Guide Specification SDP 200

Size: px
Start display at page:

Download "Guide Specification SDP 200"

Transcription

1 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sheet metal roofing panels, metal trim, accessories, fasteners, closures, and sealants. [Specifier Note: Edit paragraph below to suit project requirements.] B. Related Sections: 1. Section Structural Steel 2. Section Steel Deck 3. Section Cold-Formed Metal Framing 4. Section Wood Decking 5. Section Building Insulation 6. Section Roof and Deck Insulation 7. Section Vapor Retarders 8. Section Metal Roof and Wall Panels 9. Section Sheet Metal Flashing and Trim 10. Section Joint Sealants 11. Section Pre-engineered Structures 1.02 REFERENCES A. General: Reference latest edition of applicable codes and standards. B. American Society for Testing and Materials (ASTM): 1. ASTM A792/A792M-Standard Specification for Steel Sheet, 55% Aluminum-Zinc-Alloy-Coated by the Hot-Dip Process. 2. ASTM E1592-Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference. 3. ASTM E1646-Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference. 4. ASTM E1680-Standard Test Method for Rate of Air Leakage through Exterior Metal Roof Panel Systems C. AISI Cold-Formed Steel Design Manual, American Iron and Steel Institute (AISI). D. AISC Manual of Steel Construction, American Institute of Steel Construction (AISC). E. UL Roofing Materials Directory, Underwriters Laboratories, Inc. (UL). 1. UL Standard 580-Tests for Uplift Resistance of Roof Assemblies. [Specifier Note: Edit paragraphs below to suit project requirements]

2 F. FM Approval Guide, Factory Mutual Research Corporation (FM). 1. FM Approval Standard 4471 for Class 1 Panel Roofs. G. Building Codes and Design Standards: 1. ASCE-7, Minimum Design Loads for Buildings and Other Structures, American Society of Civil Engineers (ASCE). 2. BOCA National Building Code, Building Officials and Code Administrators, International (BOCA). 3. Uniform Building Code (UBC), International Conference of Building Code Officials (ICBO). 4. Standard Building Code (SBC), Southern Building Code Congress International (SBCC). 5. International Building Code (IBC), International Code Council (ICC) SYSTEM DESCRIPTION A. Design Requirements: 1. Provide structural standing seam metal roof system with a min. 2" high "vertical" seam side joint, mechanically seamed, with factory applied sealant. 2. Attach roof panels to support substrate with concealed anchor clips designed to allow for thermal movement of the panels. There shall be no exposed fasteners except at panel fixing line and flashing details or as indicated on approved panel drawings. 3. Roll-forming of the panels at the job site must be performed with manufacturer owned and relocatable industrial type roll-forming mill having a minimum of (12) stands to gradually shape the sheet metal. Installer owned or rented roll-formers are not acceptable. 4. Provide metal roof panel system which has been manufactured and installed to withstand specified design loads and maintains performance requirements without defects, damage, or failure. B. Performance Requirements: [Specifier Note: Edit Paragraphs below to suit project requirements.] 1. Design Loads: Design loads shall be as specified below or as indicated on the contract drawings. a. The structural standing seam metal roof system shall be designed to safely resist the positive and negative wind loads as specified below or as indicated on the contract drawings: Roof Area (+) Wind (-) Wind Main Roof psf psf Ridge psf psf Eave psf psf Rake psf psf Corners psf psf

3 b. The structural standing seam metal roof system shall be designed to safely resist a psf roof live load. c. The structural standing seam metal roof system shall be designed to safely resist a psf roof snow load. Unbalanced roof snow loads and snow drifts shall be determined in accordance with [Specify building code or design standard]. 2. Deflection Criteria: Roof panel deflection shall be limited to L/240 for positive loading. 3. Roof panels shall be free to move in response to the expansion and contraction forces resulting from a total temperature range of degrees F during the life of the structure. 4. Roof systems that incorporate foam plastic insulation must be tested by the foam plastic manufacturer in accordance with NFPA-285. C. Performance Testing: Tests shall have been conducted or witnessed by a recognized independent laboratory or independent professional engineer. 1. Allowable uniform uplift load capacity shall be determined in accordance with ASTM E1592. a. The factor of safety against ultimate failure of panel, batten, or clip shall be 1.65, with no increase due to wind. b. Allowable uplift capacity for conditions of gage, span, or loading other than those tested may be determined by interpolation of the test results. Extrapolation of conditions outside the range of the tests is not acceptable. 2. Roof panel system shall be tested for resistance to water penetration in accordance with ASTM E 1646, at a static pressure of 12.0 psf. There shall be no uncontrolled water penetration through the panel side joints. 3. Roof panel system shall be tested for resistance to air leakage in accordance with ASTM E1680, at a static air pressure of 12.0 psf. Air infiltration shall not exceed.02 cfm per sq ft of panel area. 4. Roof panel system shall be tested in accordance with UL Standard 580 and have a Class 90 rating. 5. Roof panels shall withstand a 300 lb concentrated load applied to mid-span between supports with no panel deformation, rib buckling, or panel side joint separation which will adversely affect the weather tightness of the system. 6. Roof panel system shall be tested in accordance with FM Approval Standard 4471 and achieve a windstorm classification of I-90. [Specifier Note: FM approval only applies to panel installation over open steel framing.]

