Diploma in Electrical Installations. (Buildings and Structures) Unit 204 Workbook PRE-ATTENDANCE REVISION V1

Size: px
Start display at page:

Download "Diploma in Electrical Installations. (Buildings and Structures) Unit 204 Workbook PRE-ATTENDANCE REVISION V1"

Transcription

1 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Workbook PRE-ATTENDANCE REVISION V1

2

3 Welcome This booklet is designed to outline the areas that you will study when you complete unit 204 at the centre. Throughout your time in centre you will have a qualified assessor there to help and advise you. We want you to achieve the best possible benefits from your time in centre, therefore before attending we would like you to revise by carrying out the work detailed in this booklet. Studying this workbook will ensure that you are properly prepared before attending centre and therefore help you achieve the best possible results from your time in centre. Please remember that you should not carry out any electrical practical work unless you are in class with one of our qualified assessors. We very much look forward to welcoming you at the centre.

4 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-001: Safe isolation NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that you do not endanger yourself at any time and particularly during the procedure. Procedure 1. Enter the start time on the assessment sheet. 2. Your tutor will identify a circuit or installation that requires safely isolating. 3. Under the supervision of your tutor, safely isolate the identified circuit or installation using the JIB safe isolation procedure. 4. Enter the finish time on the assessment sheet. 1. Identified the circuit or installation to be isolated 2. Selected the correct means of isolation 3. Selected appropriate test equipment 4. Satisfactorily proved selected test equipment 5. Switched off using correct means of isolation 6. Locked and secured the isolation device 7. Posted warning notices 8. Verified that the circuit or installation is dead between L-N, L-E and N-E 9. Satisfactorily reproved test equipment used in Step Confirmed with tutor that it is now safe to start work YES NO Start Date & Time:..... Target Time: 30 minutes Finish Date & Time: Time Taken:...

5 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-005: Identification of tools The following pages contain pictures of tools commonly used in the electrical installation industry. For each picture nominated by the tutor give the correct name and the use(s) of that tool. Specify any safety issues to be considered whilst using that tool.

6 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

7 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

8 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

9 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

10 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

11 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

12 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

13 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

14 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

15 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

16 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

17 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

18 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

19 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

20 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-005

21 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-010: Emergency procedures NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated Technical data You are to make sure that you do not endanger yourself at any time and particularly during the rescue. In order to save a life, you must act quickly (but note the first point). Procedure 1. Enter the start time on the assessment sheet. 2. You discover a colleague unconscious and suspect s/he has been electrocuted. 3. Ensuring your own safety, carry out a rescue of this colleague to ensure that their condition does not worsen. 4. Once safely rescued, carry out checks for vital life signs. 5. Summon assistance. 6. Carry out CPR as necessary. 7. When directed, place the casualty into the recovery position and make comfortable. 8. Enter the finish time on the assessment sheet. 1. Safe isolation of the mock casualty from the supply 2. Quick speed of action within 10 seconds 3. Checked for vital life signs 4. Summoned help 5. Performed CPR correctly on mannequin 6. Quick speed of action within 10 seconds 7. Placed casualty in the recovery position 8. Treated for shock by improvising methods to keep casualty warm 9. Correct safety procedures observed at all times YES NO Start Date & Time:..... Target Time: 10 minutes Finish Date & Time: Time Taken:...

22 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-020: Lifting and handling (alone) NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that you use only the approved lifting techniques. Never attempt to lift an object on your own if you suspect you will struggle and certainly nothing heavier than 20kg. Procedure 1. Enter the start time on the assessment sheet. 2. You are required to safely lift and move an object designated by the assessor. 3. When told to do so by the assessor, this object is firstly to be manually lifted from the floor, transported and placed on to a workbench. 4. Stand back so that the assessor can check that the object has been correctly set down. 5. When told to do so by the assessor, this object is then to be manually lifted from the workbench, transported and placed back on to the floor. 6. Stand back so that the assessor can check that the object has been correctly set down. 7. Enter the finish time on the assessment sheet. 1. Assessed the route to be taken to ensure no obstacles or hazards 2. Assessed the set down for obstacles or hazards 3. Took a firm grip with palms and fingers, using both hands 4. Feet positioned correctly (approx. width of hips, one foot slightly in front) 5. Knees bent to commence lift 6. Back straight, chin in 7. Arms tight into body 8. Carried object safely to bench (ie with face of object close to body) 9. Rested the object carefully and safely on the workbench 10. Took a firm grip and lifted correctly 11. Carried object safely and lowered correctly 12. Knees bent, back straight 13. Rested the object carefully and safely on the floor YES NO Start Date & Time:..... Target Time: 10 minutes Finish Date & Time: Time Taken:...

23 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-030: Lifting and handling (assisted) NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that you use only the approved lifting techniques. Never attempt to lift an object on your own if you suspect you will struggle and certainly nothing heavier than 20kg. Clear instructions must be given to you helper prior to the lift taking place. Procedure 1. Enter the start time on the assessment sheet. 2. You are required, with assistance, to safely lift and move an object designated by the assessor. 3. When told to do so by the assessor, this object is firstly to be manually lifted from the floor, transported and placed on to a workbench. 4. Stand back so that the assessor can check that the object has been correctly set down. 5. When told to do so by the assessor, this object is then to be manually lifted from the workbench, transported and placed back on to the floor. 6. Stand back so that the assessor can check that the object has been correctly set down. 7. Enter the finish time on the assessment sheet. YES NO 1. Assessed the route to be taken to ensure no obstacles or hazards 2. Assessed the set down for obstacles or hazards 3. Gave the helper clear and concise instructions at the start of the test 4. Took a firm grip with palms and fingers, using both hands 5. Feet positioned correctly (approx. width of hips, one foot slightly in front) 6. Knees bent to commence lift 7. Back straight, chin in 8. Arms tight into body 9. Carried object safely to bench (ie close to bodies of helper and candidate) 10. Rested the object carefully and safely on the workbench 11. Took a firm grip and lifted correctly, giving clear instructions to helper 12. Carried object safely and lowered correctly 13. Knees bent, back straight 14. Rested the object carefully and safely on the floor Start Date & Time:..... Target Time: 10 minutes Finish Date & Time: Time Taken:...

24 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-040: Use of ladders NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that you inspect the ladder fully prior to use. Ensure that you or others are not going to be endangered by use of the ladder. You are to make sure that your work area is clear and safe for work to proceed. Hard hats must be worn. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. Procedure 1. Enter the start time on the assessment sheet. 2. You are required to transport an extension ladder for a short distance and erect it in an area designated by the assessor. 3. When told to do so by the assessor, check the ladder for any defects if any defects are found, do not use the ladder but report its condition. 4. Safely transport the ladder to the designated area. 5. Safely erect the ladder (you may ask for physical assistance from another person they must be told exactly what to do). 6. After ensuring that the ladder will not move, ascend and secure the ladder to the landing stage. 7. Descend the ladder. 8. Have the ladder assembly checked before proceeding. 9. Lower the ladder safely. 10. Transport the ladder back to the starting point.

25 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Visually inspected the ladder 2. Lifted and carried the ladder correctly 3. Erected the ladder correctly 4. Slope of ladder set to correct gradient 5. Top of ladder extended the correct distance above the landing stage 6. Safe position of ladder rung adjacent to the transom 7. Secured ladder correctly before ascending 8. Ascended and descended in a safe manner 9. Secured top of ladder safely 10. Lowered ladder correctly 11. Returned ladder safely to start position 12. Wore hat at all times 13. Ensured the safety of others in the vicinity 14. Work area conformed to requirements of HASAWA 15. Correct safety procedures observed at all times. YES NO Start Date & Time:..... Target Time: 20 minutes Finish Date & Time: Time Taken:...

26 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-050: Use of towers NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that you inspect the tower fully prior to use. Ensure that you or others are not going to be endangered by use of the tower. You are to make sure that your work area is clear and safe for work to proceed. Hard hats must be worn. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. Procedure 1. Enter the start time on the assessment sheet. 2. You and a colleague are required to erect a tower in an area designated by the assessor. 3. When told to do so by the assessor, check the tower for any defects if any defects are found, do not use the tower but report its condition. 4. Safely erect the tower in the designated area (one of you will be in charge for the construction of the tower). 5. Descend the tower. 6. Have the tower assembly checked before proceeding. 7. Dismantle the tower ladder safely (the other person will be in charge for the dismantling of the tower). 8. Place the sections in the storage area designated by the assessor. 1. Visually inspected the tower components 2. Selected appropriate components 3. Positioned and prepared the tower correctly 4. All necessary braces, rails and boards correctly fitted 5. Ascended the tower in a safe manner 6. Descended the tower in a safe manner 7. Dismantled tower correctly 8. Wore hat at all time 9. Ensured the safety of others in the vicinity 10. Work area conformed to requirements of HASAWA 11. Correct safety procedures observed at all times YES NO Start Date & Time:..... Target Time: 45 minutes Finish Date & Time: Time Taken:...

