First Revision No NFPA [ Section No ]
|
|
- Elizabeth Lawson
- 6 years ago
- Views:
Transcription
1 First Revision No NFPA [ Section No ] Global FR Exterior Nonbearing Walls. Exterior nonbearing walls tested shall be permitted when tested in accordance with, and meeting the conditions of acceptance of, either one of the following: NFPA 285, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing Wall Assemblies Containing Combustible Components, shall be permitted. (1) NFPA 285 (2) FM Approval 4880, Class 1 Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall Systems Submittal Date: Tue Jul 28 15:09:36 EDT 2015 Response Message: This proposed code change offers a nationally accepted fire test (ANSI/FM 4880) as an alternative to NFPA 285. As evidenced by a peer reviewed journal article (SFPE) and Phase 1 of an FPRF study, ANSI/FM 4880 is a more stringent test than NFPA 285 so there is no reason to question the adequacy of ANSI/FM ANSI/FM 4880 is already referenced in H Public Input No. 190-NFPA [Section No ] Page 1
2 First Revision No NFPA [ Section No ] Enclosed Parking Structures with Occupancies Above. A basement or first story above grade plane of a building shall be considered as a separate and distinct building for the purpose of determining the limitation on number of stories and construction type, provided that all of the following conditions are met: (1) The basement or first story above grade plane shall be of Type I construction and shall be separated from the building above with a horizontal assembly having a minimum 3-hour fire resistance rating. (2) Shaft, stairway, ramp, or escalator enclosures through the horizontal assembly shall comply with either of the following conditions: (a) (b) The enclosures shall have not less than a 2-hour fire resistance rating with opening protectives in accordance with Table Where the walls below the horizontal assembly have a minimum 3-hour fire resistance rating with opening protectives as required for walls forming a 3-hour fire barrier, the enclosure walls extending above the horizontal assembly shall be permitted to have a 1-hour fire resistance rating, provided that all of the following conditions are met: i. The building above the horizontal assembly is not required to be of Type I construction. ii. iii. The enclosure connects less than four stories above the horizontal assembly. The enclosure opening protectives above the horizontal assembly have a minimum 1-hour fire protection rating. (3) The building above the horizontal assembly shall contain only business, mercantile, storage, or residential occupancies or assembly occupancies having an assembly room with an occupant load of less than 300. (4) The building below the horizontal assembly shall be an enclosed or open parking structure used for the parking and storage of private motor vehicles, unless otherwise permitted by the following: (a) (b) Entry lobbies, mechanical rooms, and similar uses incidental to the operation of the building shall be permitted. Business, mercantile, and assembly occupancies having an assembly room with an occupant load of less than 300 shall be permitted in addition to those uses incidental to the operation of the building (including storage areas), provided that the entire structure below the horizontal assembly is protected throughout by an approved, electrically supervised automatic sprinkler system installed in accordance with NFPA 13. (5) The maximum building height in feet shall not exceed the limits set forth in Table for the least restrictive type of construction involved. Page 2
3 Submittal Date: Tue Jul 28 15:36:11 EDT 2015 The committee agrees with the change but for the main reason that it clarifies the intent of the code. Public Input No. 43-NFPA [Section No ] Page 3
4 First Revision No NFPA [ Section No ] Residential Sprinkler Increase. For buildings classified as residential occupancies provided with an approved, electrically supervised automatic sprinkler system in accordance with NFPA 13R, the allowable height for nonsprinklered buildings shall be permitted to be increased by 20 ft (6100 mm 6.1 m ), and the allowable number of stories for nonsprinklered buildings shall be permitted to be increased by one story, provided that the building height does not exceed 60 ft (18 m) in height above grade plane, and the number of stories above grade plane does not exceed four. Submittal Date: Tue Jul 28 15:38:30 EDT 2015 Intent of the revision is to correlate the revised wording in the 2013 edition of NFPA 13R under its Scope 1.1 with NFPA Codes that reference NFPA 13R. Correlation of the NFPA 5000 with the scope of NFPA 13R will make the codes user friendly and will not leave room for misinterpretation of the requirements for application of NFPA 13R NFPA 13R Section 1.1 now states: "This standard shall cover the design and installation of automatic sprinkler systems for protection against fire hazards in residential occupancies up to and including four stories in height in buildings not exceeding 60 ft (18 m) in height above grade plane." Public Input No. 11-NFPA [Section No ] Page 4