4 1.04 SUBMITTALS A. Product Data: Submit manufacturer's product data sheet and/or product design and installation manual. B. Shop Drawings: Submit panel shop drawings consisting of design and erection drawings, finish specifications, and other data necessary to clearly describe design, materials, sizes, layouts, construction details, fasteners, and erection. Submit small scale layouts of panels and large scale details of edge conditions, joints, fastener and sealant placement, flashings, penetrations and curbs, and special details. Distinction must be made between factory and field assembled work. Drawings must be approved and field verification of all dimensions must occur prior to fabrication. C. Samples: 1. Panel: Two (2) required, Full panel width by 12" long. 2. Anchor Clips: Two (2) required. 3. Fasteners: Two (2) of each type with a statement of intended use. 4. Closure: One metal closure with foam insert. 5. Sealants: One (1) sample of each type, with a statement of intended use. D. Warranties: Submit manufacturer's applicable sample warranties of products. E. Quality Assurance Submittals: 1. Calculations: Submit structural design calculations certified by a registered professional engineer to verify load carrying capacity of the panel system. 2. Test Reports: Submit certified test reports showing that the roof system has been tested and conforms to the specified performance testing requirements. 3. Certificates: a. A written statement from the manufacturer certifying conformance with the specified manufacturer s qualifications listed in article1.05 QUALITY ASSURANCE. b. A written statement from the installer certifying conformance with the specified installer qualifications listed in article 1.05 QUALITY ASSURANCE QUALITY ASSURANCE A. Qualifications: 1. Manufacturers Qualifications: The manufacturer shall have had at least fifteen (15) years in architectural metal roofing design and installation. The manufacturer shall have a permanent, stationary, indoor, production facility.

5 2. Installer Qualifications: a. The installer shall have had a minimum of five (5) years experience in the installation of metal roofing. b. The installer shall be manufacturer certified. B. Pre-installation Meeting: Conduct pre-installation meeting to verify project requirements, substrate conditions, manufacturer's installation instructions, and manufacturer's warranty requirements DELIVERY, STORAGE, AND HANDLING A. Delivery: Material shall be delivered to the site in a dry and undamaged condition and unloaded per the manufacturers instructions. The installer shall inspect materials for damage and stains upon arrival at the site. B. Storage: Materials shall be stored out of contact with the ground in weather tight coverings to keep them dry per the manufacturer's recommendations. Storage accommodations shall provide good air circulation and protection from surface staining. C. Handling: Exercise care in unloading, storing, and handling of panels to prevent bending, warping, twisting, or surface damage. Follow manufacturer's recommendations for material handling WARRANTIES A. Manufacturer's Warranties 1. Material Warranty: The manufacturer shall warrant that the material furnished will remain free from defects in material and workmanship for a period of two (2) years from date of shipment. 2. Metal Substrate Warranty: The manufacturer shall warrant that the metal roof panel substrate will not rupture or perforate due to corrosion within a period of twenty (20) years from date of shipment. 3. Finish Warranty: The manufacturer shall warrant against fading, chalking, peeling, cracking, checking, chipping, or erosion to base metal of the roof panel paint finish for a period of twenty (20) years from date of shipment. [Specifier Note: If required choose from weather tight warranties listed below. Warranty period may extend up to twenty (20) years from date of substantial completion.] 4. Weather Tight Warranty: a. Side Joint Warranty: The manufacturer shall warrant against water penetration of the panel side joint for a period of years from date of substantial completion. Coverage shall be limited to material only. Liability shall be limited to material cost