27 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-060: Termination of cables NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. It is essential that the CSA of each conductor be maintained throughout its length. Conductor ends are usually doubled to ensure that the terminal hole is filled. Material required 1 off Single core PVC insulated cable (7 strand) 4mm 2 x 150mm 1 off Twin and cpc PVC insulated and sheathed cable 2.5mm 2 x 300mm 1 off Twin and cpc PVC insulated and sheathed cable 1.5mm 2 x 300mm 1 off Single core PVC insulated and sheathed cable 1.5mm 2 x 300mm 1 off cpc sleeving 2mm x 300mm Procedure a) Sheathed cables 1. Enter the start time on the assessment sheet. 2. Prepare the material requisition for the required materials. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. The procedures 6 to 12 apply to each of the 3 sheathed cables. 6. Ensure that the cable is cut to correct length. 7. Remove 100mm of sheathing from one end of the cable. 8. Fit cpc sleeving where applicable. 9. Remove sufficient insulation from the end of each cable core in order to expose the conductor and retain the length of insulation, as shown on the diagram. 10. Cut the exposed conductors to the required length. 11. Bend the end of each exposed conductor over to the required length in order to double its thickness. 12. Check that all the dimensions are correct. 13. Hand the work to the Lecturer for marking and assessment. b) Stranded cables 14. Ensure that the cable is cut to correct length. 15. Remove 30mm of insulation from one end of the cable to expose the conductors. 16. Twist the exposed conductor strands together and bend them over to required length in order to double its thickness. 17. Check that all dimensions are correct. 18. Hand the work to the Lecturer for marking and assessment. 19. Enter the finish time on the assessment sheet.

28 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-060

29 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed NO Cable 1 2.5mm 2 twin and cpc PVC insulated and sheathed cable 3. Sheath cut back correctly and to correct length 4. Insulation undamaged and to correct length 5. Conductor cores undamaged 6. cpc correctly sheathed and to correct length 7. Conductor cores bent over and to correct length 8. Overall appearance to a commercially acceptable standard Cable 2 1.5mm 2 twin and cpc PVC insulated and sheathed cable 9. Sheath cut back correctly and to correct length 10. Insulation undamaged and to correct length 11. Conductor cores undamaged 12. cpc correctly sheathed and to correct length 13. Conductor cores bent over and to correct length 14. Overall appearance to a commercially acceptable standard Cable 3 1.5mm 2 single core PVC insulated and sheathed cable 15. Sheath cut back correctly and to correct length 16. Insulation undamaged and to correct length 17. Conductor cores undamaged 18. Conductor cores bent over and to correct length 19. Overall appearance to a commercially acceptable standard.

30 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Cable 4 4mm 2 single core (stranded) PVC insulated cable 20. Insulation undamaged and to correct length 21. Conductor cores undamaged 22. Strands twisted in the direction of lay 23. Conductor cores bent over and to correct length 24. Overall appearance to a commercially acceptable standard All cables 25. Work area conformed to requirements of HASAWA 26. Correct safety procedures observed at all times Start Date & Time:..... Target Time: 60 minutes Finish Date & Time: Time Taken:...

31 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-070: Vice jaw protectors NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. Material required 1 off Aluminium Strip 160 x 110 x 1.5mm Procedure 1. Enter the start time on the assessment sheet. 2. Complete the material requisition. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Apply marking blue to one face of the aluminium strip and allow to dry. 6. Mark and cut the material into two equal widths. 7. Identify both pieces of your work with your initials using letter stamps. 8. Have your work checked before proceeding. 9. Mark and file the end of one piece square to one side. 10. Cut and file the other end square to the side and to the correct length. 11. Mark out the complete shape as shown. 12. Repeat items 9 to 11 above on second piece. 13. Have your work checked before proceeding. 14. Centre punch the position of the 3.3mm holes. 15. Drill holes BY HAND. 16. Saw cut and file both pieces to shape. 17. Have your work checked before proceeding. 18. Position one piece in the 102mm vice and bend to shape with a soft-faced hammer. 19. Repeat Step 18 with the second piece. 20. Hand the work to the Lecturer for marking and assessment. 21. Enter the finish time on the assessment sheet.

32 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-070

33 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Both strips of equal length 4. Both strips of equal width 5. Both strips ends square to sides 6. Both strips length marked out correctly 7. Both strips width marked out correctly 8. Both strips cut outs marked out correctly 9. Fold lines on both pieces in correct position 10. Fold lines marking caused no damage to material 11. Holes and cut-outs for both strips correct size 12. Both protectors fit correctly on 102mm vice 13. All burrs and sharp edges removed 14. Work identified correctly on final presentation 15. Work area conformed to requirements of HASAWA 16. Correct safety procedures observed at all times 17. Overall appearance to a commercially acceptable standard NO Start Date & Time:..... Target Time: 240 minutes Finish Date & Time: Time Taken:...

34 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-080: Termination of plug top NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off 3-core PVC insulated and sheathed flexible cable 0.75mm 2 x 150mm 1 off Fused plug, 13A, 3 pin Procedure 1. Enter the start time on the assessment sheet. 2. Prepare the material requisition for the required materials. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Unscrew pin and remove plug-top to expose the terminals and the cord grip. 6. Strip the sheathing from the 3-core flexible cable to expose the length of inner cores required to complete the termination. 7. Insert cord into the cable grip and secure. 8. Strip core insulation to expose sufficient conductor for termination. 9. Twist the strands for each core and bend the end of each exposed conductor over in order to double its thickness and secure to the correct terminals. 10. Hand the work to the Lecturer for marking and assessment. 11. Enter the finish time on the assessment sheet. NB: Conductors must fill and be contained within their terminals. Strands of conductors must NOT be visible outside of the terminal.

35 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-080

36 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Securely assembled 4. No unsheathed conductors visible 5. Cord grip used and cord secure 6. No stray conductor strands visible 7. Core insulation to within 2mm of the terminals 8. Terminals tight 9. Conductors secure, doubled and undamaged 10. Conductors installed into the correct terminals 11. Overall appearance to a commercially acceptable standard 12. Work area conformed to requirements of HASAWA 13. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 45 minutes Finish Date & Time: Time Taken:...

37 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-090: Termination of ceiling rose NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off Twin heat resistant flexible cord 0.5mm 2 x 300mm 1 off 3-plate ceiling rose 1 off Pendant bayonet cap (BC) lamp holder Procedure 1. Enter the start time on the assessment sheet. 2. Prepare the material requisition for the required materials. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Unscrew the top from the lamp holder body to expose terminals. 6. Strip back an appropriate amount of sheathing from one end of the heat resistant flexible cord. 7. Remove the insulation to expose a length of conductor approximately equal to twice the length of the terminal connection. 8. Twist the strands for each core and bend the end of each exposed conductor over in order to double its thickness. 9. Connect one core into each of the lamp holder terminals. 10. Ensure that the flexible cord is secured by the cord grip and screw on the lamp holder top. 11. Remove sheathing and insulation from the other end of the flexible cord (procedures 6 to 8) so that on completion the exposed sheathing on the flexible cord measures 150mm. NB: The amount of exposed core insulation needs to be longer than for the lamp holder. 12. Remove the cover from the ceiling rose base and thread onto the flexible cord. 13. Connect one core into each of the correct ceiling rose terminals. 14. Ensure that the flexible cord is secured by the cord grip and fix ceiling rose cover to base. 15. Hand the work to the Lecturer for marking and assessment. 16. Enter the finish time on the assessment sheet. NB: Conductors must fill and be contained within their terminals. Strands of conductors must NOT be visible outside of the terminal.

38 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-090

39 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Lamp holder and ceiling rose covers tight Lamp holder 4. No unsheathed conductors visible 5. Cord grip used and cord secure 6. No stray conductor strands visible 7. Core insulation to within 2mm of the terminals 8. Terminals tight 9. Conductors secure, doubled and undamaged 10. Overall appearance to a commercially acceptable standard Ceiling rose 11. No unsheathed conductors visible 12. Cord grip used and cord secure 13. No stray conductor strands visible 14. Core insulation to within 2mm of the terminals 15. Terminals tight 16. Conductors secure, doubled and undamaged 17. Conductors installed into the correct terminals 18. Overall appearance to a commercially acceptable standard General 19. Work area conformed to requirements of HASAWA 20. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 45 minutes Finish Date & Time: Time Taken:...

