Member Service Electric Wiring Guidelines

Size: px
Start display at page:

Download "Member Service Electric Wiring Guidelines"

Transcription

1

2 Member Service Electric Wiring Guidelines Table of Contents A. Definitions... 2 B. Member Service Wiring Guidelines... 2 C: Meter located on the house from an underground source - pad transformer or j-box D: Meter Pedestal connection - Maximum 200 amp self-contained E: Meter located on the house with underground service from a pole-mounted transformer F: Meter located on the transformer pole with an underground service G: Meter located on the house with an overhead drop... 4 H: Temporary meter located on the transformer pole... 4 I: Meter connection in frozen ground... 4 J: Open Trench by Developer... 4 K. Grounding... 5 L: Right to Refuse Service... 5 M: Service Utilization... 6 Appendix A.1 Temporary Meter Installation Overhead Meter Loop Source Appendix A.2 Temporary Meter Installation Overhead Source Existing Appendix A.3 Temporary Meter Installation Permanent Meter Pedestal Appendix A.4 Temporary Meter Installation Underground Source Appendix A.5 Overhead Permanent Meter on House Appendix A.6 Overhead to Underground Permanent Meter on Pole Appendix A.7 Overhead to Underground Permanent Meter on Pedestal Appendix A.8 Overhead to Underground UK5 Permanent Meter on House Appendix A.9 Underground Meter Permanent Meter on House Appendix A.10 Meter Installation Permanent Pedestal Type Appendix A.11 Overhead Permanent Large Power Meter on Pole Appendix A.12 Underground Permanent Large Power Meter on House Appendix B.1 Underground Joint Trench Detail Appendix B.2 Underground Trench Detail Conduit Installation Appendix B.3 Pad-Mount Transformer Building Separation Member Service Electric Wiring Guidelines Page 1 of 24

3 A. Definitions Association Gunnison County Electric Association, Inc. (GCEA) is referenced in this document as the Association. Electrical Inspection As referenced in this document, the electrical inspection is defined and controlled by the State of Colorado. The National Electrical Code (NEC) has been adopted by the state and all residential, commercial, and industrial building wiring must comply with NEC requirements. Reference the Colorado State website for complete information: Meter Socket The enclosure for the GCEA electric meter, sometimes called a meter can. The meter socket is provided by GCEA to the member or their electrician. Meter Pedestal The enclosure for the GCEA electric meter normally used for underground service. The meter pedestal is owned and installed by GCEA. NEC The National Electrical Code is a regionally adoptable standard for the safe installation of electrical wiring and equipment in the United States. NESC - The National Electrical Safety Code is a United States standard of the safe installation, operation, and maintenance of electric power and communication utility systems including power substations, power and communication overhead lines, and power and communication underground lines. Service Point The point of connection between the facilities of the serving utility (GCEA) and the premises wiring of the member. B. Member Service Wiring Guidelines GCEA is prohibited from connecting any electrical service until an electrical inspection is acquired from The State of Colorado. A permit may be obtained from the State of Colorado s web site at You may also contact the State of Colorado s local State Inspector at A homeowner is allowed to perform their own electrical work, but if they require assistance, Colorado Law states the person performing the work must be a Colorado licensed electrician. A Colorado Master Electrician must perform all commercial work. GCEA is prohibited from recommending electricians. A listing may be obtained from the phone book or use local references. Note: On all installations the service point varies and is defined in Appendix A. The member/electrician will be responsible to install and maintain the underground service lines from GCEA s equipment location to the service entrance on the house. When the meter is located on the house, GCEA installs and maintains the overhead service drop wire from the pole Member Service Electric Wiring Guidelines Page 2 of 24

4 to the house. The meter sockets may be obtained from GCEA. All other meter sockets must be approved prior to installation. GCEA reserves the right to designate the meter location. The meter should be located on the gable end of the house where snow will not slide down over the meter. The meter should be installed at eye level or approximately five feet above ground level. NOTE: Call before you dig: 811 C: Meter located on the house from an underground source - pad transformer or j-box. Note: call GCEA for instructions if the service is 400 amps or larger. For an underground service with the meter located on the house, GCEA requires that the member wires be dug to within 3 feet of our transformer or junction box. The Colorado Electrical Inspector will notify GCEA when the service has passed the electrical inspection. Please call the Colorado State Electrical inspector with any questions concerning service that is past GCEA equipment. GCEA will energize the service within three days of notification of the inspection approval. If coordination is required, the electrician must call the GCEA Operations Department at for scheduling. D: Meter Pedestal connection - Maximum 200 amp self-contained. For a meter located on a meter pedestal, the member/electrician will tie into the main breaker on the pedestal and run the service to the temporary and/or to the house. The meter pedestal must be owned and installed by GCEA; unless other provisions acceptable to GCEA have been made. If the meter pedestal does not have a breaker, GCEA requires that the wires be dug to within 3 feet of the pedestal and GCEA personnel will terminate member owned secondary wires into the pedestal at the time of the inspection. If the member wishes to have the pedestal changed out to one with breakers, the member must pay all costs associated with the change out. GCEA does not allow temporary or permanent outlets or service equipment to be attached to the meter pedestal. The member/electrician is responsible to install any temporary construction loop or member owned pedestal. The meter will remain in the GCEA owned meter pedestal. Note: GCEA does not allow electricians or homeowners to pull the meter, please contact GCEA if this is necessary. E: Meter located on the house with underground service from a pole-mounted transformer. Note: call GCEA for instructions if the service is 400 amps or larger. If the transformer is located on a pole and the meter is to be placed on the house, the member/electrician shall run their underground secondary wire within 3 feet of the pole and leave enough wire to reach the secondary lugs on the transformer. This will be a minimum of 30 feet on a 35 foot pole. Taller poles will require additional wire to be left. GCEA will install the wire inside GCEA provided conduit and attach it to the pole. If more than one service is fed from Member Service Electric Wiring Guidelines Page 3 of 24

