DURRELL DESIGN GROUP, PLLC ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI.
|
|
- Clarence Lawson
- 6 years ago
- Views:
Transcription
1 DURRELL DESIGN GROUP, PLLC 500-G E. WOODROW WILSON AVENUE JACKSON, MISSISSIPPI PHONE: FAX: ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI May 24, 2017 TITLE SHEET 1 ADDENDUM 1 ATTACHMENTS 4 TOTAL NUMBER OF PAGES 6 Addendum No. 2 Roof Replacement Barr Elementary School DDG Project No.:
2 THIS ADDENDUM, WHICH CONTAINS REVISIONS TO THE WORK CONTAINED IN THE ORIGINAL DRAWINGS AND SPECIFICATIONS DATED MARCH 20, 2017 SHALL BECOME A PART OF SUCH DRAWINGS AND SPECIFICATIONS AS IF BOUND THEREIN, OTHER REQUIREMENTS OF DRAWINGS AND SPECIFICATIONS RELATING TO ITEMS INVOLVED SHALL REMAIN AS SPECIFIED. THE ABOVE NAMED CONTRACT DOCUMENTS ARE HEREBY MODIFIED, CORRECTED AND/OR SUPPLEMENTED BY THIS ADDENDUM AS FOLLOWS: FOR INFORMATION ONLY 1. The Pre-Bid Meeting Minutes from the meeting on May 09, 2017 is attached with sign-in sheet. 2. The Bid Opening is at 10AM on May 26, 2017 at the Business Office of the Jackson Public School District PERTAINING TO THE SPECIFICATIONS: Item 1: SECTION TABLE OF CONTENTS ADD SECTION Masonry Assembly Tuckpointing Item 2: SECTION MEMBRANE ROOFING SYSTEMS 1. Part Referenced Standards. ADD item I that reads ASTM D 2523 Standard Practice for Testing Load-Strain Properties of Roof Membrane 2. Part Performance Requirements. Paragraph E. DELETE the paragraph in its entirety and Replace with the following: E. Roof Membrane Design: Provide ASTM Tensile Strength in Machine Direction of a minimum average value of 350 lbf/in. 3. Part Quality Assurance, Test Reports. ADD subitem 3 that reads ASTM D 2523 test. Item 3: SECTION ADD attached SECTION Masonry Assembly Tuckpointing in its entirety END OF ADDENDUM ITEMS Addendum No. 2 Roof Replacement Barr Elementary School DDG Project No.:
3 SECTION MASONRY ASSEMBLY - TUCKPOINTING PART 1 - GENERAL 1.1 SUMMARY A. Section includes maintenance and installation of existing unit masonry on roof section E low to high wall condition. 1.2 REFERENCED STANDARDS A. ACI 530/530.1/ERTA - Building Code Requirements and Specification for Masonry Structures; American Concrete Institute International; B. ACI 530.1/ASCE 6/TMS Specification For Masonry Structures; American Concrete Institute International; C. ASTM C 62 - Standard Specification for Building Brick (Solid Masonry Units Made From Clay or Shale); D. ASTM C Standard Specification for Mortar for Unit Masonry; 2008a. E. ASTM C404 - Standard Specification for Aggregates for Masonry Grout; ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2 - PRODUCTS 2.1 MORTAR MATERIALS A. Portland Cement: ASTM C 150, Type I or Type II, white or gray or both where required for color matching of exposed mortar. B. Hydrated Lime: ASTM C 207, Type S. C. Mortar Sand: ASTM C 144 unless otherwise indicated. 1. Color: Provide natural sand or ground marble, granite, or other sound stone of color necessary to produce required mortar color. 2. Match size, texture, and gradation of existing mortar sand as closely as possible. Blend several sands if necessary to achieve suitable match. D. Water: Potable. DDG Project No MASONRY ASSEMBLY - TUCKPOINTING
4 2.2 BRICK UNITS A. All existing brick units to be salvaged where removed to be reinstalled. In the event brick is broken and can t be installed, Contractor to match existing color and type. 1. Facing Brick: ASTM c216, Type FBS, Grade SW 2.3 FLASHINGS A. Rubberized Asphalt Flashing: Self-adhering composite material comprising rubberized asphalt adhesive compound bonded to cross-laminated polyethylene film, minimum inch total thickness. Provide Textroflash manufactured by Hohmann & Barnhard, Inc. B. Galvanized Steel Flashing: ASTM A653/A653M, with G90/Z275 coating, 24 gage total thickness. PART 3 - EXECUTION 3.02 PREPARATION A. Direct and coordinate placement of metal anchors supplied for installation under other sections. B. Provide temporary bracing during installation of masonry work. Maintain in place until building structure provides permanent bracing. C. Brick and mortar shall be covered from rain and weather and stored off ground on pallets. D. Sand shall be clean and stored in debris free area. E. Package tag shall be on each pallet COURSING A. Establish lines, levels, and coursing indicated. Protect from displacement. B. Maintain masonry courses to uniform dimension. Form vertical and horizontal joints of uniform thickness. C. Brick Units: 1. Bond: Running to match existing. 