1 SECTION : FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES A. Purpose. The intent of this regulation is to amend the current adopted edition of the International Residential and Building Codes and to ensure that all zero lot line, duplex, patio home, townhouse, apartment house, two family and multi-family dwellings constructed within the boundaries of the City of Republic have a masonry fire wall separating the units and, where required by ordinance below, to provide a fire suppression system to minimize damage in the event of fire in an adjoining unit, to provide increased safety to the dwelling s residents, and to conserve water resources. B. Definitions: 1. Fire Wall: A wall separating buildings or subdividing a building to prevent the spread of fire and having a fire resistance rating and structural stability. 2. Fire Partition Wall: Is a fire rated wall assembly which is not a fire wall. Typically, the main difference is that a fire barrier wall is not structurally stable, and does not extend through the roof, or to the underside of the floor above. 3. Firestop: Is a passive fire protection system of various components used to seal openings and joints in fire-resistance rated wall and/or floor assemblies, based on fire testing and certification listings. Fire walls must not be penetrated such that the wall is structurally weakened in a fire and could collapse. 4. Townhouse: A single-family dwelling unit constructed in a group of three or more attached units in which each unit extends from foundation to roof and with at least one side not attached to an adjacent dwelling. 5. Duplex: A duplex is a structure used for residential purposes and consisting of two living units with a common separating wall. 6. Patio Home: A Patio Home is a free-standing or paired home of no more than two attached units, each located on a small lot that has at least some private land, generally in the back and/or side yards, but also possibly a small front yard. 5. Zero Lot Line Home: A zero lot line home is a structure where two units are attached to another where the exterior wall of one home is the lot line of the other person's property/yard. 6. NFPA 13 Fire Suppression System: Standard for the Installation of Sprinkler Systems (Commercial).

2 7. NFPA 13D Fire Suppression System: Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes. 8. NFPA 13R Fire Suppression System: Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height. 9. R1-Z Zero Lot Line Residential District: Residential district permitting the construction of a building on any of the boundary lines of a lot, such as patio homes. 10. R2 Two Family Residential District: Residential District permitting the construction of a residence with two units sharing a common wall, such as duplex units. 11. R3 Multi-Family Residential District: Residential district permitting the construction of a residential building for use by multiple family groups such as apartments and townhouses. B. Uses Required: Any wall in zero lot line dwellings, duplexes, patio homes, townhouses, apartment houses, two-family and multi-family residential dwellings that are shared with an adjoining residence shall be a concrete masonry walls as set out in the following general regulations per zoning category. Fire Partition Walls may be substituted where allowed in R-3 zoning category. C. General Regulations. Each wall separating individual residential units shall observe the following design standards: 1. All Single-Family Dwellings in R1, R2 and PDD Zoning Categories: a. Fire Suppression System: The builder of all single family dwellings shall offer to any purchaser on or before the time of entering into the purchase contract the option, at the purchaser s cost, to install or equip NFPA13R fire sprinklers in the dwelling. 2. All Single-Family Dwellings in R1-Z, R-2 and PDD Zoning Categories: a. Two (2) Hour Concrete Masonry Fire Partition Wall: A 2-hour rated partition wall is required between all single-family attached dwellings. The fire partition wall shall be constructed using 2-hour rated 8-inch concrete masonry units (CMU) from the top of the concrete footing continuously up to the underside of the roof decking material. The roof decking material shall be 2-hour fire-retardant treated wood within 4-feet of the masonry fire partition wall. b. Fire Wall Labeling. All fire walls shall be labeled in the under floor and attic areas in letters at least 2-inches in height and no more than 10-lineal feet along