5 the transformer pole, a secondary junction box will be installed at the base of the pole and the member/electrician will run the service wires to within 3 feet of the junction box. GCEA personnel will hook up the wires at the time of the electrical inspection. F: Meter located on the transformer pole with an underground service. When the meter is located on a transformer pole, GCEA will install the meter socket and mast on the pole. The member/electrician will tie into the secondary lugs in the meter socket and run underground from the pole. GCEA will not energize the service until after the inspection has been completed. Note: the only equipment allowed on our poles is temporary meter loop. The temporary meter loop shall be removed after construction is complete. Only one meter loop is allowed per pole, with the exception of the temporary loop. G: Meter located on the house with an overhead drop GCEA installs and maintains the service wire on overhead drops when the meter is located on the house. The member/electrician shall install the meter socket and weather head on the house leaving 12 of tail wire for GCEA personnel to connect the service drop wires. This is the point of service. The member owns and maintains the meter socket and mast. The meter location should be located within 60 feet of the pole when possible. The mast height must meet NESC and NEC codes and be firmly attached to the roof. H: Temporary meter located on the transformer pole Installation of the temporary service will entail that the member/electrician mount a meter socket with a 10-foot mast on the pole, leaving wire long enough to reach the secondary lugs on the transformer. The meter socket should be mounted approximately five feet off the ground. The minimum length of the wire (on a 35 foot pole) will be 20 feet. Taller poles will require additional wire to be left. If the permanent meter is on located on the pole, the temporary receptacles with ground-fault protection may be mounted below the GCEA s meter socket for the period of construction. I: Meter connection in frozen ground If the member/electrician expects to have their service connected in the winter months, please pre-arrange to have the wires dug into GCEA s equipment, before the inspection, in the fall. There will be an additional charge for GCEA crews to dig in member wires in frozen ground. J: Open Trench by Developer The developer or contractor may provide an open trench for joint installation of power and communication cables subject to the following minimum Association requirements. The Association and the affected communication companies must agree to the installation. It shall be a minimum of 36 inches deep. The bottom of this trench must be smooth and parallel to the Member Service Electric Wiring Guidelines Page 4 of 24

6 general grade slopes with no bumps, ripples, or protrusions larger than 2 inches. Six inches of select bedding may be required by the Association prior to the installation of the Association s cable. If bedding is required, the trench must be a minimum of 42 inches deep. 12 inches of select backfill will be placed over the Association s cable. The select material must be approved by the Association. The select material will not contain any construction, organic, or foreign debris. It will not contain any rocks larger than 4 inches in diameter. It will not contain any sharp rocks or objects that in the Association s opinion may damage the cable. The remaining backfill will not contain any large rocks or objects that would damage the cable or hinder future Association maintenance and construction activities. 12 inches of vertical or horizontal separation will be maintained between the power and communication cables. The communication cables must be installed per the attached trench detailed in Appendix B. Additional depth may be required to accommodate the requirements of the communication companies but under no circumstance will the Association s cable be more than four feet deep. There must be a minimum of two feet of unencumbered ground next to the vertical face of the trench. This will ensure that workers will be safe from loose dirt and rocks falling into the trench. Spoil has to be placed so it cannot accidentally run, slide, or fall back into the excavation. It should also be placed so that it channels run off water away from the trench. The Association will install the power cable and associated devices except that the Developer will install the Association s warning tape 12 inches below the final grade. The Developer will be responsible for all compaction requirements. The Developer will provide reasonable notice to the Association so that sections of the open trench can be inspected prior to the dispatching of Association crews for cable installation. The Association may, at its option provide an inspector during all excavation and backfill activities at the Developer s expense. The Developer will be responsible for assuring that the trench is within required easements. The Developer will be responsible for mitigating problems with the open trench including but not limited to water, any required shoring, or removal of debris. K. Grounding Proper grounding is of vital importance. Follow the attached diagrams carefully. Note that separate ground lugs are required for each ground wire connected to a ground rod. L: Right to Refuse Service GCEA reserves the right to refuse service connection if member's wiring is in a condition considered unsafe. GCEA will refuse connection pending an inspection of the premises by an electrical inspector. This inspection will be performed at the member's expense. GCEA will also refuse service if the member s service entrance has been installed improperly or at the wrong location or if fees and charges have not been paid in full by the member. Member Service Electric Wiring Guidelines Page 5 of 24

