Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
|
|
- Gervais Strickland
- 6 years ago
- Views:
Transcription
1 Available online at ScienceDirect Energy Procedia 78 (215 ) th International Building Physics Conference, IBPC 215 Hygrothermal Performance of a Massive Stone Wall with Interior Insulation: an In-Situ Study for Developing a Retrofit Measure Paul Klõšeiko* a, Targo Kalamees a, Endrik Arumägi a, Urve Kallavus b a Chair of Building Physics and Energy Efficiency, Tallinn University of Technology, Ehitajate tee 5, 1986, Tallinn, Estonia b Centre for Materials Research, Tallinn Univesity of Technology, Ehitajate tee 5, 1986, Tallinn, Estonia Abstract In this study, hygrothermal performance of a newly built internally insulated exterior wall of museum building was monitored by field measurements. The double leaf rubble stone wall consisted of 55mm outer leaf, 32mm air cavity, 1mm mineral wool insulation/wooden framework, 15mm inner leaf. Although a cavity with ventilation holes was included in the design, very high moisture conditions (RH 95 99%) were present during 8 months after erection. Effects of two drying methods were tested. Analysis of the results suggests that the problems were caused by built-in moisture and erection process of such walls (either as newly built or as a renovation measure) should take it into account. 215 The Authors. Published by by Elsevier Elsevier Ltd. Ltd. This is an open access article under the CC BY-NC-ND license Peer-review ( under responsibility of the CENTRO CGRESSI INTERNAZIALE SRL. Peer-review under responsibility of the CENTRO CGRESSI INTERNAZIALE SRL Keywords: interior insulation, hygrothermal performance, mould risk, case study, energy renovation 1. Introduction Massive rubble stone walls found in various historic buildings have high thermal transmittance and low surface temperature during winter. This causes a risk of exceeding the critical relative humidity levels (for example surface condensation, or mould growth) and low thermal comfort. Due to decorative surfaces of exterior walls, thermal insulation on the outside is not acceptable from heritage protection or architectural point of view. One possible measure for thermal upgrade while preserving the visual appearance of the unplastered wall is to add insulation and a new layer of masonry wall to the interior side. However, because of high thermal transmittance of original wall, * Corresponding author. Tel.: ; fax: address: paul.kloseiko@ttu.ee The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license ( Peer-review under responsibility of the CENTRO CGRESSI INTERNAZIALE SRL doi:1.116/j.egypro
2 196 Paul Klõšeiko et al. / Energy Procedia 78 ( 215 ) interior insulation is also problematic. The designer selected such solution for a museum building, modelled its performance according to the EN standard and deemed the results satisfactory. This paper presents the in-situ measurement results and analyses the hygrothermal performance of that wall. 2. Methods The studied building is a modernized copy of a cow barn from Setu region in Estonia. It is planned to be used as a visitor center of a museum. Compared to the original, the new building has an insulated envelope and modern HVAC systems due to its new use. The wall consists of 55mm thick rubble stone masonry outer leaf, 1mm insulation/wooden framing, 18mm wooden boarding, PE foil and 2mm inner masonry leaf (Fig. 1). There is also a 32mm thick air cavity between the insulation and outer leaf, which should be naturally ventilated with outside air through Ø2mm holes (spaced 6 1mm apart) in lower part of the wall and a ventilation gap in the eaves. The main study concentrates on a wall section situated on the northern façade of the building. The studied wall was divided into 2 sections one where natural ventilation between thick masonry wall and insulation is possible according to the design and another in which the ventilation is limited. Ø1mm holes Fig. 1 Test setup: vertical section (left), horizontal section (top right) and view to the measured northern façade with dehumidification system installed (bottom right).