3 the wall and shall be placed in such a manner as to be obvious to workers in the crawl space, attic or concealed space on both sides of the wall and will read as follows: FIRE WALL: DO NOT PENETRATE OR DAMAGE. NO PENETRAR O DAÑAR ESTA PARED RESISTENTE AL FUEGO. c. Penetrations: Penetrations through any fire wall, such as for pipes and cables, shall be protected with an equivalently rated firestop. d. Openings: Any openings in any fire wall, such as doors and windows, shall have an equivalently fire rated door or window assembly. e. Fire Suppression System: The builder of all single family dwellings shall offer to any purchaser on or before the time of entering into the purchase contract the option, at the purchaser s cost, to install or equip NFPA13R fire sprinklers in the dwelling. 3. Multi-Family Housing in R-3 Zoning Category: 2-Hour Masonry Fire Partition with NFPA 13 Fire Suppression System (refer to drawing below) a. Fire walls shall have sufficient structural stability to maintain the integrity of the wall in the event of the collapse of the building construction on either side of the wall. b. Four (4) Hour Concrete Masonry Fire Partition Wall (Wall A): The midpoint common wall along the short axis of the multi-family dwelling shall be a 2- hour rated partition wall. The fire partition wall shall be constructed using 2- hour rated 8-inch concrete masonry units (CMU) from the top of the concrete footing continuously up to the underside of the roof decking material. The roof decking material shall be 2-hour fire-retardant treated wood material within 4-feet of the masonry fire partition wall. c. Two (2) Hour Concrete Masonry Fire Partition Wall (Wall B): A 2-hour rated wall assembly (positioned vertically) shall be constructed at one side of the short axis of all breezeways in all single family attached dwellings in apartment houses and multi-family dwellings. The fire partition wall shall be constructed using 2-hour rated 8-inch concrete masonry units (CMU) from the top of the concrete footing continuously up to the underside of the roof decking material. The roof decking material shall be 2-hour fire-retardant treated wood material within 4-feet of the masonry fire partition wall. d. One (1) Hour Fire Partition Wall (Wall C): A 1-hour rated wall (UL-U305 or UL-U340) assembly (positioned vertically) shall be constructed at long axis midpoint of the building from the top of the footing to the underside of the roof decking in all multi-family apartment buildings.

4 e. Two Hour Concrete Floor Separation: A 2-hour rated floor assembly (positioned horizontally) shall be constructed between one floor and the floor above in all single family attached dwellings in apartment houses and multifamily dwellings. f. Fire Suppression System: Each unit in the multi-family dwelling(s) shall be protected with a NFPA 13 fire suppression system (full commercial system). g. Fire Wall Labeling: All fire walls shall be labeled in the under floor and attic areas in letters at least 2-inches in height and no more than 10-lineal feet along the wall and shall be placed in such a manner as to be obvious to workers in the crawl space, attic or concealed space on both sides of the wall and will read as follows: FIRE WALL: DO NOT PENETRATE OR DAMAGE. NO PENETRAR O DAÑAR ESTA PARED RESISTENTE AL FUEGO. h. Penetrations: Penetrations through any fire wall, such as for pipes and cables, shall be protected with an equivalently rated firestop. i. Openings: Any openings in any fire wall, such as doors and windows, shall have an equivalently fire rated door or window assembly. j. Masonry walls shall be constructed in accordance with section R606 General Masonry Construction of the current adopted edition of the International Residential Code. k. Footings: Minimum sizes for concrete and masonry footings shall be as set forth in Table R403.1 of the current adopted edition of the International Residential Code. The footing width, W, shall be based on the load-bearing value of the soil in accordance with Table R of the current adopted edition of the International Residential Code. In areas likely to have expansive, compressible, shifting or other unknown soil characteristics, the building official shall determine whether to require a soil test to determine the soil s characteristics at a particular location. This test shall be made by an approved agency using an approved method. In lieu of a complete geotechnical evaluation, the load-bearing values in Table R shall be assumed.

5 Wall B: Two Hour Fire Partition on Either Side of Breezeway Wall B: Two Hour Fire Partition on Either Side of Breezeway Drawing below shows one floor of a multi-floor apartment building with each floor similar in construction requirements Wall C: One Hour Fire Partition from Footing to Underside of Roof Decking Wall A: Four Hour Masonry Fire Partition from Footing to Underside of Roof Decking

The Lexington Division of Fire and Emergency Services. Fire Chief Robert G. Hendricks

The Lexington Division of Fire and Emergency Services. Fire Chief Robert G. Hendricks The Lexington Division of Fire and Emergency Services Fire Chief Robert G. Hendricks The Code of Hammurabi 229. If a builder builds a house for someone, and does not construct it properly, and the house

More information

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Included are selected sections of codes taken directly from: 1997 Uniform

More information

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section ) 8-1200. International Residential Code. ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section 6-9-40) NOTE-This article

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

Single Family Residential Building Permit Questions & Answers

Single Family Residential Building Permit Questions & Answers City Of Edwardsville Public Works Department 200 East Park Street Edwardsville, IL 62025 (618)692-7535 (618)692-7505 Fax Hours: Monday thru Friday 8:00 AM to 5:00 PM Single Family Residential Building

