1 TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C Toll Free (866) DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED STEEL CONSTRUCTION SUMMARY: Slip connectors allow for vertical movement of studs or supporting structure without imposing additional axial load on wall studs and other wall elements. This Tech Note covers various types of slip connectors in bypass and below-structure conditions and gives design examples for some of the most common types. It does not address the common single or double slip track. Introduction In the design of structures, it is important to define the path of loads through the structure. When non-structural elements are installed within the structural envelope, they often end up unintentionally carrying axial loads. Beams, slabs and other floor elements are often designed for relatively long spans between columns. The unintentional loading of interior non-bearing walls can reduce the live load capacity of supporting elements. For interior drywall framing, relatively small axial loads can cause buckling of the studs and cracking of attached sheathing. Exterior members accidentally loaded can lead to excessive deflection, buckling and failure of the building envelope. Gypsum drywall manufacturers have developed a detail to prevent overloading of interior drywall partitions. This detail, called perimeter relief, includes a gap at the top of the wall and allows a standard runner track to slip over the top of the stud wall framing. For many years, this detail has been applied successfully for interior partitions with light lateral loads. However, until recently, there have been few options for exterior wall and bypass slip connections other than the common slip track. Determination of Need for Slip Connectors: Vertical Movement Slip connectors are used in conditions where vertical movement of the main structure is anticipated, but axial loading of the stud could cause adverse effects. These effects may include, but are not limited to, failure of the connections, buckling of the studs, overstressing and cracking of wall components, and increasing the permeability of roof and wall systems to air and water. Sometimes, by anticipating vertical movement and provid- Definitions Bypass condition A type of connection involving cold-formed steel framed studs, in which the stud members are continuous vertically along a spandrel edge of a floor or roof, and may or may not be connected at the spandrel for lateral support. Curtain Wall Assembly An exterior wall system designed to carry only lateral loads. This type of assembly is typically not designed to carry gravity loads other than its own self-weight. Slip connector A clip, brace, angle, plate or other device that restrains a stud in at least one lateral direction, while permitting vertical movement. Slip Track A cold-formed steel shape consisting of a web with two flanges, without stiffening lips, designed to allow the vertical movement of studs installed between the legs while restraining out-of-plane stud movement. Slip tracks typically have longer legs than standard tracks, and often require additional mechanical bracing of the stud members. Spandrel Beam a structural member loaded in bending only supporting a floor slab or roof deck on one side only. Beams typically occur at the outside edge of a floor or roof, or along the edge of a floor opening such as openings for elevators or stairs. Bypass slip connectors are often connected directly to or adjacent to edge beams. Spandrel Window A continuous window condition between floors, usually made with non-vision glass. Story Drift The lateral movement of one level of a structure with respect to adjacent levels due to the effects of wind or seismic or other lateral loads. 1 Light Gauge Steel Engineers Association TECH NOTE (544) 9/04

2 ing adequate support, systems may be designed in a manner that eliminates the requirement for slip connectors. Exterior wall studs quite often have the capacity to carry large vertical loads in addition to the lateral loads for which they are designed. However, when considering these vertical axial loads, the designer must also consider how these loads will get into the stud (the bypass or top connection) and also how these loads will be carried by the foundation below. Multi-story Construction: Slip Connection at Every Other Level Figure 1 The designer must also account for other wall elements, such as windows and doors, and provide a means for the vertical loads to bypass these elements (usually through headers and jamb studs). The footing or floor below the base of a stud wall must be capable of carrying additional loads from non-slip conditions, such as floor live loads and roof gravity loads. Where the wall studs extend to the underside of the structure, it is much easier to justify the elimination of slip connectors or slip tracks at the tops of the walls. In bypass conditions, because of the eccentricity of the load from the stud centerline, it is usually best to include slip connectors if the anticipated movement and subsequent load is not small. Drift Connectors: Permitting Horizontal Movement in the Plane of the Wall When the overall structure experiences lateral loads, such as from a wind or seismic event, story drift takes place. This is the differential movement of one floor level, or story, relative to the adjacent floors above and below. When this movement is parallel to a wall, and the wall is fixed to the floor planes above and below, the wall is racked out of shape from a rectangle to a parallelogram. If the wall is designed as a shear wall as a part of the building s lateral system, it will have structural elements to resist this racking. Drift Clip Figure 2 However, non-loadbearing curtain wall assemblies typically are not designed as shear walls, even though they may experience sizable out of plane loads. When these walls are not a part of the building s lateral system, and the designer does not want them to contribute unintentional support to the rest of the structure, they may be isolated with drift slip connectors (Figure 2). If the non-loadbearing wall supports a TYPICAL CONT. TRACK HOLD STUD SHORT W/ NO ATTACHMENT TO TRACK VERTICAL SLOTS W/ #12 SCREWS GAP 1/2" DRIFT SLIDE CLIP HORIZONTAL SLOTS WITH FASTENERS AS REQ'D. heavy exterior cladding such as masonry veneer, isolation of the wall helps prevent cracking of the veneer and may help reduce the hazard of falling debris during a lateral load event. TECH NOTE (544) 9/04 2 Light Gauge Steel Engineers Association