6 only, with a maximum of $.10 per sq ft. OR b. Standard Warranty: The manufacturer shall warrant against water penetration of the metal roof panel system, including panel side joint and trim conditions for a period of years from date of substantial completion. During the first two (2) years of the warranty, the roofing contractor shall be liable for all such costs and expenses of repair, refinishing, or replacement of the roofing system as covered by the warranty. Coverage shall be limited to material and installation. Manufacturer's liability shall be limited to material value paid to the manufacturer. Erector's liability shall be limited to the dollar amount paid for erection. OR c. Premium Warranty: The manufacturer shall warrant against water penetration of the metal roof panel system, including panel side joint and trim conditions for a period of years from date of substantial completion. During the first two (2) years of the warranty, the roofing contractor shall be liable for all such costs and expenses of repair, refinishing, or replacement of the roofing system as covered by the warranty. Coverage shall be limited to material and installation. Liability shall be limited to repair of the metal panel roof system. PART 2 PRODUCTS 2.01 MANUFACTURERS A. The CENTRIA SDP 200 structural standing seam metal roof system as manufactured by CENTRIA, 1099 US Highway 421 South, Frankfort, KY B. Requests to use alternate systems must be submitted in writing at least ten (10) days prior to the bid date. Product data, samples, test reports, and required certificates shall be included for product review and approval. C. Being listed as a pre-qualified manufacturer does not release the manufacturer from providing complete and acceptable submittal requirements MATERIALS A. Metal Panels: SDP 200 structural standing seam panel as manufactured by CENTRIA. [Specifier Note: Choose panel width, gage, and pan type in section below.] 1. Fabricate metal panels from aluminum-zinc coated steel conforming to ASTM A792 Grade 50B with AZ50 coating when painted AZ50 coating when painted or AZ55 coating

7 when unpainted. Thickness shall be minimum [24 or 22] gage. 2. Panels shall be a min. of [18", or 16"] wide with a 2" vertical seam height. 3. Panels shall [have longitudinal stiffening ribs in the pan to minimize "oil canning" effect, or be flat in the pan with no minor ribs]. B. Concealed Anchor Panel Clips: Fasten metal roof panels to support substrate with concealed anchor clips eliminating all through fastener penetrations. [Specifier Note: Choose concealed anchor panel clip type in section below.] 1. Panel Clips shall be two piece floating clip with a 16ga base and 22ga top. Clip shall be design to accommodate a minimum of 3.5 inches of total thermal movement. Clip shall have a self-centering feature to assure movement capability in both directions. OR 2. Panel Clips shall be one piece fixed clip, 22ga FINISHES [Specifier Note: Choose from panel finishes and textures listed below.] A. Galvalume Plus: Aluminum-zinc coated steel conforming to ASTM A792, Grade 50B with AZ55 coating plus a thin acrylic coating applied to both sides. B. Paint Finishes: Coating systems shall have been tested in accordance with ASTM standard test methods for factory color finish. Exterior color shall be chosen from manufacturer's standard colors. OR 1. Polyvinylidene Fluoride (PVDF): Two-coat system consisting of a nominal 0.2 mil corrosion inhibitive primer on both sides with a 0.75 mil fluoropolymer exterior topcoat and 0.30 mil backer finish. OR 2. Silicone Modified Polyester (SMP): Two-coat system consisting of a nominal 0.2 mil primer on both sides with 0.80 exterior topcoat and 0.30 mil backer finish. C. Texture: Panel finish shall be [smooth or embossed per manufacturer's standard embossed pattern.]

8 2.04 ACCESSORIES A. Fasteners: Use only high quality fasteners as recommended or approved by the roof system manufacturer. Follow fastener manufacturer's recommendations for fastener installation. B. Closures: 1. Screws: Self-drilling screws shall be min. #12 diameter. Self-tapping screws shall be min. #14 diameter. a. Exposed self-drilling and self-tapping screws shall have a zinc die-cast head with neoprene washer or be 300 series stainless steel with neoprene washer. All exposed fasteners shall be painted to match panel color. b. Concealed screws shall be carbon steel with corrosion resistant coating or 300 series stainless steel as required. 2. Rivets: a. Structural bulbed rivets shall be min.3/16" diameter, standard dome head, aluminum rivet and mandrel, with a weather tight EPDM washer under the head. Min. 5/16" diameter, large flange head, aluminum rivet and mandrel, with a weather tight EPDM washer under the head is required at panel endlaps. b. Trim rivets shall be min. 5/32" diameter, stainless steel body and stem with open end or aluminum body and stem with closed end. c. Rivets shall be painted to match panel color. 1. Pre-cut profile closure shall be cut from cross-linked, closed-cell foam. 2. All foam closures shall be protected and supported by a formed metal closure manufactured from the same material, color, and finish as the roofing. C. Sealants: Use only high quality sealants as recommended or approved by the roof system manufacturer. Sealants must not contain oils, asbestos, or asphalts. 1. Non-Curing Butyl: One-part, non-skinning, non-drying, synthetic butyl elastomer. Used for metal-to-metal sealing or bedding of panel and flashing seams or joints. 2. Butyl Tape (Webbed Mastic): Extruded polymeric butyl tape, non-skinning and not easily displaced under compression. Used for critical sealing of panel ends, endlaps, penetrations, closures, and flashings.