40 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-100: Metal fixing methods NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. Material required 1 off Metal cable trunking lid 500 x 50mm 4 off Pop rivets 3.2 dia x 10mm 4 off Steel pan head set pins M6 x 12mm 4 off Steel hexagon full nuts M6 Procedure 1. Enter the start time on the assessment sheet. 2. Complete the material requisition. 3. Have the requisition checked before proceeding. 4. Mark, cut and file one end of the material square to one side. 5. From this end mark and cut Section C and two identical pieces A and B to dimensions shown on the diagram. 6. Identify all the three pieces of your work with your initials using letter stamps. 7. Have your work checked before proceeding. 8. Mark the positions of the fixing holes and cut-outs on A and B and position of the 20/25mm holes on Section C. 9. Have your work checked before proceeding. 10. Drill the 4 x 3.2mm holes in Section A and form cut-outs. 11. Drill the 4 x 6.0mm clearance holes (6.3mm) in Section B and form cut-outs. 12. Drill 2 x 20mm and 2 x 25mm holes in the positions shown on the diagram. 13. Have your work checked before proceeding. 14. Using Sections A and B as templates, mark and drill appropriate-sized fixing holes in Section C to fix A and B to C. 15. Fix A and B to C at positions shown. 16. Remove all burrs and sharp edges. 17. Hand the work to the Lecturer for marking and assessment. 18. Enter the finish time on the assessment sheet.

41 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-100

42 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Section A length correct 4. Section B length correct 5. Section C length correct 6. All three sections identified correctly 7. Section A fixing holes positions marked correctly 8. Section A cut-outs dimensions marked correctly 9. Section B fixing holes positions marked correctly 10. Section B cut-outs dimensions marked correctly 11. Section C 20mm holes positions marked correctly 12. Section C 25mm holes positions marked correctly 13. Section A 3.2mm holes correct size and position 14. Section A cut-outs removed correctly 15. Section B 6.3mm holes correct size and position 16. Section B cut-outs removed correctly 17. Section C 20mm holes correct size and position 18. Section C 25mm holes correct size and position NO

43 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Section A and C positions of fixings correct 20. Section A and C fixings secure 21. Section B and C positions of fixings correct 22. Section B and C fixings secure 23. All burrs and sharp edges removed 24. Work identified correctly on final presentation 25. Work area conformed to requirements of HASAWA 26. Correct safety procedures observed at all times 27. Overall appearance to a commercially acceptable standard Start Date & Time:..... Target Time: 420 minutes Finish Date & Time: Time Taken:...

44 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-110: Tray bending bars NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All scribed lines, centre dot and other marks must be removed from the finished surfaces. Material required 2 off Mild steel bar 180 x 20 x 10mm 1 off Steel pan head set pins M6 x 25mm Procedure The procedure below (Steps 5 to 13) applies to both pieces of mild steel bar, which should be completed simultaneously. 1. Enter the start time on the assessment sheet. 2. Prepare the material requisition for the required materials. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Letter stamp your initials on to material for identification. 6. Clean the surface of bar to ensure that it is grease-free in preparation for marking out. 7. Coat two adjacent longitudinal surfaces thinly with marking blue and allow to dry. 8. Mark out, as detailed on the drawing. 9. Have your work checked before proceeding. 10. Centre punch the hole centres and drill pilot holes. 11. Have your work checked before proceeding. 12. Cut the slot in the end of the bar with care to ensure correct width. 13. Open the pilot hole to the correct size (as shown on the diagram). 14. Using the tap set in the correct order, cut an internal thread in ONE of the bars. 15. Using a 6.3mm twist drill, open out the hole in the other bar. 16. Using the M6 pin, join the two bars together. 17. Form the shaped end on the joined bars, as detailed on the drawing, and check that the bars are the correct length. 18. Hand the work to the Lecturer for marking and assessment. 19. Enter the finish time on the assessment sheet.

45 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-110

46 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2 Method statement completed 3. Material correctly identified on first visit 4. Both bars marked out correctly 5. Pilot holes drilled in correct locations 6. Slots cut in correct locations 7. Slots cut to correct dimensions 8. Tapped hole correct size 9. Tapped hole square to the face 10. Clearance hole correct size 11. Clearance hole square to the face 12. Formed ends correctly shaped 13. Overall dimensions correct 14. Work area conformed to requirements of HASAWA 15. Correct safety procedures observed at all times 16. Overall appearance to a commercially acceptable standard NO Start Date & Time:..... Target Time: 210 minutes Finish Date & Time: Time Taken:...

47 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-120: Cable tray support bracket NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All scribed lines, centre dot and other marks must be removed from the finished surfaces. Material required 1 off Mild steel bar 600 x 15 x 3mm Procedure The procedure below (Steps 5 to 13) applies to both pieces of mild steel bar, after cutting in step 6, which should be completed simultaneously 1. Enter the start time on the assessment sheet. 2. Prepare the material requisition for the required materials. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Clean the surface of the bar to ensure that it is grease-free in preparation for marking out. 6. Mark and cut the strip in half. NB The procedures below (Steps 7 to 14) apply to both pieces of material. 7. Letter stamp your initials on to the material for identification. 8. Mark out, as detailed on the drawing. 9. Have your work checked before proceeding. 10. Centre punch the hole centres and drill pilot holes. 11. Have your work checked before proceeding. 12. Bend the material to the dimensions shown in the diagram, taking care to keep them symmetrical. 13. Open the holes up to the sizes shown on the diagram and adjust as necessary the two tray fixing holes by slotting to fit the tray holes. 14. Remove all burrs, sharp edges and vice marks. 15. Hand the work to the Lecturer for marking and assessment. 16. Enter the finish time on the assessment sheet.

48 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-120

49 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Material correctly identified on first visit 4. Both bars marked out correctly 5. Pilot holes drilled in correct locations 6. Bends made to correct dimensions 7. Bends formed true with no twist 8. 5mm hole correct size 9. 5mm hole correct square to the face mm hole correct size mm hole correct square to the face 12. All scribed lines, centre dot and other marks removed 13. Overall dimensions correct 14. Work area conformed to requirements of HASAWA 15. Correct safety procedures observed at all times 16. Overall appearance to a commercially acceptable standard NO Start Date & Time:..... Target Time: 90 minutes Finish Date & Time: Time Taken:...

50 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 1-130: Thread gauge NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. Material required 1 off Mild steel strip 145 x 50 x 3mm Procedure 1. Enter the start time on the assessment sheet. 2. Complete the material requisition. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Clean face of metal in preparation for marking out. 6. Apply marking blue to one face and allow to dry. 7. Square off one end using a square and scriber. 8. Cut and file this end square to be used as the datum. 9. Identify the work with your initials using letter stamps. 10. Have your work checked before proceeding. 11. From the datum end, measure and mark out the position of the two angles of 135 and Mark out the six holes and angled slot, as shown on the diagram. 13. Have your work checked before proceeding. 14. Drill the eight holes at the position indicated to the correct size (if in doubt ask do not guess!). 15. Have your work checked before proceeding. 16. Tap the two holes to the correct size in the positions shown. 17. Cut out the angled slot between the 8mm holes. 18. Cut and file the angled section. 19. Ensure all burrs and sharp edges have been removed. 20. Clean work to give a bright finish. 21. Hand the work to the Lecturer for marking and assessment. 22. Enter the finish time on the assessment sheet.

51 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 1-130

52 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Datum end square mm and 110mm measurements marked out correctly angle marked out correctly angle marked out correctly 7. Position of the six holes marked correctly 8. Position and angle of the angled slot marked correctly 9. Six holes correct size 10. 8mm angled slot correct size 11. Tapped holes correct position, size and square to face 12. Angled slot correct angle and parallel to angled edge angled edge formed correctly angled edge formed correctly 15. All burrs and sharp edges removed 16. Work identified correctly on final presentation 17. Work area conformed to requirements of HASAWA 18. Correct safety procedures observed at all times 19. Overall appearance to a commercially acceptable standard NO Start Date & Time:..... Target Time: 6 hours Finish Date & Time: Time Taken:...

53 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-010: One-way lighting circuit NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off 45 amp 1-way consumer unit 1 off 5A rewireable fuse carrier and base 1 off Surface mounted moulded switch box 1-gang 1 off Plate switch 1-gang, 1-way, single pole, 5A 2 off 3.5 x 20mm raised countersunk set pins 1 off Batten lampholder with integral back plate, 5A, 3-plate 2.1 m 1.5mm 2 twin and cpc PVC insulated and sheathed cable 300mm 50mm 2mm green/yellow cpc sleeving 2mm brown sleeving Clips, screws and pins, as detailed in the exercise demonstration Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet. NB: Care must be taken to colour code all live conductors, ie on the switch drops of one-way lighting circuits both the line feed to the switch and the switch wire should be brown (twin brown cable + cpc is available).