More information

NEWS LETTER MARCH 27, 2009

NEWS LETTER MARCH 27, 2009 PLANNING, BUILDING & DEVELOPMENT SERVICES DEPARTMENT 580-1 Street S.E. Medicine Hat, Alberta T1A 8E6 Telephone: 529-8374 FAX 502-8038 1 NEWS LETTER MARCH 27, 2009 GENERAL As you are probably aware there

More information

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS:

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: DRAFT ORDINANCE FIRE SAFETY V3 06-26-2017 An ordinance amending Subsections SEC. 91.703 of Article I of Chapter IX of the Los Angeles Municipal Code to address FIRE SAFETY of residential use structures

More information

Updated references to SEI/ASCE 7 to the 2016 edition once it is available.

Updated references to SEI/ASCE 7 to the 2016 edition once it is available. Committee Input No. 8008-NFPA 5000-2015 [ Global Input ] Updated references to SEI/ASCE 7 to the 2016 edition once it is available. Submitter Information Verification Submitter Full Name: Tracy Vecchiarelli

More information

Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No

Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No We Bring Buildings to Life www.jbace.com Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No. 16.0667.000 At the request of Yihong Liu

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION BC 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Staff Analysis for Declaratory Statement Request DS

Staff Analysis for Declaratory Statement Request DS Staff Analysis for Declaratory Statement Request DS2016-081 Issue: The Petitioners [Alan Gremillion of GL Homes, Inc. and Douglas Buck of Florida Home Builders Association (FHBA)] seek clarification regarding

More information

General Residential Code Requirements

General Residential Code Requirements General Residential Code Requirements Dear Applicant: This is to advise that our review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance

More information

General Residential Code Requirements

General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the 2005 First Extraordinary Session of

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

2021 ICC Group A National Model Codes: Online Voting Guide

2021 ICC Group A National Model Codes: Online Voting Guide BACKGROUNDER NOVEMBER 2018 2021 ICC Group A National Model Codes: Online Voting Guide About NMHC Based in Washington, DC, the National Multifamily Housing Council (NMHC) is a national association representing

More information

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and &

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and & &01 GENERAL To be developed. All of the exceptions have to be coordinated. &02 SPECIAL USE AND OCCUPANCY &02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections &02.1.1 and &02.1.2.

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

* RESIDENTIAL PLAN REVIEW *

* RESIDENTIAL PLAN REVIEW * CITY OF DES MOINES, IOWA COMMUNITY DEVELOPMENT DEPARTMENT PERMIT AND DEVELOPMENT CENTER 602 Robert D. Ray Drive DES MOINES, IOWA 50309 Phone: 515.283.4200 Facsimile: 515.283.4270 Based on the scope of

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

PLASTIC CHAPTER 26. SECTION 2602 DEFINITIONS Definitions. The following terms are defined in Chapter

PLASTIC CHAPTER 26. SECTION 2602 DEFINITIONS Definitions. The following terms are defined in Chapter CHAPTER 26 PLASTIC SECTION 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer,

More information

Knowledge Objectives (3 of 3)

Knowledge Objectives (3 of 3) Building Systems Knowledge Objectives (1 of 3) Identify construction types in commercial and residential structures. Explain fire behavior as it relates to the method of construction. Discuss the structural

More information

FS , 712, 713, 714

FS , 712, 713, 714 VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL JUNE 28-29, 2012 PUBLIC COMMENTS CTC Code Change Proposal FS50-12 was Approved as Modified as shown below - No public comments for the Group

More information

By James Tente, MCP, CBO,CFM

By James Tente, MCP, CBO,CFM Significant Changes (proposed) December 20, 2018 By James Tente, MCP, CBO,CFM jtente@knoxvilletn.gov The goal of these presentations is to identify and discuss the building code changes and the impacts

More information

CHAPTER 6 INTERNATIONAL RESIDENTIAL CODE

CHAPTER 6 INTERNATIONAL RESIDENTIAL CODE CHAPTER 6 INTERNATIONAL RESIDENTIAL CODE Sec.3-6-1. Adoption of the International Residential Code. That certain documents three copies of which are on file in the office of the village clerk, being marked

More information

General Building Information

General Building Information Software Module s Description Page 1 General Building Information BUILDING AREA AND HEIGHT - This module designed to determine the height and area of buildings on the basis of occupancy group classification

More information

Interior FRT Wood. References to ICC Building Codes

Interior FRT Wood. References to ICC Building Codes Interior FRT Wood References to ICC Building Codes Table of Contents International Building Code (IBC) 1 International Residential Code (IRC) 6 International Mechanical Code (IMC) 7 INTERNATIONAL BUILDING

More information

ORDINANCE NO BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF MANHATTAN, KANSAS: Section Adoption of the International Building Code.

