Industrial Pretreatment Program Grease Abatement Requirements for Food Service Establishments (FSEs)
|
|
- Aubrey Hampton
- 6 years ago
- Views:
Transcription
1 Public Works Department Environmental Division Industrial Pretreatment Program Meridian City Hall, Suite E Broadway Avenue Meridian, Idaho Industrial Pretreatment Program Grease Abatement Requirements for Food Service Establishments (FSEs) Pretreatment staff conduct reviews of all FSE plan submittals to ensure that minimum pretreatment measures are included, assuring compliance with City Code requirements. Grease interceptors are required to be sized according to the latest Uniform Plumbing Code (adopted by the City of Meridian) at the time of plan check and approval. Refer to Chapter 10 of the UPC. City Minimum Standard for Size, Type and Installation of Grease Interceptors Each food service establishment is required to install an approved 1500-gallon, double chamber, in-ground grease interceptor. The grease interceptor should be located outside the building in a location accessible to a licensed grease pumper and hauling service provider. To decrease internal vault decomposition, application of a protective coating is recommended. Tee connections with open pipe tops are required for the primary and secondary chamber outlets to allow visual inspection of influent and effluent (discharged wastewater) by City of Meridian inspectors. The lower tee connection pipe must be installed12-14 inches from the tank bottom. Install the center baffle crossover tee pipe as recommended by the grease interceptor manufacturer. Chamber lids must prevent odors and have a built-in handle or notched side to insert a tool for easy lid removal. Temporary sealant type material is only allowed in lid holes to eliminate odors. Bolts to secure lids in place are not recommended. Each food service establishment for which a grease interceptor is required shall have an interceptor serving only that establishment, unless otherwise approved by the Wastewater Superintendent or designee. Installation of a sample station port is optional. Passive grease traps are not allowed. Public Works Department Environmental Division 33 E. Broadway Avenue, Meridian, ID Phone Fax
2 Page 2 Requesting an Exemption to City Minimum Standard for Grease Abatement Equipment and Application Requirements To request an application for exemption to the city minimum standard of an approved 1500-gallon, double chamber, in-ground grease interceptor, please contact the Pretreatment Manager in the Environmental Division at Meridian City Hall 33 E. Broadway, Second Floor, Suite 204. You may also call (208) or smaneck@meridiancity.org. Completed application checklists should be submitted to the Pretreatment Manager. Applicants will be notified within ten (10) business days upon receipt of the application regarding approval status. Exemptions: A. Automatic Grease Interceptor Unit (AGI): An appropriately sized grease collection unit may be installed at the cleanup sink wastewater discharge drain in lieu of an in-ground interceptor. The business owner must establish comparable best management practices, (Ord , ). Passive grease traps are not allowed in new tenant improvement and new building construction. B. Multi-food Service Establishment Shared Interceptor: This approved exemption requires each property owner and/or property management company for which a grease interceptor is required to enter into a permit with the City of Meridian establishing comparable best management practices. (Ord , ) C. Grease Abatement Exclusion Letter (GAEL): When approved, this exemption allows the food service establishment to operate without grease abatement equipment. The business owner must enter into a written agreement with the City of Meridian establishing comparable best management practices. (Ord , ). The GAEL is contingent upon maintaining a consistent level of compliance by utilizing best management practices and zero grease discharge. The facility is subject to unannounced inspections including sewer collection system video surveillance. When a city inspector observes grease, an immediate abatement will be required at the owner s expense. A passive grease trap is not allowed to be installed.
3 Page 3 Typical Example of In Ground Grease Interceptor
4 Page 4 Oil and Flammable Liquids Interceptor As required by the Uniform Plumbing Code : All repair garages and gasoline stations with grease racks or grease pits, and all factories that have oily, flammable, or both types of waste as a result of manufacturing, storage, maintenance, repair, or testing processes, shall be provided with an oil or flammable liquid interceptor that shall be connected to all necessary floor drains. Typical Example of Flammable Liquids Interceptor
5 Page 5 Discharge Requirements for Elevator Pit Drain and Sump Pump On December 7, 2010 the State of Idaho, Division of Building Safety issued a policy statement that the sump pump (or drain) required in elevator pits by ASME A17.1 Section will now be considered optional rather than mandatory. In the case of hydraulic elevators, if a sump pump is installed, the City of Meridian requires the drain and pump combination be connected to an oil/water separator prior to discharge to the city s sanitary sewer system. It is recommended a professional engineering analysis of the elevator s liquid hydraulic and fire suppression evacuation requirements be conducted, in order to specify an adequately-sized sump pump and interceptor system to retain and prevent oils from entertaining the sanitary sewer system.