54 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-010

55 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: Range Setting: CCU-Lampholder Reading: CCU-Switch Reading: Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Protective Device Polarity: Switch Polarity:

56 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Cable sheath taken into all accessories 12. Clip position/spacings acceptable 13. Bends formed correctly (minimum radii and uniform) 14. Circuit functions correctly 15. Consumer unit correct size protective device 16. Consumer unit correctly connected 17. cpc sheathed correctly 18. Conductors correctly coded at terminations 19. Suitable amount of spare cable left in accessories 20. Conductor insulation undamaged at terminations 21. Conductors doubled as appropriate and secure 22. Sheath/insulation stripped to correct position 23. Conductors undamaged at terminations 24. Overall appearance to a commercially acceptable standard 25. Work area conformed to requirements of HASAWA 26. Correct safety procedures observed at all times Start Date & Time:..... Target Time: 4 hours NO Finish Date & Time: Time Taken:...

57 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-020: One-way to two-way lighting circuit conversion NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off Materials from Worksheet off Surface mounted moulded switch box 1-gang 2 off Plate switch 1-gang, 2-way, single pole, 5A 2 off 3.5 x 20mm raised countersunk set pins 0.5 m 1.5mm 2 three core and cpc PVC insulated and sheathed cable 300mm 50mm 2mm green/yellow cpc sleeving 2mm brown sleeving Clips, screws and pins, as detailed in the exercise demonstration. Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet. NB: On the two-way conversion circuit it is usual practice to use the black core for the common with the brown and grey cores connected to L1 and L2, respectively. The black and grey cores should have brown sleeving applied.

58 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-020

59 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: Range Setting: CCU-Lampholder Reading: CCU-Switch Reading: Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Protective Device Polarity: Switch Polarity:

60 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Cable sheath taken into all accessories 12. Clip position/spacings acceptable 13. Bends formed correctly (minimum radii and uniform) 14. Circuit functions correctly 15. cpc sheathed correctly 16. Conductors correctly coded at terminations 17. Suitable amount of spare cable left in accessories 18. Conductor insulation undamaged at terminations 19. Conductors doubled as appropriate and secure 20. Sheath/insulation stripped to correct position 21. Conductors undamaged at terminations 22. Overall appearance to a commercially acceptable standard 23. Work area conformed to requirements of HASAWA 24. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 2 hours Finish Date & Time: Time Taken:...

61 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-030: Intermediate lighting circuit NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off Materials from worksheets and off Surface mounted moulded switch box 1-gang 2 off Plate switch 1-gang, 2-way, single pole, 5A 1 off Plate switch 1-gang, Intermediate, single pole, 5A 6 off 3.5 x 20mm raised countersunk set pins 1 off Batten lampholder with integral back plate, 5A, 3-plate 0.9 m 1.5mm 2 twin and cpc PVC insulated and sheathed cable 1.0 m 1.5mm 2 3 core and cpc PVC insulated and sheathed cable 300mm 50mm 2mm green/yellow cpc sleeving 2mm brown sleeving Clips, screws and pins, as detailed in the exercise demonstration Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet. NB: Care must be taken to colour code all live conductors, ie on the switch drops of one-way lighting circuits both the line feed to the switch and the switch wire should be brown (twin brown cable + cpc is available).

62 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-030

63 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: Range Setting: CCU-Lampholder Reading: CCU-Switch Reading: Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Protective Device Polarity: Switch Polarity:

64 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Cable sheath taken into all accessories 12. Clip position/spacings acceptable 13. Bends formed correctly (minimum radii and uniform) 14. Circuit functions correctly 15. cpc sheathed correctly 16. Conductors correctly coded at terminations 17. Suitable amount of spare cable left in accessories 18. Conductor insulation undamaged at terminations 19. Conductors doubled as appropriate and secure 20. Sheath/insulation stripped to correct position 21. Conductors undamaged at terminations 22. Overall appearance to a commercially acceptable standard 23. Work area conformed to requirements of HASAWA 24. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 4 hours Finish Date & Time: Time Taken:...

65 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-040: Radial final power circuit NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required 1 off 45 amp 1-way consumer unit 1 off 20A rewireable fuse carrier and base 2 off Surface mounted moulded socket box 1-gang 2 off Insulated switched flush socket outlet 1-gang, 13A 4 off 3.5 x 20mm raised countersunk set pins 2.5mm 2 twin and cpc PVC insulated and sheathed cable 300mm 2mm green/yellow cpc sleeving Clips, screws and pins, as detailed in the exercise demonstration Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet.

66 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-040

67 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: Range Setting: CCU-Socket 1 Reading: CCU-Socket 2 Reading: Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Socket 1 Polarity: Socket 2 Polarity:

68 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Cable sheath taken into all accessories 12. Clip position/spacings acceptable 13. Bends formed correctly (minimum radii and uniform) 14. Circuit functions correctly 15. Consumer unit correctly connected 16. Consumer unit correct size protective device 17. cpc sheathed correctly 18. Conductors connected to correct terminations 19. Suitable amount of spare cable left in accessories 20. Conductor insulation undamaged at terminations 21. Conductors doubled as appropriate and secure 22. Sheath/insulation stripped to correct position 23. Conductors undamaged at terminations 24. Overall appearance to a commercially acceptable standard 25. Work area conformed to requirements of HASAWA 26. Correct safety procedures observed at all times Start Date & Time:..... Target Time: 2.5 hours NO Finish Date & Time: Time Taken:...

69 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-050: Ring final power circuit NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required The following are the items of material required IN ADDITION to those used in the previous worksheet (Worksheet 2-040). 1 off 30A rewireable fuse carrier and base 2 off Surface mounted moulded socket box 2-gang 2 off Insulated switched flush socket outlet 2-gang, 13A 4 off 3.5 x 20mm raised countersunk set pins 2.5mm 2 twin and cpc PVC insulated and sheathed cable 300mm 2mm green/yellow cpc sleeving Clips, screws and pins, as detailed in the exercise demonstration Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet.

70 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-050

71 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: Range Setting: CCU-Socket 1 Reading: CCU-Socket 2 Reading: CCU-Socket 3 Reading: CCU-Socket 4 Reading: Continuity of Ring Final Circuit Test Instrument Used: Instrument Serial No.: Range Setting: Line-Line Loop Reading (r 1): Neutral-Neutral Loop Reading (r n): CPC-CPC Loop Reading (r 2): Line-Neutral Skt 1 Reading: Line-Neutral Skt 2 Reading: Line-Neutral Skt 3 Reading: Line-Neutral Skt 4 Reading: Line-CPC Skt 1 Reading: Line-CPC Skt 2 Reading: Line-CPC Skt 3 Reading: Line-CPC Skt 4 Reading: Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Socket 1 Polarity: Socket 2 Polarity: Socket 3 Polarity: Socket 4 Polarity:

72 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Cable sheath taken into all accessories 12. Clip position/spacings acceptable 13. Bends formed correctly (minimum radii and uniform) 14. Circuit functions correctly 15. Consumer unit correctly connected 16. Consumer unit correct size protective device 17. cpc sheathed correctly 18. Conductors connected to correct terminations 19. Suitable amount of spare cable left in accessories 20. Conductor insulation undamaged at terminations 21. Conductors doubled as appropriate and secure 22. Sheath/insulation stripped to correct position 23. Conductors undamaged at terminations 24. Overall appearance to a commercially acceptable standard 25. Work area conformed to requirements of HASAWA 26. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 3 hours Finish Date & Time: Time Taken:...

73 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-060: Fused and non-fused spurs power circuit NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that your work area is clear and safe for work to proceed. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. All practical electrical installation exercises must comply with BS7671 (IET Wiring Regulations). All terminations must be mechanically and electrically sound. Material required The following are the items of material required IN ADDITION to those used in the previous worksheet (Worksheet 2-050). 3 off Surface mounted moulded socket box 1-gang 1 off Insulated switched flush socket outlet 1-gang, 13A 1 off Insulated switched flush fused connection unit (C/W 3A fuse) 1 off FAN connection unit 2 off Surface mounted moulded socket box 2-gang 2 off Insulated switched flush socket outlet 2-gang, 13A 1 off 30 amp, 3-terminal insulated junction box 10 off 3.5 x 20mm raised countersunk set pins 2.5mm 2 twin and cpc PVC insulated and sheathed cable 1.5mm 2 twin and cpc PVC insulated and sheathed cable 300mm 2mm green/yellow cpc sleeving Clips, screws and pins, as detailed in the exercise demonstration Procedure 1. Enter the start time on the assessment sheet. 2. Study the diagram and from it draw a wiring diagram. 3. This diagram must be handed in for assessment before proceeding. 4. Prepare the material requisition for the required materials. 5. Have the requisition checked before proceeding. 6. Obtain the material from the stores. 7. Carry out the installation. 8. Carry out the necessary tests on the installation and record all readings obtained on the assessment sheet. 9. Notify the Lecturer that the work is ready for assessment. 10. Enter the finish time on the assessment sheet.