2. Coursing: Three units and three mortar joints to equal 8 inches. 3. Mortar Joints: Match existing PLACING AND BONDING A. Lay solid masonry units in full bed of mortar, with full head joints, uniformly jointed with other work. B. Lay hollow masonry units with face shell bedding on head and bed joints. C. Buttering corners of joints or excessive furrowing of mortar joints is not permitted. D. Remove excess mortar and mortar smears as work progresses. DDG Project No MASONRY ASSEMBLY - TUCKPOINTING
5 E. Remove excess mortar with water repellent admixture promptly. Do not use acids, sandblasting or high pressure cleaning methods. F. Interlock intersections and external corners. G. Do not shift or tap masonry units after mortar has achieved initial set. Where adjustment must be made, remove mortar and replace. H. Perform job site cutting of masonry units with proper tools to provide straight, clean, unchipped edges. Prevent broken masonry unit corners or edges MASONRY FLASHINGS A. Whether or not specifically indicated, install masonry flashing to divert water to exterior at all locations where downward flow of water will be interrupted. 1. Extend flashings full width at such interruptions and at least 4 inches into adjacent masonry or turn up at least 4 inches to form watertight pan at non-masonry construction. 2. Extend flashings into existing window sills 2 inches past jambs and seal around flashing and window for watertight condition 3. Remove or cover protrusions or sharp edges that could puncture flashings. 4. Seal lapped ends and penetrations of flashing before covering with mortar. B. Extend flashings to within 1/4 inch of exterior face of masonry. C. Lap end joints of flashings at least 4 inches and seal watertight with mastic or elastic sealant. D. Caulk the top of all masonry flashing termination bars with manufacturers recommended sealant REPOINTING MASONRY A. Rake out and repoint joints to the following extent: 1. All joints in areas indicated. 2. Joints where mortar is missing or where they contain holes. 3. Cracked joints where cracks are 1/16 inch or more in width and of any depth. 4. Joints where they are deteriorated to point that mortar can be easily removed by hand, without tools. B. Pointing with Mortar: 1. Rinse joint surfaces with water to remove dust and mortar particles. Time rinsing application so, at time of pointing, joint surfaces are damp but free of standing water. If rinse water dries, dampen joint surfaces before pointing. 2. Apply pointing mortar first to areas where existing mortar was removed to depths greater than surrounding areas. Apply in layers not greater than 3/8 inch until a DDG Project No MASONRY ASSEMBLY - TUCKPOINTING
6 uniform depth is formed. Fully compact each layer thoroughly and allow it to become thumbprint hard before applying next layer. 3. After low areas have been filled to same depth as remaining joints, point all joints by placing mortar in layers not greater than 3/8 inch. Fully compact each layer and allow to become thumbprint hard before applying next layer. Where existing masonry units have worn or rounded edges, slightly recess finished mortar surface below face of masonry to avoid widened joint faces. Take care not to spread mortar beyond joint edges onto exposed masonry surfaces or to featheredge the mortar. 4. When mortar is thumbprint hard, tool joints to match original appearance of joints as demonstrated in approved mockup. Remove excess mortar from edge of joint by brushing. 5. Cure mortar by maintaining in thoroughly damp condition for at least 72 consecutive hours including weekends and holidays FINAL CLEANING C. After mortar has fully hardened, thoroughly clean exposed masonry surfaces of excess mortar and foreign matter; use wood scrapers, stiff-nylon or -fiber brushes, and clean water, spray applied at low pressure. END OF SECTION DDG Project No MASONRY ASSEMBLY - TUCKPOINTING