ORDINANCE NO BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF MANHATTAN, KANSAS: Section Adoption of the International Building Code. ORDINANCE NO. 7222 AN ORDINANCE AMENDING CHAPTER 8 OF THE CODE OF ORDINANCES, REGULATING BUILDINGS WITHIN THE CORPORATE LIMITS OF THE CITY OF MANHATTAN, KANSAS; INCORPORATING BY REFERENCE THE INTERNATIONAL

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

SINGLE FAMILY REGULATIONS UNDERSTORY AREAS ORDINANCE NO.

SINGLE FAMILY REGULATIONS UNDERSTORY AREAS ORDINANCE NO. SINGLE FAMILY REGULATIONS UNDERSTORY AREAS ORDINANCE NO. AN ORDINANCE OF THE MAYOR AND CITY COMMISSION OF THE CITY OF MIAMI BEACH, FLORIDA, AMENDING THE LAND DEVELOPMENT REGULATIONS OF THE CODE OF THE

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Firewall (construction) From Wikipedia, the free encyclopedia

Firewall (construction) From Wikipedia, the free encyclopedia 페이지 1 / 5 Firewall (construction) From Wikipedia, the free encyclopedia A firewall is a fireproof barrier used to prevent the spread of fire between or through buildings, structures, electrical substation

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES The following is the Study Group report that was considered by the CTC at its October 13-14, 2011 meeting.

More information

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017 Shaft Wall Solutions for Wood-Frame Structures Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017 Shaft Walls Shaft Walls Form Shaft Enclosures The purpose

More information

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E.

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E. NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2010 CALIFORNIA BUILDING CODE (CBC ) Prepared for Wood Products Council WoodWorks Presented by James E. Churchill, P.E. Churchill Engineering,

More information

Interior FRT Wood. References of Previous Model Building Codes

Interior FRT Wood. References of Previous Model Building Codes Interior FRT Wood References of Previous Model Building Codes Table of Contents SBBCI Standard Building Code 1 ICBO Uniform Building Code 3 BOCA National Building Code 5 10-SBBCI STANDARD BUILDING CODE

More information

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SCOPE: The City of Lawrence requirements for application of current code provisions. This shall apply to alterations

More information

SECTION 702 DEFINITIONS

SECTION 702 DEFINITIONS ACTION: Final DATE: 05/6/017 :17 PM 4101:1-7-01 Fire and smoke protection features. [Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard,

More information

2012 IBC Inspection of Fire-resistance Rated Walls

2012 IBC Inspection of Fire-resistance Rated Walls Accreditation 2012 IBC Inspection of Fire-resistance Rated Walls Based on the 2012 International Building Code (IBC ) The International Code Council has been accredited as an Authorized Provider by the

More information

RESIDENTIAL DESIGN GUIDELINES FOR BENT TREE OF ROGERS

RESIDENTIAL DESIGN GUIDELINES FOR BENT TREE OF ROGERS RESIDENTIAL DESIGN GUIDELINES FOR BENT TREE OF ROGERS DATE: October 17, 2000 RESIDENTIAL DESIGN GUIDELINES FOR BENT TREE OF ROGERS INTRODUCTION These Residential Design Guidelines have been approved by

More information

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL

More information

CHAPTER 5: RESIDENTIAL USE DEVELOPMENT STANDARDS

CHAPTER 5: RESIDENTIAL USE DEVELOPMENT STANDARDS CHAPTER 5: RESIDENTIAL USE DEVELOPMENT STANDARDS ARTICLE 1: SINGLE FAMILY 305-01. Application The provisions of this Article shall apply to the following uses in any zone: (e) (f) One (1) single family

More information

CHAPTER 6 TYPES OF CONSTRUCTION

CHAPTER 6 TYPES OF CONSTRUCTION CHAPTER 6 TYPES OF CONSTRUCTION SECTION 61 GENERAL 61.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 62 CONSTRUCTION CLASSIFICATION

