2018 British Columbia Building Code Public Review of Proposed Changes
|
|
- Elinor Robertson
- 6 years ago
- Views:
Transcription
1 2018 British Columbia Building Code Public Review of Proposed Changes PROPOSED CHANGE: Asbestos CHANGE NUMBER: 2018-BCBC-03-Asbestos CODE REFERENCE: 2015 National Building Code Division B Various Articles DESCRIPTION OF THE PROPOSED AMENDMENT: It is proposed to remove all direct permissions in the British Columbia Building Code (BCBC) to asbestos containing products. PROBLEM/BACKGROUND: The BCBC is based substantially on the model National Building Code of Canada (NBC). The NBC is updated about every five years and British Columbia adopts most of the NBC requirements into the next edition of the BCBC. The 2018 BCBC will be based on the 2015 NBC with some changes specific to British Columbia. The proposed changes show variations from the model 2015 NBC. Though the 2012 BCBC contains some other references to asbestos containing products, some of these have been deleted from the 2015 NBC. For instance, the standard CAN/CGSB , Asbestos-Cement Drain Pipe, is no longer referenced in Table (formerly Table ) or Sentence (1) of the 2015 NBC. Hence, this deletion is not identified. Another instance is that Article of the 2015 NBC no longer lists asbestos millboard as acceptable protection above cooktops and that omission is not shown below. The code language provided is the proposed final code language that will appear in the 2018 BCBC. Comments submitted should focus on the changes noted. Changes from the 2012 BCBC to the 2015 NBC are not identified PROPOSED BRITISH COLUMBIA CODE LANGUAGE: (Deleted text / Added text): Duct Materials 1) Except as permitted by Sentences (2) to (5) and Article , all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay, asbestos-cement or other noncombustible material Compliance with Applicable Standards 1 1) Except as provided in Sentence (2) and elsewhere in this Part, materials and components, and their installation, shall conform to the requirements of the applicable standards in Table where those materials or components are a) incorporated into environmental separators or assemblies exposed to the exterior, and b) installed to fulfill the requirements of this Part. (See Note A (1).) 1 Article was numbered in the 2012 BCBC.
2 Issuing Agency Table Standards Applicable to Environmental Separators and Assemblies Exposed to the Exterior Forming Part of Sentence (1) Document Number Title of Document ASTM D 3019 (4) Lap Cement Used with Asphalt Roll Roofing, Non-Fibered, Asbestos- Fibered, and Non-Asbestos-Fibered ASTM D 4479/D 4479M Asphalt Roof Coatings Asbestos-Free Notes to Table : (4) For the purpose of compliance with Part 5, ASTM D 3019 shall only apply to the non-fibered and non-asbestos-fibered types of asphalt roll roofing Asbestos 2 1) Asbestos shall not be used in air distribution systems or equipment in a form or in a location where asbestos fibres could enter the air supply or return systems Waterproofing Materials 1) Materials installed to provide required waterproofing shall be a) compatible with adjoining materials, and b) resistant to mechanisms of deterioration that may reasonably be expected, given the nature, function and exposure of the materials. 2) Materials used for exterior waterproofing shall conform to a) ASTM D 1227, Emulsified Asphalt Used as a Protective Coating for Roofing, in which case, they shall be installed in accordance with Sentence (3), b) ASTM D 3019, Lap Cement Used with Asphalt Roll Roofing, Non-Fibered, Asbestos- Fibered, and Non-Asbestos-Fibered, except that ASTM D 3019 shall only apply to the non-fibered and non-asbestos-fibered types of asphalt roll roofing. c) ASTM D 4479/D 4479M, Asphalt Roof Coatings Asbestos-Free, in which case, they shall be installed in accordance with Sentence (3) and with reinforcing material, d) ASTM D 4637/D 4637M, EPDM Sheet Used In Single-Ply Roof Membrane, e) ASTM D 4811/D 4811M, Nonvulcanized (Uncured) Rubber Sheet Used as Roof Flashing, f) ASTM D 6878/D 6878M, Thermoplastic Polyolefin Based Sheet Roofing, g) CGSB 37-GP-9Ma, Primer, Asphalt, Unfilled, for Asphalt Roofing, Dampproofing and Waterproofing, where a primer is required, h) CAN/CGSB M, Hot-Applied, Rubberized Asphalt for Roofing and Waterproofing, 2 Article in the NBC 2015 appears as Article in the 2012 BC Building Code. Building and Safety Standards Branch, Province of British Columbia, Proposed Code Change Page 2 of 5
