DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

Size: px
Start display at page:

Download "DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104"

Transcription

1 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) (562) es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION TALBOT AVENUE RANKIN, PENNSYLVANIA 504 EVALUATION SUBJECT: EPICORE, ER2R, ER2RA, ER3.5, AND ER3.5A STEEL DECK PANELS Look for the trusted marks of Conformity! 204 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 207 ICC Evaluation Service, LLC. All rights reserved.

2 ICC-ES Evaluation Report (800) (562) ESR-2047 Reissued July 207 This report is subject to renewal July 209. A Subsidiary of the International Code Council DIVISION: METALS Section: Steel Decking REPORT HOLDER: EPIC METALS CORPORATION TALBOT AVENUE RANKIN, PENNSYLVANIA 504 (42) EVALUATION SUBJECT: EPICORE, ER2R, ER2RA, ER3.5, AND ER3.5A STEEL DECK PANELS.0 EVALUATION SCOPE Compliance with the following code: 202, 2009, and 2006 International Building Code (IBC) Property evaluated: Structural 2.0 USES The EPIC Metals steel deck panels are used in floor and roof decks, horizontal diaphragms, and composite floor and roof assemblies to support the code-required appropriate floor and roof loads. 3.0 DESCRIPTION Epicore, ER2R, ER2RA, ER3.5, and ER3.5A steel deck panels are cold-formed from steel conforming to ASTM A653 SS Grade 40, with a minimum G60 galvanization coating designation. The panels are made from No. 4, 6, 8, 9, 20 or 22 gage steel [base-metal thicknesses of , , , 0.048, or inch (.88,.52,.20,.06, 0.9 or 0.75 mm), respectively]. The panel profiles are as indicated in Figures and 2 of this report. Panel descriptions are as follows:. Epicore: 2-inch-deep (5 mm) floor deck panel with embossments in the top flange for use in composite floor applications. 2. ER2R: 2-inch-deep (5 mm) nonacoustic roof deck panel. 3. ER2RA: 2-inch-deep (5 mm) acoustic roof deck panel with perforations in the bottom flanges for acoustical purposes. 4. ER3.5: 3.5-inch-deep (89 mm) nonacoustic roof deck panel. 5. ER3.5A: 3.5-inch-deep (89 mm) acoustic roof deck panel with perforations in the bottom flanges for acoustical purposes. 4.0 DESIGN AND INSTALLATION 4. General: The section properties and allowable load tables for the panels in this report have been established using the design base-metal thicknesses of the panels noted in Table. Allowable gravity and wind uplift loads must be based on section properties shown in Table. Allowable reactions based on web crippling must not exceed values shown in Table 7. The minimum concentrated live loads of IBC Section 607 must be considered by the design professional based on the specific occupancy or use, as applicable. 4.2 Composite Decks with Vertical Load: Epicore deck panels maximum unshored spans and allowable superimposed uniform live loads for composite decks with various thicknesses of concrete are set forth in Tables 2, 3, 4, and 5, respectively. The concrete fill must comply with the applicable code, utilize normal weight and have a minimum compressive strength of 3000 psi (20.68 MPa). The decking must be clean and free of foreign materials prior to placement of concrete. 4.3 Bare (Non-Composite) Decks with Vertical Load: The ER2R, ER2RA, ER3.5, and ER3.5A panels allowable uniform loads (dead plus live) are shown in Table Diaphragm Design: 4.4. General: The one-third stress increase permitted for Allowable Stress Design, for load combinations in IBC Section including wind or seismic forces, must not be used for shear values in the diaphragm tables. The horizontal diaphragm ASD shear and flexibility factors for the ER2R ER2RA, ER3.5, and ER3.5A decks are shown in Tables 8a, 8b, 8c, and 8d. Typical steel deck diaphragm layouts are shown in Figures 7. End weld patterns for the various decks are shown in Figures 3 and 4. All welding must be accomplished with a minimum / 8 -inch-diameter (3.2 mm) E60XX or E70XX filler metal rod complying with the appropriate AWS standard. Other weld requirements must conform to AWS D.3. Arc seam welds or fillet welds of deck side laps must comply with requirements shown in Figures 5a and 5b. Arc spot (puddle) welds to supporting members must comply with requirements shown in Figure 6. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 207 ICC Evaluation Service, LLC. All rights reserved. Page of 20