3 Paul Klõšeiko et al. / Energy Procedia 78 ( 215 ) The following measurement devices were used in monitoring of the hygrothermal performance of the building: T&RH probes: Rotronic HygroClip HC2-C5 (accuracy ±.3 C, ±1% RH); Heat flux plates: Hukseflux HFP1 (accuracy ±5%); Data logger Grant Squirrel SQ22 1F8 (accuracy ±.5% of readings ±.25% of range); Data logger Grant Squirrel SQ21 (accuracy ±.1% of readings ±.1% of range); Temperature probes: Onset Hobo TMC6-HD (accuracy ±.25 C); T&RH data loggers: Onset Hobo U12 and UX1 (accuracy ±.21 C, ± % RH); Stick-in wood moisture pins measured with Gann Hydrotest LG3 (resistance measurement principle). The main events of the study are following: the sensors were installed in Nov.-Dec. 213; logging of measurement results started after the completion of interior construction works (Feb. 214); on 17. Jul. the structure was opened to investigate possible mould growth; enlarged ventilation holes were cut on 29.. Jul. 214; dehumidification system was installed on 7. Oct. 214; operation of the dehumidifiers was halted for the period of Oct. 214; the dismantling of the dehumidification system took place on 13. Nov To assess the hygrothermal conditions in the structure, Viitanen s mould growth model [1,2], is used. Based on the hygrothermal conditions, critical relative humidity (RH crit [% RH]) is calculated, above which mould growth is possible. Also, from hygrothermal conditions, time, and sensitivity of the material, mould growth indexes (M [-]) are calculated. The index describes the intensity of the mould growth with the lowest value corresponding to No growth and highest value 6 corresponding to Heavy and tight growth. First attempt to improve the hygrothermal situation in the structure was drilling Ø1mm ventilation holes at 2-3m intervals in lower part of the outer leaf to complement the original ventilation (Ø2mm holes). Later, more efficient solutions were sought and two Munters MCS3 rotary desiccant dehumidifiers were used. Dried and to some extent heated air was blown through temporary piping into previously drilled Ø1mm ventilation holes. The dehumidification system and drilled holes are also visible in Fig. 1 (bottom right). The rated air flow of dried air of the dehumidifier is 3m³/h, which was divided between 3 and 7 ventilation holes (for both dehumidifiers respectively). 3. Results and discussion 3.1. Post-construction monitoring Due to limited space, only more distinct results of all measurements are exhibited in this paper. Fig. 2 (top) gives the relative humidity levels between PE foil and wooden boarding during the whole measurement period representing the inner layer (Pos. 1 & 3). Also included is the critical relative humidity calculated according to Viitanen s model, above which mould growth is possible. Fig. 2 (bottom) gives the same data for the air gap between insulation and outer masonry leaf representing the outermost measured layer (Pos. 2 & 4). Unfortunately, the data from RH sensors from April till June is missing due to power outage in the line to the data logger. Measurement results from beginning of July showed RH values exceeding critical levels in all sections. Calculation of mould index according to Viitanen s model (Fig. 3) returned worrying results. For the ventilation gap in ventilated section of the wall, the value was 4.7 ( moderate to plenty of mould growth ) and around 3 ( new spores produced ) in the insulation layer. The inner layer (between PE foil and wooden cladding) had conditions suitable for initial growth of mould. Moisture content of wooden beam end (Pos. 5) supported by the outer layer (see Fig. 3) exceeded the critical levels for decay fungi of 25% [3]. Thus, it was decided to open the structure. 5 holes (situated throughout the building) were cut to the wall structure from the inside. Material samples of wooden framing and mineral wool were analyzed in two laboratories. Also, moisture content of the framing was measured using pin-type electrodes and relative humidity in air gap was sampled with a probe. Both proved to be in range similar to or below the results from wall section under constant monitoring. Despite distressing measurement and calculation results, it was fortunate to find that no large scale damage had taken place. Limited mould growth was discovered by one laboratory from 2 of the 5 locations. The probable cause of that was the use of impregnated wood in the outer layers, which were in most serious conditions, but not taken into account in calculations. As studies have shown [4], the impregnation will delay the effects of mould and decay fungi, however, if the suitable conditions remain it might not prevent them indefinitely. Also, the wooden boarding of inner layer (Pos.1&3) and beams (Pos.5) were built of untreated wood and mineral wool is also susceptible to mould growth.
4 198 Paul Klõšeiko et al. / Energy Procedia 78 ( 215 ) Relative humidity RH, % Relative humidity RH, % Feb.14 Mar.14 Apr.14 May.14 Jun.14 Jul.14 Aug.14 Sep.14 Oct.14 Nov.14 Dec.14 Jan RH Pos.1 (Vent.) RH Pos.3 (Unvent.) Feb.14 Mar.14 Apr.14 May.14 Jun.14 Jul.14 Aug.14 Sep.14 Oct.14 Nov.14 Dec.14 Jan.15 Ø1mm holes Ø1mm holes RH Pos.4 (Unvent.) RH Pos. 5 (Wooden beam, vent.) RH crit RH Pos.2 (Vent.) Fig. 2 Levels of relative humidity between wooden boarding and PE foil (Pos.1 & 3, top figure) and in the upper part of the air gap between insulation and outer masonry leaf (Pos.2, 4 & 5, bottom figure). Moisture content, % 3 25 MC crit"25%" MC wooden beam at outer masonry leaf (top), Pos.5 2 MC wooden framing (bottom) 15 MC "18%" 6 Mould index in ventilation gap (Pos. 2) 5 Mould index betw. insulation and wind barrier 1 4 Mould index betw. boarding and foil (Pos. 1) Feb.14 Mar.14 Apr.14 May.14 Jun.14 Jul.14 Aug.14 Sep.14 Oct.14 Nov.14 Dec.14 Jan.15 Ø1mm holes Mould index M, - Fig. 3 Measured moisture content of wood in two points and calculated mould index [1,2] in three layers within the ventilated section of the structure ( no growth ; 6 very heavy and tight growth ; surface class: sensitive to mould, C mat = 1).