1. Repairing brick masonry, including replacing damaged units as indicated on drawings. 2. Repointing mortar joints.
SECTION 040120 BRICK MASONRY REPAIR AND REPOINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION BRICK MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Face brick. 2. Mortar and grout. 3. Ties and anchors. 4. Miscellaneous masonry accessories. 1.2 SUBMITTALS A. Product Data: For each type
More informationSECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING
SECTION 04210 INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING PART I GENERAL 1.1 SUMMARY A. Provide installation of new or replacement of masonry units and/or repointing of masonry units
More informationB. Samples: Submit, for verification purposes, samples of the following:
SECTION 04500 - MASONRY RESTORATION AND CLEANING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings, photos and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationSECTION UNIT MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Concrete masonry units. 2. Decorative masonry units. 3. Mortar and grout. 4. Steel reinforcing bars. 5. Masonry joint reinforcement. 6. Ties and anchors.
More informationSECTION GLASS UNIT MASONRY ASSEMBLIES
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor, equipment and incidentals required to install glass unit masonry as shown on the contract drawings and
More informationMaintenance of Unit Masonry
University of New Hampshire University of New Hampshire Scholars' Repository Division 04 Masonry Chapter 5 Technical Construction and Renovation Standards 1-25-2013 040120 - Maintenance of Unit Masonry
More informationSECTION UNIT MASONRY
PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete Block. B. Architectural Concrete Block. C. Clay Facing Brick. D. Mortar and Grout. E. Reinforcement and Anchorage. F. Flashings. G. Accessories. 1.02 ADMINISTRATIVE
More informationSECTION UNIT PAVERS
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Concrete pavers. 2. Detectable warning pavers. 3. Warning stripe pavers. 1.2 SUBMITTALS A. Product Data: For the following: 1. Pavers.
More informationA. Section includes historic treatment work consisting of rep ointing brick masonry as follows:
SECTION 040323 - HISTORJC BRlCK UNIT MASONRY REPOINTING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION UNIT MASONRY
SECTION 04200 UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section.
More informationSECTION UNIT MASONRY SYSTEM
SECTION 04320 UNIT MASONRY SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete masonry and face brick units. B. Reinforcement, anchorage, and accessories. 1.03 SUBMITTALS A. Submit product data under
More informationSECTION STONE FLOORING
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 09 63 40 STONE FLOORING SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph not applicable in the section and
More informationSUNY GENESEO RED JACKET DINING HALL RENOVATION THIN BRICK MASONRY
SUNY GENESEO 042113.13-1 SECTION 042113.13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationDIVISION 4 MASONRY DIVISION 4 - MASONRY
DIVISION 4 MASONRY DIVISION 4 - MASONRY 85 SECTION 04000 - MASONRY 04000 - MASONRY PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION MORTAR
PART l - SCOPE SECTION 04100 - MORTAR A. This Section includes all labor, materials, equipment, and related items required for the work of mortar as shown on the Drawings and specified herein. The work
More informationSECTION ARCHITECTURAL CONCRETE UNIT MASONRY
SECTION 04 2223 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Split-face concrete unit masonry, burnished concrete unit masonry, and polished concrete unit masonry. 2. Split-face concrete unit masonry.
More informationConditions of the Contract and Division 1 General Requirements are a part of this section.