9 3. Urethane: One-part moisture curing, gun grade polyurethane sealant. Used for sealing in all exposed conditions. Color to be coordinated with that of panel FLASHING A. All flashing shall be of the same material, gage, finish, color, and texture as the panels unless otherwise noted. B. Flashing design shall conform to details submitted and approved by the Architect and, if required, the panel manufacturer FABRICATION A. Where possible panels shall be manufactured in continuous lengths, full length of panel runs. PART 3 EXECUTION 3.01 EXAMINATION A. The installer shall inspect the building to verify that the structure is ready for roofing installation. 1. All supports shall be in place with all bracing and connections tightened before work proceeds. 2. Field-check dimensions and check support alignment with a taut string or wire; panel misalignment may induce "oil canning" and potentially restrict panel movement. a. Panel/purlin erection tolerances: * Maximum out-of-plane deviation shall be limited to +/-3/16" from control. * Maximum deviation of 1/8" between adjacent purlins or L/500 which ever is less. 3. Do not proceed until unsatisfactory conditions are corrected INSTALLATION A. Install metal roofing system in accordance with approved erection drawings and manufacturer's installation instructions. B. Install metal roofing system so that it is weather-tight, without waves, warps, buckles, fastening stress or distortion. C. Hand-crimp at end of panels and any panel end lap(s) prior to seaming. Do not hand-crimp at each panel clip prior to seaming. Do not walk on panels until panels are mechanically seamed together.

10 D. Seam panels together with electric powered seaming machine supplied by the manufacturer. E. Protect installed panels from abuse by other trades. The general contractor shall be responsible for protecting the roofing from wet cement, plaster, and paint operations. The installer shall provide walk boards in heavy traffic areas to prevent damage to the panels DAMAGED MATERIAL AND CLEANING A. Replace panels and other components of work which have been damaged beyond repair. B. To prevent rust staining, remove immediately from finished surfaces any filings caused by drilling or cutting. C. Wipe down each area after erection is complete for final acceptance.

Specifications for FL-100 Soffit Panel

Specifications for FL-100 Soffit Panel Union Corrugating Company Specifications for FL-100 Soffit Panel SECTION 07410 METAL SOFFIT PANELS PART 1 GENERAL 1.1 DESCRIPTON A. Section Includes: 1. Preformed metal soffit panel system 2. Associated

More information

SL150 Guide Specification

SL150 Guide Specification SL150 Guide Specification This is a suggested guide specification for metal roofing projects where the SL150 panel system is applicable. Questions regarding applicability should be discussed with Union

More information

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Alply CLASSIC WALL Architectural Insulated Panel Wall System SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated

More information

Corium Brick Rainscreen System Specifications

Corium Brick Rainscreen System Specifications CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

Page 1 of 5

Page 1 of 5 SPECIFICATIONS COMPOSITE MATERIAL PANEL SYSTEM ESTOLGA 1000 DRY SEAL SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary

More information

Kodiak AWT Hangar, Kodiak Airport Alaska, Siding Specifications

Kodiak AWT Hangar, Kodiak Airport Alaska, Siding Specifications SECTION 074213.19 - INSULATED METAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

Guideline Specifications

Guideline Specifications Page 1 of 7 PART 1 Guideline Specifications Exterior Aluminum/Composite Wall Panels GENERAL ARROWHEAD 508 SYSTEM Pressure Equalized Rainscreen SECTION 07410 1.01 SUMMARY A. Work of this section included

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions (Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying perforated

More information

SECTION INSULATED METAL WALL PANELS. ATAS International, Inc. General Specification for Commercial/Industrial and Architectural Applications

SECTION INSULATED METAL WALL PANELS. ATAS International, Inc. General Specification for Commercial/Industrial and Architectural Applications SECTION 07 42 13 INSULATED METAL WALL PANELS ATAS International, Inc. General Specification for Commercial/Industrial and Architectural Applications PART 1 GENERAL 1.1. Summary The contract drawings indicate

More information

SECTION TURBINE VENTILATORS

SECTION TURBINE VENTILATORS SECTION 07 72 00 TURBINE VENTILATORS **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular project.

More information

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.*** ***This section has been updated to IBC. Verify for specific project conditions.*** PART 1 GENERAL 1.1 SUMMARY ***Edit to project requirements*** A. Section Includes: 1. Clear copper and preweathered copper

More information

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions SECTION 07 41 00 ROOF PANELS Kingspan Insulated Panels KingZip Pre-Insulated Standing Seam Metal Roof Panels PART 1 - GENERAL

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION MANUFACTURED ROOF AND WALL PANELS SECTION SHEET METAL ROOFING

SECTION MANUFACTURED ROOF AND WALL PANELS SECTION SHEET METAL ROOFING SPECIFICATIONS www.englertinc.com MANUFACTURER ENGLERT, INC. 1200 Amboy Avenue Perth Amboy, New Jersey 08861 Tel: (732) 826-8614 Fax: (732) 826-8865 PART I GENERAL 1.01 WORK INCLUDED SECTION 07410 - MANUFACTURED

More information

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM - --- -- ----..-------~------------------------------------ GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION 07415 REROOFING ADJUSTABLE FRAMING SYSTEM PART 1 - GENERAL 1.01 SCOPE A.