7 M: Service Utilization GENERAL All wiring, ducts, cables and apparatus, including protective equipment, pertaining to the electric service on the member's side of the point of delivery, shall be furnished, installed, and maintained by the member. Such equipment should be selected to provide efficient use of energy and good voltage regulation. The member shall not use any equipment or device that will adversely affect Gunnison County Electric Association (GCEA) service to the member or to other members. The member's equipment shall be suitable for the service supplied and shall be installed and maintained in good and safe condition by the member in accordance with the rules and requirements of the most current NEC, the public body having jurisdiction, and GCEA. a) Harmonics There are a growing proportion of harmonic producing nonlinear loads on the distribution system. Excessive harmonic distortion on the distribution system can have adverse effects on both utility and member equipment. In order to insure that the processes and operations of one member connected to the system do not affect another, the cooperative will follow the IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems; IEEE Std Considerable effort should be spent in the planning and design phase of plant installation. However, many unique problems could arise after the plant is in operation. In this light, members are required to demonstrate, through field measurements, that their installations comply with the harmonic current limits during the commissioning stage as well as during normal operation. Two criteria should be met by the member. First, the member's total harmonic producing loads, acting as current sources, should not distort the system voltage waveform beyond limits set in IEEE 519 with the exception that the limits on triple harmonics be reduced to one third of the limits for odd order harmonics. Second, the member's capacitors should not cause a resonance condition, both series and parallel, on the system. b) Power Factor GCEA's rates contemplate member's use of service at a power factor, at the point where service is metered, of not less than 95 percent lagging or leading. When neon, fluorescent, or other types of lighting, or other inherently low power factor equipment is used, such equipment must be provided with suitable power factor corrective equipment so that the resultant power factor of such equipment is not less than 95 percent lagging or leading. The member will maintain, at the point of delivery, a power factor as near unity as practical. In the event a low voltage condition due to lagging power factor exists in a degree sufficient to impair GCEA's service, the member may be required to install suitable capacitors or other Member Service Electric Wiring Guidelines Page 6 of 24

8 equipment necessary to raise the overall power factor at the point of delivery to a satisfactory value. The member will maintain such power factor correction equipment in good operating condition and see that fuses, relays and switches are functioning properly. Power factor correction equipment must be sized and connected (switched) with the load to avoid a resultant overall leading power factor. MOTORS Appliances and apparatus should be equipped with motors which will provide the member with satisfactory operation of the appliance and, at the same time, avoid interference with service to other members. Motors may cause voltage disturbances resulting in flickering lights, television interference and other objectionable conditions. a) Motor Identification All motors connected to GCEA's lines should bear a manufacturer's nameplate indicating horsepower, continuous or intermittent duty, speed, voltage, and current ratings. b) Voltage All new motor installations shall be designed to operate on the type of service provided by GCEA. GCEA will advise the member as to the type of service available at the location where the motor is to be used. Inquiry should be made before purchasing or installing the motor. c) Voltage Imbalance Voltage balance may exist at the electric utility revenue meter. Motor installations and their protective relaying should be designed to operate with an imbalance as great as 3%. When negative sequence voltage relays are used for three phase motor protection, the relay settings should prevent nuisance tripping when an imbalance of 3% or less exists. d) Voltage Flicker Current inrush, such as motor starting, can cause a momentary voltage dip called flicker. There are established limits for the amount of voltage flicker that relate to the number of current inrushes (motor starts) in a given period of time and the amount of voltage drop for each inrush (motor start). These conditions can vary greatly depending on the distribution system, transformer, secondary and the device (motor) characteristics. GCEA requires that all devices (motors) fall within these established limits for voltage flicker. There are several remedies available to correct excessive voltage flicker. GCEA can give the member current inrush (motor starting) limits based on a given service location, information provided by the device (motor) manufacturer and typical use of the device (motor). It is the member s responsibility to establish the most appropriate solution to correct a voltage flicker problem. Member Service Electric Wiring Guidelines Page 7 of 24

9 e) Grounding The frame of all motors and starters shall be grounded in accordance with the National Electrical Code. f) Protection of Member Equipment Whenever the inherent design of a motor or the characteristics of the load which it operates are such that automatic reclosing of the electric circuit after a power interruption or sustained low voltage would damage either the motor or the driven equipment, the member must provide adequate protection to prevent such damage. Starting compensators, auto starters, or equivalent apparatus included in each motor installation shall be equipped with under-voltage protection, to return the starting apparatus to the "off" position upon failure of the supply circuit. Three phase motors which would cause damage due to a reversal of motor rotation should be equipped with reverse phase relays to disconnect the motor from the line if it should receive single phase or reverse-phase power. In addition, mechanical devices should be installed to prevent damage due to travel of the driven mechanism in the wrong direction. GCEA assumes no liability for damage resulting from single phase or reverse-phase operation of three phase equipment. We strongly recommend phase loss relays on all three phase motors, because of possible single phasing conditions unknown to GCEA. g) Starting Single phase motors: a. Below 10 HP: can be started across-the-line. b. 10 HP or Larger: Considered an abnormal load. GCEA engineering will determine on a case by case basis if the motor may require a service upgrade. c. Written Pole Motors up to 60 HP: Reduced voltage/current starting limits current at no more than 50% of locked rotor values. d. Will be limited to 60 HP maximum on GCEA service. Three Phase Motors a. Up to 60 HP: Can be started across-the-line. b HP: Reduced starting requirements. Use one of the following starting methods: Primary Resistor or Reactor: For resistor starting, register shall be sized to limit starting currents to no more than 60% of locked-rotor current. Autotransformer: required 50% tap Wye-Delta start Solid State (soft start): required 50% or less of starting current setting. Member Service Electric Wiring Guidelines Page 8 of 24