74 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-060

75 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Test results cpc Continuity Test Instrument Used: Instrument Serial No.: CCU-Socket 1 Reading: Range Setting: CCU-Socket 2 Reading: CCU-Socket 3 Reading: CCU-Socket 4 Reading: CCU-Socket 5 Reading: CCU-Socket 6 Reading: CCU-Connection unit (FCU) Reading: CCU-Fan terminal Reading: Continuity of Ring Final Circuit Test Instrument Used: Instrument Serial No.: Range Setting: Line-Line Loop Reading (r 1): Neutral-Neutral Loop Reading (r n): CPC-CPC Loop Reading (r 2): Line-Neutral Skt 1 Reading: Line-Neutral Skt 2 Reading: Line-Neutral Skt 3 Reading: Line-Neutral Skt 4 Reading: Line-Neutral Skt 5 Reading: Line-Neutral Skt 6 Reading: Line-Neutral Skt 7 Reading: Line-Neutral FCU Reading: Line-CPC Skt 1 Reading: Line-CPC Skt 2 Reading: Line-CPC Skt 3 Reading: Line-CPC Skt 4 Reading: Line-CPC Skt 5 Reading: Line-CPC Skt 6 Reading: Line-CPC Skt 7 Reading: Line-CPC FCU Reading::

76 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Insulation Resistance Test Instrument Used: Instrument Serial No.: Range Setting: Line-Neutral Reading: Line/Neutral-Earth Reading: Polarity Test Instrument Used: Socket 1 Polarity: Socket 2 Polarity: Socket 3 Polarity: Socket 4 Polarity: Socket 5 Polarity: Socket 6 Polarity: Socket 7 Polarity: FCU Polarity: Fan terminal Polarity:

77 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Wiring diagram function correct 2. Wiring diagram drawn neatly 3. Wiring diagram drawn using correct symbols 4. Wiring diagram labelled correctly 5. Material requisition correct first time 6. Method statement completed 7. Inspection and testing completed correctly 8. Test results correctly recorded 9. Accessories fixed in correct positions 10. Accessory covers all fixed securely 11. Correct sized cable used 12. Cable sheath taken into all accessories 13. Clip position/spacings acceptable 14. Bends formed correctly (minimum radii and uniform) 15. Circuit functions correctly 16. Consumer unit correctly connected 17. Consumer unit correct size protective device 18. cpc sheathed correctly 19. Conductors connected to correct terminations 20. Suitable amount of spare cable left in accessories 21. Conductor insulation undamaged at terminations 22. Conductors doubled as appropriate and secure 23. Sheath/insulation stripped to correct position 24. Conductors undamaged at terminations 25. Overall appearance to a commercially acceptable standard 26. Work area conformed to requirements of HASAWA 27. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 4 hours Finish Date & Time: Time Taken:...

78 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-070: Tongue and groove floorboard NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. In order to prevent the floorboards splitting, nail points should be tapped with a hammer to form a blunt end. Material required 4 off Countersunk steel woodscrews 1¼ x 8 OR 8 off 40mm oval lost head nails (see note at foot of exercise) Procedure Lifting the floorboard 1. Enter the start time on the assessment sheet. 2. From the drawing and site inspection prepare a material requisition. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Place a chalk mark on the floorboard to indicate which section the Lecturer has indicated should be lifted (see diagram 1). 6. Saw through the tongues on both sides of this floorboard section, ensuring that the tongues on both sides are completely removed for a distance of one joist width in both directions beyond the required marked section. 7. The nails found in both ends of the section should then be driven through the floorboard using a nail punch. 8. Carefully prise up the floorboard until it is possible to place a length of rod under the partly raised section (diagrams 2 and 3). 9. Slide the rod along to support the board near the end of the section. 10. Saw through the floorboard squarely along the centre line of the supporting joist (see diagram 4). 11. Reposition the rod in order to again support the section at the other end and again saw through the floorboard squarely along the centre line of the joist. 12. The required section can now be removed (see diagram 6). 13. Remove the nails from both joists. 14. Have this work checked by the Lecturer before proceeding. Floorboard replacement 15. Ensure that the section is replaced in its original position. 16. Carefully fix down this section and adjoining floorboard using the correct fixings (see diagram 5 and the note at the foot of this sheet). 17. Notify the Lecturer that the work is ready for assessment. 18. Enter the finish time on the assessment sheet. NOTE: Care must be taken when the floorboard is prised up to ensure that it does not crack or split. When there is no requirement for service access to a void, the floorboard may be nailed down; otherwise, it must be screwed.

79 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-070

80 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Assessments are based on observed safety procedures, and the quality and accuracy of the completed exercise. YES 1. Material requisition correct first time 2. Method statement completed 3. Correct section lifted 4. Tongues correctly sawn (both sides) 5. Flooring each side undamaged 6. Flooring cut square 7. Joists undamaged 8. Flooring replaced in correct position 9. Flooring replaced securely 10. Fixings in correct position 11. Overall appearance to a commercially acceptable standard 12. Work area conformed to requirements of HASAWA 13. Correct safety procedures observed at all times NO Start Date & Time:..... Target Time: 2 hours Finish Date & Time: Time Taken:...

81 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet : Installation of wiring systems and enclosures Worksheet 2-080: Chipboard floor trap NB: Students must not attempt this exercise before the correct use of all tools and materials has been demonstrated. Technical data In order to correctly carry out this exercise, specialist tools are required. Standard joists are 600mm between centres but this must be checked in every case. A suitable piece of timber with a straight edge is often used in conjunction with the jigsaw in order to ensure that the cut edge is straight. You are to make sure that all your work conforms to the requirements of the Health and Safety at Work Act. In order to prevent the floorboards splitting, nail points should be tapped with a hammer to form a blunt end. Material required 8 off Countersunk steel woodscrews 75mm x no.10 4 off Countersunk steel woodscrews 42mm x no m 50mm x 50mm sawn timber Procedure 1. Enter the start time on the assessment sheet. 2. From the drawing and site inspection prepare a material requisition. 3. Have the requisition checked before proceeding. 4. Obtain the material from the stores. 5. Place a chalk mark on the chipboard floor to indicate which section the Lecturer has indicated to be lifted (see diagram 1). 6. Establish the centre, width and thickness of the supporting joists by sliding a knife in the joint of the floorboards to establish the exact position of the joists. 7. Accurately mark out the required position for the inspection trap. 8. Mark the orientation of the trap to ensure correct relocation later. 9. Have this work checked by the Lecturer before proceeding. 10. Carefully drill an 8mm diameter pilot hole in one corner of the inspection trap (see diagram 2). 11. Drill a second 8mm pilot hole in the other corner as indicated on the diagram (see diagram 2). 12. Using the jigsaw, cut out the trap by sawing along each line in turn, starting from the pilot hole each time. This cut-out section MUST be retained to form the trap lid. 13. Have this work checked by the Lecturer before proceeding.

82 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet Construction of the trap support frame 14. Cut two off 350mm lengths of timber which are to form the support members of the frame which is secured to the inside of opposing floor joists. 15. Place the timbers together against the inside of one of the joists and measure the distance between the inside timber and the other floor joist. 16. Cut two pieces of timber to this measured length, making sure that the ends are square. 17. Screw the frame together as shown in the diagram (see diagrams 3, 4 and 5), ensuring that the edges are level drill pilot holes in the outer support members. 18. Drill two 4mm holes in both of the support members to facilitate the screw fixings to the joists to be made. 19. Fix the trap support frame in position. 20. Have this work checked by the Lecturer before proceeding. 21. Drill four 4mm diameter holes in the trap lid as shown in the diagram (see diagram 6). 22. Fix the trap lid in position. 23. Notify the Lecturer that the work is ready for assessment. 24. Enter the finish time on the assessment sheet. NOTE: Extreme care must be taken when using the electric jigsaw.