3 ESR-2047 Most Widely Accepted and Trusted Page 2 of Diaphragm Design Considerations: The diaphragm design must include the following considerations:. Diaphragm classification (flexible or rigid) must comply with Section 602 of the IBC; the diaphragm deflection ( ) must be calculated using the equation noted in Table 9 of this report. 2. Diaphragm flexibility limitations must comply with Table Diaphragm deflection limits must comply with Sections 2.0. or of ASCE Horizontal shears must be distributed in accordance with Section of ASCE Installation: The deck panels must be installed in accordance with this report and the EPIC Metals Corporation published installation instructions. If there is a conflict between this report and the published installation instructions, this report governs. 5.0 CONDITIONS OF USE The Epicore, ER2R, ER2RA, ER3.5, and ER3.5A steel deck panels described in this report comply with, or are suitable alternatives to what is specified in, the code indicated in Section.0 of this report, subject to the following conditions: 5. Concrete-filled composite deck panels must not be used for loads that are predominantly vibratory, such as for operation of heavy machinery, reciprocating motors and moving loads. 5.2 Vertical load design of deck panels without a concrete fill must be based on section properties and web crippling values set forth in this report. Vertical load capacity of concrete-filled, composite deck systems must be as set forth in the tables in this evaluation report. 5.3 Special inspections must be provided in accordance Chapter 7 of the IBC. 5.4 Where use is as a diaphragm: 5.4. The one-third stress increase permitted for Allowable Stress Design, for load combinations noted in IBC Section including wind or seismic forces, must not be applied to shear values in the diaphragm tables Allowable shear values must be limited to values set forth in the tables of this report for the types of deck panels involved Diaphragm deflections must not exceed the permitted relative deflections of walls between the diaphragm level and the floor below. See Table 9 for diaphragm flexibility and deflection limitations. 5.5 Calculations and details demonstrating that the loads applied to the deck panels comply with this report must be submitted to the code official for approval. Calculations must be prepared, signed, and sealed by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.6 The minimum base-metal thickness of the steel deck panels must be 95 percent of the base-metal thickness noted in this report. 5.7 When the steel deck panels are used in a roof assembly, the panels must be covered with a codecomplying roof covering. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Steel Deck Roof and Floor Systems (AC43), dated October 200 (editorially revised September 203). 7.0 IDENTIFICATION The deck panels bear a label with the Epic Metals Corporation name and address, the job number, the deck panel type, the minimum base-metal thickness and yield strength, and the ICC-ES evaluation report number (ESR-2047).

4 ESR-2047 Most Widely Accepted and Trusted Page 3 of 20 INDEX OF TABLES TABLE: PAGE. Epicore, ER2R, ER2RA, ER3.5, and ER3.5A Section Properties Epicore Maximum Clear Spans without Shoring Epicore Live Load Capacity for Simple Span Condition Epicore Live Load Capacity for End Spans of Continuous Span Condition Epicore Live Load Capacity for Interior Spans of Continuous Span Condition ER2R, ER2RA, ER3.5, and ER3.5A Allowable Uniform Total Loads (Dead and Live), psf Allowable Loads Based on Web Crippling Diaphragm Shear (q d ) and Flexibility Factor (F) Diaphragm Flexibility Limitations... 6 FIGURE: PAGE. Profile for Epicore, ER2R, and ER2RA Profile for ER3.5 and ER3.5A End Weld Patterns for Epicore, ER2R, and ER2RA End Weld Patterns for ER3.5 and ER3.5A Welds for Epicore, ER2R, ER2RA, ER3.5, and ER3.5A Typical Arc Spot Weld at Supporting Member Parallel to Flute for all Deck Panels Typical Steel Deck Diaphragm Layout for Epicore, ER2R, ER2RA, ER3.5, and ER3.5A... 2

5 ESR-2047 Most Widely Accepted and Trusted Page 4 of 20 TABLE EPICORE, ER2R, ER2RA, ER3.5, & ER3.5A SECTION PROPERTIES DECK TYPE BASE METAL THICKNESS (inch) WEIGHT (psf) AREA (inch 2 / foot) Moment of Inertia I (inch 4 / foot) Positive, I DP Negative, I DN Section Modulus S (inch 3 / foot) Positive, S P Negative, S N Epicore ER2R ER2RA Epicore ER2R ER2RA Epicore ER2R ER2RA Epicore ER2R ER2RA ER ER3.5A ER ER3.5A ER ER3.5A ER ER3.5A For SI: inch = 25.4 mm, psf = 4.88 kg/m 2, inch 2 per foot = 2.2 x 0-3 mm 2 /m, inch 3 per foot = 5.38 x 04 mm 3 /m, inch 4 per foot =.36 x 07 mm 4 /m, psi = 6.89 kpa. Values based on a steel yield strength of 40,000 psi. TABLE 2 EPICORE MAXIMUM UNSHORED CLEAR SPANS,2,3,4,5,6,7 SPAN OVERALL SLAB DEPTH (Inches) SLAB WEIGHT (psf) 4 4 / / / / Simple 2 3 or more DESIGNATION Epicore '-3" 6'-" 6'-7" 6'-5" 6'-2" 6'-0" 5'-0" 5'-8" 5'-6" Epicore '-4" 7'-" 7'-7" 7'-4" 7'-" 6'-0" 6'-8" 6'-5" 6'-3" Epicore - 8 0'-" 9'-8" 9'-3" 8'-0" 8'-7" 8'-3" 8'-0" 7'-9" 7'-7" Epicore - 6 '-3" 0'-0" 0'-5" 0'-" 9'-9" 9'-5" 9'-" 8'-0" 8'-7" Epicore '-" 7'-7" 7'-3" 7'-0" 6'-9" 6'-6" 6'-4" 6'-" 5'-" Epicore '-9" 8'-5" 8'-" 7'-9" 7'-6" 7'-3" 7'-0" 6'-0" 6'-7" Epicore - 8 0'-3" 9'-0" 9'-5" 9'-" 8'-9" 8'-6" 8'-3" 8'-0" 7'-9" Epicore - 6 '-9" '-3" 0'-0" 0'-5" 0'-" 9'-9" 9'-5" 9'-2" 8'-" Epicore '-2" 7'-0" 7'-6" 7'-3" 6'-" 6'-9" 6'-6" 6'-4" 6'-2" Epicore '-" 8'-8" 8'-4" 8'-0" 7'-9" 7'-6" 7'-3" 7'-0" 6'-0" Epicore - 8 0'-8" 0'-2" 9'-9" 9'-5" 9'-" 8'-9" 8'-6" 8'-3" 8'-0" Epicore - 6 2'-2" '-8" '-2" 0'-9" 0'-5" 0'-" 9'-9" 9'-6" 9'-3" For SI: inch = 25.4 mm, foot = mm, psf = 4.88 kg/m 2, psi = 6.89 kpa, pcf = 6.02 kg/m 3 Runways and planking must be used for all concrete placement. 2 Slab weights are approximate, +/- 2 psf, and include deck weight 3 Applies to normal-weight concrete (45 pcf) with a minimum compressive strength, f' c, of 3,000 psi. 4 Minimum bearing length must be 2 inches at end supports and 4 inches at interior supports. 5 Construction live loads: Uniform= 20 psf; Concentrated= 50 lbf per ft. width. 6 Values based on LRFD. 7 Overall slab depth refers to the nominal concrete depth measured from the top of the concrete to the bottom of the steel deck.