More information

Prestige Roofing System

Prestige Roofing System Prestige Roofing System Installation Manual 3449 Hempland Road Lancaster, PA 17601 (800) 477-2741 308 Alabama Blvd. Jackson, GA 30233 (800) 884-4484 World Wide Web: www.fabral.com E-Mail: architecturalsystems@fabral.com

More information

SECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels.

SECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels. 1/11 SECTION 074213.23 - ALUMINUM COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes aluminum composite material wall panels. 1.2 PRE-INSTALLATION MEETINGS A. Pre-installation

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

BEARING METAL STUD FRAMING

BEARING METAL STUD FRAMING L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or

More information

CENTRIA FORMABOND II Metal Composite Wall System

CENTRIA FORMABOND II Metal Composite Wall System CENTRIA FORMABOND II Metal Composite Wall System CENTRIA FormaBond II is the only true metal composite panel wall system designed, manufactured and fabricated by a single, reliable national manufacturer

More information

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

Signature Series 5 Lap SECTION ALUMINUM WINDOWS Signature Series 5 Lap SECTION 08 51 13 ALUMINUM WINDOWS PART 1 GENERAL 1.01 SUMMARY A. Related Documents: Conditions of the Contract, Division 1 - General Requirements, and Drawings apply to Work of this

More information

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS SECTION 07 4213.25 PART 1- GENERAL 1.01 SECTION INCLUDES A. Copper metal plate wall panels. 1.02 RELATED REQUIREMENTS A. Section 05 4000 Cold-Formed Metal Framing: Wall panel substrates support framing.

More information

SECTION METAL BUILDING SYSTEMS

SECTION METAL BUILDING SYSTEMS SECTION 13 3419 PART 1 GENERAL 1.01 SECTION INCLUDES A. Manufacturer-engineered, shop-fabricated structural steel building frame. B. Insulated Metal wall and roof panels including gutters and downspouts.

More information

CENTRIA Intercept Entyre Preformed Metal Modular Panel Wall System

CENTRIA Intercept Entyre Preformed Metal Modular Panel Wall System CENTRIA Intercept Entyre Preformed Metal Modular Panel Wall System CENTRIA Intercept Entyre is a unique modular metal wall system designed, available from a reliable national manufacturer and supported

More information

DUGOUT MODEL (4 POST) 10 x 24 SPECIFICATIONS

DUGOUT MODEL (4 POST) 10 x 24 SPECIFICATIONS DUGOUT MODEL (4 POST) 10 x 24 SPECIFICATIONS Dimensions: Roof Dimensions 10-0 x 24 Column Dimensions (center to center) 6-7 x 22-9 Minimum Clearance 7-6 Minimum Clearance @ Front ±9-2 Roof Pitch 2:12 pitch

More information

SECTION CANOPIES. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved

SECTION CANOPIES. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved SECTION 10538 CANOPIES Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2009-2011 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Freestanding, pre-engineered

More information

MultiLok-24 Guide Specifications conforming to C.S.I. standards. A Division of ASC Profiles

MultiLok-24 Guide Specifications conforming to C.S.I. standards. A Division of ASC Profiles MultiLok-24 Guide Specifications conforming to C.S.I. standards A Division of ASC Profiles AEP SPAN MultiLok-24 Guide Spec i fi ca tions MANUFACTURER - AEP SPAN 5100 East Grand Avenue, Dallas, TX 75223,

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

Guide Specifications. Metl-Span Architectural Insulated Metal Panel For Commercial & Industrial Buildings PART 1 GENERAL

Guide Specifications. Metl-Span Architectural Insulated Metal Panel For Commercial & Industrial Buildings PART 1 GENERAL Guide Specifications 2012 Master Format Section 07 42 13.19 Metl-Span Architectural Insulated Metal Panel For Commercial & Industrial Buildings PART 1 GENERAL 1.1 Work Included A. Pre-insulated metal panel

More information

SECTION PRE-ENGINEERED MEMBRANE STRUCTURE

SECTION PRE-ENGINEERED MEMBRANE STRUCTURE SECTION 13125 PART 1 - GENERAL 1.1 SUMMARY A. Section includes the design, engineering, fabrication and erection of a frame-supported, tensilemembrane structure complete with entrance and exit doors and

More information

SIERRA MODEL 12 X 24 SPECIFICATIONS

SIERRA MODEL 12 X 24 SPECIFICATIONS SIERRA MODEL 12 X 24 SPECIFICATIONS Dimensions: Roof Dimensions 12-0 x 24-0 Column Dimensions (center to center) 9-0 x 21-0 Minimum Clearance 8-0 Shed Roof 1:12 pitch Square Feet Under Roof 288 Columns

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

Prestige Series Guide Specifications

Prestige Series Guide Specifications Prestige Series Guide Specifications MANUFACTURER AEP SPAN www.aepspan.com info@aepspan.com 800-733-4955 Prestige Series is a metal panel for exterior and interior walls, fascias and equipment screen applications.