83 Level 2 Diploma in Electrical Installations (Buildings and Structures) Unit 204 Worksheet 2-080

BoSS Climalite Camera and lighting tower

BoSS Climalite Camera and lighting tower Contents Safety First Safety First Quantity Schedules Toeboard 2 9 13 33 INTRODUCTION Please read this guide carefully. Please note that diagrams are for illustrative purposes only. User guides are also

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

CHAPTER 5 METERING REQUIREMENTS

CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS 5.1 General 1. All installations connected to, or intended to be connected to HK Electric s supply of electricity must comply with HK Electric

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

SEMPEO SQA Unit Code H Assembling mechanical components

SEMPEO SQA Unit Code H Assembling mechanical components Overview This standard covers a range of basic mechanical assembly competences that will prepare you for entry into the engineering or manufacturing sector, creating a progression between education and

More information

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd

Revision 1 RAM ELEVATORS. Elevator Electrical Planning Guide. RAM Manufacturing Ltd RAM ELEVATORS Elevator Electrical Planning Guide This guide is intended for people with an understanding of electricity. If you are not, please consult a licensed electrician as errors in application of

More information

Safety on Heights: Our Policy

Safety on Heights: Our Policy 11/17/14 Safety on Heights: Our Policy Only volunteers over the age of 18 are allowed to work on heights of more than six feet off the ground. This includes all work on scaffolds. Only volunteers who are

More information

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. RM140A-R3 RM140A-M-R3 RM145A-R3 RM145A-M-R3 Small Office/Home Office (SOHO) Cabinets Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. Fit under most desktops in the

More information

Model # 158-P4. 12/12/2013 Page 1 of 11

Model # 158-P4. 12/12/2013 Page 1 of 11 Model # 158-P4 12/12/2013 Page 1 of 11 2/12/2013 Page 2 of 11 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Model # 238HS-P8. 4/27/2011 Page 1 of 11

Model # 238HS-P8. 4/27/2011 Page 1 of 11 Model # 238HS-P8 4/27/2011 Page 1 of 11 4/27/2011 Page 2 of 11 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Installation instruction

Installation instruction Installation instruction Ci51 www.contura.eu 114 CERTIFICATE Declaration of performance according to Regulation (EU) 305/2011 No. Ci51-CPR-150821-SE-2 PRODUCT Product type Type designation Manufacturing

More information

Model # 800SM-PS3. 8/3/2016 Page 1 of 8

Model # 800SM-PS3. 8/3/2016 Page 1 of 8 Model # 800SM-PS3 8/3/2016 Page 1 of 8 /3/2016 Page 2 of 8 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Water Level Meter User Manual

Water Level Meter User Manual Man 054 Water Level Meter User Manual Soil Instruments Limited has an ongoing policy of design review and reserves the right to amend these specifications without notice. Man054 - Water Level Meter - MN1114

More information

BESTMOVE STANDING TRANSFER AID

BESTMOVE STANDING TRANSFER AID BESTMOVE STANDING TRANSFER AID L.L.C. MODELS BestMove 400 BestMove 450 PRODUCT FEATURES *BestMove 450 shown Ensure the product has been assembled according to the instructions in this manual. OPERATING

More information

Good Husband Brand Remote Lighting Lifter

Good Husband Brand Remote Lighting Lifter Good Husband Brand Remote Lighting Lifter National Patent Number:200520069085.5 200520075680.X 200520075677.8 200520075679.7 International Patent Number: PCT/CN2006/000409 Product Standard: Q/QABC002-2009

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

Speedlock Pallet Racking

Speedlock Pallet Racking Assembly specification These instructions are to assemble Dexion Speedlock Pallet Racking which conforms with the specifications below. Frame heights not more than 4800mm Frame depths 840mm Not less than

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

Suspension System Data Center Ceiling Solutions

Suspension System Data Center Ceiling Solutions Hardware That Needs to be Purchased Separately Screws are fine listed as shown: Min 1-1/4" or longer #8 Truss head self-tapping screws for attaching structural wall angle, lateral support bar 16" or 4"

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 1 of 6 INSTALLATION INSTRUCTIONS IMPORTANT! Store the floorboards at room temperature for at least 48 hours, still in their packaging, prior to commencing installation. Ideal room temperature is 18-22

More information

SECTION I -- IRONWORK

SECTION I -- IRONWORK SECTION I -- IRONWORK CONTENTS PAGE 1. GENERAL... I-2 1.1. Introduction... I-2 2. REQUIREMENTS... I-2 2.1. General... I-2 2.2. Auxiliary Framing... I-2 2.3. High Seismic Risk Zone Requirements... I-3 2.4.

More information

MODULAR ACOUSTIC FENCING INSTALLATION GUIDE

MODULAR ACOUSTIC FENCING  INSTALLATION GUIDE MODULAR ACOUSTIC FENCING WWW.QUICKBUILTSYSTEMS.COM.AU INSTALLATION GUIDE INTRODUCTION THE QUICKBUILT FENCE SYSTEM IS A SMARTLY DESIGNED MODULAR SYSTEM EASY AND FAST TO INSTALL AND COST EFFECTIVE. // THE

More information

Turbocharger / TPL-C Original assembly instructions English

Turbocharger / TPL-C Original assembly instructions English Assembly Instructions Turbocharger / TPL-C Original assembly instructions English This document is valid for the TPL-C series: TPL79-C Purpose The assembly instructions explain how the ABB turbocharger

More information

Modular Coldroom Installation Manual

Modular Coldroom Installation Manual Modular Coldroom Installation Manual May 2005 Disclaimer: The information contained in this installation guide is provided "as is". Bromic Pty Ltd does not warrant the accuracy, adequacy or completeness

More information

Installation Guide Details correct as of December 2013

Installation Guide Details correct as of December 2013 Installation Guide Details correct as of December 2013 Pre-installation checklist Solid/Screed floors 1. Insulation fitted neatly and stable with all gaps and joints taped 2. If using liquid screed, a

More information

BESTMOVE STANDING TRANSFER AID

BESTMOVE STANDING TRANSFER AID BESTMOVE STANDING TRANSFER AID MODELS BestMove 400 BestMove 450 PRODUCT FEATURES *BestMove 450 shown Ensure the product has been assembled according to the instructions in this manual. OPERATING ASSEMBLY

More information

BESTMOVE STANDING TRANSFER AID

BESTMOVE STANDING TRANSFER AID BESTMOVE STANDING TRANSFER AID L.L.C. MODELS BestMove 400 BestMove 450 PRODUCT FEATURES *BestMove 450 shown Ensure the product has been assembled according to the instructions in this manual. OPERATING

More information

Saber Saw. Given a properly adjusted saber saw, accessories, instruction and use demonstration, each student will be able to:

Saber Saw. Given a properly adjusted saber saw, accessories, instruction and use demonstration, each student will be able to: Saber Saw I. Competencies Given a properly adjusted saber saw, accessories, instruction and use demonstration, each student will be able to: A. Identify the major parts of the saber saw. B. Pass a written

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

Section 2: Underground

Section 2: Underground Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,

More information

1675 Locust Street Red Bud, IL Phone: Fax: WARRANTY & TERMS

1675 Locust Street Red Bud, IL Phone: Fax: WARRANTY & TERMS Model # 349S-P6 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic coated elements. Ultra Play guarantees all

More information

Model # 358H-PR. 4/8/2011 Page 1 of 12

Model # 358H-PR. 4/8/2011 Page 1 of 12 Model # 358H-PR 4/8/2011 Page 1 of 12 4/8/2011 Page 2 of 12 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Installation Manual. Orion. TL-3 Steel Barrier. VHD (v2)

Installation Manual. Orion. TL-3 Steel Barrier. VHD (v2) Installation Manual Orion TL-3 Steel Barrier VHD (v2) 300914 Table of Contents Orion Introduction.......... 3 Limitations & Warnings. 4 Before Installation..... 3 System Design & Design Considerations

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual FORM HEADWALL (floating) Installation Manual FORM HEADWALL (floating) OVERVIEW The Form is a UL-listed configurable headwall system. This system includes multiple horizontal equipment channels integrated

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

Product Manual Release 05/17

Product Manual Release 05/17 Temporary Safety Barrier (TL-2 MASH) Product Manual VHD (v3) www.valmonthighway.com Table of Contents 1.0 ArmorZone Introduction... 3 2.0 Before Installation... 3 3.0 Limitations & Warnings... 3 4.0 System

More information

Model # 338S-OP. 9/30/2011 Page 1 of 13

Model # 338S-OP. 9/30/2011 Page 1 of 13 Model # 338S-OP 9/30/2011 Page 1 of 13 9/30/2011 Page 2 of 13 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Model # BARK-358-RDP

Model # BARK-358-RDP Model # BARK-358-RDP 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic/Canine coated elements. guarantees all

More information

Allround Scaffolding. Layher Allround Bridging System Instructions for Assembly and Use. Modular truss system for wide spans