6 ESR-2047 Most Widely Accepted and Trusted Page 5 of 20 TABLE 3 EPICORE DESIGN UNFACTORED SUPERIMPOSED UNIFORM LIVE LOADS (psf),2,3,4 FOR SIMPLE SPAN CONDITION f y = 40 ksi, Normal Weight Concrete (45 pcf) f' c = 3 ksi OVERALL SLAB DEPTH 5 (inches) STEEL DECK (GAGE) DECK SPANS, CENTER TO CENTER OF SUPPORTS (ft) / / / / For SI: ksi = 6.89 MPa, pcf = 6.0 kg/m 3, psf = kn/m 2, inch = 25.4 mm, foot = mm, in 2 /foot = mm 2 /m The maximum unshored span for the panels is shown in Table 2. 2 All loads are assumed to be statically applied. 3 Deflection limit of the composite slab is / 360 of span under total load, which includes live load (as shown in Table), and dead load (weight of reinforced concrete and weight of the steel deck). 4 Longitudinal and transverse reinforcement bars having a yield strength of at least 60 ksi or welded wire fabric must be provided. Area of this reinforcement must be equal to times the area of concrete above the steel deck but not less than square inch per foot of width. 5 Overall slab depth refers to the nominal concrete depth measured from the top of the concrete to the bottom of the steel deck.

7 ESR-2047 Most Widely Accepted and Trusted Page 6 of 20 TABLE 4 EPICORE DESIGN UNFACTORED SUPERIMPOSED UNIFORM LIVE LOADS (psf),2,3,4,5 FOR END SPANS OF CONTINUOUS SPAN CONDITION f y = 40 ksi, Normal Weight Concrete (45 pcf) f' c = 3 ksi OVERALL SLAB DEPTH 6 (inches) STEEL DECK (GAGE) DECK SPANS, CENTER TO CENTER OF SUPPORTS (ft) / / / / For SI: ksi = 6.89 MPa, pcf = 6.0 kg/m 3, psf = kn/m 2, inch = 25.4 mm, foot = mm, in 2 /foot = mm 2 /m The maximum unshored span for the deck is shown in Table 2. 2 All loads are assumed to be statically applied. 3 Deflection limit of the composite slab is / 360 of span under total load, which includes live load (as shown in Table), and dead load (weight of reinforced concrete and weight of the steel deck). 4 Longitudinal and traverse reinforcement bars having a yield strength of at least 60 ksi or welded wire fabric shall be provided. Area of this reinforcement must be equal to times the area of concrete above the steel deck but not less than square inch per foot of width. 5 The use of reinforcing bars over interior supports is required and they must be designed and placed in accordance with Chapter 9 of the IBC. 6 Overall slab depth refers to the nominal concrete depth measured from the top of the concrete to the bottom of the steel deck.

8 ESR-2047 Most Widely Accepted and Trusted Page 7 of 20 TABLE 5 EPICORE DESIGN UNFACTORED SUPERIMPOSED UNIFORM LIVE LOADS (psf),2,3,4,5 FOR INTERIOR SPANS OF CONTINUOUS SPAN CONDITION fy = 40 ksi, Normal Weight Concrete (45 pcf) f'c = 3 ksi OVERALL SLAB DEPTH 6 (inches) 4 4 / / / / 2 8 STEEL DECK (GAGE) DECK SPANS, CENTER TO CENTER OF SUPPORTS (ft) For SI: ksi = 6.89 MPa, pcf = 6.0 kg/m 3, psf = kn/m 2, inch = 25.4 mm, foot = mm, in 2 /foot = mm 2 /m The maximum unshored span for the deck is shown in Table 2. 2 All loads are assumed to be statically applied. 3 Deflection limit of the composite slab is / 360 of span under total load, which includes live load (as shown in table), and dead load (weight of reinforced concrete and weight of the steel deck). 4 Longitudinal and traverse reinforcement bars having a yield strength of at least 60 ksi or welded wire fabric shall be provided. Area of this reinforcement must be equal to times the area of concrete above the steel deck but not less than square inch per foot of width. 5 The use of reinforcing bars over interior supports is required and they must be designed and placed in accordance with Chapter 9 of the IBC. 6 Overall slab depth refers to the nominal concrete depth measured from the top of the concrete to the bottom of the steel deck.