3 This isolation also reduces stresses on windows, fixtures, and other openings in curtain wall systems. Locations of Slip Connectors Slip Connection at Base (Not Typical) Figure 5 The most common location for a slip connection is at the top of a wall panel, where it comes to the underside of, or bypasses, a structural element, such as a floor slab or spandrel beam. Under load, this upper portion of the structure may deflect up or down. The connector is designed to allow this Panelized Stacked Wall: Slip Connection at Every Other Floor Figure 3 Figure 4 movement, without axially loading the stud. Note that in this configuration, the only axial load a wall component experiences is the dead load from its own self-weight, and the weight of any cladding that the wall is supporting. Slip Pin Figure 4 3/4" JOINT SECTION VIEW É 5 1/2" x 5 1/2" É 5 1/2" x 5 1/2" É 5 1/2" x 5 1/2" x 1/4" THK. W/ 3/4"Æ x 3 3/16" LONG É 5 1/2" x 5 1/2" x 1/4" THK. W/ 3/4"Æ x 3 3/16" LONG NELSON STUD STUD ( FIELD INSTALLED ) ( FIELD INSTALLED ) OVER-SIZED HOLE IN BOTTOM TRACK OVER-SIZED HOLE IN BOTTOM TRACK É 5 1/2" x 5 1/2" x 1/4" thk. W/ 13/16"Æ HOLE ( ASS'BLY SHOP WELDED É 5 1/2" x 5 1/2" x 1/4" thk. W/ 13/16"Æ HOLE ( ASS'BLY SHOP WELDED IN IN PLACE PLACE ) ) Slip connectors may be located between individual panels that bypass a structure. The panel connections shown in Figures 1, 3 and 4 demonstrate this type of connector: each individual floor level can move independently of every other floor level. The panels are two stories tall, and the slip connector is located at a level that is convenient for the installer and finisher (usually at window sill level). Note that either the male or female portion of this connection (Figures 3 and 4) may be on top. It is very rare for a slip connector to be at the bottom of a wall (Figure 5). In retrofitting existing structures (especially where multi-level roof systems are involved), when the lower portion of the roof cannot take the dead load of the wall in combination with drifting snow, the wall may be clipped to the upper portion of the structure and be seated inside a series of slip connectors or a slip track. Constructability of this type of system is more difficult because the wall studs must be suspended in place with the proper gap at the bottom before being connected to the structure above. ( 4 () 4 PLACES ) t PLAN VIEW Note that this Tech Note addresses under structure, bypass, and horizontal slip conditions. In the bypass condition, the stud or panel system is located outside the structure, rather than underneath floor or roof elements. At a bypass condition, the slip connector must extend from the structural element out to the stud wall system. If there is no slip connec- 3 Light Gauge Steel Engineers Association TECH NOTE (544) 9/04

4 Building Elevation with Partial Spandrel Windows (full spandrel windows similar) Figure 6 6B 6A Spandrel condition Figure 6a 2ND FLOOR (SIMILAR AT ROOF) 2ND FLOOR (SIMILAR AT ROOF) FIXED CONNECTIONS Spandrel condition between windows Figure 6b 2ND FLOOR 2ND FLOOR (SIMILAR AT AT ROOF) ROOF) MAY BE BE EITHER EITHER STACKED STACKED (AS (AS SHOWN) OR OR CONTINUOUS STUD. STUD. FIXED CONNECTIONS SPANDREL BEAM CONTINUOUS WINDOW SLIP CONNECTION MAY BE SLIP SUPPLIED CONNECTION HERE MAY BY WINDOW BE SUPPLIED MANUFACTURER HERE BY WINDOW MANUFACTURER COLD-FORMED STEEL STEEL KICKER IF IMMEDIATELY ADJACENT TO IF IMMEDIATELY ADJACENT TO COLUMN, COLUMN,, THIS MAY THIS MAY BE FIXED BE FIXED CONNECTION. CONNECTION. AWAY AWAY FROM FROM COLUMN, SLIP CONNECTION SLIP CONNECTION MAY MAY BE REQUIRED. BE MOMENT CONNECTION TO RESIST TO RESIST OVERTURNING OF OF KNEE KNEE WALL. WALL. tion, and the connector is assumed to transfer load from the vertical movement of the structure into the stud, the connector must be designed for the moment caused by the point of application of the load being offset from the centerline of the stud. If this is the case, and a moment connection is made between the connector and the stud, the wall stud must also be designed for this moment. Continuity of Horizontal Joints in a Structure In a multi-story structure, there are often horizontal control joints to separate the cladding materials of an exterior wall between floors. At a spandrel condition, with continuous or partial ribbon windows around the entire building, this joint is typically at the top of the windows. With brick or masonry veneer, there is usually a shelf angle or relief angle at each floor level carrying the dead load of the veneer. In this case, the control joint is usually directly below this shelf angle. When very long windows are not continuous around the structure, the location of the horizontal control joint is not always detailed at the same elevation. This can create a condition where wall segments immediately adjacent to one another are expected to slip vertically. Currently, there are no joints available on the market for wall systems to move in this manner. Therefore, detailing of the slip TECH NOTE (544) 9/04 4 Light Gauge Steel Engineers Association