Allround Scaffolding. Layher Allround Bridging System Instructions for Assembly and Use. Modular truss system for wide spans Layher Allround Bridging System Instructions for Assembly and Use Modular truss system for wide spans Certification according to DIN ISO 9001/EN 29 001 by TÜV-CERT Allround Scaffolding } CONTENT 1. Introduction...3

More information

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available. Concrete inserts offered in this section are designed to provide a pre-set support point in concrete ceilings, walls, and floors. A range of inserts with varying design loads are available. Materials Carbon

More information

OPO-SHORT Installation Instructions Manual Version

OPO-SHORT Installation Instructions Manual Version 10200 South Kedzie Avenue Evergreen Park, IL 60805 800.499.0400 708.499.0400 Fax 708.499.4620 OPO-SHORT Installation Instructions Manual Version OPO-1S, OPO-3S, OPO-4S PreSell Main Board (shown as Standard

More information

Original Scandinavian rainwater system

Original Scandinavian rainwater system Original Scandinavian rainwater system Siba Siba Square Contents Siba rainwater systems 3 Measuring 15-16 Siba 4-9 Gutter brackets 18-19 Siba Square 10-11 Gutters 20-23 Materials 12 Angles 24 Technical

More information

STANDARD PRACTICE INSTRUCTION

STANDARD PRACTICE INSTRUCTION STANDARD PRACTICE INSTRUCTION DATE: March 1, 2001 SUBJECT: Scaffolding Safety Program. REGULATORY STANDARDS: 29 CFR 1910.28 Safety Requirements For Scaffolding. 29 CFR 1910.29 Manually Propelled Mobile

More information

-SQA- SCOTTISH QUALIFICATIONS AUTHORITY. Hanover House 24 Douglas Street GLASGOW G2 7NQ NATIONAL CERTIFICATE MODULE DESCRIPTOR

-SQA- SCOTTISH QUALIFICATIONS AUTHORITY. Hanover House 24 Douglas Street GLASGOW G2 7NQ NATIONAL CERTIFICATE MODULE DESCRIPTOR -SQA- SCOTTISH QUALIFICATIONS AUTHORITY Hanover House 24 Douglas Street GLASGOW G2 7NQ NATIONAL CERTIFICATE MODULE DESCRIPTOR -Module Number- 4110361 -Session- 1991-92 -Superclass- TH -Title- ELECTRICAL

More information

Chapter 7. Roof Framing

Chapter 7. Roof Framing Chapter 7. Roof Framing 7.1 ROOFING PREP WORK 7.2 INSTALLING ROOF TRUSSES 7.3 INSTALLING PORCH TRUSSES 7.4 SHEATHING ROOF 7.5 INSTALLING SUB-FASCIA 7.6 BUILDING AND INSTALLING SCUTTLE BOX 7.7 INSTALLING

More information

A-0312 ASSEMBLY GUIDE

A-0312 ASSEMBLY GUIDE 760265-A-0312 ASSEMBLY GUIDE 1 Contents Section Contents Introduction Know Your MiTOWER Know Your MiTOWER s Components Know Your Kit List and Specifications Know Your Storage and Transport Pack Safety

More information

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com MODEL : PHM-12 ARC WELD GUN PART NO. : PHM-12 (PHM-12-RS) SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@

More information

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

HIGH MAST CAMERA POLE ASSEMBLY GENERAL 10-3.24 HIGH MAST CAMERA POLE ASSEMBLY GENERAL The Contractor must furnish and install the following equipment for high mast camera pole assembly as described herein and as shown on the plans: 1. Camera

More information

Division 11 - Equipment Section 11401

Division 11 - Equipment Section 11401 PART 1 - GENERAL 1.1 GENERAL A. Division 1 General Requirements applies and becomes a part of this Section of the Specification as fully as if repeated herein. B. Items of equipment which are included

More information

HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION

HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION INSTALLATION INSTRUCTIONS ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used for

More information

Guidance for installers when making connections in consumer units. electricalsafetyfirst.org.uk beama.org.uk

Guidance for installers when making connections in consumer units. electricalsafetyfirst.org.uk beama.org.uk Guidance for installers when making connections in consumer units electricalsafetyfirst.org.uk beama.org.uk Published by: Electrical Safety First 45 Great Guildford Street London SE1 0ES Tel: 0203 463

More information

INSTALLATION INSTRUCTIONS CMP SERIES

INSTALLATION INSTRUCTIONS CMP SERIES INSTALLATION INSTRUCTIONS CMP 25677 SERIES 1. PRODUCT OVERVIEW Thank you for choosing our 25677 Series Brilliant Wonders LED Waterfall. This lighted waterfall will add a unique ambiance to your pool or

More information

Shackles. Applications. Range. Design. CAD drawings. Finish

Shackles. Applications. Range. Design. CAD drawings. Finish Applications Shackles are used in lifting and static systems as removable links to connect (steel) wire rope, chain and other fittings. Screw pin shackles are used mainly for non-permanent applications.

More information

Scaffolding. Safety Guide. STOP! Before you climb

Scaffolding. Safety Guide. STOP! Before you climb Scaffolding Safety Guide Printed FEB 2015 rebr. AUG 2016 Contents Safety Guide Disclaimer... 1 Safety Guide Objectives... 2 Roles & Responsibilities of Workplace Parties Employers, Supervisors, Workers...

More information

OmniFlex 300 Plus Installation Instructions

OmniFlex 300 Plus Installation Instructions OmniFlex 300 Plus Installation Instructions IMPORTANT PortaFab advises a thorough reading of these instructions before beginning installation. INTRODUCTION Instructions should be read thoroughly and cross-referenced

More information

DOUBLE SLIDE RAIL INSTALLATION METHOD. Double Slide Rail August

DOUBLE SLIDE RAIL INSTALLATION METHOD. Double Slide Rail August Double Slide Rail August 2015 1 DOUBLE SLIDE RAIL INSTALLATION METHOD Introduction Slide rail shoring systems can be used for trenches up to 12m wide and 6m deep. Module length is determined by panels

More information

DUQUESNE UNIVERSITY SAFETY PROGRAM FOR WORKING AT ELEVATED HEIGHTS

DUQUESNE UNIVERSITY SAFETY PROGRAM FOR WORKING AT ELEVATED HEIGHTS DUQUESNE UNIVERSITY SAFETY PROGRAM FOR WORKING AT ELEVATED HEIGHTS Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Responsibilities 1 Scaffolding 2 Ladders

More information

ArmorZone TL-2 Barrier and End Treatment

ArmorZone TL-2 Barrier and End Treatment ArmorZone TL-2 Barrier and End Treatment Product and Installation Manual ANOTHER AMORFLEX DEVELOPMENT Table of contents Introduction 3 System Overview 3 Before Installation 3 Limitations and Warnings 4

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Three-sided barrier compliant to DIN EN ISO Depending on location, design also as wind protection. Clear height (DH) Three-sided barrier

Three-sided barrier compliant to DIN EN ISO Depending on location, design also as wind protection. Clear height (DH) Three-sided barrier of 5 Page Car SingleVario 06 Stack Parker 06 50 for vehicle up to 5.00 m = 6 long (50 for vehicle up to 5.0 m 7 long) Depending on location, design also as wind protection. Product Data CONFORMITY 06/06/G63

More information

BUILD A SHOWER CUBICLE

BUILD A SHOWER CUBICLE BUILD A SHOWER CUBICLE Building a shower cubicle requires some experience in carpentry and tiling. You also need a degree of expertise in wiring and plumbing in order to install a shower unit. By all means

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

Model # 358-R48. 7/7/2011 Page 1 of 11

Model # 358-R48. 7/7/2011 Page 1 of 11 Model # 358-R48 7/7/2011 Page 1 of 11 7/7/2011 Page 2 of 11 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Welding Accessories

Welding Accessories Welding Accessories www.airliquide.ca 1-800-817-7697 Welding Accessories BLUESHIELD Welding Cables Blueshield Welding Cables: Excellent flexibility (stays flexible at -50 C) Abrasion resistant Oil, solvent

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

GROUND RELEASE SHACKLE

GROUND RELEASE SHACKLE INNOVATIVE PILING EQUIPMENT HYDRAULIC PILING HAMMERS GROUND RELEASE SHACKLE EURO GROUND RELEASE SHACKLE OPERATORS INSTRUCTIONS & SPARE PARTS LIST EXCAVATOR MOUNTED VIBRATORS EXCAVATOR MOUNTED DRILLS QUIET,