Information and Instructions for Obtaining a. Fats, Oils, and Grease Wastewater Discharge Permit
Information and Instructions for Obtaining a Fats, Oils, and Grease Wastewater Discharge Permit THIS PERMIT APPLICATION PACKET CONTAINS INFORMATION ON: I. Fats, Oils, and Grease (FOG) Wastewater Discharge
More informationHARNETT COUNTY NC OIL & GREASE CONTROL ORDINANCE
HARNETT COUNTY NC OIL & GREASE CONTROL ORDINANCE In an effort to curb sanitary sewer overflows (SSO s) from grease accumulation in its sanitary sewer mains, the Harnett County Board of Commissioners adopted,
More informationSECTION SANITARY WASTE INTERCEPTORS
SECTION 22 13 23 SANITARY WASTE INTERCEPTORS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationCommonwealth of Massachusetts Title 5 Official Inspection Form Subsurface Sewage Disposal System Form - Not for Voluntary Assessments
Inspection results must be submitted on this form. Inspection forms may not be altered in any way. Important: When filling out forms on the computer, use only the tab key to move your cursor - do not use
More informationChapter 102 SEWERS AND SEWAGE DISPOSAL
Chapter 102 SEWERS AND SEWAGE DISPOSAL [HISTORY: Adopted by the Board of Commissioners of the Town of Thurmont 4-6-1966. Readopted as revised 1-8-1986 by Res. No. 85-6.Readopted as revised 2005 by Res.
More information6.1 Introduction to Wastewater Issues
Section 6: Water Pollution This Section will help you: Understand if you generate industrial wastewater; Understand where your wastewater goes; Make sure you meet requirements for floor drains; Properly
More informationVillage of Arlington Heights. Sewer Back-up Rebate Program
Village of Arlington Heights Sewer Back-up Rebate Program (Including Enhanced Program Information) Updated: October 1, 2017 Village of Arlington Heights Building & Life Safety Department 33 S. Arlington
More information2007 WSSC PLUMBING AND FUEL GAS CODE AMENDMENT #2 OUTLINE OF CODE CHANGES
2007 WSSC PLUMBING AND FUEL GAS CODE AMENDMENT #2 ADOPTING NEW FATS, OILS, AND GREASE REQUIREMENTS EFFECTIVE DATE: NOVEMBER 1, 2008 AMENDMENT #2 OUTLINE OF CODE CHANGES Changed Section Reference to the
More informationExisting System Evaluation Report for Onsite Wastewater Systems
Existing System Evaluation Report for Onsite Wastewater Systems State of Oregon Department of Environmental Quality Onsite Program 165 East 7 th Avenue, Suite 100 Eugene, Oregon 97401 For more information,
More informationFood Service Establishment Permit Application
Pinellas County Department of Environment and Infrastructure Water & Sewer Division, Grease Management Program Food Service Establishment Permit Application SECTION A: INTRODUCTION Pinellas County s Grease
More informationResidential Sewer Backup Prevention Program
City of Wheaton Residential Sewer Backup Prevention Program Please Note: The City reserves the right to modify the policies, procedures and rules of this program or discontinue the program in its entirety
More informationBALTIMORE COUNTY MARYLAND FATS, OILS, AND GREASE (FOG) CONTROL PROGRAM MANUAL
BALTIMORE COUNTY MARYLAND FATS, OILS, AND GREASE (FOG) CONTROL PROGRAM MANUAL 105 W Chesapeake Avenue, Suite 400 Towson, Maryland 21204 Section 1 Introduction Baltimore County (the County) is responsible
More informationTHIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE.
(f) The minimum requirements for construction, materials and foundations of grease traps shall be the same as those required for septic tanks, as prescribed in N.J.A.C. 7:9A-8.2. (g) The inlet and outlet
More informationDEPARTMENT OF CODE ENFORCEMENT CITY OF NIAGARA FALLS, NEW YORK FEE SCHEDULE
DEPARTMENT OF CODE ENFORCEMENT CITY OF NIAGARA FALLS, NEW YORK 1/1/15 FEE SCHEDULE No permit shall be issued by the Director of Code Enforcement until fees hereinafter prescribed have been paid to the
More informationGrease Interceptors. Design & Operation. Material & Characteristics
Grease Interceptors Dormont offers a full line of grease interceptors for installation on cooking/prep sinks, pot, pan & scullery sinks and dishwasher applications. Dormont offers a variety of interceptor
More informationFigure 1. Report of Inspection Process Flowchart.