5 First Revision No NFPA [ Section No. A ] A The system of designating types of construction also includes a specific breakdown of the types of construction through the use of arabic numbers. These arabic numbers follow the roman numeral notation where identifying a type of construction [e.g., Type I(442), Type II(111), Type III(200)] and indicate the fire resistance rating requirements for certain structural elements as follows: (1) First arabic number exterior bearing walls (2) Second arabic number columns, beams, girders, trusses and arches, supporting bearing walls, columns, or loads from more than one floor (3) Third arabic number floor construction Where Table references floor/ceiling assemblies or roof/ceiling assemblies, the term assembly refers to a combination of materials comprising the walking surface of the floor or the exterior surfaces of the roof, horizontal supporting construction and possibly the ceiling membrane. Typically, such assemblies include the walking surface of the floor or the exterior surfaces of the roof and all horizontal structural members (elements) supporting the walking surface of the floor or the exterior surfaces of the roof. Where the assembly has a fire resistance rating, cavity insulation, ceiling membrane layers affixed or suspended from the underside of the horizontal structural members (elements), and any required opening protection for penetrations such as, but not limited to, recessed lights, HVAC diffusers, penetrating cables, or pipes are regulated. See 8.6 for requirements governing horizontal assemblies having a fire resistance rating. See Section (1) for horizontal assemblies not having a fire resistance rating. Table A provides a comparison of the types of construction for various model building codes. Table A Cross-Reference of Building Construction Types NFPA 5000 I(442) I(332) II(222) II(111) II(000) III(211) III(200) IV(2HH) V(111) V(000) UBC I FR II FR II 1 hr II N III 1 hr III N IV HT V 1 hr V N B/NBC 1A 1B 2A 2B 2C 3A 3B 4 5A 5B SBC I II IV 1 hr IV UNP V 1 hr V UNP III VI 1 hr VI UNP IBC IA IB IIA IIB IIIA IIIB IV VA VB UBC: Uniform Building Code. FR: Fire rated. N: Nonsprinklered. HT: Heavy timber. B/NBC: National Building Code. SBC: Standard Building Code. UNP: Unprotected. IBC: International Building Code. Page 5
6 Submittal Date: Tue Jul 28 15:50:06 EDT 2015 Response Message: The added wording will assist users in understanding what is meant by the term assembly. Public Input No. 185-NFPA [Section No. A ] Page 6
7 7 First Revision No NFPA [ Section No. D ] D Plenums. Plenums shall be permitted to be used to supply air to the occupied area, or return and exhaust air from the occupied area, provided that the requirements through NFPA 90A are met. Submittal Date: Tue Jul 28 15:54:38 EDT 2015 Response Message: The referenced sections through do not exist within NFPA Those provisions were removed in the 2012 edition but the corresponding changes to Annex D were not made. This corrects that oversight. Public Input No. 71-NFPA [Section No. D ] Page 7
Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION
Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES
More informationUBC. (1997 Edition) (p.1-116) 2-hr. shaft required for
Protection of Shaft Enclosures (Exit Stairs) Protection of Shaft Enclosures (Other Shafts) Comparison on Fire Safety Provisions* (Revised 2/28/03) (S) = Small difference in fire protection, (M) = Moderate
More informationWoodWorks. Learning Objective. Presentation Overview. Fire Protection II Requirements for rated assemblies and common detailing
WoodWorks Fire Protection II Requirements for rated assemblies and common detailing Scott Lockyear, PE Learning Objective Discuss the type of rated assembly requirements in the International Building Code.