5 Paul Klõšeiko et al. / Energy Procedia 78 ( 215 ) Analysis of moisture excess (difference between moisture content of air in studied section and that of outdoor air; ν [g/m³]) showed that the moisture content of the air in the structure was higher than both in indoor and outdoor air (positive ν, see Fig. 4). The indoor air moisture excess was ~ 2g/m³ for most of the measurement period. The building has until May 215 been rarely used and moisture excess present in indoor air could be the result of drying of the structure. ν between the PE foil and insulation was about twice the indoor ν. In the case of air gap, the moisture excess was 2 (ventilated section) to 4 times higher than indoors (unventilated section, limited by saturation). The previous hinted that the root cause of the problem could be built-in moisture of the thick masonry leaves Drying efforts To prevent further complications, more effective air gap ventilation was considered to complement the 2mm ventilation holes. On 29 th of July Ø1mm holes were cut to the bottom of the outer masonry leaf with a step of 2-3m. The measurement results for the different drying periods are given in Fig. 4. Considering the RH levels, the effect of the ventilation holes seems to be negligible. In the ventilation gap, the critical RH was exceeded considerably, while the reduction of RH levels between PE foil and wooden cladding (Pos. 1 & 3) was caused by the increasing temperature difference of autumn period. Mould indexes for the outer layers showed either rise or no decline (see Fig. 3). Installation of the dehumidifier blowing warmer dried air (average temperature in the wall inlets was on average 6-9 C higher and their moisture content was 3-4 g/m³ lower than that of the outdoor air) into the ventilation holes enhanced the situation throughout all layers of the structure. Turning the dehumidification off revealed the surge in RH levels in the ventilation gap suggesting that the structure was not sufficiently dry yet and it was decided to continue the procedure. Relative humidity RH, % Relative humidity RH, % ν Pos.3 (unvent.) ν Indoor air ν Pos.1 (vent.) 2 Ø1mm holes RH crit RH Pos.3 (unvent.) 6 8 RH Pos.1 (vent.) Jul.14 Aug.14 Sep.14 Oct.14 Nov.14 Dec.14 Jan.15 Ø1mm holes ν Indoor air RH Pos.4 (Unvent.) RH Pos 5. (Wooden beam, vent.) RH Pos.2 (Vent.) RH crit ν Pos.2 (Vent.) Jul.14 Aug.14 Sep.14 Oct.14 Nov.14 Dec.14 Jan.15 ν Pos.4 (Unvent.) h avg moisture excess ν, g/m³ 24h avg moisture excess ν, g/m³ Fig. 4 Drying periods: levels of relative humidity and moisture excess between wooden boarding and PE foil (Pos.1 & 3, top figure) and in the upper part of the air gap between insulation and outer masonry leaf (Pos.2, 4 & 5, bottom figure).
6 2 Paul Klõšeiko et al. / Energy Procedia 78 ( 215 ) Low outdoor air moisture content caused by low air temperatures rendered the drying of the structure by using dehumidified air less effective and the system was disassembled in mid-november. Later analysis also revealed that dehumidification in the studied section during the second period was also hampered by electrical problems of one dehumidifier. In contrary to the pre-dehumidification periods, the moisture excess in ventilation gap (see Fig. 4 bottom) was reduced (Pos. 2) and it stayed similar to that of the indoor air, suggesting at least some success in the efforts of drying the wall. Moisture content in unventilated section of the wall (Pos. 4) was still limited by saturation. Although the unventilated section of the wall was not directly connected to the dehumidifier, it was possibly affected by it through air leakages (especially in wooden cladding layer). Monitoring of the structure will continue into the year of 215, thus providing data on the hygrothermal performance of the solution and helps to take the seasonal changes into account. 4. Conclusions In this study, hygrothermal performance of a newly built internally insulated exterior wall of museum building was monitored by field measurements. The double leaf rubble stone wall consists of 55mm outer leaf, 32mm air cavity, 1mm mineral wool insulation/wooden framework, 15mm inner leaf. RH and temperature monitoring points covered every layer of the wall structure. Wood moisture pins were installed in wooden framing and in a wooden beam that was supported by the outer leaf. The wall was built during the autumn-winter period as building as usual. However, massive rubble stone walls consist of a lot of built-in moisture that was not allowed to dry out before insulating and constructing the inner leaf. Even though an air cavity with ventilation holes was included in the design, conditions with very high relative humidity (RH 95 99% RH) were present during 8 months after erection. Structure was opened and from two of the five locations limited mould growth was found by one laboratory. Effects of two drying methods were tested and monitored. Enlarged natural ventilation holes had little or no effect on the moisture levels of air in different layers of the structure. Installation of a dehumidifier and blowing warmer dried air to the ventilation holes enhanced the situation throughout the construction and RH levels were reduced to safer levels. Analysis of the results suggests that erection process of such walls (either as newly built or as a renovation measure) should take into account the drying of masonry wall. Inability to do so will cause levels of high relative humidity throughout the structure, which is especially dangerous when using materials sensitive to mould and rot. Acknowledgements The study has been conducted as part of the IUT1-15 project Nearly-zero energy solutions and their implementation on deep renovation of buildings. Publication of this article was supported by the ESF measure 1.2.4, Development of cooperation and innovation of universities, the sub-measure Doctoral Schools that finances the project Construction and Environmental Engineering PhD School project code The