 (3.6 kg/m 2 ). The Noise Reduction Coefficient (NRC) of the loaded mastic is available from the VENDOR. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 5 of 5
PIP INSA1000 Acoustic Insulation Systems Specification
TECHNICAL REVISION April 2015 Insulation PIP INSA1000 Acoustic Insulation Systems Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,
More informationAddendum to Specifications
Addendum to Specifications SOW #: Construction Specification #: Date: Additions to Specifications: Deletions to Specifications: Engineer Date Design Engineering Manager Date Page 2 of 7 PART 1 - GENERAL
More informationFIRE STATION 55 June 14, 2010
SECTION 15250 MECHANICAL INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work Includes 1. Insulation of Domestic Water Piping. 2. Pipe Insulation of refrigerant piping. 3. Insulation of ductwork. 4. Aluminum
More informationSECTION HVAC INSULATION
PART 1 GENERAL 1.1 SUMMARY SECTION 23 07 00 HVAC INSULATION A. Section Includes: 1. Ductwork insulation. 2. Duct liner. 3. Insulation jackets. 4. Equipment insulation 5. Piping system insulation. 6. Insulation
More informationThis specification describes the minimum requirements for industrial thermal insulation.
016/09/7 1/7 1.0 PURPOSE This specification describes the minimum requirements for industrial thermal insulation. Read it in conjunction with the applicable insulation and insulation finish specifications
More informationDesign & Construction Standards, Revised January
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationA. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.
SECTION 23 07 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationNORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION
PART 1 GENERAL 1.01 SUMMARY Section 15145 This Section includes insulation for piping and equipment as called out on the Plans. 1.02 MEASUREMENT AND PAYMENT No separate payment will be provided for the
More informationA. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.
SECTION 230713 DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationINSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS
INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS Dyplast Products Copyright 2014 1 Rev 0414 DYPLAST PRODUCTS INSTALLATION GUIDELINES ISO-C1 POLYISOCYANURATE
More informationINSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS
INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS Dyplast Products Copyright 2018 1 Rev 0618 DYPLAST PRODUCTS INSTALLATION GUIDELINES ISO-C1 POLYISOCYANURATE
More informationA. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More information10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2
SECTION 10: 10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING 2 10.2 FINISHES 2 10.3 PIPING FORMAT 3 A. PIPE INSULATION 3 B. PIPE INSULATION 3 C. INSULATION ATTACHMENT 3 D. INSULATION
More informationPROJ. NO SECTION HVAC DUCT INSULATION
SECTION 23 07 13 HVAC DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationUBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Refer to Division 33 and Division 23 - Underground Steam and Condensate Piping.2 Refer to Division 23 - Steam and Condensate Piping Above Grade 1.2
More informationD. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationITW INSULATION SYSTEMS
ITW INSULATION SYSTEMS 1SCOPE TRYMER RIGID POLYISOCYANURATE INSULATION IN LIQUEFIED NATURAL GAS APPLICATIONS (Cryogenic to -70 F) 1.1 This guideline covers the installation of TRYMER Rigid Polyisocyanurate
More information1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.
SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationAPPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION
APPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION Jim Young, Director of Technology and Pjeter Skrelji, Eastern Canada Regional Manager Vers. 2 November 19, 2011 Preliminary
More informationUBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Refer to Division 33 and Division 23 - Underground Steam and Condensate Piping.2 Refer to Division 23 - Steam and Condensate Piping Above Grade.3 Section
More information.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.
BID OPPORTUNITY NO. 253-2011 PAGE 1 OF 8 PART 1 GENERAL 1.1 SUMMARY.1 Section Includes: 1.2 REFERENCES.1 Thermal insulation for insulated piping and piping accessories affected by construction and new
More informationA. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.