3 i) CAN/CGSB-37.54, Polyvinyl Chloride Roofing and Waterproofing Membrane, j) CGSB 37-GP-56M, Membrane, Modified, Bituminous, Prefabricated, and Reinforced for Roofing, k) CAN/CGSB M, Membrane, Elastomeric, Cold-Applied Liquid, for Non-Exposed Use in Roofing and Waterproofing, l) CAN/CSA-A123.2, Asphalt-Coated Roofing Sheets, m) CAN/CSA-A123.4, Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems, in which case, they shall be installed with reinforcing material, or n) CSA A123.17, Asphalt Glass Felt Used in Roofing and Waterproofing Installation of Thermal Insulation 1) Insulation shall be installed so that there is a reasonably uniform insulating value over the entire face of the insulated area. 2) Insulation shall be applied to the full width and length of the space between furring or framing. 3) Except where the insulation provides the principal resistance to air leakage, thermal insulation shall be installed so that at least one face is in full and continuous contact with an element with low air permeance. (See Note A (3).) 4) Insulation on the interior of foundation walls enclosing a crawl space shall be applied so that there is not less than 50 mm clearance above the crawl space floor, if the insulation is of a type that may be damaged by water. 5) Insulation around concrete slabs-on-ground shall be located so that heat from the building is not restricted from reaching the ground beneath the perimeter, where exterior walls are not supported by footings extending below frost level. 6) Where insulation is exposed to the weather and subject to mechanical damage, it shall be protected with not less than Slope a) 6 mm asbestos-cement board, a)b) 6 mm preservative-treated plywood, or b)c) 12 mm cement parging on wire lath applied to the exposed face and edge. 1) Except as provided in Sentences (2) and (3), the slopes on which roof coverings may be applied shall conform to Table Table Roofing Types and Slope Limits Forming Part of Sentence (1) Type of Roofing Minimum Slope Maximum Slope Asbestos-Cement Corrugated Sheets 1 in 4 no limit Building and Safety Standards Branch, Province of British Columbia, Proposed Code Change Page 3 of 5
4 Attachment 1) Except as permitted by Sentences (2) to (6), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members. 2) Vertical lumber and stucco lath or reinforcing are permitted to be attached to sheathing only where the sheathing consists of not less than a) 14.3 mm lumber, b) 12.5 mm plywood, or c) 12.5 mm OSB or waferboard. 3) Vertically applied metal siding and wood shingles and shakes are permitted to be attached to the sheathing only where the sheathing consists of not less than a) 14.3 mm lumber, b) 7.5 mm plywood, or c) 7.5 mm OSB or waferboard. 4) Where wood shingles or shakes are applied to sheathing which is not suitable for attaching the shingles or shakes, the shingles or shakes are permitted to be attached to a wood lath not less than 38 mm by 9.5 mm thick securely nailed to the framing and applied as described in Article ) Where asbestos-cement shingles are applied to sheathing that is not suitable for attaching the shingles, the shingles are permitted to be fastened to a wood lath not less than 89 mm by 9.5 mm thick securely nailed to the framing. 6) Lath referred to in Sentence (5) shall be applied so that it overlaps the preceding shingle course by not less than 20 mm Materials 1) Resilient flooring used on concrete slabs supported on ground shall consist of asphalt, rubber, vinyl-asbestos, unbacked vinyl or vinyl with an inorganic type backing Asbestos 1) Asbestos shall not be used in air distribution systems or equipment in a form or in a location where asbestos fibres could enter the air supply or return systems Materials in Air Duct Systems 1) Except as provided in Sentences (2) to (6) and in Article , all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay, asbestos-cement or similar noncombustible material. Building and Safety Standards Branch, Province of British Columbia, Proposed Code Change Page 4 of 5