authors wish to thank Estonian Open Air Museum for pleasant collaboration and the possibility to carry out the study. References [1] Viitanen H, Ojanen T, Peuhkuri R. Mould growth modelling to evaluate durability of materials. In: Freitas VP de, Corvacho MH, Lacasse M, editors. Proceedings of the 12DBMC - International Conference on Durability of Building Materials and Components, Porto: 211. [2] Hukka A, Viitanen H. A mathematical model of mould growth on wooden material. Wood Science and Technology 1999;33: doi:1.17/s [3] Viitanen H, Vinha J, Salminen K, Ojanen T, Peuhkuri R, Paajanen L, et al. Moisture and Bio-deterioration Risk of Building Materials and Structures. Journal of Building Physics 21;33: doi:1.1177/ [4] Metsä-Kortelainen S, Paajanen L, Viitanen H. Durability of thermally modified Norway spruce and Scots pine in above-ground conditions. Wood Material Science and Engineering 211;6: doi:1.18/
Air leakage and hygrothermal performance of an internally insulated log house
Air leakage and hygrothermal performance of an internally insulated log house Üllar Alev, M.Sc 1 Andres Uus, M.Sc 2,3 Marko Teder, M.Sc 2 Martti-Jaan Miljan, M.Sc 2 Targo Kalamees, Professor 1 1 Tallinn
More informationField measurements of moisture variation in cold ventilated attics with different ceiling constructions
Aalborg Universitet Field measurements of moisture variation in cold ventilated attics with different ceiling constructions Hansen, Thor; Møller, Eva B. Published in: Energy Procedia DOI (link to publication
More informationMoisture conditions in passive house wall constructions
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 219 224 6th International Building Physics Conference, IBPC 2015 Moisture conditions in passive house wall constructions
More informationHygrothermal behaviour of timber frame walls finished with a brick veneer cladding
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 363 368 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 907 912 6th International Building Physics Conference, IBPC 2015 Potential for finance and energy savings of detached
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1443 1448 6th International Building Physics Conference, IBPC 2015 Hygrothermal Behaviour of Partly Insulated and Partly
More informationDeterioration of building envelope of wooden apartment buildings built before 1940 based on external survey Paul Klõšeiko, Tõnis Agasild, Targo Kalame
Deterioration of building envelope of wooden apartment buildings built before 1940 based on external survey Paul Klõšeiko, Tõnis Agasild, Targo Kalamees Chair of Building Physics and Architecture, Tallinn
More informationAnalysis of the suitability of mould growth models for the risk assessment of woodfibre internal wall insulation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 183 188 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3458 3464 6th International Building Physics Conference, IBPC 2015 Green building envelopes Moisture safety in ventilated
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3043 3048 6th International Building Physics Conference, IBPC 2015 Integrating Low-temperature Heating Systems into Energy
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1907 1912 6th International Building Physics Conference, IBPC 2015 The principles of sauna physics K. Nore*, D. Kraniotis,
More informationThis is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.
Powered by TCPDF (www.tcpdf.org) This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail. Thalfeldt, Martin; Simson, Raimo;
More informationMould growth in building materials Experiments & Modelling
TTY Laboratory of Structural Engineering, Tampere University of Technology, Finland VTT Indoor Environment and Building Services, Technical Research Centre of Finland Mould growth in building materials
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1478 1483 6th International Building Physics Conference, IBPC 2015 Measuring the Hygrothermal Performance of an Interior
More informationAvailable online at ScienceDirect. Energy Procedia 96 (2016 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 96 (2016 ) 768 778 SBE16 Tallinn and Helsinki Conference; Build Green and Renovate Deep, 5-7 October 2016, Tallinn and Helsinki Energy
More informationA MATHEMATICAL MODELING OF MOISTURE BEHAVIOUR AND MOULD GROWTH IN BUILDING ENVELOPES
A MATHEMATICAL MODELING OF MOISTURE BEHAVIOUR AND MOULD GROWTH IN BUILDING ENVELOPES Kati Salminen, M. Sc. Student 1) Juha Vinha, Lic.Tech. 1) Hannu Viitanen, Ph.D. 2) 1) Laboratory of Structural Engineering,
More informationProcedia - Social and Behavioral Sciences 216 ( 2016 )
Available online at www.sciencedirect.com ScienceDirect Procedia - Social and Behavioral Sciences 216 ( 2016 ) 655 661 Urban Planning and Architecture Design for Sustainable Development, UPADSD 14-16 October
More informationDevelopment of an improved model for mould growth: Modelling
Development of an improved model for mould growth: Modelling Hannu Viitanen, Ph.D., ) hannu.viitanen@vtt.fi Juha Vinha, Dr. Tech.,) juha.vinha@tut.fi Ruut Peuhkuri, Ph.D.,) ruut.peuhkuri@vtt.fi Tuomo Ojanen,
More informationAssessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels
Assessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels Pär Johansson, M.Sc. 1 1 Chalmers University of Technology, Sweden KEYWORDS: vacuum insulation panels, retrofitting,
More informationMoisture supply Set Point for avoidance of moisture damage in Swedish multifamily houses
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Moisture supply Set Point
More informationConcept 9: Exterior refurbishment of wooden frame walls with flex system board insulation
Concept 9: Exterior refurbishment of wooden frame walls with flex system board insulation Cross section figures of the existing wall / the refurbishment concept Market potential and reasoning Application
More informationA sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.