NOTES TO SPECIFIER General notes about the specifications and the reasons for them are listed here in general statements. Use this as a guide when choosing the correct selection of statements that apply
More informationParagraph Description Page No General Materials Concrete Masonry Work Altitude Valve Vault Cover 25-4
City of Columbia Engineering Regulations PART 25: SPECIFICATIONS FOR ALTITUDE VALVE VAULT Table of Contents Paragraph Description Page No. 25.1 General 25-1 25.2 Materials 25-1 25.3 Concrete Masonry Work
More informationPROGRAM COMMENT FOR DEPARTMENT OF DEFENSE REHABILITATION TREATMENT MEASURES
PROGRAM COMMENT FOR DEPARTMENT OF DEFENSE REHABILITATION TREATMENT MEASURES APPENDIX 1 SECTION 04100.01 REMOVAL OF MORTAR JOINTS AND REPOINTING PART 1 GENERAL 1.01 DESCRIPTION A. This specification provides
More informationSECTION FLUID-APPLIED WATERPROOFING
SECTION 07140 FLUID-APPLIED WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied rubberized asphalt and/or elastomeric membrane waterproofing; and surface dusting and/or protective
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT SPECIFICATION EO-1007 REVISION 13 DECEMBER 2013 EFFECTIVE DATE DECEMBER 16,
More informationProduct Guide Specification
Product Guide Specification SECTION 04850 (04 40 00) NATURAL THIN VENEER STONE PART 1 GENERAL 1.1 SECTION INCLUDES Specifier Notes: Edit the following as required. A. Natural thin veneer stone for [exterior]
More informationSECTION SPLIT FACE CONCRETE MASONRY UNITS
SECTION 04223 SPLIT FACE CONCRETE MASONRY UNITS ***** E. Dillon & Company manufactures the following high quality, custom produced, architectural concrete masonry units (CMU) using superior colored aggregates
More informationBRICKWORK 3.5 BRICKWORK 1 GENERAL
BRICKWORK 1 GENERAL 1.1 INSPECTION Notice Give sufficient notice so that inspection may be made of the following: - Set out of brickwork to lintels, arches and other architectural features. - Damp-proof
More informationSECTION UNIT MASONRY
PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete Masonry Units. B. Mortar and Grout. C. Accessories. 1.02 RELATED REQUIREMENTS 1.03 REFERENCE STANDARDS SECTION 042000 UNIT MASONRY A. Unless otherwise noted
More informationSPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
More informationSECTION Vitrified Clay Wall Coping 2014
SECTION 04220 2014 PART 1 GENERAL 1.1 DESCRIPTION A. SCOPE OF WORK 1. Provide new coping as indicated on Drawings. B. RELATED SECTIONS 1. Section 02050: Selective Demolition. 2. Section 07650: Metal Flashing.
More informationDIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories
04 00 00 MASONRY 04 01 00 Maintenance of Masonry 04 01 20 Maintenance of Masonry 04 05 13 Masonry Mortaring 04 05 23 Masonry Accessories 04 20 00 UNIT MASONRY 04 21 00 Clay Unit and Brick Veneer 04 22
More information2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:
SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance
More informationREINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION SELF-ADHERING SHEET FLASHING
MANUFACTURER S GUIDE SPECIFICATIONS SECTION 076526 SELF-ADHERING SHEET FLASHING 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 604129 03.24.15 Carlisle, Flexphalt, Sure-Seal and CAV-GRIP
More informationSpec Master 5/7/ For each product requiring color and texture selection, provide full size samples.
SECTION 04812 (042012) MECHANICALLY ATTACHED BRICK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationCUT LIMESTONE - ANCHORED
SECTION 04851 CUT LIMESTONE - ANCHORED This guide specification has been prepared by TexaStone Quarries LLC to assist design professionals in the preparation of a specification section covering cut limestone,
More informationPART 1 GENERAL MANUFACTURED STONE MASONRY
SECTION 04 73 00 (04730) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Simulated Stone B. Products installed, but not furnished, under this Section include the following: 1. Steel Lintel and Shelf
More informationTechnical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION
Technical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION This Technical Notes contains the guide specifications in CSI format for Part III
More informationPROJECT NAME: PROJECT ADDRESS: Farmers Market Structural Repairs 4-6 Gordon Street Guelph, Ontario DATE: November, 2010 I N D E X Page(s) Index... 1 to 1 Introduction... 1 to 1 DIVISION 04 - MASONRY Section
More informationStudent Services & Classroom Addition
SECTION 093000 - TILING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION LIMESTONE PAVING
(Specifier Notes: The purpose of this guide specification is to assist the specifier in correctly specifying limestone paving and its installation. The specifier needs to edit this guide specification
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-04 23 00 (November 2009) ----------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MORTAR AND MASONRY GROUT
SECTION 04110 MORTAR AND MASONRY GROUT PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. In the absence of other information, the methods and recommendations of the National Concrete Masonry Association
More information1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:
SECTION 04220 CONCRETE UNIT MASONRY PART 1 - GENERAL 1.01 SCOPE: A. The CONTRACTOR shall furnish all labor, materials and equipment necessary for the masonry construction as shown on the drawings or as
More informationEditing notes to assist users are separated from specification text by rows of asterisks. Delete these notes prior to final printing.