5 Appendix D - FIRE PERFORMANCE RATING D-4.3. MATERIALS CLASSIFIED AS NONCOMBUSTIBLE D Typical Examples Noncombustible materials include brick, ceramic tile, concrete made from Portland cement with noncombustible aggregate, asbestos cement, plaster made from gypsum with noncombustible aggregate, metals commonly used in buildings, glass, granite, sandstone, slate, limestone and marble. RATIONALE FOR CHANGE The BCBC currently contains several direct references to asbestos containing materials. Due to health concerns related to asbestos containing materials, all direct permissions for these are proposed to be removed from the BCBC. Airborne particulate asbestos from handling or disturbing asbestos-containing materials can cause adverse health effects. JUSTIFICATION/EXPLANATION: The proposed change does not expressly prohibit asbestos containing materials to be used, as there are some instances where asbestos containing materials could be accepted as an alternative solution to the code s prescriptive requirements. There are also cases where a product standard referenced by the code may permit the use of asbestos containing products. However, the proposed changes remove all direct references to asbestos containing products from the BCBC as acceptable solutions because of the potential risk to the health and safety of building occupants. Sentences (5) and (6) have been deleted entirely. Although these Sentences were formerly changed in the 2012 BCBC to refer to fibre-cement shingles, new information indicates that these requirements may not be appropriate for attachment of fibre-cement shingles. Building and Safety Standards Branch, Province of British Columbia, Proposed Code Change Page 5 of 5
PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-09-13-03 Ontario-NBC CODE REFERENCE: Division B / 9.13.3. DESCRIPTION OF THE PROPOSED
More informationSECTION BUILT-UP BITUMINOUS WATERPROOFING
SECTION 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING SPEC WRITER NOTE: Delete any item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section
More informationGA APPLICATION OF GYPSUM SHEATHING
1. Scope 1.1 This specification describes the minimum requirements for, and the methods of handling, storage, and application of, gypsum sheathing for use as a substrate for exterior claddings. 1.1.1 Exterior
More informationPlan /Submission Requirements
Plan /Submission Requirements As a result of the Code changes additional information will be required at the building permit application stage to ensure compliance with new 2012 BCBC requirements. This
More informationR-Matte Plus-3: Insulation for the Building Envelope
Attic and Crawl Space Applications R-Matte Plus-3 may be applied to the interior face of stud walls or roof rafters within attics and crawl spaces to provide a layer of continuous insulation (ci). Simply
More informationROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
More informationSUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:
IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:
More informationThe better way to build TM. Installation Manual NAILBASE PANELS
The better way to build TM Installation Manual PANELS November 2018 SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
More informationBuilding Envelope
9.36.2. Building Envelope Module 2 BCBC 9.36. 2014 1 Richard Kadulski Architect 9.36.2. Building Envelope Focus is on total building performance, not just thermal insulation Heat transfer and air leakage
More informationROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
More informationROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES > SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. Pursuant to ORS 215.730; if
More informationBUILDING CODES Presented by CORUM ENGINEERING
BUILDING CODES Presented by CORUM ENGINEERING AGENDA I. The Basics of Foundations A. Footer Designs B. Foundation Walls 1. Non-Backfilled Walls 2. Backfilled Walls (Retaining Walls) C. Slabs vs. Crawl
More informationStone and Masonry Veneer
Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over
More information9.36. Energy Efficiency
Resources and Information NRCAN Energy Efficiency http://www.nrcan.gc.ca/energy/efficiency Canadian Wood Council Wall Thermal Design Tool http://cwc.ca/resources/wall-thermal-design/ 9.36. Energy Efficiency
More informationSection 5.7. Surface Water
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-05-07-01 Ontario-mNBC CODE REFERENCE: Division B / 5.7. Division B / 5.8. DESCRIPTION
More informationOCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers.
OCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers. Designed to save material by functioning as an exterior cladding in thicknesses ranging from 3/8
More informationNEWS LETTER MARCH 27, 2009
PLANNING, BUILDING & DEVELOPMENT SERVICES DEPARTMENT 580-1 Street S.E. Medicine Hat, Alberta T1A 8E6 Telephone: 529-8374 FAX 502-8038 1 NEWS LETTER MARCH 27, 2009 GENERAL As you are probably aware there
More informationASTM Volume 04.04, June 2017 Roofing and Waterproofing
Table of Contents 1 C836/C836M-15 Standard Specification for High Solids Content, Cold Liquid-Applied Elastomeric Membrane for Use with Separate Wearing Course 2 C898/C898M-09 Standard Guide for Use of
More informationThe better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................
More informationEvaluation Report CCMC R StoGuard (w/ Sto Gold Coat and Sto Gold Fill ) sheathing membrane
CONSTRUCTION Evaluation Report CCMC 13612-R StoGuard (w/ Sto Gold Coat and Sto Gold Fill ) sheathing membrane MASTERFORMAT: 07 25 10.05 Evaluation issued: 2012-04-12 Revised: 2012-08-17 1. Opinion It is
More informationROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
More informationSPECIFICATION GUIDELINE
Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section
More informationNOTE TO READER: Where applicable, the content of this page is replicated in the RoofStar Guarantee Standards sections of this Manual
Roof Decks Contents 1 General 2 Wood Decks 2.1 Wood Board Decks 2.2 Plywood Decks 2.3 Non-veneer Wood Decks 3 Concrete Decks 4 Steel Decks 5 Roof Expansion Joints 6 Roof Divider / Control Joints NOTE TO
More informationSTATUTORY AUTHORITY: NMSA 1978 Section and [ NMAC - Rp, NMAC, ]
1 of 7 10/21/2013 12:11 PM TITLE 14 CHAPTER 7 PART 3 HOUSING AND CONSTRUCTION BUILDING CODES GENERAL 2009 NEW MEXICO RESIDENTIAL BUILDING CODE 14.7.3.1 ISSUING AGENCY: Construction Industries Division
More informationNational Master Specification (NMS) Section SECTION INCLUDES.1 Materials and installation for modified bituminous roofing.
Page 1 of 6 Part 1 General 1.1 SECTION INCLUDES.1 Materials and installation for modified bituminous roofing. 1.2 REFERENCES.1 American Society for Testing and Materials International, (ASTM)..1 ASTM C1396/C1396M-[04],
More informationNATIONAL BUILDING CODE OF CANADA 1980
NATIONAL RESEARCH COUNCIL OF CANADA ASSOCIATE COMMITTEE ON THE NATIONAL BUILDING CODE NATIONAL BUILDING CODE OF CANADA 1980 REVISIONS AND ERRATA January 1983 Incorporates emergency revisions published
More informationSPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
More informationCarroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage
Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public
More informationNATIONAL BUILDING CODE OF CANADA 1985
NATIONAL BUILDING CODE OF CANADA 1985 FIFTH REVISIONS Issued by the Associate Committee on the National Building Code National Research Council of Canada Ottawa January 1988 Revisions to the National Building
More informationWVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION
075000 ROOFING SYSTEMS PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. ASTM American Society
More informationFORTIFIED Home High Wind. Bronze New Roof Requirements
THE DECK (PREP MATERIAL, FASTENING) THE ROOF DECK SEALING THE ROOF DECK All existing roof cover and flashings shall be removed; deck shall be a clean, workable surface free from debris. Damaged or rotten
More informationCity of Republic Community Development Department. Residential Roofs REVISION DATE: JANUARY 2017
City of Republic Community Development Department Residential Roofs REVISION DATE: JANUARY 2017 A residential roof permit is required for new roofs and for replacement roofs when the replacement area is
More informationWOOD USE IN NONCOMBUSTIBLE BUILDINGS
INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such
More informationPerimeter Relief and Control Joints in Fire-Rated Gypsum Board
Perimeter Relief and Control Joints in Fire-Rated Gypsum Board In multi-family residential construction, involving fire-rated assemblies stress relief in the firerated assemblies is important, but often
More informationA. This Section provides information regarding vapor permeable roof underlayment for the exterior roof.