A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. Published in: Symposium Building Physics in honour of Prof. Hugo Hens, Leuven, October 2008 Published: 01/01/2008
More informationImpacts of energy retrofits on hygrothermal behavior of Finnish multi-family buildings
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 700 704 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,
More informationScienceDirect. Influence of Moisture Dry-out on Hygrothermal Performance of Prefabricated Modular Renovation Elements
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 96 (2016 ) 745 755 SBE16 Tallinn and Helsinki Conference; Build Green and Renovate Deep, 5-7 October 2016, Tallinn and Helsinki Influence
More informationMeasured temperature and moisture conditions in the roof attic of a one-and-a-half story house Nielsen, Anker; Morelli, Martin
Aalborg Universitet Measured temperature and moisture conditions in the roof attic of a one-and-a-half story house Nielsen, Anker; Morelli, Martin Published in: Energy Procedia DOI (link to publication
More informationA sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.
A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. Published in: Symposium Building Physics in honour of Prof. Hugo Hens, Leuven, October 2008 Published: 01/01/2008
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1513 1518 6th International Building Physics Conference, IBPC 2015 Assessment of natural ventilation within buildings
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 860 864 6th International Building Physics Conference, IBPC 2015 Energy retrofits in multi-family buildings in north-east
More informationMould growth in building materials in laboratory and field experiments
Mould growth in building materials in laboratory and field experiments Kati Salminen, Ruut Peuhkuri, Kimmo Lähdesmäki, Hannu Viitanen, Juha Vinha, Leena Paajanen, Hanna Iitti, Tuomo Ojanen, Tomi Strander
More informationMoisture supply in Danish single-family houses the influence of building style Hansen, Ernst Jan de Place; Møller, Eva B.
Aalborg Universitet Moisture supply in Danish single-family houses the influence of building style Hansen, Ernst Jan de Place; Møller, Eva B. Published in: Energy Procedia DOI (link to publication from
More informationEnergy impact of ASHRAE s museum climate classes: a simulation study on four museums with different quality of envelopes
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Energy impact of ASHRAE
More informationMoisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation
Moisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation Targo Kalamees, Jarek Kurnitski HVAC-Laboratory, Helsinki
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3007 3012 6th International Building Physics Conference, IBPC 2015 A Study on Experimental Performance of Air-Type PV/T
More informationScienceDirect. Energy and environmental monitoring of a school building deep energy renovation in Italy
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3318 3323 6th International Building Physics Conference, IBPC 2015 Energy and environmental monitoring of a school building
More informationScienceDirect. Comparison of steady-state and in-situ testing of high thermal resistance walls incorporating vacuum insulation panels
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3246 3251 6th International Building Physics Conference, IBPC 2015 Comparison of steady-state and in-situ testing of high
More informationDocumentation of the component 25. May 2011 Thermal transmittance (U-value) according to BS EN ISO 6946
Thermal transmittance (U-value) according to BS EN ISO 6946 Page 1/6 OUTSIDE INSIDE Assignment: External wall Manufacturer Name Thickness [m], number Lambda [W/(mK)] R [m²k/w] Rse 0.0400 1 Generic Building
More informationHygrothermal Performance of Timber External Walls Insulated with Natural and Industrial Materials
Hygrothermal Performance of Timber External Walls Insulated with Natural and Industrial Materials Martti-Jaan Miljan 1[0000-0001-7038-5653] and Jaan Miljan 1[0000-0001-6800-8859] 1 Estonian University
More informationTechnical Condition of Prefabricated Concrete Large Panel Apartment Buildings in Estonia
Technical Condition of Prefabricated Concrete Large Panel Apartment Buildings in Estonia Targo Kalamees 1 Karl Õiger 2, Teet-Andrus Kõiv 3, Roode Liias 4 Urve Kallavus 5, Lauri Mikli 6, Andres Lehtla 7,
More informationThe Double Glass Skin Façade: a sustainable option for the Curtain Wall in Mediterranean Climate Countries?