More informationComparison of the life safety elements of the 1997 UBC and the IBC 2000.
Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.
More informationWELCOME TO: ARCH 2330 BUILDING TECHNOLOGY III
WELCOME TO: ARCH 2330 BUILDING TECHNOLOGY III GateWay Community College / SmithGroup JJR http://www.archdaily.com/268232/gateway-community-college-smithgroup-jjr/ photo Liam Frederick Building Structure
More informationBuilding Codes and Ordinances ARC 227
Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive
More informationFCIA Webinar Gypsum Wall Patching
FCIA Webinar Gypsum Wall Patching Firestop Contractors International Association Hillside, IL +1-708-202-1108 - office Bill McHugh bill @ fcia.org Nestor Sanchez, USG Corp. nsanchez@usg.com DIIM Firestopping
More informationINTERIOR FINISHES CHAPTER 8
CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.2 Interior wall and
More informationFirst Revision No NFPA [ Section No ]
National Fire Protection Association Report of 13 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 10/28/2015 10:35 AM First Revision No. 5501-NFPA 5000-2015 [ Section No. 3.3.220.4
More informationFIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
More information2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)
2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:
More informationCHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION
CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic
More informationFire Retardants and Truss Design. Overview
Fire Retardants and Truss Design Overview Introduction Fire retardant treatments (FRT) were developed to be applied to building materials, such as dimension lumber (FRTW) and plywood, to reduce the ability
More informationIBC FIRE SAFETY. Code Change No: FS1-07/08. Original Proposal SECTION 702 DEFINITIONS
DOCUMENTATION IBC FIRE SAFETY Code Change No: FS1-07/08 Sections: 702.1, 704.8.2, 706.7 Proponent: Philip Brazil, PE, Reid Middleton, Inc., representing himself SECTION 702 DEFINITIONS 702.1 Definitions.
More informationApplying the Building Code During Design
Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education
More informationCODE 101 How To Read The California Building Code
CODE 101 How To Read The California Building Code Part 2 MA Continuing Education August 3, 2015 Instructor: Jay Hyde CSI, Member CALBO, Certified Interior Designer Architect Part 3 Occupancy Groups (Chapters
More informationIBC GENERAL. Code Change No: G4-06/07. Original Proposal
DOCUMENTATION IBC GENERAL Code Change No: G4-06/07 Original Proposal Sections: 112.1, 1612.3, 3109.4.1.8, 3202.1.2, 3202.3.4, 3202.4, 3303.6, 3306.2 (IEBC [B] 1401.6.1), 3308.1(IEBC [B] 1403.1), 3409.9
More informationFollowing are the NMHC/NAA Recommendations for the ICC Online Consensus Voting which opens on February 8 th, 2016:
Following are the NMHC/NAA Recommendations for the ICC Online Consensus Voting which opens on February 8 th, 2016: These recommendations are only for those issues that are of concern to the multifamily
More informationGENERAL BUILDING HEIGHTS AND AREAS
CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress
More information2009 IBC Ht. & Area Calculations Talk. Calculation of Building Height & Area under the 2009 IBC. Consultant s Motto
Calculation of Building Height & Area under the 2009 IBC Marshall Klein, P.E. Marshall A. Klein & Associates, Inc. Eldersburg, MD 410-781-6474 Jeff Shapiro, P.E. International Code Consultants Austin,
More informationINTERIOR FINISHES CHAPTER 8
CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.2 Interior wall and
More information2018 IBC Update. Based on the 2018 International Building Code, (IBC ) Goal. Objectives. Content
Based on the 2018 International Building Code, (IBC ) The International Building Code (IBC ), establishes minimum regulations for building safety. This handout will identify important changes in the IBC
More informationWhat is a Won-Door FireGuard Door?