SECTION 09635 LIMESTONE FLOORING This guide specification has been prepared by TexaStone Quarries LLC to assist design professionals in the preparation of a specification section covering cut limestone
More informationSECTION MODIFIED BITUMINOUS SHEET WATERPROOFING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 13 52 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph
More informationREFLECTIVE FACE CONCRETE MASONRY UNITS
SECTION 04221 REFLECTIVE FACE CONCRETE MASONRY UNITS ***** E. Dillon & Company manufactures the following high quality, custom produced, architectural concrete masonry units (CMU) using superior colored
More informationSECTION SANDSTONE RESTORATION
SECTION 04 01 40.91 - SANDSTONE RESTORATION Part 1 GENERAL 1.1 SUMMARY OF WORK A. For repairing and patching of sandstone. B. Related Sections 1. Section 01351 Special Procedures for Historic Treatment
More informationA. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:
04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY) SPECIFIER: Use this section only for UNREINFORCED concrete masonry. Its only reinforcement is in the horizontal joints. It covers ONLY plain blockwork (no
More informationCONSULT COLDSPRING FOR ASSISTANCE IN EDITING THIS SPECIFICATION GUIDE FOR SPECIFIC APPLICATIONS.
SECTION NUMBERS AND TITLES IN THIS SPECIFICATION UTILIZE MASTERFORMAT 2004. THIS SPECIFICATION GUIDE IS WRITTEN ACCORDING TO THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) THREE-PART SECTION FORMAT (1998)
More informationSECTION PORTLAND CEMENT PLASTERING
SECTION 09 2400 PORTLAND CEMENT PLASTERING This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as hidden text, and can be
More informationThin Architectural Splitface Block Veneer Specification Guide
Thin Architectural Splitface Veneer System with AccuTab Technology R Thin Architectural Splitface Block Veneer Specification Guide Section 04711: Manufactured Concrete Veneer Use this specification guide
More informationTILE TILE
09300 - TILE 09300-1 PART ONE: GENERAL 1.1 Description TILE 1.1.1 Work of this Section, as shown or specified, shall be provided by the Interior Contractor and shall be in accordance with the requirements
More informationCONSULT COLDSPRING FOR ASSISTANCE IN EDITING THIS SPECIFICATION GUIDE FOR SPECIFIC APPLICATIONS.
SECTION NUMBERS AND TITLES IN THIS SPECIFICATION UTILIZE MASTERFORMAT 2004. THIS SPECIFICATION GUIDE IS WRITTEN ACCORDING TO THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) THREE-PART SECTION FORMAT (1998)
More informationB. Related Sections include: 1. Division 2, Section , Miscellaneous Cast-in-Place Concrete 2. Division 9, Section , Stone Paving
SECTION 04 43 00 - STONE VENEER WALLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following applications: 1. Stone Veneer on Cast-in-Place Concrete retaining walls, 2. Stone Veneer on CMU
More informationA. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.
Product Specification for: Rapid Set DOT Repair Mix SECTION 03 01 30 MAINTENANCE OF CAST-IN-PLACE CONCRETE SECTION 03 01 40 MAINTENANCE OF PRECAST CONCRETE SECTION 03 01 50 MAINTENANCE OF CAST DECKS AND
More informationA. The work of this section includes, but is not limited to, the following:
SECTION 07 14 00 FLUID APPLIED WATERPROOFING SYSTEM PART 1: GENERAL 1.1 RELATED DOCUMENTS A. All of the Contract Documents, including General and Supplementary Conditions and Division 01 General Requirements,
More informationSection Pre-Applied Sheet Membrane Waterproofing
Section 071324 Pre-Applied Sheet Membrane Waterproofing PART 1 GENERAL 1.01 SUMMARY A. The Work of this Section includes, but is not limited to, pre-applied sheet membrane waterproofing that forms an integral
More informationSECTION EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE. A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels.