1 The Double Glass Skin Façade: a sustainable option for the Curtain Wall in Mediterranean Climate Countries? Pere Alavedra¹, Mauricio Torres², Amado Guzmán³, Samantha Gallowayº, Daniel Alavedra" Department
More informationRESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS
Section Green Buildings Technologies and Materials RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS Dr. Staņislavs Gendelis Assoc. Prof. Dr. Andris Jakovičs
More informationTitle Inner Wall in Hagia Sophia, Istanbu. Citation Energy Procedia (2015), 78:
Title Influence of the Infiltrated Rainwa Inner Wall in Hagia Sophia, Istanbu Author(s) Mizutani, Etsuko; Ogura, Daisuke; I Masaru; Sasaki, Juni Citation Energy Procedia (2015), 78: 1353-13 Issue Date
More informationDocumentation of the component 25. May 2011 Thermal transmittance (U-value) according to BS EN ISO 6946
Thermal transmittance (U-value) according to BS EN ISO 6946 Page 1/6 OUTSIDE INSIDE Assignment: External wall Manufacturer Name Thickness [m], number Lambda [W/(mK)] R [m²k/w] Rse 0.0400 1 Generic Building
More informationPreservation of cultural heritage: the design of low-energy archival storage
Preservation of cultural heritage: the design of low-energy archival storage Dr Tim Taylor a,b* a Atkins, Woodcote Grove, Ashley Road, Epsom, Surrey KT18 5BW, United Kingdom b Cardiff Metropolitan University,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2663 2668 6th International Building Physics Conference, IBPC 2015 The daylighting contribution in the electric lighting
More informationCOMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES
COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of
More informationDocumentation of the component 11. January 2010 Thermal transmittance (U-value) according to BS EN ISO 6946
Thermal transmittance (U-value) according to BS EN ISO 6946 Page 1/5 OUTSIDE INSIDE Assignment: External wall Manufacturer Name Thickness [m], number Lambda [W/(mK)] Q R [m²k/w] Rse 0.04 1 Generic Building
More informationRetrofit of an historical building toward NZEB
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Retrofit of an historical
More informationBest Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL).
Best Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL). Wall retrofit strategies for retrofit on the interior side of
More informationAvailable online at ScienceDirect. Procedia Engineering 146 (2016 ) 60 68
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 146 (2016 ) 60 68 8th International Cold Climate HVAC 2015 Conference, CCHVAC 2015 Condensation resistance evaluation of a double-sliding
More informationAvailable online at ScienceDirect. Procedia Engineering 111 (2015 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 111 (2015 ) 311 316 XXIV R-S-P seminar, Theoretical Foundation of Civil Engineering (24RSP) (TFoCE 2015) Analysis of the possibilities
More informationExperimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 82 (2015 ) 465 471 ATI 2015-70th Conference of the ATI Engineering Association Experimental Performance Analyses of a Heat Recovery
More informationControl of moisture safety design by comparison between calculations and measurements in passive house walls made of wood
Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood Mundt Petersen, Solof; Harderup, Lars-Erik Published in: Proceedings fo the 12th
More informationThe comparative in situ hygrothermal performance of. Hemp and Stone Wool insulations in vapour open timber
The comparative in situ hygrothermal performance of Hemp and Stone Wool insulations in vapour open timber frame wall panels Eshrar Latif a *, Mihaela Anca Ciupala b, D C Wijeyesekera c a University of
More informationPerformance-Risk Methodology for the Design of High-Performance Affordable Homes
April 3 rd, 2012 1 Performance-Risk Methodology for the Design of High-Performance Affordable Homes Building Enclosure Science & Technology Conference BEST3, Atlanta Rodrigo Mora, British Columbia Institute
More informationDocumentation of the component 25. May 2011 Thermal transmittance (U-value) according to BS EN ISO 6946
Thermal transmittance (U-value) according to BS EN ISO 6946 Page 1/6 OUTSIDE INSIDE Assignment: External wall Manufacturer Name Thickness [m], number Lambda [W/(mK)] R [m²k/w] Rse 0.0400 1 Generic Building
More informationMoisture Solution Becomes Efficiency Bonanza in Southeastern United States
Moisture Solution Becomes Efficiency Bonanza in Southeastern United States Bruce Davis and Cyrus Dastur, Advanced Energy ABSTRACT This study compares the energy performance for space conditioning for a
More informationabridged report analysis of climate conditions in crawl spaces with high insulated wooden floor plates for the prevention of structural damages
Gesellschaft für Materialforschung und Prüfungsanstalt für das Bauwesen Leipzig mbh, Hans-Weigel-Str. 2 b, 04319 Leipzig Bereich IV Bauphysik AG: Wärme- und Feuchteschutz www.mfpa-leipzig.de Fakultät für
More informationAnalysis of climate conditions in crawl spaces with high insulated wooden floor plates for the prevention of structural damages
Gesellschaft für Materialforschung und Prüfungsanstalt für das Bauwesen Leipzig mbh, Hans-Weigel-Str. 2 b, 04319 Leipzig Bereich IV Bauphysik AG: Wärme- und Feuchteschutz www.mfpa-leipzig.de Fakultät für
More informationAvailable online at ScienceDirect. Energy Procedia 72 (2015 ) 27 33
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 72 (2015 ) 27 33 International Scientific Conference Environmental and Climate Technologies CONECT 2014 Analysis of mechanical ventilation
More informationScienceDirect. Hygrothermal Performance of Highly Insulated Timber-frame External Wall
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 96 (2016 ) 685 695 SBE16 Tallinn and Helsinki Conference; Build Green and Renovate Deep, 5-7 October 2016, Tallinn and Helsinki Hygrothermal
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 753 758 6th International Building Physics Conference, IBPC 2015 Thermal Performance of Cultural Heritage Italian Housing