What is a Won-Door FireGuard Door?. A horizontal sliding accordion fire door that meets all IBC requirements for use in a means of egress and has fire ratings up to 3 hours. A Reference Guide to special
More informationWON-DOOR CORPORATION Won-Door FireGuard Applications
WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis THE INTERNATIONAL BUILDING CODE is widely recognized in the United
More information780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016
780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)
More informationThe Building Codes A.R.E. Building Design and Construction Exam Prep
Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire
More informationAPPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:
COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION
More informationCombustible Exterior Wall Cladding Systems: An ICC Perspective
Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting
More informationINTERIOR FINISHES CHAPTER 8
CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.1.1 Interior finishes.
More informationBUILDING CODES & DESIGN CRITERIA
BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing
More informationGENERAL BUILDING HEIGHTS AND AREAS
CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress
More informationStorage Buildings. Wood Uses In. Introduction. Table of Contents
Wood Uses In Storage Buildings Introduction Wood construction offers distinct design options typically not found in a single structural material. It is inexpensive, readily available, easy to work with,
More informationPLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL
FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors
More informationWOOD USE IN NONCOMBUSTIBLE BUILDINGS
INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such
More informationCode Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)
Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently
More information2012 IBC Fundamentals
Presenter Instructions Based on the 2012 International Building Code (IBC ), Building Code Basics Commercial Many slides contain animation Review of this presentation should be done in the presentation
More informationJune 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES
June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:
More information11.1.2* Adjacent Hazards or Design Methods. For buildings with two or more adjacent hazards or design methods, the following shall apply:
10 of 474 11/7/2013 12:33 PM First Revision No. 260-NFPA 13-2013 [ Section No. 11.1.2 ] 11.1.2* Adjacent Hazards or Design Methods. For buildings with two or more adjacent hazards or design methods, the
More information2015 Code Conforming Wood Design
2015 Code Conforming Wood Design AMERICAN WOOD COUNCIL 2015 Code Conforming Wood Design 1 About the The (AWC) is the voice of North American traditional and engineered wood products. AWC develops state-of-the-art
More informationChapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE
Chapter 23.12 UNIFORM CODES FOR CONSTRUCTION BUILDING CODE 23.12.010 Adoption of the 2010 California Building Code. Part 2. Title 24 of the California Code of Regulations. There is adopted and incorporated
More informationPRESCRIPTIVE COMPLIANCE METHOD
CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already
More informationCode Review for Theaters and Props
Code Review for Theaters and Props I. INTRODUCTION Fire- and Life-Safety Group (FLS) This document was prepared to list the requirements for theaters and props. These requirements are based on the 2007
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationSECTION : FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES
SECTION 500.110: FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES A. Purpose. The intent of this regulation is to amend the current adopted edition of the International
More informationINTERIOR ENVIRONMENT
CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,
More informationREINFORCING TABLES INSTALLATION MANUAL
REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been
More informationNFPA 30-FLC-SWC Second Revisions Report
of 44 9/6/2016 1:40 PM Second Revision No. 214-NFPA 30-2016 [ Global Comment ] See attached Word doc for changes to Sections 9.2, 12.2, and 16.2. Supplemental Information File Name 30-GLOBAL_SR_214-EDITED.docx
More informationProtecting Penetrations in Fire Rated Construction
Protecting Penetrations in Fire Rated Construction NY State Fire Marshals and Inspectors Conference September 7 th Bruce E. Johnson UL Codes and Advisory Services UL and the UL logo are Trademarks of UL
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationCode Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)
Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently
More information2009 IBC Section 1024 Approved Luminous Egress Path Markings
2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient
More informationBuilding Code 8 th Edition
Massachusetts State Building Code 8 th Edition Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com RW R.W. Sullivan Engineering
More informationwww.safti.com 888.653.3333 202 IBC 76 TABLES 76.3 Marking Rated Glazing Assemblies 76.5 Opening Assemblies, Ratings and Markings (previously 75.4) 76.6 Window Assembly Ratings (previously 75.5) These tables
More informationMinnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017
Minnesota Healthcare Engineers Association, Fall Conference Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Categories of Rehabilitation Work in Healthcare Facilities Bob Dehler, P.E. robert.dehler@state.mn.us
More informationAccessible Means Of Egress
Accessible Means Of Egress 2 New ADA Standards DOJ s 2010 standards (mandatory as of March 15) Based on the Board s ADA-ABA Guidelines (2004) 3 Standards Department of Transportation s ADA Standards Federal
More informationAKF Group LLC. A. Vernon Woodworth FAIA
AKF Group LLC 780 CMR 9 th Edition: Major Changes AKF T A. Vernon Woodworth FAIA 3/14/17 Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion
More informationSIDEWALK & RAILING REPLACEMENT BOARD OF ED BUILDING
PROJECT: 25 E 5 S SALT LAKE CITY, UTAH 84111 CODE ANALYSIS APPLICABLE CODES 675 E. 5 S. Suite 4 DFCM PROJECT NUMBER: 182782 DFCM CONTRACT NUMBER: 18793 STRUCTURAL ENGINEER: REAVELEY ENGINEERS + ASSOCIATES
More informationUniform Building Code For Head-of-Wall, Vertical Shaft Walls and Wall Backing Excerpts from the 1997 Uniform Building Code
For Head-of-Wall, Vertical Shaft Walls and Wall Backing Excerpts from the 1997 FIRE-RESISTIVE JOINT SYSTEM is an assemblage of specific materials or products that are designed, tested and fire resistive
More informationTitle: Building Construction for the Fire Service. Time: 3 hours. Teaching Materials: White board Building Construction for the Fire Service (PDF)
Title: Building Construction for the Fire Service Time: 3 hours Teaching Materials: White board Building Construction for the Fire Service (PDF) Motivation: With the evolution of newer building construction
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION
PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED
More informationAssemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance
Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation
More informationEXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,
More informationPermit Fee Schedule from Fee Ordinance
Permit Fee Schedule from Fee Ordinance SECTION II. A. PERMIT FEES At the department s discretion, 25% of fees may be required at the time plans are submitted for review. The permit fee plus the plan review
More informationBy: David H. Kendall Science Park Drive Cleveland, Ohio CARLON ( )
This article is an interpretation of the 00 National Electrical Code Introduction By: David H. Kendall The 00 National Electrical Code (NEC) is permitting the use of Nonmetallic Sheathed (NM) cables to
More informationChapter 2: Foundation
Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup
More informationBoulder City NV Prepared by (Print Name) Signature Date
City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy
More information2012 INTERNATIONAL CODES SIGNIFICANT CHANGES
2012 INTERNATIONAL CODES SIGNIFICANT CHANGES TIM PATE CHIEF BUILDING OFFICIAL CITY AND COUNTY OF BROOMFIELD 2012 IRC 1. Section R302.1 has been modified to allow reduced fire separation distances when
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationPermit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department:
Permit Requirements: Any owner, authorized agent, or contractor who desires to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,
More informationDIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00
More informationE d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e
I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00
More informationbuildings. design of post-frame gyms and multipurpose
Research + Technology Xxxxx design of post-frame gyms and multipurpose buildings by Timothy Royer, PE, and Amanda Stauffer Post-frame construction is ideal for non-code-exempt buildings of many shapes
More informationTraining Certification Categories
Training Certification Categories Residential Residential Building Inspector structures are free from hazardous structural conditions and comply with the UCC. Duties include inspection of footings and
More informationBASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS
BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a
More information2014 Commercial Plan Submittal Checklist