5 Common Types of Slip Connectors The following details show examples of slip connectors commonly used. Other connector configurations not shown here are also possible and permissible. P.D.F.'s AS EACH CLIP EDGE ANGLE (BY OTHERS) 1 1/2" x 6" x 68 MIL x 0'-5" LONG SLIDE CLIP 1 1/2" LONG SLOTS W/ #12 SCREWS P.D.F.'s AS EACH CLIP 1 1/2" x 2 3/4" x 68 MIL x 1'-0" LONG SLIDE CLIP 1 1/2" LONG SLOTS W/ #12 SCREWS A. Slotted angle for attachment to vertical face of structure. B. Slotted angle for attachment to underside or top of structure. t t EDGE ANGLE (BY OTHERS) 97 MIL SLIDE EACH STUD C. Mechanical clip or channel formed to fit inside or over stud, to allow for vertical movement while attaching to vertical face of structure. t PROPRIETARY SLIDE EA. STUD D. Mechanical clip that fits around flange and lip or inside stud, which is attached to top or bottom of the structure. P.D.F.'s AS EACH CLIP TWO-PIECE PROPRIETARY SLIDE CLIP EDGE ANGLE (BY OTHERS) #10 SCREWS AS REQ'D, TOP & BOTTOM E. Angle or clip made up of multiple pieces, where one part of the clip slides with respect to the other part: one part is anchored or fastened to the structure, and the other part is screwed or welded to the stud. 5 Light Gauge Steel Engineers Association TECH NOTE (544) 9/04

6 Multi-Story Construction: Single Member Full Height Figure 7 Multi-story Construction: Slip Connection at Every Level Figure 8 AT BACK-TO-BACK TRACK LOCATIONS, CONTROL JOINTS SHOULD BE INSTALLED IN EXTERIOR FINISH MATERIAL INSIDE FINISH MUST PERMIT DIFFERENTIAL MOVEMENT AT THESE LOCATIONS, TYP. EACH FLOOR. SLIP CONNECTORS AT EVERY LEVEL (TYPICAL) BACK TO BACK TRACK: NO SLIP "STACK" LOCATION IS USUALLY PLACED JUST ABOVE THE FLOORLINE, TO MAKE IT EASIER FOR ACCESS BY INSTALLERS. FOOTING MUST BE CAPABLE OF CARRYING DEAD LOAD OF ENTIRE WALL TYPICAL connections in this type of wall needs to prevent this type of adjacent vertical movement. Testing of Slip Connectors for Capacity The American Society for Testing and Materials (ASTM) currently does not have a test protocol specifically for slip connectors. The Center for Cold Formed Steel Structures (CCFSS) has developed one possible testing protocol based upon ASTM standards and the AISI North American Specification for the Design of Cold Formed Steel Structural Members. This test method is published as LGSEA Research Note Testing and Establishing Design Values for Slip Clips (RN 2-02). In the CCFSS testing protocol, both strength and serviceability capacities are considered. Some or all of the following design items should be considered when designing slip connectors: 1. In-Plane Movement of Wall With seismic or high-wind loading of a wall system, wall components may experience forces along the length of the wall. The connection at the base to the structure below, as well as the diaphragm action of the sheathing, is usually enough to prevent lateral wall movement. However, if slip connectors at the top of a wall restrain such movement, they may become loaded during a seismic event. Relative to seismic forces, this load may be calculated based on the wall weight, and should be considered in design of wall slip connections in high seismic zones. 2. Anticipated Amount of Vertical Movement Slip connectors are typically designed for live load deflection only, and possibly some anticipated deflection due to creep of concrete or wood structures. For roof systems, there could possibly be some upward deflection due to wind uplift conditions. Additional downward gravity loads due to snow accumulation and ponding should be considered. Also, multispan or cantilevered floor and roof conditions can deflect TECH NOTE (544) 9/04 6 Light Gauge Steel Engineers Association