9 ESR-2047 Most Widely Accepted and Trusted Page 8 of 20 TABLE 6 ALLOWABLE UNIFORM TOTAL LOADS (DEAD PLUS LIVE), psf -5 ER2R Span Length Center to Center of Supports (ft.) No. Spans Gage Design Thick. (in) 6'-0" 6'-6" 7'-0" 7'-6" 8'-0" 8'-6" 9'-0" 9'-6" 0'-0" 0'-6" '-0" 2'-0" 3'-0" 4'-0" 5'-0" /6 02/9 88/73 77/59 68/49 60/4 53/34 48/ /43 29/2 /90 97/73 85/60 75/50 67/42 60/36 54/ /92 78/5 53/2 34/98 8/8 04/67 93/57 83/48 75/4 68/36 62/ / /89 93/5 68/23 48/0 3/84 7/7 05/6 94/52 86/45 78/39 66/ /278 95/29 82/75 7/42 63/7 55/98 49/82 44/70 40/60 36/52 33/45 28/ /344 7/27 0/27 88/76 78/45 69/2 6/02 55/87 50/74 45/64 4/56 34/43 29/ /46 63/363 40/290 22/236 08/95 95/62 85/37 76/6 69/00 62/86 57/75 48/58 4/45 35/36 3/ /500 26/455 86/364 62/296 43/244 26/203 3/7 0/46 9/25 83/08 75/94 63/72 54/57 47/46 4/ /28 8/7 02/37 89/ 78/92 69/77 62/64 55/55 50/47 45/4 4/35 35/ /269 47/22 27/70 0/38 97/4 86/95 77/80 69/68 62/58 56/50 5/44 43/34 37/ /36 204/284 76/227 53/85 34/52 9/27 06/07 95/9 86/78 78/67 7/59 60/45 5/35 44/ / / / /232 78/9 58/59 4/34 26/4 4/98 03/84 94/73 79/57 67/44 58/36 5/29 ER2RA No. Spans 2 3+ Gage Design Thick. (in) Span Length Center to Center of Supports (ft.) 6'-0" 6'-6" 7'-0" 7'-6" 8'-0" 8'-6" 9'-0" 9'-6" 0'-0" 0'-6" '-0" 2'-0" 3'-0" 4'-0" 5'-0" /09 98/86 85/69 74/56 65/46 58/38 5/32 46/ /34 25/05 08/84 94/68 83/56 73/47 65/40 59/34 53/ /79 74/4 50/3 3/92 5/76 02/63 9/53 82/45 74/39 67/33 6/ / /77 89/42 65/5 45/95 28/79 5/67 03/57 93/49 84/42 77/37 64/ /263 9/207 78/66 68/35 60/ 53/93 47/78 43/66 38/57 35/49 32/43 27/ /322 0/253 95/203 82/65 73/36 64/3 57/95 5/8 46/70 42/60 38/52 32/40 27/ /432 5/340 3/272 4/22 00/82 89/52 79/28 7/09 64/93 58/8 53/70 44/54 38/42 33/34 28/ / /426 76/34 54/277 35/228 20/90 07/60 96/36 86/7 78/0 7/88 60/68 5/53 44/43 38/ /206 4/62 98/30 85/06 75/87 66/73 59/6 53/52 48/45 44/38 40/ /252 37/98 8/59 03/29 9/06 80/89 72/75 64/63 58/54 53/47 48/4 40/ /338 89/266 63/23 42/73 25/43 /9 99/00 89/85 80/73 73/63 66/55 56/42 47/ / / /267 92/27 69/79 49/49 33/26 20/07 08/92 98/79 89/69 75/53 64/42 55/33 48/27 (continued)