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

CENTRIA EcoScreen Perforated Screen Wall Panels

CENTRIA EcoScreen Perforated Screen Wall Panels CENTRIA EcoScreen Perforated Screen Wall Panels CENTRIA EcoScreen Perforated Screen Wall Panels offer a variety of aesthetic solutions to equipment and other screening design requirements. EcoScreen Panels

More information

A. Product Data: For each type of deck, accessory, and product indicated.

A. Product Data: For each type of deck, accessory, and product indicated. SECTION 053100 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Roof deck. 2. Composite floor deck. 3. Noncomposite form deck. 1.2 SUBMITTALS A. Product Data: For each type of deck, accessory, and

More information

SECTION METAL COMPOSITE MATERIAL WALL PANELS

SECTION METAL COMPOSITE MATERIAL WALL PANELS SECTION 07 4264 METAL COMPOSITE MATERIAL WALL PANELS USE THIS SECTION WHEN SPECIFYING C.R. LAURENCE EWS SERIES 100 STANDARD WET SEAL FOR ALUMINUM-FACED, STAINLESS STEEL, COPPER, OR TITANIUM COMPOSITE MATERIAL

More information

by Rollfab Metal Products

by Rollfab Metal Products by Rollfab Metal Products SECTION 07460 ALUMINUM SIDING AND SOFFITS PART 1 GENERAL 1.2 RELATED SECTIONS 1.3 REFERENCES A. SECTION INCLUDES B. Aluminum Siding. C. Aluminum Soffits. D. Aluminum trim and

More information

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1 GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials and services to furnish and install SECURITY

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions

Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions Specifiers: Click on the icon in the WD toolbar to reveal detailed instructions (Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying metal wall panels

More information

A. Access doors and frames are part of an access door and frame allowance.

A. Access doors and frames are part of an access door and frame allowance. SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

PW251 21/2 x7 GUIDE SPECIFICATION. Curtain Wall

PW251 21/2 x7 GUIDE SPECIFICATION. Curtain Wall Manufacturer: Coral Architectural Products 3010 Rice Mine Road Tuscaloosa, AL. 35406 Voice: (800) 772-7737 Fax: (800) 443-6261 SECTION 08900 ALUMINUM CURTAIN WALL This suggested guide specification has

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2218 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

Magnum Board Section Digicon Information Inc. Page 1

Magnum Board Section Digicon Information Inc. Page 1 Digicon Information Inc. Page 1 This section includes sheathing for exterior walls for use in a potentially damp or wet exterior cladding environment. This sheathing section forms an exterior flat plane

More information

CENTRIA Profile Series Exposed Fastener Metal Roof Panels

CENTRIA Profile Series Exposed Fastener Metal Roof Panels CENTRIA Profile Series Exposed Fastener Metal Roof Panels CENTRIA Profile Series Exposed Fastener Metal Roof Panels are a versatile design choice for both new and retrofit projects. Panels are manufactured

More information

TRIAD CORRUGATED METAL, INC.

TRIAD CORRUGATED METAL, INC. TRIAD CORRUGATED METAL, INC. C O M M E R C I A L R E S I D E N T I A L A G R I C U L T U R A L Snap Loc Panel Guide Snap Loc metal panels are a perfect fit for residential, architectural and commercial

More information

CENTRIA FORMABOND. Aluminum Composite Wall System

CENTRIA FORMABOND. Aluminum Composite Wall System CENTRIA FORMABOND Aluminum Composite Wall System CENTRIA FormaBond is the only true aluminum composite panel wall system designed, manufactured and fabricated by a single, reliable national manufacturer

More information

ARCHITECTURAL DESIGN GUIDE

ARCHITECTURAL DESIGN GUIDE CFR INSULATED METAL ROOF PANEL ARCHITECTURAL DESIGN GUIDE PIONEERING INSULATED METAL PANEL TECHNOLOGY PIONEERING INSULATED METAL PANEL TECHNOLOGY CONTENTS INTRODUCTION........................................................2