10 Part winding motor may be considered if starting current is limited to 60% (typical range is 60% - 75%) of locked-rotor. c HP requires a solid state start with 50% or less of normal starting current is required. A GCEA engineering study may be conducted to determine expected voltage dip and determine if alternate settings will be required. Motors 200 HP or larger are considered abnormal loads and may require a service upgrade. d. 500 HP or larger: The member will need to provide engineered design. Design should include at a minimum a one-line diagram, load information, and motor starting information. Engineered design must be signed by an Electrical Engineer with a P.E. license. Design must be approved by GCEA engineering before the member can proceed with project. If after installation, voltage dip limits are exceeded, the service will be disconnected until corrective action is taken by the member to the satisfaction of GCEA. SPECIAL APPARATUS The member shall consult with GCEA before any special apparatus or any apparatus requiring extremely close voltage regulation is connected. It is necessary that electrical equipment be installed and operated in a manner that will not impair service to other members. The use of welding machines, medical imaging machines, VFD s (variable frequency drives), elevators, or other equipment having fluctuating or intermittent load characteristics, or having an abnormal effect on voltage, may require furnishing service through isolated transformers and separate service drops, or excess capacity facilities in order to protect the quality of service to the member or to other members. GCEA reserves the right to charge the member the full cost of facilities necessary to provide any special service required by such equipment and to prevent any impairment in service to members. Member Service Electric Wiring Guidelines Page 9 of 24

11

12

13

14

15

16

17

18

19

20

21

22

23

Basic Service. This Section provides information regarding a. Introduction

Basic Service. This Section provides information regarding a. Introduction Basic Service Introduction This Section provides information regarding a new electric Basic Service for a single phase service less than or equal to 400 amps, and a three phase service less than 50kW.

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

Electric Service Handbook

Electric Service Handbook Electric Service Handbook Revised August 2017 Contact Information Telephone (253): Electrical Inspection Office 502-8277 7:30 am - 4:30 pm Electrical Inspectors Area Map on Website 7:30 am - 8:30 am Automated

More information

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2015 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION.

More information

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service. CHAPTER3 Clark Public Utilities Commercial Electric Service Handbook Commercial Underground Services Preparing for the installation The following checklist will assist in preparing a project for the installation

More information

Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA Phone (703)

Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA Phone (703) Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA 20155 Phone (703) 754-6750 Work Request # UNDERGROUND DISTRIBUTION FACILITIES AGREEMENT (FOR COMMERCIAL CUSTOMER) Developer/Builder/Owner

More information

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy. General The following general requirements shall apply to street lights installed in new underground residential subdivisions or developments located within the service area of Springville City Power (within

More information

ELECTRICAL SERVICE EXTENSION POLICY

ELECTRICAL SERVICE EXTENSION POLICY I. OBJECTIVE A. To provide a fair and consistent method of extending, upgrading and downgrading power lines and other service facilities within the Mason County PUD No.1 (PUD 1) service area. B. To encourage

More information

Welcome to Douglas County PUD

Welcome to Douglas County PUD Welcome to Douglas County PUD We are committed to providing the best possible utility services at the lowest possible cost consistent with sound business principles. To better serve you, please fill out

More information

SERVICE ENTRANCE SPECIFICATIONS FOR RESIDENTIAL AND COMMERCIAL

SERVICE ENTRANCE SPECIFICATIONS FOR RESIDENTIAL AND COMMERCIAL SERVICE ENTRANCE SPECIFICATIONS FOR RESIDENTIAL AND COMMERCIAL 0 3000 AMPERES AT SINGLE-PHASE, 3 WIRE THREE-PHASE, 4 WIRE 120/240 VOLTS 120/240 VOLTS * 240/480 VOLTS 277/480 VOLTS Y 120/208 VOLTS 120/208

More information

PRIMARY LINE EXTENSION

PRIMARY LINE EXTENSION PRIMARY LINE EXTENSION Installation of new electric service to an empty parcel/lot or extending a transformer to within 150' of proposed meter location. This includes installing a permanent branch, addition,

More information

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O. Siemens, Model # SUAS877-PG (or Landis & Gyr # UAS877-PG) Eaton-Durham Model # UTRS223ACH Milbank Midwest Model # U980-O UTRS223AMEP These are some examples of the single meter sockets we require for underground

More information

Section 2: Underground

Section 2: Underground Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,

More information

CUSTOMER SERVICE POLICIES

CUSTOMER SERVICE POLICIES Resolution U-10670 Effective December 18, 2013 Section Title Page No. 1.0 Statement of General Policy... 2 2.0 Electrical Service... 3 2.1 Electrical Service Availability and Characteristics... 3 2.2 Large-Load

More information

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION The following rules and information are issued to make it possible for anyone engaged in electrical wiring or installation of electrical

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

Large Basic Service. This Section applies to members requiring new. Introduction. Service Types

Large Basic Service. This Section applies to members requiring new. Introduction. Service Types Large Basic Service Introduction This Section applies to members requiring new Large Basic electric service installations, greater than 400 amps single phase and greater than 50kW three phase. This Section