More information

2018 IBC Chapter 6 Types of Construction

2018 IBC Chapter 6 Types of Construction Study Session 3 2018 IBC Chapter 6 Types of Construction OBJECTIVE: REFERENCE: KEY POINTS: To gain an understanding of how a building is classified as a specific type of construction, based on the construction

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

General Residential Code Requirements

General Residential Code Requirements General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the

More information

RESIDENTIAL GARAGE AND DRIVEWAY

RESIDENTIAL GARAGE AND DRIVEWAY RESIDENTIAL GARAGE AND DRIVEWAY GENERAL REQUIREMENTS: PERMIT: For new garages or garage additions the fee is $20.00 per hundred square feet or portion thereof ($50 minimum). Demolition permits are $65.00

More information

RESIDENTIAL DISTRICT (R)

RESIDENTIAL DISTRICT (R) ARTICLE 12 RESIDENTIAL DISTRICT (R) Sections: 12-1 Application/Purpose 12-2 Permitted Uses 12-3 Conditional Uses 12-4 Development Standards 12-5 Parking Regulations 12-6 Sign Regulations 12-7 Height, Area,

More information

ARCHITECTURAL REVIEW CHECKLIST ARCHITECTURAL REVIEW SUBMITTAL REQUIREMENTS SINGLE MODEL

ARCHITECTURAL REVIEW CHECKLIST ARCHITECTURAL REVIEW SUBMITTAL REQUIREMENTS SINGLE MODEL 9500 Civic Center Drive Thornton, CO 80229 CITY DEVELOPMENT DEPARTMENT ARCHITECTURAL REVIEW CHECKLIST 303-538-7295 Single-Family Detached and Single-Family Attached Homes developmentsubmittals@cityofthornton.net

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

G59 12: Final Decision AMPC1

G59 12: Final Decision AMPC1 G59 : Final Decision AMPC 0, 406.3, 406.3., 406.3., 406.3.3, 406.3.4 Add new definition as follows: Proposed Change as Submitted PRIVATE GARAGE. A building or portion of a building in which motor vehicles

More information

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors

More information

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017 Shaft Wall Solutions for Wood-Frame Structures Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017 Course Description It is fairly common for light wood-frame commercial

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code (IBC) Introduction Determining fire resistance Test standards Definitions Alternate

More information

Morgan County Planning Commission. Petition for: Text Amendment

Morgan County Planning Commission. Petition for: Text Amendment Staff Report Morgan County Planning Commission Petition for: Text Amendment Applicant: Applicant s Agent: Zoning Ordinance: Morgan County Planning & Development City of Bostwick Zoning Ordinance Article

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 21 13 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code

More information

NAHB s Recommendations on Critical 2015 ICC Code Change Proposals

NAHB s Recommendations on Critical 2015 ICC Code Change Proposals NAHB s Recommendations on Critical 2015 ICC Code Change Proposals NAHB is urging our members to get involved locally in the ICC code development process and schedule a meeting with your state and local

More information

Westtown Township Building Permit Application Instructions Notes:

Westtown Township Building Permit Application Instructions Notes: Building Permit Application Instructions Notes: All work performed in conjunction with this permit shall conform with the Pennsylvania Uniform Construction Code (PA UCC), all current adopted building codes,

More information

IRC Fire Protection of Floors Code Language 2012 IRC R IRC R302.13

IRC Fire Protection of Floors Code Language 2012 IRC R IRC R302.13 IRC Fire Protection of Floors Code Language 2012 IRC R501.3 2015 IRC R302.13 Current IRC Code Adopted into Some State Laws R501.3 Fire Protection of Floors Floor assemblies, not required elsewhere in this

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760)

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760) BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS INFORMATION GUIDELINE 9 January 2017 CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA 92025 (760) 839-4647 This information bulletin

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Accreditation 2012 IBC Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code The International Code Council has been accredited as an Authorized Provider

More information

MINIMUM PLAN INFORMATION REQUIRED FOR A BUILDING PERMIT

MINIMUM PLAN INFORMATION REQUIRED FOR A BUILDING PERMIT DEVELOPMENT SERVICES DEPARTMENT BUILDING & SAFETY DIVISION 156 S. BROADWAY, SUITE 130 TURLOCK, CALIFORNIA 95380 PHONE 209-668-5560 FAX 209-668-5107 MINIMUM PLAN INFORMATION REQUIRED FOR A BUILDING PERMIT