More informationControl of moisture safety design by comparison between calculations and measurements in passive house walls made of wood
Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood Mundt Petersen, Solof; Harderup, Lars-Erik Published in: Proceedings fo the 12th
More informationPublisher Rights CC BY-NC-ND Published version available via:
Citation for published version: Latif, E, Ciupala, MA & Wijeyesekera, DC 2014, 'The comparative in situ hygrothermal performance of Hemp and Stone Wool insulations in vapour open timber frame wall panels'
More informationHygrothermal behaviour of compact roofs under Belgian climate
Hygrothermal behaviour of compact roofs under Belgian climate Glenn De Meersman 1 Nathan Van Den Bossche 2 Arnold Janssens 3 Robbe Verelst 4 T 2 ABSTRACT Compact flat roofs are more and more constructed
More informationSOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business
European Nearly Zero Energy Buildings Conference 28 February 1.March 13, Wels/Austria Summary SOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business
More informationBackground. BSC Website Builder Resources. Building America Innovations
Building America Innovations 1. Advanced Technologies & Practices 2. House as a System Business Case 3. Effective Guidance and Tools 4. Infrastructure Development Kohta Ueno Internal Insulation of Masonry
More informationFull scale experimental performance assessment of a prefabricated timber panel for the energy retrofitting of multi-rise buildings
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 122 (2017) 3 8 www.elsevier.com/locate/procedia CISBAT 2017 International Conference Future Buildings & Districts Energy Efficiency
More informationBasements are Changing. Basements Part of the Enclosure. Basements. Control: Moisture. Moisture: Old ideas. Energy Efficient, Durable, Healthy
Basements are Changing John Straube, Ph.D., P.Eng Basements: New & Retrofit Energy Efficient, Durable, Healthy Building Science Corporation presented by www.buildingscience.com Increasingly used as living
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2857 2862 6th International Building Physics Conference, IBPC 2015 Optimized Blind Control Method to minimize Heating,
More informationAvailable online at ScienceDirect. Energy Procedia 48 (2014 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 (2014 ) 1412 1418 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25,
More informationCost Optimal Retrofitting Of Shopping Malls In Europe
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2058 2063 6th International Building Physics Conference, IBPC 2015 Cost Optimal Retrofitting Of Shopping Malls In Europe
More informationWall Selection Guide Section 1.1
Page 1 MASONRY WALL TYPES Masonry is the most enduring of all building materials, as exemplified by the oldest and most revered architecture from around the world. The exceptional structural integrity
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1568 1573 6th International Building Physics Conference, IBPC 2015 Dynamic facades, the smart way of meeting the energy
More informationStudies energy efficiency of the renewable sources use considering climate in Latvia
Available online at www.sciencedirect.com ScienceDirect Energy Procedia (25) www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 25 Studies energy efficiency of the renewable
More informationThermal insulation performance of reflective foils in floor cavities - Hot box measurements and calculations
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 333 338 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,
More informationMOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER
MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER USDA FOREST SERVICE RESEARCH PAPER FPL 290 1977 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3264 3269 6th International Building Physics Conference, IBPC 2015 Optimising test environment and test set up for characterizing
More informationScienceDirect. Simulation based mixed mode building design
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2016) 000 000 www.elsevier.com/locate/procedia 5th International Conference on Advances in Energy Research, ICAER 2015, 15-17
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 561 566 6th International Building Physics Conference, IBPC 2015 Analysis of user behavior profiles and impact on the
More informationExperimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season
Journal of Energy and Power Engineering 9 (2015) 386-392 doi: 10.17265/1934-8975/2015.04.008 D DAVID PUBLISHING Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season Ghanim
More informationIMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction
IMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction C. RUDBECK, S. SVENDSEN Technical University of Denmark, Department of Buildings and Energy, Lyngby, Denmark Durability
More informationExperimental Assessment of Hygrothermal Performance of Wood Frame Wall System in Suzhou's Lake Tai Climate Zone
Experimental Assessment of Hygrothermal Performance of Wood Frame Wall System in Suzhou's Lake Tai Climate Zone Xiaohuan Wang, a Benhua Fei, b, * and Jun Ni c A long-term onsite assessment of the hygrothermal
More informationThe Effect of Moisture Content of Insulation Boards on the Adhesion Strength of ETICS
The Effect of Moisture Content of Insulation Boards on the Adhesion Strength of ETICS ENELI LIISMA, LEMBI-MERIKE RAADO, SILVER LUMI, IRENE LILL, VIRGO SULAKATKO Department of Building Production Tallinn
More informationZero Energy Building Example in Estonia. Tõnu Mauring
Zero Energy Building Example in Estonia Tõnu Mauring University of Tartu, Estonia Jan 22 2014, Riga Site location Põlva, Estonia (58 N, 27 E) Long-term average dry bulb temperature for inland part of Estonia
More informationPerformance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool
Performance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool Valentina Marincioni, M.Sc. 1 Hector Altamirano-Medina, Ph.D. 1 Ian Ridley, Ph.D.