More information

COMMERCIAL CONDUIT RULES AND REGULATIONS

COMMERCIAL CONDUIT RULES AND REGULATIONS Electric Engineering Division COMMERCIAL CONDUIT RULES AND REGULATIONS S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies B - 1 1805 NE 30th Ave., Bldg. 400 Ocala, FL 34470-4875

More information

The Idaho Power Company

The Idaho Power Company Preventing Electrical Pollution Working with Customers to Control Electrical Pollution Idaho Power s Approach By Jon D Roholt For the IEEE PES T&D Conference & Exposition Chicago IL, April 23, 2008 The

More information

TYPICAL INSTALLATION INSTRUCTIONS

TYPICAL INSTALLATION INSTRUCTIONS TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect

More information

Technical Requirements for Distributed Generation Connection

Technical Requirements for Distributed Generation Connection Technical Requirements for Distributed Generation Connection Distributed Generation Connection Requirements SECTION 1: INTRODUCTION 1.1 General Purpose This document defines the requirements for connecting

More information

Underground Service Requirements and Instructions

Underground Service Requirements and Instructions This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page

More information

Specifications for Electrical Underground Residential Distribution Systems

Specifications for Electrical Underground Residential Distribution Systems Specifications for Electrical Underground Residential Distribution Systems Specification DDS-2 Revision 13, February 2010 ONCOR ELECTRIC DELIVERY COMPANY SPECIFICATIONS FOR ELECTRICAL UNDERGROUND RESIDENTIAL

More information

Southern California Edison Revised Cal. PUC Sheet No E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No.

Southern California Edison Revised Cal. PUC Sheet No E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No. Southern California Edison Revised Cal. PUC Sheet No. 24700-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No. 22993-E Rule 16 Sheet 1 Applicability: This rule is applicable to both

More information

WIND ENERGY CONVERSION SYSTEMS

WIND ENERGY CONVERSION SYSTEMS CHAPTER 159 WIND ENERGY CONVERSION SYSTEMS 159.01 Purpose and Intent 159.05 Location 159.02 Definitions 159.06 Design and Technical Standards 159.03 General Regulations 159.07 Abandonment and Removal Procedure

More information

TEMPORARY METER POLE INSTALLATION

TEMPORARY METER POLE INSTALLATION TEMPARY METER POLE INSTALLATION MEMBER PROVIDED Location to be made by REMC within 50' of our transformer or existing service Temporary pole to be properly braced 24" 3 wire weatherhead (located 24" from

More information

Energy Delivery Service Guide

Energy Delivery Service Guide Energy Delivery Service Guide Connecting to Gainesville Regional Utilities TM M o r e t h a n E n e rg y. January 17, 2018 Volume 1, Issue 36 TM . A reference guide for planning and designing electric

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2005 Edition of the National Electrical Code (NFiPA-70-2005) as approved by the

More information

ELECTRIC METERING GENERAL

ELECTRIC METERING GENERAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 EQUIPMENT 5.0 METER REQUIREMENTS 6.0 METER FACILITIES 7.0 ELECTRICAL CONNECTIONS 2.0 SCOPE This guide covers general requirements and codes for

More information

1. All underground utilities under railroad tracks shall be encased in a larger pipe or conduit called the casing pipe.

1. All underground utilities under railroad tracks shall be encased in a larger pipe or conduit called the casing pipe. MTS Jack and Bore Design Criteria Note: For the purposes of this Design Criteria and subsequent Construction Notes, the term Jack and Bore is used generically to refer to a number of trenchless construction

More information

PORT OF SAN FRANCISCO ELECTRICAL CODE. Based on the 2016 California Electrical Code

PORT OF SAN FRANCISCO ELECTRICAL CODE. Based on the 2016 California Electrical Code 2016 PORT OF SAN FRANCISCO ELECTRICAL CODE Based on the 2016 California Electrical Code The complete 2016 Port of San Francisco Electrical Code adopts and amends the 2013 edition of the California Electrical

More information

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions.

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions. SECTION 31 23 33 - TRENCHING, BACKFILLING AND COMPACTION PART 1 - GENERAL 1.1 SCOPE A. This Section specifies the requirements for excavating and backfilling for storm sewer, sanitary sewer, water distribution

More information

Electric Service Handbook

Electric Service Handbook Electric Service Handbook Port Orford Office Coquille Office 43050 Highway 101 220 S. Mill Ave Port Orford, OR 97465 Coquille, OR 97423 Phone: (541) 332-3931 Phone: (541) 396-3118 Brookings Office Gold

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

PHILADELPHIA GAS WORKS SPECIFICATION BOOK For Common Trenching For Natural Gas Mains and Services

PHILADELPHIA GAS WORKS SPECIFICATION BOOK For Common Trenching For Natural Gas Mains and Services PHILADELPHIA GAS WORKS SPECIFICATION BOOK For Common Trenching For Natural Gas Mains and Services Introduction This manual is designed as a guide and reference source for developers, builders, contractors,

More information

WOOD POLE SPAN WIRE SIGNAL SYSTEMS

WOOD POLE SPAN WIRE SIGNAL SYSTEMS 7 A wood pole span wire traffic control signal system differs from a mast arm steel pole traffic control signal system in that it uses wood poles and span wires to place the signal indications in the driver

More information

SECTION PACKAGE BOOSTER PUMP STATIONS

SECTION PACKAGE BOOSTER PUMP STATIONS SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to

More information

Welcome! Thank you for your interest in upgrading your service with Great Lakes Energy Cooperative (GLE).