DELTA -VENT S Vapor Permeable (Breathable) Roof Underlayment Division 7 Thermal and Moisture Protection PART 1 GENERAL 1.1 SUMMARY A. This Section provides information regarding vapor permeable roof underlayment
More informationInstallation Standard For TILE-LINED ROMAN BATH TUBS IAPMO IS (10) Wall Finish. (3) Test Required. (2) Waterproof. Tile. (8) Concrete Shell
Installation Standard For TILE-LINED ROMAN BATH TUBS IAPMO IS 2-2003 (9) Ceramic Tile Floor Set in Portland Cement Mortar Sub-Floor & Building Felt 2 x 6 Floor Furring Wood Floor Joists Deflection of floor
More informationASTM Standards with Products on BuildSite
with on.org Active A36 Standard Specification for Carbon Structural Steel A36/A36M-05 A82 Standard Specification for Steel Wire, Plain, for Concrete Reinforcement A82/A82M-05a site says A36/A36M-03a has
More informationInterior FRT Wood. References of Previous Model Building Codes
Interior FRT Wood References of Previous Model Building Codes Table of Contents SBBCI Standard Building Code 1 ICBO Uniform Building Code 3 BOCA National Building Code 5 10-SBBCI STANDARD BUILDING CODE
More informationSRP-AirOutshield ROOF Issued:
SECTION 07276: Breathable Underlayment Guide Specification This specification is a guide only and may need editing for the specific intended application. It is the responsibility of the design professional
More informationSECTION THERMAL INSULATION
Pactiv Building Products 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 Toll Free: (800) 241-4402 Web Site: www.green-guard.com SECTION 07210 THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS
More informationU.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw
RESIDENTIAL CONSTRUCTION DETAILS U.S. EDITION A visual guide to construction detailing Emma Walshaw Contents INTRODUCTION 4 PRINCIPLES OF CONSTRUCTION DETAILING 6 FOUNDATIONS 9 PRINCIPLES OF FOUNDATION
More informationCoal Tar Application and Design Considerations
Coal Tar Application and Design Considerations 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com The proper specification of any roof system is extremely
More informationSECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):
SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials
More informationGYPSUM BOARD AND PLASTER
CHAPTER 25 SECTION 2501 GENERAL 2501.1 Scope. 2501.1.1 General. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, lath, gypsum plaster and cement
More informationExterior Stucco and Siding Installation
Exterior Stucco and Siding Installation CITY OF NEWARK, CALIFORNIA BUILDING INSPECTION DIVISION 37101 Newark Boulevard, Newark, CA 94560-3796 510-578-4261 Fax 510-578-4307 e-mail: building.inspection@newark.org
More informationBVSC BVSC. Midwest Technical Inspections Survey Worksheet. Account / Account Code: Insured: Policy #: Building Data - Section 1
Midwest Technical Inspections Survey Worksheet BVSC BVSC Account / Account Code: Agency: Insured: Policy #: Telephone: Alt. Phone: Building Data - Section 1 Building Name (Entire Valuation) Section Name
More informationSECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal.
SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials
More informationSECTION ROOF AND DECK INSULATION
SECTION 07 22 00 ROOF AND DECK INSULATION SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Follow recommendations of National Roofing Contractors
More informationBC BUILDING CODE ERRATA
BC BUILDING CODE ERRATA The following changes should be made to print and offline copies of the 2012 BC Codes. The 2012 BC Codes subscription products include these changes. Highlighted text is used in
More informationFIRE RESISTANCE RATING OF TEK 7-1A CONCRETE MASONRY ASSEMBLIES
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology FIRE RESISTANCE RATING OF TEK 7-1A CONCRETE MASONRY ASSEMBLIES Fire Resistance
More information6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION
6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING SYSTEMS REQUIREMENTS ROOFING TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements. This
More information6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING B30 GENERAL SYSTEM DESCRIPTION
6. ENGINEERING SYSTEMS REQUIREMENTS B30 ROOFING SYSTEMS REQUIREMENTS ROOFING TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements. This
More informationSECTION Fiber Reinforced Stucco 1
CSI SECTION 09200 FIBER REINFORCED STUCCO PART 1 GENERAL 1.01 SUMMARY A. Section Description: Provided lath and plaster where shown on the Drawings, as specified herein, and as needed for complete and
More informationIRC - ROOFING - ROOFING TAC
IRC - ROOFING - ROOFING TAC W A R N I N G Copyright Notice: This document has been reproduced solely for considering proposed changes to the Florida Building Code with the permission of the International
More informationProduct Guide Specification
Product Guide Specification SECTION 04850 (04 40 00) NATURAL THIN VENEER STONE PART 1 GENERAL 1.1 SECTION INCLUDES Specifier Notes: Edit the following as required. A. Natural thin veneer stone for [exterior]
More informationDuPont RainVent Batten Installation Guidelines
DuPont RainVent Batten Installation Guidelines Purpose: To improve the ventilation and draining space behind a cladding system or 3-coat stucco system in residential construction. The DuPont RainVent Batten
More informationFirstEnergy Program Overview
FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio
More informationGeneral Requirements for Mobile Homes
Mobile homes shall conform in all respects to the CAN/CSA-Z240 MH Series of Standards and shall be complete structurally with the entire plumbing, electrical, and heating services installed. Prior to moving
More informationA Design Review of Waterproofing Codes
A Design Review of Waterproofing Codes Section 1807 of Chapter 18 of the International Building Code addresses waterproofing under the section title of Dampproofing and Waterproofing. The section defines
More informationSECTION PREPARATION FOR RE-ROOFING
SECTION 07 01 50.19 PREPARATION FOR RE-ROOFING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Edit Summary article below after establishing
More information1 Exam Prep NRCA Roofing Manual: NRCA Roofing Manual: Membrane Roof Systems 2011 Tabs and Highlights
1 Exam Prep NRCA Roofing Manual: NRCA Roofing Manual: Membrane Roof Systems 2011 Tabs and s These 1 Exam Prep Tabs are based on the National Roofing Contractors Association (NRCA) manual listed below:
More informationThermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY
Insulation for the Building Envelope ROOF WALL SPECIALTY PRODUCT DESCRIPTION Rmax Thermasheath-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam
More information2014 Advanced FBC Fifth Edition Chapter 15 Florida Specific Review
2014 Advanced FBC Fifth Edition Chapter 15 Florida Specific Review Mark Zehnal, CPRC Florida Roofing & Sheet Metal Contractors Association FRSA Director of Technical Services 2012 International Building
More informationSupplementary Standard SB-12. Energy Efficiency For Housing
OBC Excerpt: SB 12 Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing November
More informationWARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS
WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS Per: 2006 B.C.B.C. Part 9 DISCLAIMER: THE INFORMATION CONTAINED IN THIS DOCUMENT REPRESENTS CURRENT WOOD FRAME
More informationSECTION GYPSUM BOARD
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 29 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationDeer Ridge Consulting, Inc.