INSTRUCTIONS FOR A REPORT OF INSPECTION FOR AN ON-SITE WASTEWATER TREATMENT FACILITY INSTRUCTIONS Within six months before the date of a property transfer, the person who is transferring a property served
More informationINSTALLING A SEPTIC SYSTEM IN LIVINGSTON COUNTY LIVINGSTON COUNTY PUBLIC HEALTH DEPARTMENT 310 TORRANCE AVENUE PONTIAC, IL /
INSTALLING A SEPTIC SYSTEM IN LIVINGSTON COUNTY LIVINGSTON COUNTY PUBLIC HEALTH DEPARTMENT 310 TORRANCE AVENUE PONTIAC, IL 61764 815/844-7174 MALINDA HILLMAN, ADMINISTRATOR DONNIE SIMMONS, L.E.H.P. DIRECTOR
More informationFirst things first.. A Brief Overview of the PTI Program. Why offer training? PTI Survey Results. Today s Main Topics:
The Ohio EPA Division of Surface Water Presents: First things first.. Can I have your attention??? What You Need to Know About a Permit to Install (PTI) Application A Brief Overview of the PTI Program
More informationREQUEST FOR DEVIATION WATER AND WASTEWATER SYSTEM STANDARD SPECIFICATIONS
REQUEST FOR DEVIATION WATER AND WASTEWATER SYSTEM STANDARD SPECIFICATIONS PRODUCT NAME: PRODUCT DESCRIPTION: DISTRIBUTOR'S NAME: DISTRIBUTOR'S ADDRESS: DISTRIBUTOR'S PHONE NUMBER: MANUFACTURER S NAME:
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS INTERIM GUIDE CRITERIA FOR AEROBIC BACTERIAL GENERATOR FOR INSERT INTO SEPTIC TANKS, GREASE INTERCEPTORS AND GREASE TRAPS IAPMO IGC 180-20023
More informationCity of Grosse Pointe Park Sanitary Sewer System Inflow and Infiltration Investigation Smoke Testing
City of Grosse Pointe Park Sanitary Sewer System Inflow and Infiltration Investigation Smoke Testing August 2017 Definitions Sanitary Sewer System Sanitary sewer pipes and pump stations that collect wastewater
More informationONSITE WASTEWATER TREATMENT
ONSITE WASTEWATER TREATMENT SYSTEMS MANUAL Updated Draft December 2016 Alameda County Department of Environmental Health 1131 Harbor Bay Parkway Alameda, CA 94502 MANUAL INTRODUCTION This Manual provides
More informationFats, Oils & Grease (FOG) Management Policy
Fats, Oils & Grease (FOG) Management Policy Purpose: The purpose of this policy is to protect Sanitation District No. 1 (SD1) collection systems, pumping stations and treatment works from the discharge
More informationOWNER S, OPERATIONAL, AND MAINTENANCE MANUAL
OWNER S, OPERATIONAL, AND MAINTENANCE MANUAL H-TWO-O SERIES 2 WASTEWATER TREATMENT PLANTS CLASS 1 SYSTEMS 500/600/750/1,000 GALLONS PER DAY DESOTO CONCRETE PRODUCTS, INC. P.O. BOX 336 CERTIFIED OLIVE BRANCH,
More informationOhio EPA Permit to Install. When do you need one? What do you have to submit?