7 Parapet Bypass at Roof Figure 9 Stick Framed Stacked Wall: Slip Connection at Every Other Floor Figure 10 upward when adjacent spans are loaded downward. Standard rational engineering analysis, appropriate to the type of structure and loading conditions, should be used to calculate the anticipated deflection. Once this is done, a connector should be selected that has the capacity to accommodate the anticipated movement. Several of the connectors have a limited range of movement, based on the length of a slot or gap in the connector. Note that most manufacturers recommend that the screw or bolt be centered in the slot, which effectively reduces the allowable movement in any one direction to half the slot length. It is recommended that designers do not specify that connectors be bottomed out in either the top or bottom of a slot, since if the fastener is installed in the wrong end of the slot, the slip connector will be completely ineffective. 3. Amount of Lateral Load on the Connector Based on lateral wind and seismic loads, the connectors must be capable of carrying the lateral loads from the studs back to the structure. Not only must the connectors be capable of carrying the load, but the fasteners used for both the stud and the structure must be investigated separately. Some slide clip manufacturers have tested the entire assembly, which includes their clip, the connection to the structure, and the connection to the studs. Design tables from the manufacturer often give different values for different mil thickness studs, because the stud itself or the connection at the stud will fail before the slip connector will. Designers are responsible for ensuring the validity of published data from manufacturers, and verifying that the appropriate Ω or φ factors are used, based on AISI Chapter F design requirements. 4. Control Joints Walls are typically made up of multiple types of materials. Where a structural slip connector allows for movement of the structure with respect to the cold-formed steel system, additional consideration must be given to movement of the other wall materials. Locations where this occurs include, but are not limited to: At face of slab edge, where a control joint may be needed on the exterior finish system. At the roof side of a bypass parapet (see Figure 9). Below relief angles. At the inside face of bypass walls (see Figure 8). At this location, allowance for movement is typically not as critical, since movement does not compromise the building envelope and allow for thermal or moisture penetration. Stacked Wall Conditions In tall, multi-story bypass conditions, it is difficult and sometimes impractical to ship and install studs longer than feet. For one-, two-, and sometimes three-story structures, a single stud is usually used (Figure 7). Most often, wall stud systems in taller, multi-story bypass conditions are made to span two stories, and stud panels above are stacked on top of the lower panels (Figure 8). This configuration has 7 Light Gauge Steel Engineers Association TECH NOTE (544) 9/04

8 the dead load of the system bear on the strip footing or foundation at the ground wall, and at each floor a slip connection is installed. This slip connection carries only the lateral load from the stud, and all vertical load is transferred to the ground below. Similarly, some projects will have slip connections at every other floor, and fixed connections at the floor below (Figure 1, page 2). With this configuration, less dead load is transferred to the foundation at the wall perimeter, and only half as many slip connectors are required. However, the fixed connections must be designed for both vertical and lateral load. At the interface between panels, a connection must be made that prevents dead loads from the upper panel from being transferred to the lower panel, yet allows lateral loads to be transferred. This may be done with a plate and pin connection, as shown in Figures 3 and 4 (shown on page 3). Other Conditions In certain conditions, slip connections are either not functional or not appropriate for the system being designed. Below is a summary of some of these special conditions: Very high vertical movement, exceeding the capacity of typical connectors. Connections where exterior cladding will not tolerate excessive movement of substrate, or detailing does not include control joints at slip locations. Bridging across building expansion joints. Anticipated building movements will be very small. Author of this Technical Note: Don Allen, P.E. This Technical Note on Cold-Formed Steel Construction is published by the Light Gauge Steel Engineers Association. The information provided in this publication shall not constitute any representation or warranty, express or implied, on the part of LGSEA or any individual that the information is suitable for any general or specific purpose, and should not be used without consulting with a qualified engineer, architect, or building designer. ANY INDIVIDUAL OR ENTITY MAKING USE OF THE INFORMATION PROVIDED IN THIS PUBLICATION ASSUMES ALL RISKS AND LIABILITIES ARISING OR RESULTING FROM SUCH USE. LGSEA believes that the information contained within this publication is in conformance with prevailing engineering standards of practice. However, none of the information provided in this publication is intended to represent any official position of the LGSEA or to exclude the use and implementation of any other design or construction technique. Copyright 2004 Light Gauge Steel Engineers Association Washington, D.C Toll Free (866) TECH NOTE (544) 9/04 8 Light Gauge Steel Engineers Association

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS 1 LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS Thomas Castle, S.E. 2 This presentation is published by the Cold-Formed Steel Engineers Institute ( CFSEI ). The information herein shall not constitute

More information

INTRODUCTION TO CURTAIN WALL DESIGN USING COLD-FORMED STEEL

INTRODUCTION TO CURTAIN WALL DESIGN USING COLD-FORMED STEEL TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. Toll-Free: 1 (866) 465-4732 www.lgsea.com INTRODUCTION TO CURTAIN WALL DESIGN USING COLD-FORMED

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05.40.00 COLD-FORMED METAL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cold-formed metal framing for: B. Exterior load-bearing steel stud walls. 1. Interior load-bearing steel stud walls. 2.