Deer Ridge Consulting, Inc. Code Compliance Research Report 505 Deer Ridge Lane Ararat, VA 24053 Office: 276-755-9162 Fax: 866-441-1054 www.deer-ridge-consulting.com Subject: NCFI 12-008 Spray Polyurethane
More informationChapter 2: Foundation
Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup
More informationSECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof
SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812
More informationZARA & ASSOCIATES, INC. Peter L. Zara 8435 Sunrise Lake Blvd -# Sunrise, Florida Phone
12 ZARA & ASSOCIATES, INC. Peter L. Zara 8435 Sunrise Lake Blvd -#43-307 Sunrise, Florida 33322 Phone 305-345-3793 E-Mail: peterizara@hotmail.com COURSE MATERIALS ROOFING COURSE WITH UPDATED MATERIALS
More informationList of products of harmonised standards Code 21: INTERNAL & EXTERNAL WALL AND CEILING FINISHES. INTERNAL PARTITION KITS
List of products of harmonised standards Code 21: INTERNAL & EXTERNAL WALL AND CEILING FINISHES. INTERNAL PARTITION KITS As internal or external finishes, as complete elements, d for fire Protection of
More informationCode Compliance Research Report CCRR-0231
Code Compliance Research Report CCRR-0231 Issue Date: 09-01-2015 Revision Date: 10-01-2018 Renewal Date: 09-01-2019 DIVISION: 09 00 00 FINISHES Section: 09 24 00 Portland Cement Plastering REPORT HOLDER:
More informationSECTION ASPHALT SHINGLE ROOFING SYSTEMS. Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text".
SECTION 07311 ASPHALT SHINGLE ROOFING SYSTEMS Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text". PART 1 GENERAL 1.1 SECTION INCLUDES A. Granule surfaced asphalt shingle
More informationENCLOSURE: SIMPLE LAYERS
ENCLOSURE: SIMPLE LAYERS THE BEST RESIDENTIAL WALL ASSEMBLY Brick Face/ cavity/ impermeable membrane as drainage plane Impermeable foam as insulation 1 Moisture Movement through Air Leakage vs. Diffusion
More informationProduct Information Bulletin
Product Information Bulletin BULLETIN NO. ISSUED: REPLACES: 258 September 12, 2014 April 16, 2007 National Building Code 2010 Prescriptive Requirements for ICF Construction (see also attached Detail Dwgs.
More informationCHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION
CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic
More informationMetal Roof Certification & Listing Program
145 Limekiln Road, Suite 100B Issue Dated: 10/27/2017 New Cumberland, PA 17070 Revision Date: 10/27/2017 www.keystonecerts.com Expiration Date: 10/27/2022 Construction Specifications Institute (CSI) Category:
More informationCity of Rohnert Park Building Department Inspection Descriptions
200 SITE REVIEW: Prior to a permit being issued the Fire / Building Department is authorized to examine existing buildings, structures, and site for which an application has been filed. 201 PRECONSTRUCTION
More informationThe City of Winnipeg Section EAST ELMWOOD STORAGE SHED 490 KEENLEYSIDE ST. Page 1 of 5
EAST ELMWOOD STORAGE SHED 490 KEENLEYSIDE ST. Page 1 of 5 Part 1 General 1.1 REFERENCES.1 American National Standards Institute (ANSI).1 ANSI/NPA A208.1-[1999], Particleboard, Mat Formed Wood..2 American
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-07 11 13 (August 2011) Change 1-05/17 --------------------------- Preparing Activity: NAVFAC Superseding UFGS-07 11 13 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationNational Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ].
National Master Specification (NMS) Section 07 21 16 BLANKET INSULATION Publisher: Spex.ca Page 1 Approved: 2014-12-31 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section [ ]. 1.2 REFERENCES.1 CSA Group.1
More informationA. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.