SECTION 15250 PIPING AND EQUIPMENT INSULATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification
More information079 Quick Installation Guide
INSULATION 2212 W. 5th Pl., Tempe, AZ 85268 (480) 967-8888 Step 1: 079 Quick Installation Guide Step 2: *see attached literature for complete installation instructions Step 3: Position the next piece and
More informationITW INSULATION SYSTEMS
ITW INSULATION SYSTEMS 1SCOPE TRYMER RIGID POLYISOCYANURATE INSULATION IN LIQUEFIED NATURAL GAS APPLICATIONS (-260 F) 1.1 This guideline covers the installation of Trymer* Rigid Polyisocyanurate Insulation
More informationB. Refer to Section : Air Distribution for lined ductwork requirements.
SECTION 230700 MECHANICAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationINSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION
PermaTherm, Inc. 269 Industrial Park Road Monticello, GA 31064 (706) 468-7500 www.insulate.pipe.com/ Temperature Range 34 F to 167 F INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION PERMATHERM,
More informationA. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.
SECTION 230719 - HVAC PIPING INSULATION PART 1 GENERAL 1.1 SECTION INCLUDES A. Piping insulation. B. Jackets and accessories. 1.2 RELATED REQUIREMENTS A. Section 07813 - Fire Procection, HVAC & Plumbing
More informationSECTION (15081) - HVAC INSULATION
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 23 07 00 (15081) - HVAC INSULATION 1. Insulation Materials 2. Jackets 3. Accessories and Attachments 4. Vapor Retarders B. Related Sections: 1.02
More informationSPECIFICATION FOR COLD INSULATION
SPECIFICATION FOR COLD INSULATION Specification for Cold Insulation 1 of 21 TABLE OF CONTENTS 1.0. SCOPE..... 3 2.0. REFERENCED PUBLICATIONS... 3 3.0. GENERAL CONDITIONS... 3 4.0. MATERIALS... 5 5.0. APPLICATIONS...
More informationINSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS
INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN HOT APPLICATIONS (80 F to 300 F) 1 SCOPE 1.1 This guideline covers the installation of TRYMER
More informationITW INSULATION SYSTEMS
Installation Guidelines for TRYMER Insulation ITW INSULATION SYSTEMS TRYMER Rigid Polyisocyanurate Insulation in Refrigeration Applications (-70 F to 35 F) 1 SCOPE 1.1 This guideline covers the installation
More informationINSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS
INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN HOT APPLICATIONS (80 F to 300 F) 1 SCOPE 1.1 This guideline covers the installation of Trymer*
More informationA. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION PIPING INSULATION
SECTION 23 07 19 PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Piping insulation for refrigerant piping within building envelope. 2. Furnishing and installation of insulation.
More informationInstallation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe
Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe 1 SCOPE 1.1 This guideline covers the installation of ITW Insulation Systems Pabco-Childers brand aluminum and
More informationINSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION
PermaTherm, Inc. 269 Industrial Park Road Monticello, GA 31064 (706) 468-7500 www.insulate.pipe.com/ Temperature Range -310 F to 32 F INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION PERMATHERM,
More informationINSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER
INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER Dyplast Products Copyright 2012 1 Rev 0112 DYPLAST PRODUCTS
More informationSECTION PLUMBING INSULATION
SECTION 22 07 00 PLUMBING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes equipment insulation, covering, and thermal insulation for piping systems including vapor retarders, jackets and accessories.
More informationSECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:
SECTION 15250 PART I - GENERAL 1.01 WORK INCLUDED A. Types of insulation specified in this section include the following: 1. Piping System Insulation: a. Domestic Cold Water b. Domestic Hot water c. Heating
More informationDivision 15 INSULATION Section 15100
Page 1 of 5 SECTION PAGE PART 1 GENERAL 2 1.1 General 2 1.2 References 2 1.3 Work Included 2 1.4 Related Work 2 1.5 Quality Assurance 3 PART 2 PRODUCTS 3 2.1 Description 3 PART 3 EXECUTION 3 3.1 Workmanship
More informationDSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION
SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 233113 Ductwork and Accessories 1.2 REFERENCES A. American Society for Testing and Materials (ASTM): 1. E84-96a Test Method
More informationMECHANICAL INSULATION
MECHANICAL INSULATION GENERAL INFORMATION 1.1 Comply with more stringent of following latest edition of Energy Conservation and Construction Code of New York City, ASHRAE and this Guideline. DESIGN REQUIREMENTS
More informationINSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS
INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS TRYMER RIGID POLYISOCYANURATE INSULATION IN REFRIGERATION APPLICATIONS (-70 F to 35 F) 1 SCOPE 1.1 This guideline covers the installation
More informationAddendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5
Burrow Avenue Pumping Station Upgrades Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Thermal insulation for piping and piping accessories in commercial type applications. 1.2 REFERENCES.1
More informationPIP INSC1000 Cold Service Insulation Materials and Installation Specification
COMPLETE REVISION Ocber 2017 Insulation PIP Cold Service Insulation Materials and Installation Specification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort minimize the cost of process industry
More informationSECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
PART 1 GENERAL SECTION 22 0553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT 1.01 SECTION INCLUDES A. Pipe markers. 1.02 REFERENCE STANDARDS A. ASME A13.1 - Scheme for the Identification of Piping
More informationSECTION MECHANICAL INSULATION
SECTION 15250 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationSPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT
SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT Page 1 of 15 Ver. 3-0 March 2010 TABLE OF CONTENTS 1. Scope... 3 2. General System Requirements... 3 3. Installation Details...
More informationINSTALLATION GUIDELINE FOR TRYMER INSULATION
INSTALLATION GUIDELINE FOR TRYMER INSULATION TRYMER RIGID POLYISOCYANURATE INSULATION IN CHILLED WATER APPLICATIONS (35 F to 60 F) 1 SCOPE 1.1 This guideline covers the installation of Trymer Rigid Polyisocyanurate
More informationPipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems
Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,
More informationMechanical Insulation for Refrigeration Systems
Mechanical Insulation for Refrigeration Systems INDUSTRIAL REFRIGERATION CONSORTIUM RESEARCH & TECHNOLOGY FORUM MAY 2-3, 2012 Peter Gauchel, President/CEO L&C Insulation Inc. Overview Current trends in
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 23 0700 - HVAC INSULATION PART 1 - GENERAL 1.1 DESCRIPTION OF WORK: A. All work covered in this section consists of furnishing all labor, equipment, materials and accessories, and performing all
More informationThis Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin
PART 1: GENERAL 1.01 Purpose: This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin 1.02 Scope: A. Extent of mechanical insulation
More information1 of 17. PO Box Bellevue Rd, Newark, DE V F
1 of 17 Raw Material Manufactured from 4 8-foot sheets Fiber-reinforced 1-mil aluminumfaced polyisocyanurate panels 0.032 embossed aluminum Other patterns and stainless steel are available Necessary supplies
More information379 Quick Installation Guide
Step 1: INSULATION 2212 W. 5th Pl., Tempe, AZ 85268 (480) 967-8888 379 Quick Installation Guide Step 2: Step 3: *see attached literature for complete installation instructions Remove and discard packing
More informationNCCER Progress Blvd, Alachua, Florida Tel: (888)
NCCER 13614 Progress Blvd, Alachua, Florida 32615 Tel: (888) 622-3720 E-mail: info@nccer.org INSULATING Competencies / Objectives Level One MODULE 19101 - ORIENTATION 1. Explain what insulation is and
More informationINSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION
INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION TRYMER SUPERCEL PHENOLIC INSULATION IN CHILLED WATER APPLICATIONS (35 F to 60 F) Vers. 1.0 1 SCOPE 1.1 This guideline covers the installation
More informationSECTION HVAC INSULATION
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. B. Related
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 22 0700 - PLUMBING INSULATION PART 1 - GENERAL 1.1 DESCRIPTION OF WORK: A. All work covered in this section consists of furnishing all labor, equipment, materials and accessories, and performing
More informationUniversity of Delaware
University Contact: Energy & Engineering Group (302) 831-1744 SECTION 23 07 00_ HVAC INSULATION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Piping system insulation. 2. Equipment insulation. 3.
More informationTENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION
SECTION 230719 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes insulating the following HVAC piping systems: 1. Chilled-water and brine piping, [indoors] [and] [outdoors]. 2. Heating hot-water piping,
More informationSECTION MECHANICAL INSULATION
SECTION 15250 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationFOAMGLAS INSULATION SPECIFICATION
FOAMGLAS INSULATION SPECIFICATION PITTSBURGH CORNING CORPORATION FOAMGLAS Products Technical Support 800 Presque Isle Drive Pittsburgh, PA 15239 724-327-6100 SPECIFICATION # I-H/C-89-02-01 REVISION 06/28/2004
More informationSTANDARD SPECIFICATIONS. Followings have been covered in this section. The work is to be carried based on the standard specifications:
STANDARD SPECIFICATIONS APPENDIX -3 Followings have been covered in this section. The work is to be carried based on the standard specifications: 1) Standard Specifications for Cold Insulation 2) Standard
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC.
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2213 Reissued 04/2018 This report is subject to renewal 04/2019. DIVISION: 07 00
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 07 00 - SYSTEM INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical
More informationDesign No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1
FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"
More informationINSULATION SECTION 15250
INSULATION SECTION 15250 PART 1 GENERAL 1.1 DESCRIPTION A. Provide complete systems of insulation for piping, ducts, boiler stacks and breeching, and mechanical equipment as specified. B. Related work
More informationSECTION HVAC PIPING INSULATION
SECTION 23 0719 HVAC PIPING INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install insulation on above ground refrigerant piping and fittings as described in Contract
More informationINDUSTRIAL SYSTEMS. Application Manual for Piping Equipment. ARMASOUND INDUSTRIAL SYSTEMS - Application Manual for Piping Equipment
INDUSTRIAL SYSTEMS Application Manual for Piping Equipment INDEX Introduction................................ 2 Tools for Installing ArmaSound.............. 2 INTRODUCTION The advice contained within this
More informationColphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate
Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,
More informationEXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,
More informationSECTION GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Gypsum board screw attached to wood framing and furring members, joint treatment, and accessories. 2. Installation of
More informationA. Source Limitations: Obtain each type of building insulation through one source.
SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION BUILT-UP BITUMINOUS WATERPROOFING
SECTION 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING SPEC WRITER NOTE: Delete any item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section
More informationB. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.
SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping
More informationSECTION GYPSUM BOARD & SHEATHING SYSTEMS
PART 1!GENERAL! 1.01! SECTION INCLUDES SECTION 09260 GYPSUM BOARD & SHEATHING SYSTEMS! Metal stud wall framing. Metal channel ceiling framing.! Gypsum board.! Sheathing.! Taped and sanded joint treatment.!