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS

VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. Toll-Free: 1 (866) 465-4732 www.lgsea.com DESIGN VALUES FOR VERTICAL AND HORIZONTAL LATERAL

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05.40.00 COLD-FORMED METAL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cold-formed metal framing for: B. Exterior load-bearing steel stud walls. 1. Interior load-bearing steel stud walls. 2.

More information

TECHNICAL NOTE On Cold-Formed Steel Construction

TECHNICAL NOTE On Cold-Formed Steel Construction TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 6a 1996 Light Gauge Steel Engineers Association Washington, D.C. Toll-Free: 1 (866) 465-4732 www.lgsea.com DESIGN GUIDE FOR PERMANENT BRACING OF COLD-FORMED

More information

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006

More information

LIGHT-GAUGE PANELIZED WALL SYSTEMS. Michael Waggoner Mark Schroeder

LIGHT-GAUGE PANELIZED WALL SYSTEMS. Michael Waggoner Mark Schroeder LIGHT-GAUGE PANELIZED WALL SYSTEMS Michael Waggoner Mark Schroeder INTRODUCTION Development of Light-Gauge Panelized Wall Systems Selecting the Right Framing Systems Building Code Design Considerations

More information

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures Attachment A USG Minimum Design and Construction Requirements for Wood Framed Structures 1. General Design Criteria 1.1. Per Adopted Georgia State Minimum Standard Building Code 1.2. Minimum Live Loads

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05 40 00 COLD-FORMED METAL FRAMING SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the

More information

Specifying Pre-Engineered CFS Floor and Roof Trusses 551f-98

Specifying Pre-Engineered CFS Floor and Roof Trusses 551f-98 Archived Technical Note Cover Page Cold-Formed Steel Engineers Institute (CFSEI) Technical Notes are reviewed and revised on a regular basis. Often, during the review process, the evaluation of the note

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and soffits.

1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and soffits. SECTION 09 2216 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and

More information

COFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016

COFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016 COFS Mission North American Standards for Cold-Formed Steel Framing Roger LaBoube, Ph.D., P.E. Curators Distinguished Teaching Professor Emeritus Director, Wei-Wen Yu Center for Cold-Formed Steel Structures

More information

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1 16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 092216 - COLD FORMED STEEL FRAMING - NON-STRUCTURAL (CFSF-NS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 ACTION

More information

BEARING METAL STUD FRAMING

BEARING METAL STUD FRAMING L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or

More information

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09 PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section

More information

A. Product Data: For each type of cold-formed steel framing product and accessory.

A. Product Data: For each type of cold-formed steel framing product and accessory. SECTION 05400 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior non-load-bearing wall framing. 1.2 ACTION SUBMITTALS A. Product Data: For each type of cold-formed

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior load-bearing steel stud wall systems. 2. Exterior gypsum sheathing. B. Related Sections: 1. Section 04810 - Unit Masonry: for moisture

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

Thermal Bridging in Building Thermal Envelope Assemblies: Repetitive Metal Penetrations

Thermal Bridging in Building Thermal Envelope Assemblies: Repetitive Metal Penetrations Thermal Bridging in Building Thermal Envelope Assemblies: Repetitive Metal Penetrations Educational Overview Revised 2/6/2017 Introduction Thermal bridging is caused by highly conductive elements that

More information

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS This chapter explains the International Residential Code s (IRC s) general earthquake-resistance requirements as well as specific IRC requirements concerning

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer

More information

An Insight into Cold Rolled Steel and its Application to Mid-Rise Building

An Insight into Cold Rolled Steel and its Application to Mid-Rise Building An Insight into Cold Rolled Steel and its Application to Mid-Rise Building Sojoy Deb, B.Tech, Civil Associtate Editor What is Cold Rolled Steel? Thin sheet steel products are extensively used in building

More information

SECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications.

SECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications. SECTION 09.22.16 NON-LOAD BEARING WALL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Non-load bearing metal studs for wall assemblies. B. Area Separation and shaft wall framing products. 1.2 RELATED SECTIONS

More information

4.6 Procedures for Connections

4.6 Procedures for Connections 4.6 Procedures for Connections This section provides Tier 2 evaluation procedures that apply to structural connections: anchorage for normal forces, shear transfer, vertical components, interconnection

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2013 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06110 WOOD FRAMING PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But Not Supplied

More information

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E. STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS SPRING 2017 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2014 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

SECTION NON--STRUCTURAL METAL FRAMING

SECTION NON--STRUCTURAL METAL FRAMING The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives

More information

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives

More information

Building Division Informational Handout

Building Division Informational Handout CITY OF SAN JOSÉ, CALIFORNIA Building Division Informational Handout Conventional Light Frame Construction Design Provisions 2007 CBC Handout No. 2-21 Published: 1/1/08 Page 1 of 3 This document summarizes

More information

STEEL STRUCTURAL SYSTEMS

STEEL STRUCTURAL SYSTEMS STEEL STRUCTURAL SYSTEMS Steel elements are of two basic types: Structural steel shapes are formed into their final shapes by hot-rolling. This method produces such common elements as wide flange sections,

More information

THE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB)

THE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB) THE STEELFORM GOLD STANDARD Product Data Sheet Non-loadbearing Steel Studs (NLB) SPECIFICATION OF NON-LOADBEARING STEEL STUDS (NLB) Steelform provides Prime Materials that are listed below and the profiles

More information

Pre-schematic Considerations. Who. What. Where

Pre-schematic Considerations. Who. What. Where Who What Where Who, What & Where Who are the users? Church School Manufacturers Researchers Who, What & Where What is the purpose? Fellowship Teaching Manufacturing Production Who, What & Where Location,

More information

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification

More information

Connection Design Assistance Manual

Connection Design Assistance Manual Connection Design Assistance Manual Architectural Precast Concrete Glass Fiber Reinforced Concrete Cast Stone Architectural Precast Association 6710 Winkler Road, Suite 8 Fort Myers, FL 33919 Phone: 239-454-6989

More information

STEEL DECK INSTITUTE Industry Standard Terms & Definitions

STEEL DECK INSTITUTE Industry Standard Terms & Definitions s Industry Standard Terms & Definitions November 2016 Industry Standard Terms & Definitions A specialized set of jargon to describe common terms used by manufacturers and other professionals associated

More information

Industry Standard Terms & Definitions Of The Steel Deck Institute

Industry Standard Terms & Definitions Of The Steel Deck Institute Industry Standard Terms & Definitions Of The Steel Deck Institute A specialized set of jargon to describe common terms used by manufacturers and other professionals associated with the usage of Steel Deck

More information

Detailing For Wood Shrinkage

Detailing For Wood Shrinkage Detailing For Wood Shrinkage Presented to: 2014 Texas Wood Solutions Fair Presented by: Doug Steimle Schaefer Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks

More information

Accommodating Building Deflections What every EOR should know about accommodating deflections in secondary cold-formed steel systems

Accommodating Building Deflections What every EOR should know about accommodating deflections in secondary cold-formed steel systems Accommodating Building Deflections What every EOR should know about accommodating deflections in secondary cold-formed steel systems Schafer, B.W. (Chair*) DiGirolamo, E. Eiler, M. Fisher, J. Lindenberg,

More information

Retain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.

Retain Preinstallation Conference Paragraph below if Work of this Section is extensive or complex enough to justify a conference. SECTION 05 40 00 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TECHNICAL NOTE HEADER DESIGN. On Cold-Formed Steel Construction INTRODUCTION BOX HEADERS $5.00

TECHNICAL NOTE HEADER DESIGN. On Cold-Formed Steel Construction INTRODUCTION BOX HEADERS $5.00 TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 HEADER DESIGN Summary: The Standard for Cold-Formed Steel Framing - Header Design

More information

ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax:

ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax: ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA 02144 Tel: 617.628.1700 Fax: 617.628.1711 March 3, 2016 Mr. Jeff Hoover, Principal Tappe Architects, 6 Edgerly Place

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

GENERAL & WIND BEARING

GENERAL & WIND BEARING LIGHTWEIGHT STEEL FRAMING DETAILS GENERAL & WIND BEARING THE STRENGTH WITHIN MONTREAL TORONTO CALGARY EDMONTON VANCOUVER WALL ELEVAT IO N S Bailey Wind Bearing Walls (BWB) Lightweight Steel Framing Bailey

More information

Structural Inspection

Structural Inspection General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized

More information

[TECHNICAL REPORT 3] Lateral System Analysis

[TECHNICAL REPORT 3] Lateral System Analysis Science Center Research Park 3711 Market St. The Pennsylvania State University Department of Architectural Engineering Senior Thesis 2009-2010 Prepared by: November 30, 2009 [TECHNICAL REPORT 3] Lateral

More information

Contents. 1.1 Introduction 1

Contents. 1.1 Introduction 1 Contents PREFACE 1 ANCIENT MASONRY 1 1.1 Introduction 1 1.2 History of Masonry Materials 1 1.2.1 Stone 2 1.2.2 Clay Units 2 1.2.3 Calcium Silicate Units 4 1.2.4 Concrete Masonry Units 4 1.2.5 Mortars 5

More information

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

R CODE CHANGE PROPOSAL FORM (See instructions on page 2) CODE CHANGE PROPOSAL FORM (See instructions on page 2) Code: IRC 12/13 Sections 301.2.2.2.1 Proponent: Charles S. Bajnai, Chesterfield County, VA, ICC Building Code Action Committee 1. Delete as shown

More information

CURTAINWALL DEFLECTION SOLUTIONS

CURTAINWALL DEFLECTION SOLUTIONS l l l l l CURTAINWALL DEFLECTION SOLUTIONS Provides lateral support for curtain wall systems. One of the highest tested load capacities available. Direct attachment to web and support. Most clips are reversible.