SECTION 092900 - GYPSUM BOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDivision 15 INSULATION Section 15100
Page 1 of 5 SECTION PAGE PART 1 GENERAL 2 1.1 General 2 1.2 References 2 1.3 Work Included 2 1.4 Related Work 2 1.5 Quality Assurance 3 PART 2 PRODUCTS 3 2.1 Description 3 PART 3 EXECUTION 3 3.1 Workmanship
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-29899-9 Edition 1 ASTM E 108:2011 Edition 13 SOUTH AFRICAN NATIONAL STANDARD Fire testing of materials, components and elements used in buildings Part 12: Test methods for fire tests of
More informationSECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division
More informationASSEMBLY DESIGN CRITERIA
Issue: 01 Revision: 00 Page 1 of 7 1 ASSEMBLY - GENERAL 1.1 The work of this section includes the provision of all design, labour, materials, equipment and services required to fabricate and install roof
More informationINSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT
INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY 2009 prepared by N. A. JACOBSEN, P.Eng. CIVIL ENGINEERING CONSULTANT Whitehorse, Yukon ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY
More informationReroofing Requirements for Commercial Buildings in the 2015 International Energy Conservation Code
Reroofing Requirements for Commercial Buildings in the 2015 International Energy Conservation Code NEBOEA 2015 Michael Fischer, Kellen Company The Polyisocyanurate Insulation Manufacturers Association
More informationMetal Roof Certification & Listing Program. 4. Evaluated Roof System Description: 1. Program Licensee: 2. Certified Roof Covering: 5.
11030 002 KCI 145 Limekiln Road, Suite 100B Issue Dated: 11/29/2017 New Cumberland, PA 17070 Revision Date: 11/29/2017 www.keystonecerts.com Expiration Date: 11/29/2022 Construction Specifications Institute
More information** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required. A. Section Mechanical Insulation.
SECTION 15083 HVAC DUCT PROTECTION OVER INSULATION FlexClad This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812 Toll
More informationDRY CONSTRUCTION SYSTEMS
DRY CONSTRUCTION SYSTEMS Adrienn LEPEL BUTE Dry construction systems Prefabricated elements assembly on site Minimal use of water dry construction systems Assembled partitions Suspended ceilings Raised
More informationTABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS
AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding
More informationMetal Roof Certification & Listing Program
Certification Report 145 Limekiln Road, Suite 100B Issue Dated: 1/22/2018 New Cumberland, PA 17070 Revision Date: 1/27/2018 www.keystonecerts.com Expiration Date: 1/22/2023 Construction Specifications
More informationPART 2 - AIR BARRIERS SELF-ADHESIVE
Part 1 - General 1.1 General.1 Related Documents: Provisions established within General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and the Drawings are collectively
More informationSECTION TEMPORARY ROOFING MEMBRANE INSTALLATION. A. Areas of the roof deck for asbestos abatement.
PART 1 GENERAL 1.01 APPLICATIONS SECTION 07500 TEMPORARY ROOFING MEMBRANE INSTALLATION A. Areas of the roof deck for asbestos abatement. B. Areas of the roof deck exposed to the structural roof deck substrate.
More information2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:
SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance
More informationTHE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB)
THE STEELFORM GOLD STANDARD Product Data Sheet Non-loadbearing Steel Studs (NLB) SPECIFICATION OF NON-LOADBEARING STEEL STUDS (NLB) Steelform provides Prime Materials that are listed below and the profiles
More informationSTONE COATED METAL ROOF SHINGLE
GUIDE SPECIFICATION Manufacturer: A Fletcher Building Company 1230 Railroad Street Corona, CA 92882 951-272-8180 phone 951-272-4476 facsimile www.decra.com SECTION 07313 [07 31 13] STONE COATED METAL ROOF
More informationMANUFACTURER S SPECIFICATIONS SECTION EXTERIOR-INTERIOR LIME PLASTER
LE DECOR LIMEPLASTER MANUFACTURER S SPECIFICATIONS SECTION 09220 EXTERIOR-INTERIOR LIME PLASTER PART I - GENERAL 1.1 General A. This is a manufacturer s short form specification. Contact TransMineral USA,
More informationISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Typically RMS Class 1 Wood frame walls, floors, and roof deck Brick Veneer, wood/hardiplank siding, stucco cladding Wood frame roof with wood decking and typical
More information