More information

Steel Door Frame Installation in Masonry Construction

Steel Door Frame Installation in Masonry Construction Steel Door Frame Installation in Masonry Construction Steel Door Frame Installation in Masonry Construction This manual provides step-by-step instructions for the installation of a steel door frame in

More information

BOILER INSTALLATION INSTRUCTIONS FOR RU 1S / BRU 1 RU 2S / BRU 2 RU 3S

BOILER INSTALLATION INSTRUCTIONS FOR RU 1S / BRU 1 RU 2S / BRU 2 RU 3S BOILER INSTALLATION INSTRUCTIONS FOR RU 1S / BRU 1 RU 2S / BRU 2 RU 3S ASSEMBLY INSTRUCTIONS General Instructions: The STREBEL RU boilers are special boilers for oil or gas-fired (forced) burners. They

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

Model # 922-S4. 12/18/2013 Page 1 of 8

Model # 922-S4. 12/18/2013 Page 1 of 8 Model # 922-S4 12/18/2013 Page 1 of 8 2/18/2013 Page 2 of 8 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

min. 50min. 65min. PIT / P3 / P4 Ø

min. 50min. 65min. PIT / P3 / P4 Ø Flush design Stop switch, IP 65 Equipment consisting of (schematic overview) 2 78 23 Actuator Anti-twist ring 2... 6 Pressure ring = Screw terminal Product can differ from the configuration. Bayonet flange

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

Universal Panels & Accessories

Universal Panels & Accessories Universal Panels & Accessories Erection Procedures INTRODUCTION Use common sense when working with Scaffold Your Safety is our #1 Concern Universal Scaffolds are designed with your safety in mind every

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

HANDING-OVER CERTIFICATE - SCAFFOLDING

HANDING-OVER CERTIFICATE - SCAFFOLDING HANDING-OVER CERTIFICATE - SCAFFOLDING Contractor : Site : Contractor. customername Site. Site name Date : Time : Erected by : Signature : Description of section handed over Job specification. description

More information

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS Rev. 1.5 1.10.13 Toll free (800) 288-6000 or www.hubbell-wiring.com P a g e 0 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING- When using

More information

HEKAPLAST. PE-HD twin wall cable ducts and cable protection pipes for underground installation. Corrugated and Twin Wall Pipes of Plastics

HEKAPLAST. PE-HD twin wall cable ducts and cable protection pipes for underground installation. Corrugated and Twin Wall Pipes of Plastics HEKAPLAST PE-HD twin wall cable ducts and cable protection pipes for underground installation HEGLER HEKAPLAST III/ HEKAPLAST: Twin wall cable ducts or cable protection pipes to DIN 696, manufactured from

More information

Fire Protection Valves

Fire Protection Valves 4/4/EN/6 Fire Protection Valves Type FV-K90 FVZ-K30 with German Test Certificate (General Building Approval) Z-41.3-317 Z-41.3-319 TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/202-265 Heinrich-Trox-Platz

More information

WIRING METHODS CHAPTER 38

WIRING METHODS CHAPTER 38 CHAPTER 38 WIRING METHODS SECTION E3801 GENERAL REQUIREMENTS E3801.1 Scope. This chapter covers the wiring methods for services, feeders and branch circuits for electrical power and distribution. E3801.2

More information

TECHNICAL GUIDANCE XXXX 2015 EXXON QUESTION ANSWER. page 1 of 9

TECHNICAL GUIDANCE XXXX 2015 EXXON QUESTION ANSWER. page 1 of 9 MARKINGWALLING OF SAFETY GLASS SPANDREL CURTAIN PANELS FORMED TO COLDFROM ROOFS STACKED WINDOW 7.2 /25 January ARRANGEMENTS (First Issue) XXXX EXXON QUESTION Which factors should be taken into account

More information

TAKING YOU TO NEW HEIGHTS IN SAFETY... kwikstage

TAKING YOU TO NEW HEIGHTS IN SAFETY... kwikstage limited one bay kwikstage stair unit user guide One Bay Stair Tower used in conjunction with Kwikstage System Scaffolding and designed to conform to all current British and European Standards. With only

More information

Trench Duct Class Catalog 5230CT9601R10/08

Trench Duct Class Catalog 5230CT9601R10/08 5230CT9601R10/08 2009 Class 5230 CONTENTS Application.................................................5 Unassembled Trench Duct Components.........................6 Factory Assembled Trench Duct..............................11

More information

Installation Guide. PrivacyShield Outdoor Enclosure

Installation Guide. PrivacyShield Outdoor Enclosure Installation Guide PrivacyShield Outdoor Enclosure Table of Contents 1.0 Introduction... 2 2.0 Materials, Delivery & Tools... 2 3.0 Layout and Post Locations. 3 4.0 Foundations... 5 5.0 PVC Installation....

More information

Installation Instruction photovoltaic modules E-PV 250W on the flat roof or fundation 10/2013 Get acquainted before the installation.

Installation Instruction photovoltaic modules E-PV 250W on the flat roof or fundation 10/2013 Get acquainted before the installation. Installation Instruction photovoltaic modules E-PV 250W on the flat roof or fundation 10/2013 Get acquainted before the installation. 1. General information Lightning Protection System In case of LPS we

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT ADVANCE WORLD LIMITED Lalkha Shair Char, Fatullah, Narayanganj, Dhaka, Bangladesh Factory List: 1.. Inspected by: Sherub Tenzin & Md. Moin Hasan Report Generated by:

More information

layout instructions provides both left and right hand facilities without the need to specify

layout instructions provides both left and right hand facilities without the need to specify DOC M Shower Room Pack Shower Facility for Wheelchair Users layout instructions DIMENSIONS AND EQUIPMENT To comply with Approved Document M of the Building Regulations BS 8300:2001, 2009 a Shower Compartment

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE This specification is intended to describe the general requirements applicable to a proper structural cantilever rack design. In addition, it is

More information

hss.com / Safety / Value / Availability / Support The 2013 HSS Guide to Working Safely at Height

hss.com / Safety / Value / Availability / Support The 2013 HSS Guide to Working Safely at Height The 2013 HSS Guide to Working Safely at Height Working Safely at Height - Your Guide to the Law 2011 / 2012-40 fatal injuries to workers and over 3,000 major injuries as a result of a fall from height

More information

2-finger angular gripper SGB 32-50

2-finger angular gripper SGB 32-50 www.comoso.com Translation of the original manual 2-finger angular gripper SGB 32-50 Assembly and Operating Manual Superior Clamping and Gripping Imprint www.comoso.com Imprint Copyright: This manual remains

More information

ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR

ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR INSTALLATION INSTRUCTIONS ENERGY AND SANITARY SYSTEMS Installation requirements Generel requirements The on-roof attachment set is capable for installation of

More information

TYPICAL INSTALLATION INSTRUCTIONS

TYPICAL INSTALLATION INSTRUCTIONS TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect

More information

Channel Drain Shower Base. Aqua Line pro. Installation Instructions

Channel Drain Shower Base. Aqua Line pro. Installation Instructions Channel Drain Shower Base. Aqua Line pro Installation Instructions 02 JACKOBOARD Aqua Line pro System components a JACKOBOARD Aqua Line pro b JACKOBOARD Aqua Line pro - Horizontal Drain (Art. No. 4510370)

More information

CAL/OSHA ELECTRICAL HIGH VOLTAGE

CAL/OSHA ELECTRICAL HIGH VOLTAGE Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to high voltage for employees and contractors

More information

Basic Requirements for Residential Electrical Installations

Basic Requirements for Residential Electrical Installations Basic Requirements for Residential Electrical Installations Wayne County Building Department 428 West Liberty Street Wooster, Ohio 44691 Phone: 330-287-5525 Fax: 330-287-5649 This brochure is intended

More information

You are also similarly responsible for any part crossing any neighbouring land, including any length of private service pipe in the public highway.

You are also similarly responsible for any part crossing any neighbouring land, including any length of private service pipe in the public highway. Shared supply or lead water pipe replacement connections guidance notes Up to 25mm diameter supplies Introduction Our aim is to deliver an excellent standard of service. In order for us to do this and

More information

Basic Suspension Systems

Basic Suspension Systems CEILING & WALL SYSTEMS Commercial Ceilings and Walls Solutions Guide Installing Armstrong Suspended Ceilings The ceiling system is made up of Armstrong panels which are supported by a suspension system

More information

Dwarf Wall Assembly Instructions. Including Important Safety Information to be read fully and understood before attempting assembly

Dwarf Wall Assembly Instructions. Including Important Safety Information to be read fully and understood before attempting assembly Dwarf Wall Assembly Instructions Including Important Safety Information to be read fully and understood before attempting assembly Contents Important Information... 2 Health, Safety & Environmental...

More information