SECTION 03460 EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels. B. Shop/Plant Cast CMU/Split Face
More informationDesign and Construction Standards SECTION REINFORCED UNIT MASONRY
SECTION 04810 REINFORCED UNIT MASONRY PART 1 GENERAL 1.1 SECTION INCLUDES: A. Concrete masonry or brick units B. Reinforcement, anchorage, and accessories C. Parged masonry surfaces 1.2 REFERENCES A. ACI
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-04 21 26 (November 2009) ----------------------------- Preparing Activity: USACE Superseding UFGS-04 21 26 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationSTONE PAVING
SECTION 321440 - STONE PAVING 1.1 GENERAL 1.2 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationMANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION
STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's
More informationMANUFACTURERS (SHORT FORM) SPECIFICATION / SECTION
STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURERS (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's
More informationSECTION UNIT MASONRY ASSEMBLIES
SECTION 04810 UNIT MASONRY ASSEMBLIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Concrete Block. 2. Clay Facing Brick. 3. Reinforcement and Anchorage. 4. Flashings. 5. Accessories. B. Related
More informationSECTION CAST STONE MASONRY
SECTION 047200 - CAST STONE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION BRICK FLOORING
SECTION 09 63 13 BRICK FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Brick flooring
More informationMaster Specifications for Microcotta November 2017
SECTION 042130 - MICROCOTTA PART 1 - GENERAL 1.1 SUMMARY A. Provide Architectural Microcotta, cast architectural polymer resin units manufactured in accordance with the Contract Documents. 1.2 WORK INCLUDED
More informationITEM 458 WATERPROOFING FOR STRUCTURES
ITEM 458 WATERPROOFING FOR STRUCTURES 458.1. Description. This Item shall govern for the furnishing and placing of waterproofing on concrete and steel bridge decks of railroad structures and on other structures
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 04810 - UNIT MASONRY ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply to this Section.
More informationNEBRASKA ARMY NATIONAL GUARD 1776 ARMORY ROOF REPLACEMENT
MILITARY DEPARTMENT STATE of NEBRASKA LINCOLN, NEBRASKA 09 February 2018 NEBRASKA ARMY NATIONAL GUARD 1776 ARMORY ROOF REPLACEMENT at The Armory 1776 North 10th Street Lincoln, NE 68508 PROJECT NO. 31030180
More informationMANUFACTURER'S SPECIFICATIONS Section ST. ASTIER LIME PLASTER (NHL) PLASTER ON CONCRETE
MANUFACTURER'S SPECIFICATIONS Section 09225 ST. ASTIER LIME PLASTER (NHL) PLASTER ON CONCRETE ST. ASTIER NATURAL HYDRAULIC LIME PLASTER PART 1 GENERAL 1.1 Summary A. This Section includes St. Astier Natural
More informationINSULATED CONCRETE MASONRY UNITS Section 04220
INSULATED CONCRETE MASONRY UNITS Section 04220 PART 1 GENERAL 1.01 Summary A. Section Includes 1. Insulated masonry wall units (CMU's) 2. Decorative insulated masonry wall units 1.02 SUBMITTALS A. Samples:
More informationDIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.