More information

The International Building Code (IBC ) is a model code that provides minimum requirements to safeguard the public health, safety and general welfare

The International Building Code (IBC ) is a model code that provides minimum requirements to safeguard the public health, safety and general welfare AIA Austin is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program will be reported to AIA/CES for AIA

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

Adds a new definition for tenant

Adds a new definition for tenant CODE CHANGE RATIONALE SUMMARY Mod 1628) 202 TENANT. Any person, agent, firm, corporation or division, who uses or occupies land, a building or portion of a building by title, under a lease, by payment

More information

SECTION R327.3 STANDARDS OF QUALITY

SECTION R327.3 STANDARDS OF QUALITY California Residential Code Section R327 Conformance Checklist Per CRC R327.1.4 The local building official shall, prior to construction, provide the owner or applicant a certification that the building

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

PART R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT

PART R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT PART 3.2 - R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT Uses 1 The following uses are permitted: (a) single family dwellings; (b) two family dwellings; (c) multiple dwellings; (d) churches; (e) public

More information

Design & Testing of Fire Resistance and Smoke Resistant Barriers. Rich Walke UL Codes and Advisory Services

Design & Testing of Fire Resistance and Smoke Resistant Barriers. Rich Walke UL Codes and Advisory Services Design & Testing of Fire Resistance and Smoke Resistant Barriers Rich Walke UL Codes and Advisory Services UL and the UL logo are Trademarks of UL 2014 June 4, 2014 Fire-Resistance-Rated Construction 2

More information

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) TWELFTH PRINTING (Updated December 6, 2016) Note for 706.5.1: This is an erratum in the 8 th, 9 th, 10 th and 11 th printing only. The reference is correct in other editions. 706.5.1 Exterior walls. Where

More information

MOBILE HOME DISTRICT OR "MH" DISTRICT AND MOBILE HOMES EXCLUSIVE OF MOBILE HOME DISTRICTS (Ord.No )

MOBILE HOME DISTRICT OR MH DISTRICT AND MOBILE HOMES EXCLUSIVE OF MOBILE HOME DISTRICTS (Ord.No ) Page 1 of 6 SECTION 27 MOBILE HOME DISTRICT OR "MH" DISTRICT AND MOBILE HOMES EXCLUSIVE OF MOBILE HOME DISTRICTS (Ord.No.315-450) A. GENERAL DESCRIPTION: The purpose of this Zoning District is to provide

More information

AEROSOLS CHAPTER 28. Level 3 aerosol products. Those with a total chemical heat

AEROSOLS CHAPTER 28. Level 3 aerosol products. Those with a total chemical heat CHAPTER 28 AEROSOLS SECTION 2801 GENERAL 2801.1 Scope. The provisions of this chapter, the construction code in effect at the time of construction and NFPA 30B shall apply to the manufacturing, storage

More information

Let s begin, your first session, module 1, which will cover chapter 2, definitions and a portion of chapter 3, building planning.

Let s begin, your first session, module 1, which will cover chapter 2, definitions and a portion of chapter 3, building planning. Let s begin, your first session, module 1, which will cover chapter 2, definitions and a portion of chapter 3, building planning. 1 This chapter sets forth the definitions of terms used in the 2013 edition

More information

CITY OF TROY, MISSOURI Building Permit Application. Type of Permit: Residential Commercial. Company: Contact person: Address # Street Name:

CITY OF TROY, MISSOURI Building Permit Application. Type of Permit: Residential Commercial. Company: Contact person: Address # Street Name: CITY OF TROY, MISSOURI Building Permit Application Instructions: Please print clearly and complete the entire form or the application will not be processed and the permit will not be issued. Date of Application

More information

NOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable.

NOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable. Applicant s Name: New Commercial - Commercial Additions Renovations Permit Plan Submittal Check List Applicant s Phone Number (s): Project Address: Project Type: _New Commercial or Commercial Addition

More information

Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential. presented by

Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential. presented by Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential presented by T. Eric Stafford T. Eric Stafford & Associates, LLC This material is protected

More information

Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17)

Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17) Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17) Plan Check #: Permit App. #: Job Address: Zone: Maximum Allowed RFA: Plan Check Engineer: Phone: Fax: (E-mail: firstname.lastname@lacity.org)

More information

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system. Draft curtains are typically used in warehouses, aircraft hangars and large industrial plants to contain or channel smoke that rises to the ceiling in a fire. They can keep the smoke from rolling across

More information

Fences, Wall and Hedge Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations

Fences, Wall and Hedge Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations Section 16.40.040 Fence, Wall and Hedge Regulations 16.40.040.1 All fences, walls and hedges shall comply with the following requirements which relate to height, location and design. 16.40.040.2 Definitions

More information

Wood Frame. from the Pacific Northwest. British Columbia Building Enclosure Council

Wood Frame. from the Pacific Northwest. British Columbia Building Enclosure Council Mid-Rise Wood Frame Buildings Experiences from the Pacific Northwest British Columbia Building Enclosure Council April 2009 Outline of Talk Regulations Key Issues Project Case Studies 2 Speaker Background

More information

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer,

More information

Learning Objectives. Copyright Materials NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC )

Learning Objectives. Copyright Materials NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC ) NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC ) Prepared dfor Wood dproducts Council WoodWorks Presented by James E. Churchill, P.E. ChurchillEngineering

More information

Butte County Fire Department Fire Prevention Bureau 176 Nelson Avenue Oroville, CA Office (530)

Butte County Fire Department Fire Prevention Bureau 176 Nelson Avenue Oroville, CA Office (530) 2016 CBC Chapter 7A and CRC Section R337 (The use of paints, coatings, stains, or other surface treatments are not an approved method of protection as required in this chapter.) The Wildland Urban Interface

More information

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:

More information

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction.

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction. Plan Examination 1 Plan ExaminationPurpose 2 Catch problems in advance of construction. 3 1 Discovery of problems in the field results in higher cost. 4 Can a good plan review eliminate all problems in

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018 OLDCASTLE ARCHITECTURAL INSULTECH CSI Sections: 04 22 00 Concrete Unit Masonry 04 22 00.13 Concrete Unit Veneer Masonry 1.0 RECOGNITION Oldcastle Architectural Insultech insulated concrete masonry unit

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

City of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota Phone Fax emi mn s

City of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota Phone Fax emi mn s City of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota 56601-3116 Phone 218-759-3573 Fax 218-759-3590 emi mn s Residential Header and Girder Spans Requirements 2015 MSBC Chapter

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

CITY OF KIRKWOOD SINGLE FAMILY SITE PLAN WORKSHEET

CITY OF KIRKWOOD SINGLE FAMILY SITE PLAN WORKSHEET S. F. Review No. ZONING DISTRICT PROPERTY ADDRESS CITY OF KIRKWOOD SINGLE FAMILY SITE PLAN WORKSHEET A Missouri Minimum Standards Boundary Survey is required to be filed in support of this worksheet, showing

More information

635 BUREAU OF BUILDING CODES AND STANDARDS MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE

635 BUREAU OF BUILDING CODES AND STANDARDS MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE 16 DEPARTMENT OF PUBLIC SAFETY 635 BUREAU OF BUILDING CODES AND STANDARDS Chapter 3: MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE SUMMARY: This chapter establishes the Commercial

More information

BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA

BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA 2016-449 BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA RESOLUTION AMENDING THE SARPY COUNTY BUILDING CODE THROUGH THE ADOPTION OF THE FOLLOWING REVISED CODES: THE INTERNATIONAL BUILDING CODE, 2012

More information

City of Republic Community Development Girder and Header Spans for Exterior Walls

City of Republic Community Development Girder and Header Spans for Exterior Walls City of Republic Community Development Girder and Header Spans for Exterior Walls Revision Date: January 2017 2012 IRC Table R502.5(1) Girder Spans a and Header Spans a for Exterior Bearing Walls (Maximum

More information

ARTICLE 987. PD 987. PD 987 was established by Ordinance No , passed by the Dallas City Council on June 14, (Ord.

ARTICLE 987. PD 987. PD 987 was established by Ordinance No , passed by the Dallas City Council on June 14, (Ord. ARTICLE 987. PD 987. SEC. 51P-987.101. LEGISLATIVE HISTORY. PD 987 was established by Ordinance No. 30512, passed by the Dallas City Council on June 14, 2017. SEC. 51P-987.102. PROPERTY LOCATION AND SIZE.

More information