Ohio EPA Permit to Install When do you need one? What do you have to submit? Ohio EPA Permit to Install Required: ORC 6111.45 Plans for the disposal of the waste to be submitted to director of environmental
More informationPermit for Construction of an Extension to a JEA Drinking Water Distribution System and/or JEA Wastewater Collection/Transmission System
Permit for Construction of an Extension to a JEA Drinking Water Distribution System and/or JEA Wastewater Collection/Transmission System INSTRUCTIONS: This form shall be completed and submitted (in duplicate)
More informationS.O.P. No. HMD
Page: 1 of 9 PURPOSE: To establish (SOP) for submission requirements, review process and approval of applications for Non-vehicular Access Permits for the purpose of connection or discharge to any MassDOT
More informationWhy a FOG program with FSEs? USEPA CSO Consent Order requirement Restaurants leading producers of FOG Reduce/eliminate SSOs Reduce time and money
Agenda Introduction Akron FOG Ordinance Coordination with Building Department Coordination with Health Department Procedures for FOG Violations Case Studies & Lessons Learned Questions Why a FOG program
More informationTYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps:
Effluent Pumps: Effluent pumps are the pumps most often used in small on-site systems. They are designed to pump effluent, the effluent flowing out of a septic tank. This effluent is relatively clear liquid
More informationRecommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Plumbing Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Plumbing Code
More informationGRAY WATER SYSTEMS (Reference California Plumbing Code Chapter 16 and 16A) Revised: 6/11/14
Planning and Building Department 525 San Anselmo Avenue Building Division San Anselmo, CA 94960 Phone: (415) 258-4616 Fax: (415) 454-4683 GRAY WATER SYSTEMS (Reference California Plumbing Code Chapter
More informationDIVISION 6, WASTEWATER
DIVISION 6, WASTEWATER 6-00 General Considerations: 6-10 General: Sanitary sewerage refers to wastewater derived from domestic, commercial and industrial pretreated waste to which storm, surface, and ground
More informationGRAY WATER SYSTEMS FOR RESIDENTIAL BUILDINGS
INFORMATION BULLETIN / PUBLIC - PLUMBING CODE REFERENCE NO.: LAMC 94.1502.0 Effective: 01-01-2017 DOCUMENT NO.: P/PC 2017-012 Revised: Previously Issued As: P/PC 20014-012 GRAY WATER SYSTEMS FOR RESIDENTIAL
More informationPrepared for Florida State University Facilities Planning& Construction By Environmental Health & Safety Tallahassee, Fl
SITE ASSESSMENT CHECKLIST FOR DEMOLITION AND RENOVATION PROJECTS INSERT BUILDING NAME FSU BUILDING NUMBER XXX CAMPUS OF FLORIDA STATE UNIVERSITY TALLAHASSEE, FLORIDA Prepared for Florida State University
More informationOn-Site Sewage Disposal Systems. Santa Barbara County Environmental Health Services
On-Site Sewage Disposal Systems Santa Barbara County Environmental Health Services On-Site Sewage Disposal Systems History Standard Septic Systems Regulation and Inspection of Septic Systems Septic System
More informationPRESENTATION TO MWRD ADVISORY TECHNICAL PANEL
VILLAGE OF SCHAUMBURG FOOTING DRAIN DISCONNECTION COST-SHARE PROGRAM PRESENTATION TO MWRD ADVISORY TECHNICAL PANEL MARCH 21, 2012 Village of Schaumburg, IL SCHAUMBURG, ILLINOIS Located 26 miles northwest
More informationOIL / WATER SEPARATORS UNDERGROUND FIBERGLASS STORAGE TANKS MODELS: CSI-10 / CSI-15 / UL 2215
OIL / WATER SEPARATORS UNDERGROUND FIBERGLASS STORAGE TANKS MODELS: CSI-10 / CSI-15 / UL 2215 FIBERGLASS UNDERGROUND OIL/WATER SEPARATORS Containment Solutions, Inc. (CSI) provides a full range of dependable
More informationENVIRONMENTAL SITE ASSESSMENT QUESTIONNAIRE
100 Broadway Road, Dracut, MA 01826 ENVIRONMENTAL SITE ASSESSMENT QUESTIONNAIRE TO BE COMPLETED BY THE APPLICANT ADDRESS: 1a. Is the property used for an industrial use? 1b. Is any adjoining property used
More informationONSITE WASTEWATER TREATMENT
ONSITE WASTEWATER TREATMENT SYSTEMS MANUAL Revised Draft March 2017 Alameda County Department of Environmental Health 1131 Harbor Bay Parkway Alameda, CA 94502 MANUAL INTRODUCTION OVERVIEW This Onsite
More informationThe following is required for a complete permit submittal for each unit.