Welcome! Thank you for your interest in upgrading your service with Great Lakes Energy Cooperative (GLE). Welcome! Thank you for your interest in upgrading your service with Great Lakes Energy Cooperative (GLE). Enclosed is the information needed to upgrade your service with GLE. Please read the documents

More information

Excavations and Blind Penetrations into Walls & Floors

Excavations and Blind Penetrations into Walls & Floors Excavations and Blind Penetrations into Walls & Floors (Instructions for using JLab DIGGING, EXCAVATING, FLOOR/WALL PENETRATION PERMIT REQUEST) Permits are required on JLAB property for any penetrations

More information

METER INSTALLATION SPECIFICATIONS HANDBOOK

METER INSTALLATION SPECIFICATIONS HANDBOOK METER INSTALLATION SPECIFICATIONS HANDBOOK METER INSTALLATION SPECIFICATIONS HANDBOOK This booklet is provided to assist customers, architects, engineers, contractors, developers, electricians and inspectors

More information

NOVA SCOTIA POWER INC. UTILITY SERVICE REQUIREMENTS

NOVA SCOTIA POWER INC. UTILITY SERVICE REQUIREMENTS NOVA SCOTIA POWER INC. UTILITY SERVICE REQUIREMENTS May, 2017 NOVA SCOTIA POWER INC. UTILITY SERVICE REQUIREMENTS NOVA SCOTIA POWER INC. UTILITY SERVICE REQUIREMENTS Preface The Utility Services Requirements

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

Trico Electric Cooperative, Inc. Interconnection Requirements. For. Distributed Generation

Trico Electric Cooperative, Inc. Interconnection Requirements. For. Distributed Generation Version Dated May 5, 2017 Trico Electric Cooperative, Inc. Interconnection Requirements For Distributed Generation TRICO ELECTRIC COOPERATIVE, INC. INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION

More information

Requirements for Transmission System Interconnections to Generation, Transmission and End-User Facilities Revised June 10, 2014

Requirements for Transmission System Interconnections to Generation, Transmission and End-User Facilities Revised June 10, 2014 Requirements for Transmission System Interconnections to Generation, Transmission and End-User Facilities Revised June 10, 2014 1040 O Street, P.O. Box 80869 p: 402.475.4211 Lincoln, NE 68501-0869 www.les.com

More information

ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers

ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers 1 st Edition ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers Dear customer, This booklet contains some of the most common metering equipment

More information

Public Utility District Number 1 of Snohomish County

Public Utility District Number 1 of Snohomish County Public Utility District Number 1 of Snohomish County Facility Connection Requirements September 29, 2011 1 Revision History: Number Date Description Original Sept. 29, 2011 Document Origination Compilation

More information

Facility Interconnection Requirements

Facility Interconnection Requirements Facility Interconnection Effective 1/1/2016 1. Purpose Facility Interconnection Facility Interconnection (FAC-001-2) To avoid adverse impacts on the reliability of the Bulk Electric System (BES), RPU documents

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

Distributed Generation. Technical Requirements and Interconnection Agreements

Distributed Generation. Technical Requirements and Interconnection Agreements Distributed Generation Technical Requirements and Interconnection Agreements February 2005 Table of Contents Section 1: Interconnection Process for Distributed Generation Systems (17 pages) Section 2:

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

NEW JERSEY BOARD OF PUBLIC UTILITIES N.J.A.C. 14:4-9 Net Metering and Interconnection Standards for Class I Renewable Energy Systems

NEW JERSEY BOARD OF PUBLIC UTILITIES N.J.A.C. 14:4-9 Net Metering and Interconnection Standards for Class I Renewable Energy Systems NEW JERSEY BOARD OF PUBLIC UTILITIES N.J.A.C. 14:4-9 Net Metering and Interconnection Standards for Class I Renewable Energy Systems SUBCHAPTER 9 NET METERING AND INTERCONNECTION STANDARDS FOR CLASS I

More information

Building Regulations; Construction 11

Building Regulations; Construction 11 Building Regulations; Construction 11 b. Ceilings or roofs shall have a minimum of an "R" factor of 12; and c. Where the roof serves also as the finished ceiling a vent space of two inches shall be required

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

YOUR SPLASH PAD RESOURCE

YOUR SPLASH PAD RESOURCE 1 Index Permits & Inspections Material List Warnings Splash Pad Types Pre-Site Grading Plumbing Schematic Pressure Testing Concrete Preparation and Pour Housing/Nozzle Installation Above Ground Water Feature

More information

1 Introduction. 2 Office Locations/Map. 3 General Requirements. 4 Structures and Planting. 5 Equipment Crossings. 6 Excavations. 7 Utility Crossings

1 Introduction. 2 Office Locations/Map. 3 General Requirements. 4 Structures and Planting. 5 Equipment Crossings. 6 Excavations. 7 Utility Crossings G U I D E L I N E S F O R L A N D O W N E R S, D E V E L O P E R S A N D C O N T R A C T O R S T A B L E O F C O N T E N T S 1 Introduction 2 Office Locations/Map 3 General Requirements 4 Structures and