More information

1.1 SECTION INCLUDES A. Insulated Metal and FRP Wall and Ceiling Panels and Related Accessories.

1.1 SECTION INCLUDES A. Insulated Metal and FRP Wall and Ceiling Panels and Related Accessories. Permatherm Specification SECTION 07435 (CSI MasterFormat 1995) SECTION 07 42 43 (CSI MasterFormat 2004) SECTION 07 42 13.19 (CSI MasterFormat 2012) INSULATED METAL and FRP WALL PANELS Part 1: General General:

More information

March 26, 2017 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES

March 26, 2017 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES March 26, 2017 Page 1 DESCRIPTION PRODUCT FEATURES Factory fabricated metal wall siding/cladding with related flashings and accessory components. Online brochure available at: http://www.lenmak.com BASIC

More information

EVO ALUMINUM COMPOSITE METAL (ACM) WALL PANEL SPECIFICATION

EVO ALUMINUM COMPOSITE METAL (ACM) WALL PANEL SPECIFICATION SECTION 07 42 43 EVO ALUMINUM COMPOSITE METAL (ACM) WALL PANEL SPECIFICATION SPEC NOTE: Optional text is indicated by square brackets []. Delete unwanted items and square brackets in final specification.

More information

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION Section 08520 Aluminum Windows PART 1: WORK INCLUDED A. The conditions of the contract and applicable sections of Division

More information

VITRABOND Aluminum Composite Panel Façade System Specification Template

VITRABOND Aluminum Composite Panel Façade System Specification Template VITRABOND Aluminum Composite Panel Façade System Specification Template SECTION 07 - COMPOSITE METAL WALL PANELS UTILIZING VITRABOND MATERIAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Provide metal composite

More information

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Part 1 General 1. RELATED SECTIONS 1. Section 07 92 10 Joint Sealing 2. Section 08 71 00 Door Hardware 2. REFERENCES 1. American Society

More information

PROJECT LOCATION SECTION TEXTURED METAL PLATE WALL PANELS

PROJECT LOCATION SECTION TEXTURED METAL PLATE WALL PANELS SECTION 07 4213.29 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Textured, aluminum metal plate wall panels. 1.02 RELATED REQUIREMENTS A. Section 05 4000 Cold-Formed Metal Framing: Wall panel substrates support

More information

Steelway Building Systems. Product Specifications Guide

Steelway Building Systems. Product Specifications Guide Steelway Building Systems Product Specifications Table of Contents 1.0 Scope... 2 2.0 Design Standards... 3 3.0 Product Standards... 3 3.1 Plate, Coil and Hot-Rolled... 3 3.2 Bolts and Fasteners... 3 4.0

More information

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. 1.2 PERFORMANCE REQUIREMENTS A. Structural

More information

INSULATED PANEL OVERVIEW

INSULATED PANEL OVERVIEW INSULATED PANEL OVERVIEW Our various series of wall and roof panels are filled with non CFC polyisocyanurate foam. The panels are manufactured in a uniform pressure laminating process that bonds metal

More information

PROJECT LOCATION SECTION ZINC ALLOY METAL PLATE WALL PANELS

PROJECT LOCATION SECTION ZINC ALLOY METAL PLATE WALL PANELS SECTION 07 42 13.26 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Zinc alloy metal plate wall panels. 1.02 RELATED REQUIREMENTS A. Section 05 4000 Cold-Formed Metal Framing: Wall panel substrates support framing.

More information

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,

More information

Metal Roof Panels

Metal Roof Panels University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal

More information

Metl-Span Insulated BattenLok Metal Roof Panels

Metl-Span Insulated BattenLok Metal Roof Panels Metal Roof Panels Insulated BattenLok (IBL) is one of Metl-Span s popular insulated standing seam metal roof panels. The IBL panel is ideal for architectural, commercial, industrial, institutional and

More information

A. Pre-engineered, pre-finished extruded aluminum Pavilions.

A. Pre-engineered, pre-finished extruded aluminum Pavilions. 10 73 00 SECTION Pavilions PART 1 GENERAL 1.1 SECTION INCLUDES A. Pre-engineered, pre-finished extruded aluminum Pavilions. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and Accessories. B. Section

More information

TerraClad TM General Specifications

TerraClad TM General Specifications TerraClad TM General Specifications PRODUCT NAMES: Terra cotta Panels and Related Work MANUFACTURER: Boston Valley Terra Cotta 6860 S. Abbott Road Orchard Park, NY 14127 Phone: 888-214-3655 Phone: 716-649-7490

More information

Metl-Span ThermalSafe Insulated Metal Wall and Ceiling Panels

Metl-Span ThermalSafe Insulated Metal Wall and Ceiling Panels Insulated Metal Wall and Ceiling Panels Metl-Span's ThermalSafe insulated metal wall and ceiling panels (IMP) are developed to protects against fire penetration. Unlike traditional wall materials, this