P: (847)810-3502 OR (847)810-3503/3521, F: (847)615-4383 MULTI-FAMILY OR COMMERCIAL ADDITION OR ALTERATION PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. MULTI-FAMILY
More informationA.B.A. Well and Septic Services Inc. P.O. Box 35 Ivor, VA (757) A Homeowner s Guide to Septic Systems
A.B.A. Well and Septic Services Inc. P.O. Box 35 Ivor, VA 23866 (757) 859-9494 A Homeowner s Guide to Septic Systems The Main Components of a Septic System Septic Tank The septic tank is a buried, watertight
More informationCity of Lawrence. Private Inflow and Infiltration Program. Plumber s Guidelines
City of Lawrence Private Inflow and Infiltration Program Plumber s Guidelines Revisions to this document were made December 2015 as follows: Building Permits: The Plumbing Contractor will be responsible
More informationHOLDING TANK PLANNING & INSTALLATION GUIDELINES
HOLDING TANK PLANNING & INSTALLATION GUIDELINES Under no circumstances is sewage from a holding tank to be discharged onto the surface of the ground or into groundwater or surface waters. TABLE OF CONTENTS
More information1.0 Overview Compliance Checklist Information Best Management Practices Checklist Information...13
Acknowledgements 1.0 Overview..... 3 2.0 Compliance Checklist Information..........6 3.0 Best Management Practices Checklist Information.........13 4.0 FOG BMP Self Certification Program.....18 5.0 Rhode
More informationUNINCORPORATED JACKSON COUNTY BUILDING PERMITS
UNINCORPORATED JACKSON COUNTY BUILDING PERMITS May, 2014 Department of Public Works Planning and Environmental Health PREFACE The purpose of this manual is to provide an overview of the procedures to apply
More informationGGI-750. Gravity Grease Interceptor Technical Data. Submittal Special Precautions Specifications Installation
Gravity Grease Technical Data Submittal Special Precautions Specifications Installation 75" 81" (205.7 (94.0 cm) 19½" 20" (50.8 (49.5 cm) 21½" 20" (50.8 (54.6 cm) 76½" (194.3 cm) 56½" 57" (144.8 (143.5
More informationAmendments to the 2012 International Plumbing Code
Amendments to the 2012 International Plumbing Code The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby amended as follows: Standard type is text from the
More informationSeptic System Basics. Today s Presentation:
Septic System Basics Kitt Farrell-Poe Extension Water Quality Specialist Ag & Biosystems Engineering Dept. Today s Presentation: What is an onsite wastewater treatment system? Components of a septic system
More informationSSO- WDR Compliance Workshop Electronic Reporting: Reporting Requirements & Tips. Sewer System Management Plan Chapter
Chapter Contents Introduction SSMP Requirements and Suggested Content SSMP Preparation Deadlines Introduction This chapter provides a brief overview of the GWDR requirements for an SSMP and provides some
More information4.0 INDUSTRIAL/COMMERCIAL DISCHARGE PERMITS
4.0 INDUSTRIAL/COMMERCIAL DISCHARGE PERMITS 4.1 EXISTING UNPERMITTED INDUSTRIAL USERS Within 60 calendar days after the effective date of this SUO, or at such time when the participant ties into the Authority's
More informationInstructions for Short Form Baseline Report for Nonresidential Establishments
Instructions for Short Form Baseline Report for Nonresidential Establishments Please type or print clearly. A.1 The address required is the company who owns the business. Give complete company name mailing
More information2016 DENVER AMENDMENTS TO THE 2015 EDITION OF THE INTERNATIONAL MECHANICAL CODE AND APPENDICES AS PUBLISHED BY INTERNATIONAL CODE COUNCIL (ICC)
2016 DENVER AMENDMENTS TO THE 2015 EDITION OF THE INTERNATIONAL MECHANICAL CODE AND APPENDICES AS PUBLISHED BY INTERNATIONAL CODE COUNCIL (ICC) The content of the sections in this Code that begin with
More informationVehicle and Equipment Cleaning
Vehicle and Equipment Cleaning SC-21 Objectives Cover Contain Educate Reduce/Minimize Product Substitution Description Photo Credit: Geoff Brosseau Wash water from vehicle and equipment cleaning activities
More informationSUPPLEMENTAL 2011 PLUMBING CORRECTION SHEET FOR HIGH-RISES
SUPPLEMENTAL 2011 PLUMBIN CORRECTION SHEET FOR HIH-RISES 2010 CPC ENERAL REQUIREMENTS A1. Plans shall bear the registration or license number and signature of an architect, contractor, or engineer, registered
More informationWest Virginia Department of Health & Human Resources Department of Health
SS-182A Rev 6/07 West Virginia Department of Health & Human Resources Department of Health Application for a Permit to Install or Modify an Onsite Sewage Disposal System Property Owner Phone (H) (W) Address
More informationBYRON TOWNSHIP BUILDING PERMIT APPLICATION 8085 Byron Center Ave SW., Byron Center, MI /Fax
BYRON TOWNSHIP BUILDING PERMIT APPLICATION 8085 Byron Center Ave SW., Byron Center, MI 49315 616-878-9155/Fax 616-878-0699 Applicant to complete all items in Section I, II, III, IV, V Note: Separate applications
More informationUNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION
PART 1 - GENERAL 1.01 Elevator manufacturer to provide equipment and installation warranty and maintenance services for at least one year after acceptance. This requires routine monthly inspection, emergency
More informationNORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION
NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION INNOVATIVE WASTEWATER SYSTEM APPROVAL, Attachment INNOVATIVE WASTEWATER SYSTEM
More information400 Gal. Grease Interceptor
400 Gal. Grease Interceptor PC-000-331 Secondary chamber volume equal to 1/2 total capacity. Verify compliance with local regulations. STM-C-478 specifications for water and wastewater structures. utyl
More informationA PUMPED SEPTIC TANK IS A HAPPY SEPTIC TANK!!