More information

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification. SECTION 26 05 02 - BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation,

More information

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska Temporary Wiring Practices And Guidelines For NECA National Electrical Contractors Association Omaha, Nebraska Table of Contents I. Planning II. Lighting and Power III. Maintenance IV. Inspections V. Routing

More information

Public Utility District Number 1 of Snohomish County. Facility Connection Requirements February 9, 2018

Public Utility District Number 1 of Snohomish County. Facility Connection Requirements February 9, 2018 Public Utility District Number 1 of Snohomish County Facility Connection Requirements February 9, 2018 1 Revision History: Number Date Description By Reviewed by Approved by: Original Sept. 29, 2011 Document

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS 2190 Dagenais Blvd.West Laval (Quebec) Canada H7L 5X9 Tel. : 514.337.4415 Fax : 514.337.4029 info@burcam.com see us at www.burcam.com VERSION Z MODELS 300500 SUMP PUMPS Your pump

More information

Basic Requirements for Residential Electrical Installations

Basic Requirements for Residential Electrical Installations Basic Requirements for Residential Electrical Installations Wayne County Building Department 428 West Liberty Street Wooster, Ohio 44691 Phone: 330-287-5525 Fax: 330-287-5649 This brochure is intended

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MODELS PH PH PH

MODELS PH PH PH WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

Specifications and Installation Requirements for Underground Service for Residential Developments

Specifications and Installation Requirements for Underground Service for Residential Developments Specifications and Installation Requirements for Underground Service for Residential Developments December 12, 2005 NOVEC Requirements for Underground Residential Developments 1. Scope This specification

More information

REQUIREMENTS for ELECTRIC SERVICE and METER INSTALLATIONS. Florida Service Area. REVISED 2012 Amended (7/2013)

REQUIREMENTS for ELECTRIC SERVICE and METER INSTALLATIONS. Florida Service Area. REVISED 2012 Amended (7/2013) REQUIREMENTS for ELECTRIC SERVICE and METER INSTALLATIONS Florida Service Area REVISED 2012 Amended (7/2013) Section TABLE OF CONTENTS Page Number Committee Member Listing... 1 Important Telephone Numbers...

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Advanced Education ELECTRICAL BULLETIN 2012-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 8 Provincial Chief Electrical Inspector Date : March 1, 2012

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd RAM ELEVATORS Elevator Electrical Planning Guide This guide is intended for people with an understanding of electricity. If you are not, please consult a licensed electrician as errors in application of

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

Why Do I Need a Permit? D ID Y OU K N OW? Protects property values. Makes Selling Property Easier. Site Plan Page 2. Plan Requirements Page 2

Why Do I Need a Permit? D ID Y OU K N OW? Protects property values. Makes Selling Property Easier. Site Plan Page 2. Plan Requirements Page 2 Swimming Pools Building Guide for Homeowners Why Do I Need a Permit? D ID Y OU K N OW? There are many important reasons to obtain building permits and to have inspections performed for your construction

More information

Applying For New or Revised Electric Service. ComEd is happy to assist you in initiating new or revised electric service to your location.

Applying For New or Revised Electric Service. ComEd is happy to assist you in initiating new or revised electric service to your location. ComEd Applying For New or Revised Electric Service ear Customer: ComEd is happy to assist you in initiating new or revised electric service to your location. ComEd must be notified prior to any new construction,

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

Section 4 Underground Service

Section 4 Underground Service Table of Contents Section 4 Underground Service A. GENERAL... 4-7 B. PRIMARY SERVICE - RESIDENTIAL SYSTEMS ON PRIVATE PROPERTY... 4-7 C PRIMARY SERVICE - COMMERCIAL SYSTEMS ON PRIVATE PROPERTY... 4-7 D.

More information

Foundation Manual. Part Number: Version: Updated: July 5, S. Meadows Pkwy. A-9, #329 Reno, NV

Foundation Manual. Part Number: Version: Updated: July 5, S. Meadows Pkwy. A-9, #329 Reno, NV Foundation Manual Part Number: 150002 Version: 1.22 Updated: July 5, 2009 748 S. Meadows Pkwy. A-9, #329 Reno, NV 89521 775-831-9463 www.mariahpower.com July 2009, Mariah Power, All Rights Reserved Dear

More information

Rule 21 Sheet 1 GENERATING FACILITY INTERCONNECTIONS

Rule 21 Sheet 1 GENERATING FACILITY INTERCONNECTIONS Southern California Edison Revised Cal. PUC Sheet No. 31574-E Rosemead, California Cancelling Revised Cal. PUC Sheet No. 30685-E Rule 21 Sheet 1 A. Applicability 1. This Rule describes the Interconnection,

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

Gerber M Series Site Requirements

Gerber M Series Site Requirements Gerber M Series Site Requirements Preparing for the arrival of your new machine. P rior to the arrival of your Gerber M Series Cutting System there are certain things you can prepare to facilitate a quick

More information

2015 Code Rollout Meeting Q & A

2015 Code Rollout Meeting Q & A 1 SECTION QUESTION SaskPower Inspections Dept. ANSWER 2 3 4 5 6 7 8 9 10 11 12 15-02-024 15-02-200 15-02-200 15-02-200 15-02-314 Are existing single or double 'weather proof when not in use' covers allowed