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove Duo-Gard Industries Inc. 40442 Koppernick Road Canton, Michigan 48187 Phone (734) 207-9700 Fax (734) 207-7995 www.duo-gard.com SECTION 08 45 13 Structured Polycarbonate Panel Assemblies Series 3500 BPC

More information

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1. 07555 - ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART 1.00 - GENERAL 1.01 SUMMARY: A. The work of this section consists of furnishing and installing

More information

SECTION IMPACT RESISTANT WALL PROTECTION

SECTION IMPACT RESISTANT WALL PROTECTION SECTION 10265 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation necessary to provide Impact-Resistant Wall Protection including Wall guards,

More information

SPECIFICATIONS: Architectural Aluminum Railings

SPECIFICATIONS: Architectural Aluminum Railings PART ONE: GENERAL 1.1 SUMMARY SPECIFICATIONS: Architectural Aluminum Railings A. Work in this section includes custom and standard Interior and Exterior aluminum railings and guardrails. 1.2 PERFORMANCE

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Built to Last a Lifetime

Built to Last a Lifetime Built to Last a Lifetime Welcome to Lincoln 2 This brochure will introduce you to Lincoln Steel Buildings from the ground up starting with the framing of the building all the way to the roof and finally

More information

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification

More information

General. 2. Design. 3. Anchor Bolts And Foundations. 4. Drawings. 5. Structural Framing. 6. Roof Covering Nucor Classic Roof Panel

General. 2. Design. 3. Anchor Bolts And Foundations. 4. Drawings. 5. Structural Framing. 6. Roof Covering Nucor Classic Roof Panel The following Nucor Building Systems Specification Guide provides the owner or design professional a detailed description of all standard Nucor Building Systems (NBS) products. This guide is designed to

More information

SECTION 1043 FENCE MATERIAL

SECTION 1043 FENCE MATERIAL SECTION 1043 FENCE MATERIAL 1043.1 Scope. This specification covers the material required in the construction of chainlink fence and woven wire fence. 1043.2 Basis of Acceptance. The basis of acceptance

More information

SECTION ALUMINUM COMPOSITE WALL PANEL SYSTEM

SECTION ALUMINUM COMPOSITE WALL PANEL SYSTEM SECTION ALUMINUM COMPOSITE WALL PANEL SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Includes drawings and provisions of the General Conditions, Supplementary Conditions and the sections included under

More information

PIPE AND TUBE RAILINGS

PIPE AND TUBE RAILINGS SECTION 05521 - PIPE AND TUBE RAILINGS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF WELDED SYSTEM PART 1 GENERAL 1.1 SECTION

More information

SECTION PROFILED METAL WALL PANEL SYSTEM

SECTION PROFILED METAL WALL PANEL SYSTEM MANUFACTURER Firestone Building Products 1001 Lund Boulevard Anoka, MN 55303-1089 Telephone: (800) 426-7737 or (763) 576-9595 FAX: (763) 576-9596 VR Classic Omega Profiled Panel PART 1 GENERAL SECTION

More information

TOPCOAT Restoration Specifications Structural Concrete

TOPCOAT Restoration Specifications Structural Concrete TOPCOAT Restoration Specifications Structural Concrete Updated: 1/11 Quality You Can Trust From North America s Largest Roofing Manufacturer! www.gaf.com TOPCOAT Restoration Specifications Structural Concrete

More information

CURTAINWALL DEFLECTION SOLUTIONS

CURTAINWALL DEFLECTION SOLUTIONS l l l l l CURTAINWALL DEFLECTION SOLUTIONS Provides lateral support for curtain wall systems. One of the highest tested load capacities available. Direct attachment to web and support. Most clips are reversible.

More information

SECTION GUTTERS AND DOWNSPOUTS

SECTION GUTTERS AND DOWNSPOUTS SECTION 07712 GUTTERS AND DOWNSPOUTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gutters and Downspouts. B. Related Accessories. 1.2 RELATED SECTIONS A. Section 07611 - Sheet Metal Roofing. B. Section 07220

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS DIVISION 10 SPECIALTIES SECTION 10 22 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING 7160 Krick Rd., Walton Hills, OH 44146 800-321-3827 - Tel 440-439-8650 - Fax 440-439-6889 SECTION 12 48 16 ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING PART 1. GENERAL 1.01 SUMMARY: This section includes

More information

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT SHEET FLOORING SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.

More information

UFGS (May 2009) UNIFIED FACILITIES GUIDE SPECIFICATION

UFGS (May 2009) UNIFIED FACILITIES GUIDE SPECIFICATION USACE / NAVFAC / AFCEC / NASA UFGS-07 41 63 (November 2016) ----------------------------- Preparing Activity: NASA Superseding UFGS-07 41 63 (May 2009) UNIFIED FACILITIES GUIDE SPECIFICATION References

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information