More informationAir pressure difference measurements in Finnish municipal service buildings
Tampere University of Technology Air pressure difference measurements in Finnish municipal service buildings Citation Kiviste, M., & Vinha, J. (2017). Air pressure difference measurements in Finnish municipal
More informationAir pressure difference measurements in Finnish municipal service buildings
Tampere University of Technology Air pressure difference measurements in Finnish municipal service buildings Citation Kiviste, M., & Vinha, J. (2017). Air pressure difference measurements in Finnish municipal
More informationThis presentation. Functions of the building enclosure. University of Waterloo and Balanced Solutions. Straube Presentation Building Canada
Hygrothermal Basement Performance, or Why do we get water when we dig holes in the ground? Dr John Straube October, 2004 This presentation What do basements do Examine performance Why problems What solutions
More informationOverview. Insulating Load-Bearing Masonry Buildings. Mass Walls (Rain Control) Inside or Outside Insulation? 11/17/2017
Kohta Ueno November 16, 2017 Insulating Load-Bearing Masonry Buildings Overview Insulating Load-bearing Masonry Buildings 2 Mass Walls (Rain Control) Moisture is absorbed/safely stored during rain Moisture
More informationAdhered Veneers and Inward Vapor Drives: Significance, Problems and
Feature Adhered Veneers and Inward Vapor Drives: Significance, Problems and Solutions By Dr. John Straube, P.Eng., Chris Schumacher, Jonathan Smegal and Marcus Jablonka Adhered veneers, in which masonry
More informationPublished in: Proceedings Thermal Performance of the Exterior Envelopes of Whole Buildings XI, Dec 5-9, 2010, Clearwater Beach, Florida
Aalborg Universitet Timber frame walls Hansen, Ernst Jan de Place; Brandt, Erik Published in: Proceedings Thermal Performance of the Exterior Envelopes of Whole Buildings XI, Dec 5-9, 2010, Clearwater
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2 ) 1937 1943 6th International Building Physics Conference, IBPC 2 Operation Analyse of a U-tube Ground Heat Exchangers of GSHP
More informationCOMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS
COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS Andreas Holm, Dipl.-Phys. Hartwig M. Künzel, Dr.-Ing. * 1. THE PROBLEM When an exterior thermal insulation
More informationBasements: New & Retrofit
John Straube, Ph.D., P.Eng Basements: New & Retrofit Energy Efficient, Durable, Healthy Building Science Corporation presented by www.buildingscience.com This presentation Basement functions Basement Performance
More informationAvailable online at ScienceDirect. Procedia Engineering 117 (2015 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 117 (2015 ) 766 774 International Scientific Conference Urban Civil Engineering and Municipal Facilities, SPbUCEMF-2015 Design
More informationCan you Believe Energy Savings Forecasts
Can you Believe Energy Savings Forecasts By: Tony Woods Introduction Yes, says TonyWood. Especially when your project includes an upgrade to the building envelope. The relationship between high performance
More informationAdhered Veneers and Inward Vapor Drives: Significance, Problems and
Feature Adhered Veneers and Inward Vapor Drives: Significance, Problems and Solutions By Dr. John Straube, P.Eng., Chris Schumacher, Jonathan Smegal and Marcus Jablonka ADHERED VENEERS, IN WHICH MA- SONRY
More informationIntroduction Retrofit interior insulation of masonry buildings Exterior insulation ideal solution Interstitial condensation, freeze thaw issues
Introduction Retrofit interior insulation of masonry buildings Exterior insulation ideal solution Interstitial condensation, freeze thaw issues Kohta Ueno, Building Science Corporation Masonry Wall Interior
More informationInnovative Passive Ventilation Water-Resistive Barriers How Do They Work?
building science.com 2010 Building Science Press All rights of reproduction in any form reserved. Innovative Passive Ventilation Water-Resistive Barriers How Do They Work? Conference Paper - 1010 13 December
More information