A PUMPED SEPTIC TANK IS A HAPPY SEPTIC TANK!! Homeowners of Septic Systems Chatham County Environmental Health Pittsboro, North Carolina March 24, 2016 Topics to be reviewed Why do we use septic systems?
More informationFacilities Planning and Construction (FP&C)
Appendix 8.4a Facilities Planning and Construction (FP&C) UAA FP&C Quality Assessment Checklist (A) Project: PM: Project ID: Updated:
More informationRESIDENTIAL CONSTRUCTION PERMIT FEES
RESIDENTIAL CONSTRUCTION PERMIT FEES R-1 Building Permit: One- or Two-Family New Construction (Complete Permit Packet) Combination permit to include Building, Electrical, Mechanical, Plumbing (to include
More informationAs used in 314 CMR 7.00, the following words have the following meaning:
Version12-12-06 314 CMR 7.00: SEWER SYSTEM EXTENSION AND CONNECTION PERMIT PROGRAM Section 7.01: Purpose and Authority 7.02: Definitions 7.03: Activities Requiring a Permit 7.04: Additional Restrictions
More informationFats, Oil and Grease (FOG) Manual and Policy
Fats, Oil and Grease (FOG) Manual and Policy Adopted per 2012 IPC SOUTHLAKE PUBLIC WORKS DEPARTMENT 1950 E. CONTINENTAL BLVD SOUTHLAKE, TX 76092 817-748-8638 TABLE OF CONTENTS Table of Contents... 1 Executive
More informationC. Up to Two and One-half (2-1/2) inches: Full port, 2-piece, bronze body ball valves with teflon seat conforming to MSS SP-110.
SECTION 220000 PLUMBING SYSTEMS 1.0 Valves A. ASME compliance: 1. ASME B1.20.1 2. ASME B16.1 3. ASME B16.10 4. ASME B16.34 5. ASME B16.18 6. ASME B31.9 B. All branch mains shall be provided with shutoff
More informationFS-DUO. Wastewater Flow Distributor Technical Data. Submittal Special Precautions Specifications Installation. (62.2 cm) (62.2 cm)
Wastewater Flow Distributor Technical Data Submittal Special Precautions Specifications Installation 24½" (62.2 cm) 12½" (31.8 cm) 24½" (62.2 cm) (30.5 cm) SUBMITTAL STANDARD: 4" plain end inlet/outlet
More informationPORT OF SAN FRANCISCO PLUMBING CODE. Based on the 2010 California Plumbing Codes
2010 PORT OF SAN FRANCISCO PLUMBING CODE Based on the 2010 California Plumbing Codes 2010 Port of San Francisco Plumbing Code The complete 2010 Port of San Francisco Plumbing Code adopts and amends the
More informationDRIP EMITTER SYSTEM STUDY GUIDE
DRIP EMITTER SYSTEM STUDY GUIDE Minimum Criteria for Pressurized Subsurface Absorption Fields Utilizing Emitters. Subsurface systems utilizing emitters may be used in lieu of conventional or other alternative
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Fire Water Supply without a Purveyor Residential & Commercial STANDARD #D-003 EFFECTIVE 01-04-2016 1. PURPOSE 1.1. The California Fire Code (CFC) requires
More informationPrivate Side Sewer Inspections for Sources of Inflow & Infiltration Frequently Asked Questions
Private Side Sewer Inspections for Sources of Inflow & Infiltration Frequently Asked Questions As of Oct. 1, 2010, Tacoma property owners are required to have a certified inspection of their private side
More informationWASTEWATER EFFLUENT DISPOSAL PUBLICLY OWNED TREATMENT WORKS (CAMP BARRETT WASTEWATER PUMP STATION)
ENVIRONMENTAL STANDARD OPERATING PROCEDURE 17 WASTEWATER EFFLUENT DISPOSAL PUBLICLY OWNED TREATMENT WORKS (CAMP BARRETT WASTEWATER PUMP STATION) 1. Version, Date. 1, 12 Feb 08 (EMS) 2. Purpose. This document
More informationYour Water Treatment Technology Partners for Wash Water & Industrial Water Treatment. Design Supply Integration Installation Maintenance
Your Water Treatment Technology Partners for Wash Water & Industrial Water Treatment Design Supply Integration Installation Maintenance The Challenge for Businesses that Use Water PUBLIC HEALTH EPA state