More information

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2 research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-005 REVISION 006 American Iron and Steel Institute Cold-Formed

More information

Masonry and Cold-Formed Steel Requirements

Masonry and Cold-Formed Steel Requirements PC UFC Briefing September 21-22, 2004 Masonry and Cold-Formed Steel Requirements David Stevens, ARA Masonry Requirements Composite Construction Masonry is often used in composite construction, such as

More information

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering

More information

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6 DECEMBER, 2016 Page 1 of 6 1 GENERAL 1.01 RELATED SECTIONS.1 Section 01 33 00 - Submittal Procedures..2 Section 07 21 16 - Batt and Blanket Insulation..3 Section 07 92 10 - Sealants..4 Section 09 91 00

More information

CONNECTOR S T U D S H E A R. Design for Composite Structural Action STUD SHEAR CONNECTOR APPLICATION

CONNECTOR S T U D S H E A R. Design for Composite Structural Action STUD SHEAR CONNECTOR APPLICATION S T U D S H E A R CONNECTOR STUD SHEAR CONNECTOR APPLICATION Design for Composite Structural Action Exterior ashlar-type masonry veneer, typically of clay brick or concrete block masonry, are commonly

More information

SECTION FABRICATED WALL PANEL ASSEMBLIES. A. American Institute of Steel Construction (A.I.S.C.) "Manual of Steel Construction.

SECTION FABRICATED WALL PANEL ASSEMBLIES. A. American Institute of Steel Construction (A.I.S.C.) Manual of Steel Construction. SECTION 07 42 63 FABRICATED WALL PANEL ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Provide ACCEL-E steel thermal-efficient-panel wall system. 1.2 RELATED SECTIONS A. Section 05 40 00 - Cold Formed

More information

The designer shall also submit additional information required by the University as described and underlined below.

The designer shall also submit additional information required by the University as described and underlined below. I. Structural Engineering Submissions The designer shall submit all information required by the State Construction Office (SCO) as described in the State Construction Manual Chapter 300 - Project Design

More information

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC Division 93 Effective: 11/22/15 DOCUMENT NO.: P/BC 2014-137 Revised: 06/07/16 Previously Issued As: N/A Mandatory Wood Frame Soft-story

More information

WOOD I-JOIST AWARENESS GUIDE

WOOD I-JOIST AWARENESS GUIDE WOOD I-JOIST AWARENESS GUIDE American Wood Council Flange Web Flange American Forest & Paper Association WOOD I-JOIST AWARENESS GUIDE The American Wood Council is part of the wood products group of the

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

12 - V0 CFP-12 PANEL INDEX. Delta Series CONCEALED FASTENED PANELS BUILDING PRODUCTS VERTICAL PANELS

12 - V0 CFP-12 PANEL INDEX. Delta Series CONCEALED FASTENED PANELS BUILDING PRODUCTS VERTICAL PANELS CONCEALED FASTENED PANELS CFP-12 PANEL INDEX 12 - V0 BASE DETAILS HORIZONTAL JOINT DETAIL PARAPET ROOF DETAIL INSIDE CORNER DETAIL OUTSIDE CORNER DETAIL SOFFIT DETAIL WINDOW JAMB DETAIL WINDOW HEAD DETAIL

More information

LPI 56 Technical Guide

LPI 56 Technical Guide LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform

More information

IBC 2015 and Cold-Formed Steel Design Standards and Design Aids. Roger LaBoube Wei-Wen Yu Center for Cold-Formed Steel Structures

IBC 2015 and Cold-Formed Steel Design Standards and Design Aids. Roger LaBoube Wei-Wen Yu Center for Cold-Formed Steel Structures IBC 2015 and Cold-Formed Steel Design Standards and Design Aids Roger LaBoube Wei-Wen Yu Center for Cold-Formed Steel Structures AISI Specifications 1946 1 st edition 2012 13 th edition 1946 Specification

More information

2012 & 2015 International Building Code. Section Section Section 713.4

2012 & 2015 International Building Code. Section Section Section 713.4 Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated and has an Assembly Evaluation

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3145 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 05 00 00 METALS SECTION:

More information

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings ISSUE A Code Change # 2 Class 3 and Class 4 Buildings (new) Section 1604.9 Disproportionate Collapse. Design for structural integrity of new buildings to protect against disproportionate collapse shall