10 ESR-2047 Most Widely Accepted and Trusted Page 9 of 20 TABLE 6 ALLOWABLE UNIFORM TOTAL LOADS (DEAD PLUS LIVE), psf -5 ER3.5 No. Spans 2 3+ Gage Design Thick. (in) Span Length Center to Center of Supports (ft.) 2'-0" 3'-0" 4'-0" 5'-0" 6'-0" 7'-0" 8'-0" 9'-0" 20'-0" 2'-0" 22'-0" 23'-0" 24'-0" 25'-0" /70 65/55 56/44 49/36 43/ /82 8/65 70/52 6/42 54/35 48/ /95 96/74 82/60 72/48 63/40 56/33 50/ /2 29/95 /76 97/62 85/5 75/42 67/36 60/30 54/ /67 77/32 66/05 58/86 5/7 45/59 40/50 36/42 32/36 29/ /99 9/56 78/25 68/02 60/84 53/70 47/59 43/50 38/43 35/35 32/ /228 04/79 90/43 78/7 69/96 6/80 54/67 49/57 44/49 40/40 36/34 33/ /29 33/229 5/83 00/49 88/23 78/02 70/86 62/73 56/63 5/52 47/43 43/36 39/30 36/ /3 96/03 83/83 72/67 63/ /55 4/22 98/98 85/80 75/ /78 30/40 2/2 98/9 86/ /228 67/79 44/43 25/7 0/96 ER3.5A No. Spans 2 3+ Gage Design Thick. (in) Span Length Center to Center of Supports (ft.) 2'-0" 3'-0" 4'-0" 5'-0" 6'-0" 7'-0" 8'-0" 9'-0" 20'-0" 2'-0" 22'-0" 23'-0" 24'-0" 25'-0" /65 64/5 56/4 48/33 43/ /78 80/6 69/49 60/40 53/33 47/ /89 94/70 8/56 70/46 62/38 55/3 49/ /4 26/89 09/72 95/58 83/48 74/40 66/34 59/29 53/ /57 72/24 62/99 54/8 48/66 42/55 38/47 34/40 30/34 28/ /87 85/47 73/8 64/96 56/79 50/66 44/55 40/47 36/40 33/33 30/ /24 98/68 84/35 73/0 64/90 57/75 5/63 46/54 4/46 37/38 34/32 3/ /274 26/25 09/72 95/40 83/5 74/96 66/8 59/69 53/59 48/49 44/40 40/34 37/28 34/ /23 90/97 78/78 68/63 59/ /46 07/5 92/92 80/75 70/ /68 22/32 05/05 92/86 80/ /24 57/68 36/35 8/0 04/90 Loads are based on ASD Design. 2Uniform load values listed on the left side of the box are governed by stress or web crippling and the values listed on the right side of the box are governed by deflection. 3The deflection criteria used for generating the tables above are L/240 or " maximum. 4Stress governed values assume a maximum allowable stress of 24 ksi. 5Minimum end and interior support bearing lengths are 2" and 4", respectively.

11 ESR-2047 Most Widely Accepted and Trusted Page 0 of 20 TABLE 7 EPICORE, ER2R, ER2RA, ER3.5, AND ER3.5A ASD LOADS BASED ON WEB CRIPPLING ALLOWABLE LOADS (plf) DECK TYPE BASE METAL THICKNESS End Bearing Length Interior Bearing Length (inch) / 2 inches 2 inches 3 inches 3 inches 4 inches 5 inches Epicore-22, ER2R-22, ER2RA Epicore-20, ER2R-20, ER2RA Epicore-8, ER2R-8, ER2RA Epicore-6, ER2R-6, ER2RA ER3.5-20, ER3.5A ER3.5-9, ER3.5A ER3.5-8, ER3.5A ER3.5-6, ER3.5A For SI: inch = 25.4 mm, plf = 4.6 N/m FOOTNOTES FOR TABLES 8a through 8d ALLOWABLE DIAPHRAGM SHEAR AND FLEXIBILITY NOTES F = Flexibility factor is the distance measured in average micro-inches a diaphragm web will deflect in a span of foot under a shear of pound per foot. q D = Allowable diaphragm shear, in pounds per linear foot. R = Ratio of vertical load span of the deck to length of each deck sheet. 2 Arc Seam or spot (puddle) weld end-weld patterns are shown in Figures 3 and 4. 3 The one-third stress increase must not be permitted for resistance to horizontal forces due to earthquake or wind. 4 See Table 9 for diaphragm flexibility limitations and the footnotes to Table 9 for guidance on diaphragm deflection computations. 5 Arc seam or spot (puddle) welds must have an effective fusion area to supporting members at least equivalent to a 3 / 8 " x " long (arc seam welds) or / 2 " diameter (spot-puddle weld), respectively. 7 Spacing of marginal welds to members parallel to flutes: a. Arc seam or spot (puddle welds to members such as chords and to collector elements such as struts or ties must have a spacing in feet equal to 32,000 (t) / v: where: t = Uncoated base-metal thickness of fluted deck, in inches. v = Actual diaphragm shear at marginal supports parallel to flutes or actual shear to be transferred to collector elements (at struts or ties), in pounds per foot b. The spacing of welds parallel to flutes must not exceed the deck span divided by three. 8 Attachments at interior lines of shear transfer perpendicular to deck corrugation: The shear transfer from a diaphragm to interior tie or strut lines perpendicular to deck corrugations must not exceed the shear values indicated in the tables. Two lines of puddle welds may be used to develop the actual shear transfer of these collector elements. 9 Where individual panels are cut, the partial panel must be fastened to ensure complete transfer of design shear forces at the point of the diaphragm to adjacent full panels to attain the values specified in the tables.