More informationA. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationBOARD OF PUBLIC UTILITIES SCHEDULE OF WASTEWATER RATES PROVISIONS APPLICABLE TO ALL CONSUMERS
NATURE OF SERVICE PROVIDED: VOTE: November 21, 2016 Effective Date: All billing after January 1, 2017 Service Area: All Wastewater service shall be provided for the purposes provided to users in accordance
More informationLifetime Guaranteed Construction with unique built-in installation and maintenance features
Lifetime Guaranteed Construction with unique built-in installation and maintenance features Great Basin grease interceptors provide the best in quality materials and engineered craftsmanship. Units are
More informationInfiltration and Inflow. Michael Sassaman Phone
Infiltration and Inflow Michael Sassaman msassaman@entecheng.com Phone 610-373-3345 Inflow and Infiltration PA DEP Learning Objectives Do you have Excessive I/I? Sources of Inflow and Infiltration I/I
More informationCommonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA
Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Issued to: Technology: Premier Tech Aqua 1160, rue Levis, bureau
More informationSECTION Plumbing and Sewerage Construction and Maintenance Plumbing and Sewerage Inspector
SECTION 28.0.0 Plumbing and Sewerage Construction and Maintenance 28.1.0 Plumbing and Sewerage Inspector The Plumbing Inspector of the Village, appointed by the Mayor and with the consent of the Village
More informationBEAU CHÊNE HOMEOWNERS ASSOCIATION, INC. CROSS CONNECTION CONTROL RULE
BEAU CHÊNE HOMEOWNERS ASSOCIATION, INC. CROSS CONNECTION CONTROL RULE Section 1: Cross-Connection Control Device or Method Required. A. Each existing or new structure is required to implement and maintain
More informationWASTEWATER SYSTEM STANDARDS
8.1 SCOPE Wastewater pipelines and appurtenances shall be provided as shown on the plans and as specified herein. Clearing, grubbing, trench excavation and backfill, pipe material, valves, cutting and
More informationNORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH
NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH INNOVATIVE WASTEWATER SYSTEM APPROVAL INNOVATIVE WASTEWATER
More informationREAD ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX C - ALTERNATE PLUMBING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority
More informationCHAPTER 10 SOURCE CONTROL
CHAPTER 10 SOURCE CONTROL Chapter Organization 10.1 Purpose... 10-1 10.1.1 Goals and Objectives of Source Control... 10-1 10.2 Applicability... 10-1 10.2.1 Site Uses That Require Source Control... 10-2
More informationCHAPTER 12 DOMESTIC AND INDUSTRIAL WASTE DISPOSAL. Article 1.Domestic and Industrial Waste Disposal Program Created
CHAPTER 12 DOMESTIC AND INDUSTRIAL WASTE DISPOSAL Article 1.Domestic and Industrial Waste Disposal Program Created Sec. 12-1. Declaring a Public Utility and General Provisions 1. The Sanitary Sewer System
More informationChapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE
Chapter 23.12 UNIFORM CODES FOR CONSTRUCTION BUILDING CODE 23.12.010 Adoption of the 2010 California Building Code. Part 2. Title 24 of the California Code of Regulations. There is adopted and incorporated
More informationCHAPTER 6. Sanitary Sewer
CHAPTER 6 Sanitary Sewer A. Introduction All proposed developments, subdivisions, and buildings must have a properly designed and constructed sanitary sewer collection system. The system shall provide
More informationGUIDELINES FOR PREPARATION OF CAPACITY ANALYSIS REPORTS
GUIDELINES FOR PREPARATION OF CAPACITY ANALYSIS REPORTS Florida Department of Environmental Regulation July 1992 TABLE OF CONTENTS PURPOSE AND APPLICABILITY................... 1 Purpose............................