More information

Canadian Electrical Code, Part I Full Impact Assessment

Canadian Electrical Code, Part I Full Impact Assessment Copyright CSA Group 2015 Canadian Electrical Code, Part I Full Impact Assessment Subject 3644 Polarity identification for photovoltaic (PV) dc system conductors & Subject 3694 Photovoltaic (PV) dc arc-fault

More information

CITY OF GRANDE PRAIRIE

CITY OF GRANDE PRAIRIE Inspection Services CITY OF GRANDE PRAIRIE HOMEOWNER S PERMIITS AND WIRING GUIDE FOR ELECTRICAL INSTALLATIONS 2016 INDEX Page Applying for an Electrical Permit 3 Permit Application Requirements 3 Permit

More information

NASSAU COUNTY ELECTRICAL PERMIT APPLICATION FOR CONTRACTORS

NASSAU COUNTY ELECTRICAL PERMIT APPLICATION FOR CONTRACTORS BUILDING PERMIT# (Revised 12/31/17) AP# PERMIT # Cost $ Check# Receipt# NASSAU COUNTY ELECTRICAL PERMIT APPLICATION FOR CONTRACTORS 6 TH EDITION (2017) OF THE FLORIDA BUILDING CODE IS IN EFFECT 2014 NATIONAL

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

UPS Electrical Design and. Installation. critica POWER SUPPLIES

UPS Electrical Design and. Installation. critica POWER SUPPLIES UPS Electrical Design and critica POWER SUPPLIES Installation Important considerations for the electrical design and installation of UPS systems in mission critical applications Where Critical Power applications

More information

SECTION TRENCHING & BACKFILLING

SECTION TRENCHING & BACKFILLING SECTION 02225 - TRENCHING & BACKFILLING 1.0 GENERAL 1.1 Work included in this Section includes trenching and backfilling for underground pipelines and related structures only. 1.2 Reference Specifications

More information

GV 001 Equipment Bases and Enclosures General Information

GV 001 Equipment Bases and Enclosures General Information Eq u ip me n tba s e s a n d En c lo s u re s Ge n e ra lin fo rma tio n E n g in e e r :R.An th o n GV0 0 1 Ap p r o v e r :Jo s h u a Jo n e s Ap r 1 7 2 0 Ap r1 7 GV 001 Equipment Bases and Enclosures

More information

Building Codes in Effect: 2010 California Building, Residential, Fire, Energy and Electrical Codes, including Article 690.

Building Codes in Effect: 2010 California Building, Residential, Fire, Energy and Electrical Codes, including Article 690. AGUA CALIENTE BAND OF CAHUILLA INDIANS A SOVEREIGN TRIBAL GOVERNMENT Planning & Development Department Building and Safety Division 5401 Dinah Shore Drive Palm Springs, CA 92264 (760) 669-6800 RESIDENTIAL

More information

PAYSON CITY POWER AND LIGHT. Electrical Construction Standard Specifications

PAYSON CITY POWER AND LIGHT. Electrical Construction Standard Specifications PAYSON CITY POWER AND LIGHT Electrical Construction Standard Specifications Revised January 27, 2005 1 Payson City Power Standard Specifications 3/5/2009 Table of Contents 4-2.1 Purpose... 4 4-2.2 Codes

More information

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT PERFORMANCE DATA Wholesale Products Page: 6570-1 RPM: 1550 Discharge: 1 ½ Solids: ½ V-A1 W-A1 D-A1 Head, meters 8 4 Head, feet 30 20 10.3 HP 0 0 Capacity, US GPM 0 10 20 30 40 50 60 liters/second 0.0 1.0

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc.

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Franklin County Septic & Zoning permit application: A septic and zoning permit is required for residential or commercial

More information

300828TWP INSTALLATION INSTRUCTIONS MODEL SUBMERSIBLE SUMP PUMP

300828TWP INSTALLATION INSTRUCTIONS MODEL SUBMERSIBLE SUMP PUMP www.burcam.com 2190 Dagenais Blvd. West TEL : 514.337.4415 LAVAL (QUEBEC) FAX : 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during

More information

SECTION FACILITY SANITARY SEWERS

SECTION FACILITY SANITARY SEWERS SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. The Contractor shall limit his construction activities, including materials storage, to areas designated by the Owner's Representative.

A. The Contractor shall limit his construction activities, including materials storage, to areas designated by the Owner's Representative. DIVISION 1 - GENERAL REQUIREMENTS CONSTRUCTION AREA A. The Contractor shall limit his construction activities, including materials storage, to areas designated by the Owner's Representative. VEHICLE PARKING

More information

Electric T&D Bulletin

Electric T&D Bulletin UTILITY OPERATIONS Bulletin Number: 2007-09A FOR IMMEDIATE RELEASE Date: 08-01-07 Title: Check all appropriate boxes Electric T&D Bulletin Underground Residential & Commercial Construction SAFETY ALERT

More information

ELECTRICAL SAFE WORK PRACTICES

ELECTRICAL SAFE WORK PRACTICES ELECTRICAL SAFE WORK PRACTICES I. PURPOSE To establish minimum acceptable standards for AC and DC electrical safe work practices. The program includes requirements for the training of qualified and unqualified

More information