DIVISION 04 MASONRY 04720 CAST STONE A. Design Considerations 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone. 2. Care must be taken in the design of individual units
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR ANCHORED MASONRY VENEER SYSTEM WITH POLYSTYRENE FOAM PLASTIC BACKING EC 021-2014 (Adopted
More informationGUIDE SPEC SECTION Injection Grout (IG10)
Part 1 GENERAL MASONRY UNIT RESTORATION 1.1 SUMMARY OF WORK A. For repairing, patching, injecting cracks and re-attaching stone fragments to original substrate. B. Related Sections 1. Section 01351 Special
More informationDIVISION 9 - FINISHES Section Protective Coatings
Spec Component: SC-202-03/10 SikaTop Seal 107 DIVISION 9 - FINISHES Section 09880 - Protective Coatings Part 1 - General 1.01 Summary A. This specification describes the coating of substrates with a non-vapor
More informationSECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof
SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812
More informationSECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS
SECTION 03 05 00 COMMON WORK RESULTS FOR CONCRETE 09 97 00 SSPECIALTY COATINGS Weld Crete ************************************************************************************************************************
More informationSECTION DRY-PLACED GRANITE
SECTION 04 41 11 DRY-PLACED GRANITE This guide specification utilizes recommendations and formats contained in references of the Construction Specifications Institute (CSI), including the CSI Practice
More informationConstruction Specification for Utility Adjustments
Engineering & Construction Services Division Standard Specifications for Road Works TS 4.50 September 2017 for Utility Adjustments Table of Contents TS 4.50.01 SCOPE... 2 TS 4.50.02 REFERENCES... 2 TS
More informationCommercial Flashing Details
This technical note illustrates many of the most common flashing details for commercial buildings. The purpose for flashing is to direct moisture to the exterior and in so doing, prevent moisture from
More informationSPECIFICATIONS MODERRA MORTARLESS MASONRY VENEER
SPECIFICATIONS MODERRA MORTARLESS MASONRY VENEER PART 1: GENERAL 1.01 Section Includes A. Product description and definitions. B. Constructing base ledge for concrete wall units. C. Installing modular
More informationSECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING
P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationReCote Finish System over Concrete
Part 1 General 1.01 GENERAL A. The Master Wall ReCote Finish System for smooth precast and cast in place concrete consists of an acrylic primer and ReCote acrylic finish. When needed an acrylic modified
More informationSECTION CAST-IN-PLACE CONCRETE
SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing
More informationSECTION CONCRETE PAVING
SECTION 32 13 13 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for providing portland cement concrete work and all other incidental concrete improvements for the project
More informationColphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate
Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,
More informationMadewell Products Corporation December Industrial Court Alpharetta, GA Office: (770) Fax: (770)
Madewell Products Corporation December 2014 7561 Industrial Court Alpharetta, GA 30004 Office: (770) 475-8199 Fax: (770) 475-8167 Product Guide Specification SECTION 03935 RESTORATION MORTAR AND EPOXY
More informationA. Section includes fluid applied, vapor permeable membrane air barriers.
Master Construction Specifications Insert Project Name SECTION 072726 FLUID APPLIED MEMBRANE AIR BARRIERS PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied, vapor permeable membrane air barriers.
More information6. Cavity wall mortar retainer ("mortar net") behind brickwork at flashing locations within exterior masonry wall construction.
SECTION 042000 - UNIT MASONRY PART 1- GENERAL 1.1 SUMMARY A. Section Includes: 1. Concrete block construction. 2. Face brick construction. 3. Cast stone bands and shapes built into exterior masonry construction.
More informationSECTION GROUND FACE CONCRETE MASONRY UNITS
SECTION 04222 GROUND FACE CONCRETE MASONRY UNITS ***** E. Dillon & Company manufactures the following high quality, custom produced, architectural concrete masonry units (CMU) using superior colored aggregates
More informationA. JANDRIS & SONS Guide Specifications in CSI Format SECTION CONCRETE UNIT MASONRY
SECTION 042200 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Work Included: Provide labor, materials and equipment necessary to complete the work of this Section, including but not limited to the following:
More informationCopyright 2013 AIA MasterSpec Premium 12/13
SECTION 042000 - UNIT MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION BRICKWORK PART I GENERAL
SECTION 04210 BRICKWORK PART I GENERAL 101 Scope General: supply and build the brickwork shown on the drawings or needed to complete the brickwork, including but not limited to the following: Provide all
More informationSPECIFICATION GUIDELINE
Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section
More informationDivision 04 Masonry Section New Westminster Multi-Use Civic Facility & Office Building Project No Page 1
Project No. 210022 Page 1 1 GENERAL 1.1 REQUIREMENTS INCLUDED.1 Furnish all labour, material, services and equipment necessary for the supply, delivery and erection of brick veneer as indicated on the
More informationArchitectural Wall Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is
More informationStudent Services & Classroom Addition
SECTION 071326 - SELF-ADHERING SHEET WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION Tile Roof Guideline. B. "Pan" Tile: Clay tile on the underlayment, convex in shape.
SECTION 07 32 13 Tile Roof Guideline PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The drawings and general provisions of the contract, including General and Specific Conditions, and Division 1 (General Requirements)
More information