More informationK-FLEX K-FONIK INDUSTRIAL
J a n u a r y 2 0 1 3 K-FLEX K-FONIK INDUSTRIAL Sound & Thermal Insulation design compliant with ISO 15665 www.kflexenergy.com Flexible Elastomeric Foam layer INSULATING PIPING WITH K-FLEX SHEETS > FIRST
More informationDivision 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17
07 21 16 Blanket Insulation Page 1 of 17 Design Number UNI/BI 120-03 FIRE RESISTANT GREASE DUCT Unifrax I LLC FyreWrap Elite 1.5 Duct Insulation CAN/ULC S144 Fire Resistance Rating 2 hours Fire Inside
More informationPIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service
TECHNICAL REVISION August 2015 Insulation PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
More information.1 The following is a list of standards which may be referenced in this Section:
Construction of Sodium Hypochlorite and Chemical Storage Buildings Page 1 of 14 1. GENERAL 1.1 References.1 The following is a list of standards which may be referenced in this Section:.1 ASHRAE:.1 Standard
More informationRevision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC
PIPEWORK INSULATION CU14 14/11/2012 Page 1 of 10 - RevC Contents INTRODUCTION 5 General 5 Scope 5 Surfaces to be Insulated 5 Pumps, Turbines etc 5 Performance 6 Minimum Pipe Insulation Thickness 6 Physical
More informationPIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D
PIPEWORK INSULATION 14/10-2014 Page 1 of 10 Pipework Insulation Rev D Contents INTRODUCTION General Scope Surfaces to be Insulated Pumps, Turbines etc Performance Minimum Pipe Insulation Thickness Physical
More informationCFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE
Resolco Insul-Phen CFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE TABLE OF CONTENTS RESOLCO INC. Specification: Insul-Phen closed cell CFC & HCFC free phenolic foam Pipe & Equipment
More informationDuct Wrap Flexible Wraps
Design No. 3MU/ 60-01 December 23, 2010 VENTILATION DUCT PROTECTION 3M Company 3M Fire Barrier Duct Wraps: 615 and 615+ 3M Fire Barrier Sealants: Water-Tight 1000-NS Silicone, Water-Tight 1003-SL Silicone
More informationSECTION DUCT INSULATION
SECTION 23 07 13 - DUCT INSULATION PART I - GENERAL 1.1 SECTION INCLUDES A. Ductwork Insulation B. Fan and Equipment Insulation C. Insulation Jackets D. Insulation Lagging 1.2 RELATED SECTIONS A. Section
More informationNational Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ].
National Master Specification (NMS) Section 07 21 16 BLANKET INSULATION Publisher: Spex.ca Page 1 Approved: 2014-12-31 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section [ ]. 1.2 REFERENCES.1 CSA Group.1
More informationState of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Specific requirements, products and methods of execution which relate to the insulation of ductwork, piping, valves and fittings. B. Related Sections:
More informationICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.
ICC-ES Evaluation Report ESR-1255 Reissued May 1, 2010 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
More informationRecommended Installation and Repair Guide
Revision 1 7/20/2017 Insulation Jacketing Products Recommended Installation and Repair Guide Pipe and Equipment Insulation Jacketed with Factory and Field Installed Products Table of Contents 1. Scope...
More informationInstallation Manual PIPE AND EQUIPMENT INSULATION
PIPE AND EQUIPMENT INSULATION Contents (Click below to jump to section) Safety First 3 Material Handling 3 Preparation and Storage 4 Optimal Work Setup 5 Single Wrap Pipe 6 Double Wrap Pipe 7 Multi-Layer
More informationSept 30, 2004 Page 1
Sept 30, 2004 Page 1 This section includes a manufacturer's guide specification for TERRAFOAM EPS building insulation. Refer also to Product Description for detailed product properties, options, and other
More informationSECTION GYPSUM BOARD ASSEMBLIES
SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.
More informationTENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION
SECTION 220719 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes insulating the following plumbing piping services: 1. Domestic hot-water piping. 2. Domestic recirculating hot-water piping. 3. Supplies
More informationBuildingName The Description of the Project P DOCUMENTS
P00000000 0000 DOCUMENTS ARCHITECTURE ENGINEERING AND CONSTRUCTION ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION DIVISION
More informationSECTION MECHANICAL SYSTEMS INSULATION
SECTION 23 0700 MECHANICAL SYSTEMS INSULATION PART 1 - GENERAL 1.1 RELATED WORK A. Section 23 0529 - Mechanical Supporting Devices B. Section 23 3114 - Ductwork (Duct Lining) 1.2 REFERENCE A. Work under
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT SPECIFICATION EO-1007 REVISION 13 DECEMBER 2013 EFFECTIVE DATE DECEMBER 16,
More informationFIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5
Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a
More informationPERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION
PermaTherm, Inc. 269 Industrial Park Road Monticello, GA 31064 (706) 468-7500 www.insulate.pipe.com/ PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION The specification guideline in the three-part
More information