12 ESR-2047 Most Widely Accepted and Trusted Page of 20 TABLE 8a ALLOWABLE DIAPHRAGM SHEAR (qd) AND FLEXIBILITY FACTOR (F) PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: GAGE SIDE LAP CONN. SPACING (in) ER2R,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/4 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: GAGE SIDE LAP CONN. SPACING (in) ER2RA,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/4 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R For SI: inch = 25.4 mm, foot = mm, lbf/ ft = 4.6 N/m

13 ESR-2047 Most Widely Accepted and Trusted Page 2 of 20 TABLE 8b ALLOWABLE DIAPHRAGM SHEAR (q D ) AND FLEXIBILITY FACTOR (F) PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: ER2R,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/8 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: ER2RA,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/8 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R For SI: inch = 25.4 mm, foot = mm, lbf / ft = 4.6 N/m

14 ESR-2047 Most Widely Accepted and Trusted Page 3 of 20 PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: TABLE 8c ALLOWABLE DIAPHRAGM SHEAR (q D ) AND FLEXIBILITY FACTOR (F) ER3.5,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/3 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: ER3.5A,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/3 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R For SI: inch = 25.4 mm, foot = mm, lbf/ ft = 4.6 N/m

15 ESR-2047 Most Widely Accepted and Trusted Page 4 of 20 TABLE 8d ALLOWABLE DIAPHRAGM SHEAR (q D ) AND FLEXIBILITY FACTOR (F) PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: ER3.5,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/6 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R PRODUCT: SUPPORT CONNECTIONS/LAYOUT: SIDE LAP CONNECTIONS: ER3.5A,2,3,4,5,6,7,8,9 /2" DIAMETER (EFFECTIVE) ARC SPOT WELDS, 24/6 PATTERN.5" LONG ARC SEAM WELDS OR 2.0" LONG FILLET WELDS GAGE SIDE LAP CONN. SPACING (in) LENGTH OF SPAN, CENTER-TO-CENTER DISTANCE BETWEEN SUPPORTS (ft) qd F qd F qd F qd F qd F qd F qd F qd F qd F R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R For SI: inch = 25.4 mm, foot = mm, lbf / ft = 4.6 N/m

16 ESR-2047 Most Widely Accepted and Trusted Page 5 of 20 TABLE 9 DIAPHRAGM FLEXIBILITY LIMITATIONS,2,3,4,5 FLEXIBILITY FACTOR, F 3 MAXIMUM SPAN FOR MASONRY OR CONCRETE WALLS (feet) Rotation Not Considered in Diaphragm Masonry or Concrete Walls SPAN / DEPTH LIMITATION Flexible Walls 4 Rotation Considered in Diaphragm Masonry or Concrete Walls Flexible Walls 4 Over 50 Not used Not used 2 : Not used / 2 : No limitation Less than No limitation 2:, or as required for deflection 2 / 2 :, or as required for deflection 3:, or as required for deflection As required for deflection 3 : Not used 2 : As required 4 : 2 / 2 : for deflection As required 5 : for deflection 3 : As required No limitation 3 / 2 : for deflection For SI: inch = 25.4 mm, foot = mm, psi = 6.89 kpa, psf = 4.88 kg/m 2, plf = 4.6 N/m Diaphragms are to be investigated regarding their flexibility and recommended span-depth limitations. Refer to Table 8 for determination of the value F. 2 Diaphragms supporting masonry or concrete walls are to have their deflections limited to the following amount: wall = (H 2 / 0.0E t ) f c where: E = Modulus of elasticity of wall material for deflection determination, in pounds per square inch. f c = Allowable compressive strength of wall material in flexure, in pounds per square inch. For concrete, fc = 0.45 f'c For masonry, fc = Fb = 0.33 f'm H = Unsupported height of wall, in feet. t = Thickness of wall, in inches. 3 The total deflection,, of the diaphragm may be computed from the equation: = f + w where: f = Flexural deflection of the diaphragm determined in the same manner as the deflection of beams. w = Web deflection determined by the equation: w = (q avg L F) / 0 6 where: F = Flexibility factor (the average micro-inches a diaphragm web will deflect in a span of foot under a shear of pound per foot). L = Distance between vertical resisting element (such as shear wall) and the point to which the deflection is to be determined, in feet. q avg = Average shear in diaphragm., in pounds per square foot, over length L. 4 When applying these limitations to cantilevered diaphragms, the allowable span-depth ratio will be half that shown. 5 Diaphragm classification (flexible or rigid) and deflection limits must comply with Section of the report.

17 ESR-2047 Most Widely Accepted and Trusted Page 6 of 20 (a) PROFILE DIMENSIONS FOR EPICORE, ER2R AND ER2RA (b) PERFORATION PATTERN FOR ER2RA FIGURE PROFILE FOR EPICORE, ER2R, AND ER2RA

18 ESR-2047 Most Widely Accepted and Trusted Page 7 of 20 (a) PROFILE DIMENSIONS FOR ER3.5 AND ER3.5A (b) PERFORATION PATTERN FOR ER3.5A FIGURE 2 PROFILE FOR ER3.5 AND ER3.5A

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued January 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

DIVISION: METALS SECTION: STEEL DECKING SECTION: STEEL FLOOR DECKING SECTION: STEEL ROOF DECKING REPORT HOLDER:

DIVISION: METALS SECTION: STEEL DECKING SECTION: STEEL FLOOR DECKING SECTION: STEEL ROOF DECKING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2050 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 05 00

More information

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT:

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 2-6587 (562) 699-05 www.icc-es.org ESR-787 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 05 00 00 METALS

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:

More information

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-409 Reissued June, 00 This report is subject to re-examination in one year. www.icc-es.org (800) 4-6587 (56) 699-054 A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1729 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 05 00 00 METALS SECTION:

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3833 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 03 00

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1767 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 05 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2937 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1530 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2037 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 03 00 00 CONCRETE

More information

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3788 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 04 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2229 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 07 00

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS 0 ICC-ES Report ICC-ES (800) 42-6587 (562) 699-054 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-45 Reissued 06/206 This report is subject to renewal 06/207 DIVISION: 0 00 00CONCRETE SECTION:

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 82 Reissued 0/207 This report is subject to renewal 0/209. DIVISION: 0 00 00 CONCRETE

More information

DIVISION: CONCRETE SECTION: CEMENTITIOUS WOOD FIBER DECKS DIVISION: FINISHES SECTION: ACOUSTIC ROOM COMPONENTS

DIVISION: CONCRETE SECTION: CEMENTITIOUS WOOD FIBER DECKS DIVISION: FINISHES SECTION: ACOUSTIC ROOM COMPONENTS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-1112 Reissued 05/2017 Revised 08/2018 This report is subject to renewal 05/2019.