More informationPretreatment Streamlining Rule
Pretreatment Guidance 2 Final Pretreatment Streamlining Rule Statutory references: ORC 6111.03(Q) and 6111.042 Rule references: OAC 3745-3; 40 CFR 403 Ohio EPA, Division of Surface Water Revision 0, October
More informationTABLE 1 OAR MINIMUM SEPARATION DISTANCES
Items Requiring Setback TABLE 1 OAR 340-071-0220 MINIMUM SEPARATION DISTANCES From Subsurface Absorption Area Including Replacement Area From Septic Tank and Other Treatment Units, Effluent Sewer and Distribution
More informationES Cleaning/Washing - Aircraft, Vehicles and Equipment Document Identification Number Date: March 15, 2018
ES-301-1.02 Cleaning/Washing - Aircraft, Vehicles and Equipment Document Identification Number ES-301-1.02 Date: March 15, 2018 Document Owner: Keith Pass 1) Activity Description: The following guideline
More informationUniversity of Delaware
University Contact: Energy & Engineering Group (302) 831-1744 SECTION 22 40 00_PLUMBING FIXTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Water closets. 2. Urinals. 3. Lavatories. 4. Sinks. 5.
More informationSCHEDULE B RESIDENTIAL BUILDING FEES
SCHEDULE B RESIDENTIAL BUILDING FEES Residential Building Fees 48 Hour Notice to Schedule Inspections 72 Hour Notice to Schedule Final Inspections $4.50 Add to All UCC (Act 45 of 1999) Permits ADMINISTRATION
More informationSIEMEX OIL SEPARATOR MAINTAINANCE MANUAL SIEMEX OIL SEPARATOR MAINTAINANCE MANUAL. SIEMEX (M) Sdn Bhd
SIEMEX OIL SEPARATOR MAINTAINANCE MANUAL SIEMEX (M) Sdn Bhd LOCATION 23, JALAN PJU 3/45 SUNWAY DAMANSARA 47810 PETALING JAYA SELANGOR CONTACT info@siemex.com.my WEBSITE www.siemex.com.my GENERAL SIEMEX
More informationAQUA AIRE Concrete Class I Wastewater Treatment Plants
ECOLOGICAL TANKS, INC. AQUA AIRE Concrete Class I Wastewater Treatment Plants OWNER S MANUAL Alternate Aerator Locations Alternate Aerator Locations Alternate Aerator Locations Aerator Aerator Aerator
More informationCommercial Remodel Permit
Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each
More informationThis policy will generally explain the following in regards to the City sewerage collection systems:
CITY OF SACO POLICY ON SEWER AND STORMWATER BACK-UPS PURPOSE The purpose of this policy is to explain how and why sewer or stromwater backups occur, what to do in the event a homeowner has a backup, and
More informationCONNECTICUT RECOMMENDED MINIMUM EXISTING SEPTIC SYSTEM INSPECTION REPORT
CONNECTICUT RECOMMENDED MINIMUM EXISTING SEPTIC SYSTEM INSPECTION REPORT DATE: (1) PROPERTY ADDRESS: TOWN:. Type of Dwelling or Use:. (2) CLIENT INFORMATION: Client s Name: Phone #:. Mailing Address:.
More informationB-500 / B-600 SERIES
B-500 / B-600 SERIES VAPOR VENT TRANSITION INSTALLATION GUIDE SINGLE WALL VENT TRANSITION SUMPS B-500 VENT TRANSITION SINGLEWALL SERIES SHOWN WITH WATERSPLASH LID, AND SUPPORT FOR 5 VENT LINES. B-500 SINGLEWALL
More informationGB-50. Submittal Special Precautions Specifications Installation Application Specific Details
Submittal Special Precautions Specifications Installation Application Specific Details 37" (94.0 cm) 10½" (26.7 (27 cm) 28½" (72.4 cm) (46.7 (45.7 cm) 28" (71.1 cm) SUBMITTAL STANDARD: 4" plain end inlet/outlet
More informationECOLOGICAL TANKS, INC. AQUA AIRE Concrete Class I Wastewater Treatment Plants OWNER S MANUAL
ECOLOGICAL TANKS, INC. AQUA AIRE Concrete Class I Wastewater Treatment Plants OWNER S MANUAL Alternate Aerator Locations Aerator Air Supply Line Inlet Outlet Assembly Chlorinator as Req. Aeration/Mixing
More information