More information

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK

DIVISION 5 - STRUCTURAL STEEL AND IRON WORK DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05 40 00 COLD-FORMED METAL FRAMING This performance guide specification is part of an architectural specification and is intended to provide a guideline for product selection and may not be appropriate

More information

GENERAL & AXIAL LOADBEARING

GENERAL & AXIAL LOADBEARING LIGHTWEIGHT STEEL FRAMING DETAILS GENERAL & AXIAL LOADBEARING THE STRENGTH WITHIN MONTREAL TORONTO CALGARY EDMONTON VANCOUVER WALL ELEVATIONS Bailey Wind Bearing Walls (BWB) Lightweight Steel Framing (LSF)

More information

Lateral Design of Mid- Rise Wood Structures

Lateral Design of Mid- Rise Wood Structures Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following

More information

Pulaski County, Virginia Practical Wall Bracing

Pulaski County, Virginia Practical Wall Bracing Pulaski County, Virginia Practical Wall Bracing Based on the 2012 Virginia Residential Code The information herein provides guidelines for complying with the most common Practical Wall Bracing provisions

More information

W. Mark McGinley March 3, 2016 ISEA MEETINGS 1

W. Mark McGinley March 3, 2016 ISEA MEETINGS 1 J.B. SPEED SCHOOL OF ENGINEERING Design of s for Masonry Veneers W. Mark McGinley, Ph. D., PE FASTM MASONRY DAY Indianapolis March 3, 2016 Objectives Present a Brief Overview of: Masonry Veneer Wall systems

More information

Product Designation As specified in the AISI standard for cold formed steel framing General provisions A5.2.

Product Designation As specified in the AISI standard for cold formed steel framing General provisions A5.2. Steel Structural Systems (TRI-S) was founded in 2004 to meet the service needs of a growing industry. The company is a world-class manufacturer of light gauge steel framing components for the commercial

More information

STEEL FRAMING INDUSTRY ASSOCIATION OBSERVATION REPORT PROTOCOL STRUCTURAL FRAMING GUIDELINES FOR THE INSPECTOR

STEEL FRAMING INDUSTRY ASSOCIATION OBSERVATION REPORT PROTOCOL STRUCTURAL FRAMING GUIDELINES FOR THE INSPECTOR STEEL FRAMING INDUSTRY ASSOCIATION OBSERVATION REPORT PROTOCOL STRUCTURAL FRAMING GUIDELINES FOR THE INSPECTOR 1. On site Observation Report by Recognized Engineer (PE) every year (prior to issuance of

More information

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

RCKW Kneewall Connectors

RCKW Kneewall Connectors This product is preferable to similar connectors because of a) easier installation, b) higher loads, c) lower installed cost, or a combination of these features. The Simpson Strong-Tie RCKW rigid connectors

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016 Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016 SBCA has been the voice of the structural building components industry since 1983, providing

More information

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC. ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC. Paul Lackey, P.E., Muhammad Ghoraba, Nabil A. Rahman, Ph.D., P.E. and Kurtis Kennedy MidWall is a hold-down product intended to

More information

Typical Deck Details. Albemarle County, Virginia. Based on the 2012 Virginia Residential Code

Typical Deck Details. Albemarle County, Virginia. Based on the 2012 Virginia Residential Code Albemarle County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential decks only. Framing requirements are limited to single

More information

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4 Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated and has an Assembly Evaluation

More information

The System Slotted Deflection Track (pat# 5,913,788)

The System Slotted Deflection Track (pat# 5,913,788) The System Slotted Deflection Track (pat# 5,913,788) UBC 1997/CBC 1997 Section 702. Definitions A FIRE-RESISTIVE JOINT SYSTEM is an assemblage of specific materials or products that are designed, tested,

More information

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

SECTION GYPSUM BOARD & SHEATHING SYSTEMS PART 1!GENERAL! 1.01! SECTION INCLUDES SECTION 09260 GYPSUM BOARD & SHEATHING SYSTEMS! Metal stud wall framing. Metal channel ceiling framing.! Gypsum board.! Sheathing.! Taped and sanded joint treatment.!

More information

Copyright. magazine. CFS Load Bearing Construction

Copyright. magazine. CFS Load Bearing Construction Progressive Collapse Requirements Cold-Formed Steel Load Bearing Construction By Nabil A. Rahman, Ph.D., P.E., Michael Booth and Gary Bennett Figure 1: Cold formed steel load bearing mid-rise construction.

More information

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 Virginia Residential Code

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 Virginia Residential Code Shenandoah County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential decks only. Framing requirements are limited to single

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

SECTION COLD-FORMED METAL TRUSSES

SECTION COLD-FORMED METAL TRUSSES SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information