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2445 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 06 00

More information

DIVISION: METALS SECTION: METAL FASTENINGS DIVISION: STEEL DECKING REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS DIVISION: STEEL DECKING REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: 0 ICC-ES Evaluation Report ICC-ES 000 (800) 43-6587 (56) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-97 Reissued /7 Revised / This report is subject to renewal /. DIVISION: 05 00 00 METALS

More information

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2328 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2182 Reissued 08/2018 This report is subject to renewal 06/2019. DIVISION: 06 00

More information

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3105 Reissued 08/2017 Revised 10/2018 This report is subject to renewal 08/2019.

More information

ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years.

ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: LAMINATED VENEER LUMBER REPORT HOLDER: REDBUILT LLC EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: LAMINATED VENEER LUMBER REPORT HOLDER: REDBUILT LLC EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ESR 299 Reissued 01/2019 This report is subject to renewal 01/2021. DIVISION: 06 00 00

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3145 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 05 00 00 METALS SECTION:

More information

LEGACY REPORT REPORT HOLDER: ITW RAMSET EVALUATION SUBJECT:

LEGACY REPORT REPORT HOLDER: ITW RAMSET EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 4 6587 (56) 699 054 www.icc es.org ER 580 Reissued 07/08 This report is subject to renewal 07/0. DIVISION: 05 00 00 METALS SECTION:

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2787 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3902 Reissued 04/2017 This report is subject to renewal 04/2019. SECTION: 03 15 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-298 Reissued 0/2018 This report is subject to renewal 0/2019. DIVISION: 0 00 00 CONCRETE

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3902 Reissued 04/2017 This report is subject to renewal 04/2019. SECTION: 03 15 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2570 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 05 00 00 METALS SECTION:

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 999 Reissued 0/07 This report is subject to renewal 0/08. DIVISION: 06 00 00 WOOD, PLASTICS AND

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3317 Reissued 07/2018 This report is subject to renewal 07/2020. SECTION: 03 15 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588 0 ICC ES Report ICC ES (800) 4 687 (6) 699 04 www.icc es.org 000 Most Widely Accepted and Trusted ESR 06 Valid: 0/ to 0/6 DIVISION: 04 00 00 MASONRY SECTION: 04 0 9.6 MASONRY ANCHORS REPORT HOLDER: SIMPSON

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-1752 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 0 00 00

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 3754 Reissued 09/07 This report is subject to renewal 09/09. DIVISION: 03 00 00 CONCRETE

More information

REPORT HOLDER: WARE INDUSTRIES, INC., d/b/a MARINO\WARE 400 METUCHEN ROAD SOUTH PLAINFIELD, NEW JERSEY EVALUATION SUBJECT:

REPORT HOLDER: WARE INDUSTRIES, INC., d/b/a MARINO\WARE 400 METUCHEN ROAD SOUTH PLAINFIELD, NEW JERSEY EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4062 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 05 00

More information

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-2269 Reissued 02/2017 Revised 11/2018 This report is subject to renewal 02/2019.

More information

REPORT HOLDER: CALIFORNIA EXPANDED METAL PRODUCTS COMPANY (CEMCO) CROSSROADS PARKWAY NORTH, SUITE 325 CITY OF INDUSTRY, CALIFORNIA 91746

REPORT HOLDER: CALIFORNIA EXPANDED METAL PRODUCTS COMPANY (CEMCO) CROSSROADS PARKWAY NORTH, SUITE 325 CITY OF INDUSTRY, CALIFORNIA 91746 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3016 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 05 00

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1663 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 03 00 00 CONCRETE

More information

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 3779 Reissued 01/2017 Revised 10/2018 This report is subject to renewal 01/2019.

More information

DIVISION: WOOD, PLASTICS, AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS, AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2553 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 06 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-687 (62) 699-04 www.icc-es.org ESR-2907 Reissued 2/207 This report is subject to renewal 2/208. DIVISION: 0 00 00 CONCRETE

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1722 Reissued 05/2018 This report is subject to renewal 05/2020. DIVISION: 09 00

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER: 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3336 Reissued 01/2015 This report is subject to renewal 01/2017. DIVISION: 09 00 00 FINISHES

More information

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3275 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1163 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 03 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1678 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 04 00 00 MASONRY

More information

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A MITEK COMPANY

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A MITEK COMPANY 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1723 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 05 00 00 METALS SECTION:

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: MMFX TECHNOLOGIES A COMMERCIAL METALS COMPANY

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: MMFX TECHNOLOGIES A COMMERCIAL METALS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2107 Reissued 02/2018 This report is subject to renewal 01/2019. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2873 Issued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00 00

More information

REPORT HOLDER: OLMAR SUPPLY INC RESEARCH DRIVE LIVERMORE, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: OLMAR SUPPLY INC RESEARCH DRIVE LIVERMORE, CALIFORNIA EVALUATION SUBJECT: 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3503 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 05 00 00 METALS SECTION:

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2269 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 03 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286 0 ICC-ES Report ICC-ES (800) -687 (6) 6-0 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-678 Reissued 0/0 This report is subject to renewal 0/06 DIVISION: 0 00 00 MASONRY SECTION: 0 0.6 MASONRY

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2218 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2966 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 04 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-2648 Reissued 06/2018 Revised 10/24/2018 This report is subject to renewal 06/2020.

More information

*Corrected October 2005

*Corrected October 2005 ESR-1056* Reissued December 1, 2004 This report is subject to re-examination in two years. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: BARSPLICE PRODUCTS INC WEBSTER STREET DAYTON, OHIO

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: BARSPLICE PRODUCTS INC WEBSTER STREET DAYTON, OHIO 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3517 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 ESR 1040 Reissued 09/2018 Revised 03/2019 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3056 Reissued 10/2015 This report is subject to renewal 10/2017. DIVISION: 04 00 00 MASONRY

More information

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 4-6587 (56) 699-054 ESR-06 Reissued May, 0 This report is subject to renewal June, 05. A Subsidiary of the International Code Council DIVISION: 0 00 00 CONCRETE

More information

DIVISION: CONCRETE SECTION: PRECAST STRUCTURAL CONCRETE REPORT HOLDER: SUPERIOR WALLS OF AMERICA, LTD.

DIVISION: CONCRETE SECTION: PRECAST STRUCTURAL CONCRETE REPORT HOLDER: SUPERIOR WALLS OF AMERICA, LTD. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1662 Reissued 08/2016 This report is subject to renewal 08/2018. DIVISION: 03 00 00 CONCRETE

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3831 Reissued 12/2017 This report is subject to renewal 12/2018. SECTION: 09 29 00

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD.

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2166 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-900 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 0 00 00 CONCRETE

More information

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED STRUCTURAL WOOD REPORT HOLDER: SWEET S JOISTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED STRUCTURAL WOOD REPORT HOLDER: SWEET S JOISTS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2504 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 06 00

More information

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3009 Reissued 02/2018 This report is subject to renewal 02/2020. SECTION: 03 16 00

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2184 Reissued 06/2017 This report is subject to renewal 06/2019. DIVISION: 03 00

More information

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1723 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 05 00 00 METALS SECTION:

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC.

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1271 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 05 00 00 METALS SECTION:

More information

Trusted WOOD I JOISTS SECTION: 06 ON WEB i. Conformity! ICC-ES Evaluation. Copyright 2015

Trusted WOOD I JOISTS SECTION: 06 ON WEB i. Conformity! ICC-ES Evaluation. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2974 Reissued 07/4 This report is subject to renewal 07/5. DIVISION: 06 00 00 WOOD, PLASTICS

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 3-6587 (562) 699-03 www.icc-es.org ESR-3743 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 07 00 00 THERMAL

More information

Joint Evaluation Report ICC-ES (800) (562)

Joint Evaluation Report ICC-ES (800) (562) 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1336 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1812 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 09 00

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1040 Reissued 09/2018 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1040 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3071 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 06 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2810 Reissued 02/2018 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3336 Reissued 01/2017 This report is subject to renewal 01/2019. DIVISION: 09 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION:

More information

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org Most Widely Accepted and Trusted ESR-66 Reissued 0/207 Revised 2/208 This report is subject to renewal 0/209. DIVISION:

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS REPORT HOLDER: WORTHINGTON ARMSTRONG VENTURE (WAVE)

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS REPORT HOLDER: WORTHINGTON ARMSTRONG VENTURE (WAVE) 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2311 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 09 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2966 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 04 00 00 MASONRY

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1210 Reissued 09/2018 This report is subject to renewal 09/2020. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1166P Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 05 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2362 Reissued 05/2017 This report is subject to renewal 05/2019. SECTION: 06 05 23

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD. EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD. EVALUATION SUBJECT: 0 ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org Most Widely Accepted and Trusted ESR-1705 Reissued 07/2018 Revised 09/2018 This report is subject to renewal 07/2019. DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 2562 Reissued 08/206 This report is subject to renewal 08/208. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: COVESTRO, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: COVESTRO, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1221 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 07 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 687 (6) 699 04 www.icc es.org ESR 78 Reissued 07/018 This report is subject to renewal 07/019. DIVISION: 04 00 00 MASONRY

More information

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3606 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 03 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 06 Reissued 0/207 This report is subject to renewal 0/208. DIVISION: 04 00 00 MASONRY

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California Reissued June 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Concrete DURISOL WALL FORMS FOR CONCRETE CONSTRUCTION DURISOL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: ISOLATEK INTERNATIONAL

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: ISOLATEK INTERNATIONAL 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1092 Reissued 12/2015 This report is subject to renewal 12/2016. DIVISION: 07 00 00 THERMAL

More information