City of Aurora Public Works Department AURORA PUBLIC SCHOOLS AND CHERRY CREEK PUBLIC SCHOOLS 2014 Commercial Plan Submittal Checklist Permit Center 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
More informationRESIDENTIAL BUILDING REQUIREMENTS
RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell
More informationBuilding & Fire Appeals Board
Building & Fire Appeals Board Date: March 10, 2016 Time: 3:30 p.m. - 5:00 p.m. Location: St Etienne Room City of Des Moines Armory Building 602 Robert D. Ray Drive Des Moines, Iowa 50309-1881 Summersfield
More informationOne and Two Family Additions
One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri
More informationReport on First Revision June 2014 NFPA 5000
5000 FR520 BLD-FUR (10.1 and 10.2) 10.1* General. 10.1.1 Application. Interior finish for buildings shall comply with this chapter. 10.1.2 Automatic Sprinkler Systems. Where another provision of this chapter
More informationJune 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS
ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant
More informationMSC Guidelines for Review of Ventilation System Plans
K. B. FERRIE, CDR, Chief, Hull Division Purpose: This Plan Review Guideline (PRG) explains the requirements for seeking plan approval of ventilation systems from the Marine Safety Center (MSC) for most
More informationOrdinance No July 1, 2016
(Insert Facing Page 3 IRC) 2.02.540 Amendment to IRC Section R105.2 Work Exempt From Permit, Building and Electrical Sections. The following additional exception shall be added to R105.2 Building: Building:
More informationBuilding Code Updates and How They Affect Your Self-Storage Project
Building Code Updates and How They Affect Your Self-Storage Project Presented by Jamie Lindau, National Sales Manager Ross Mori, Engineering Manager Trachte Building Systems Building Codes IBC Codes Starting
More informationBASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from
More information2015 IBC Chapters 1 and 35
Study Session 1 2015 IBC Chapters 1 and 35 Administration OBJECTIVE: To obtain an understanding of the administrative provisions of the International Building Code Ò (IBC Ò ), including the scope and purpose
More informationUNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011
UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011 CONTENTS A. PURPOSE B. DESIGNATED RESPONSIBILITIES C. DEFINITIONS D. PROJECT SUBMITTAL PROCEDURE E. REQUIREMENTS
More informationDemolition Safety!!!!
Sample Written Program For Your Company For Demolition Safety Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-718-4957 Email: info@se-safety.com Demolition Safety Program Purpose
More informationQ. Do residential and historical buildings that are going to be protected with sprinklers need to conduct an LSE?
TECHNICAL AND CODE INTERPRETATION QUESTIONS: Q. For evaluation and scoring purposes, the Rules distinguish between Residential and Commercial occupancies. In terms of the referenced sections of the Chicago
More informationSPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS
BuildingName The Description of the Project P00000000 0000 DOCUMENTS Title Page Table of Contents Instruction to Bidders Form of Proposal Equal Opportunity Statement Form of Guarantee Supplemental General
More informationTechnical Notes 43G - Brick Passive Solar Heating Systems - Part 7 - Details and Construction [Mar./Apr. 1981] (Reissued Sept.
Technical Notes 43G - Brick Passive Solar Heating Systems - Part 7 - Details and Construction [Mar./Apr. 1981] (Reissued Sept. 1986) Abstract: Details and construction of brick masonry for passive solar
More informationCITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA
CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248-3594 www.danapoint.org B005 COM STRUCT 2016 CALIFORNIA CODES CODE CYCLE 01/01/2017
More informationCompliance Certificate
REScheck Software Version 4.6.4 Compliance Certificate Project RESIDENCE Energy Code: 2009 IECC Location: Perkasie, Pennsylvania Construction Type: Single-family Project Type: New Construction Conditioned
More informationBuilding Design Data
Building Design Data.. 1. Building Design The KORE ICF System is designed to meet the requirements of the Building Regulations 1997-2006, in the case of two storeys, single occupancy dwellings. If the
More informationACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE
ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,
More informationCITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application
CITY OF CAMDENTON OFFICE OF THE BUILDING OFFICIAL Commercial Building & Architectural Review Permit Application DATE: / / PERMIT # REQUEST FOR: NEW BUILDING ADDITION REMODEL PLUMBING ONLY ELECTRIC ONLY
More information