1 SECTION FLASHING AND SHEET METAL PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: Provide all flashing and sheet metal not specifically described in other Sections of these Specifications but required to prevent penetration of water through exterior shell of building. Scope of Work shall be as shown on the Drawings: B. Related work described elsewhere: 1. Selective Demolition Section Adhered PVC Roofing System Section Sealants and Caulking Section QUALITY ASSURANCE A. Standards: Comply with standards specified in this Section. B. Qualification of manufacturer: Prefabricated products used in the work of this Section shall be produced by manufacturers regularly engaged in manufacture of similar items and with a history of successful production acceptable to the Owner. C. Qualification of installers: Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this Section SUBMITTALS A. General: Comply with provisions of General Conditions. B. Manufacturer's data: Within ten (10) calendar days after receipt of the Notice to Proceed, submit: 1. Complete materials list of all items proposed to be furnished and installed under this Section indicating amount, gauge and/or weight, dimensions, and type. 2. Manufacturer's specifications and other data required to demonstrate compliance with the specified requirements. 3. The manufacturer's recommended installation procedures and the shop drawings, when approved by the Owner, will become the basis for inspecting and accepting or rejecting actual installation procedures used on the Work PRODUCT HANDLING A. Protection: Use all means necessary to protect materials of this Section before, during, and after installation and to protect installed work and materials of all other trades. B. Replacements: In the event of damage, immediately make all repairs and replacements necessary to the approval of the Owner and at no additional cost the Owner. 1.5 PERFORMANCE REQUIREMENTS A. General: Install sheet metal flashing and trim to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failing, rattling, leaking, and fastener disengagement. FLASHING AND SHEET METAL SECTION
2 B. Fabricate and install roof edge flashing according to ANSI/SPRI ES-1. C. Thermal Movements: Provide sheet metal flashing and trim that allow for thermal movement to prevent buckling, opening joints, hole elongation, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Provide clips that resist rotation and avoid shear stress as a result of sheet metal and trim thermal movements. Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss. D. Water Infiltration: Provide sheet metal flashing and trim that do not allow water infiltration to building interior. PART 2 - PRODUCTS 2.01 DESIGN A. Standard commercial items may be used for flashing, trim, and reglets, provided all such items meet or exceed the quality standards specified herein. B. Quality standards: In addition to complying with all pertinent codes and regulations, comply with all pertinent recommendations contained in "Architectural Sheet Metal Manual," current edition of the Sheet Metal and Air Conditioning Contractors National Association COUNTER FLASHING A. Provide min. 4 counter flashing at all vertical flashing locations. B. New counter flashing metal shall match the existing metal which it is to be in contact with (.040 mil finish aluminum,.018 stainless steel, 26 gauge galvanized and/or 16 oz copper). If there is no existing metal to match, new counter flashing shall be 26 gauge galvalume with a Kynar (or approved equal) finish. C. Counter flashing cleats, where required, shall be a minimum one gage heavier than the counter flashing material PITCH POCKETS A. Material for pitch pockets for EPDM Roof Systems shall be manufacturer s approved pitch pocket dam material. B. Where manufacturer s components can not be used, material for pitch pockets shall be 16 oz. copper. All joints shall be soldered prior to the installation of stripping/flashing materials. Provide a sample of a 4x4 pitch pocket with the project submittals prior to job start. C. Hoods for pitch pockets shall be 16 oz. copper. All joints shall be soldered. New hoods shall be required at all pitch pan locations. Provide a sample of a pitch pocket hood with the project submittals prior to job start METAL EDGE / FASCIA A. Pre-manufactured metal edge / fascia shall be 24 gauge galvalume with a Kynar (or approved equal) finish. Back-up plates shall be of equal or greater thickness material. Finish shall be minimum 70% Kynar fluorocarbon coating. B. Color shall be selected by the Owner from manufacturer s full range of colors. FLASHING AND SHEET METAL SECTION
3 C. Continuous cleat shall be of equal thickness and material as the metal edge. D. All metal edges shall be in compliance with ANSI/SPRI ES FLOW THROUGH OVERFLOW SCUPPER A. Pre-manufactured overflow scupper shall be designed to work with the new pre-manufactured metal edge. B. Color shall be selected by the Owner from manufacturer s full range of colors GUTTERS AND DOWNSPOUTS A. Materials for new gutters and downspouts shall be 24 gauge galvalume with a Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating. Color shall be selected by the Owner from manufacturer s full range of colors. B. Gutter profile: 6 box style C. Downspout size: 4 x4 D. Material for new hidden gutter straps shall be 2 x 18 gauge galvalume with Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating and shall match the selected gutter color. E. Material for new gutter hangers shall be 2 x 18 gauge galvalume with Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating and shall match the selected gutter color OTHER MATERIALS A. All other materials, not specifically described but required for a complete and proper installation of the work of this Section, shall be new, first quality of their respective kinds, and as selected by the Contractor subject to the approval of the Owner FABRICATION, GENERAL A. Sheet Metal Fabrication Standard: Fabricate sheet metal flashing and trim to comply with recommendations of SMACNA s Architectural Sheet Metal Manual that apply to the design, dimensions, metal, and other characteristics of the item indicated. B. Comply with details shown to fabricate sheet metal flashing and trim that fit substrates and result in waterproof and weather-resistant performance once installed. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal. C. Form exposed sheet metal Work that is without excessive oil canning, buckling, and tool marks and that is true to line and levels indicated, with exposed edges folded back to form hems. D. Seams: Fabricate nonmoving seams in sheet metal with flat-lock seams. Tin edges to be seamed, form seams, and solder. E. Expansion Provisions: Space movement joints at maximum of 10 feet with no joints allowed within 12 inches of corner or intersection. Where lapped or bayonet-type expansion provisions in Work cannot be used or would not be sufficiently weatherproof and waterproof, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant (concealed within joints). See details. FLASHING AND SHEET METAL SECTION
4 F. Sealed Joints: Form non-expansion, but movable, joints in metal to accommodate elastomeric sealant to comply with SMACNA standards. G. Separate metal from non-compatible metal or corrosive substrates by coating concealed surfaces at locations of contact with asphalt mastic or other permanent separation as recommended by manufacturer. H. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of sheet metal exposed to public view. I. Fabricate cleats and attachment devices from same material as sheet metal component being anchored or form compatible, non-corrosive metal recommended by sheet metal manufacturer. Size shall be as recommended by SMACNA manual or sheet metal manufacturer for application but never less than thickness of metal being secured. PART 3 - EXECUTION 3.01 INSPECTION A. Examine the areas and conditions under which work of this Section will be installed. Correct conditions detrimental to the proper and timely completion of the Work. Do not proceed until unsatisfactory conditions have been corrected WORKMANSHIP A. General: 1. Form all sheet metal accurately and to the dimensions and shapes required, finishing all molded and broken surfaces with true, sharp, and straight lines and angles and, where intercepting other members, soldering securely. 2. Unless otherwise specifically permitted by the Owner, turn all exposed edges back 13 mm (1/2"). B Weatherproofing: 1. Finish watertight and weathertight where so required. 2. Make all lock seam work flat and true to line. Make all lock seam and lap seams, when soldered, at least 13 mm (1/2") wide. 3. Make all flat and lap seams in direction of flow. 4. Counter flashing at curbs shall be lapped a minimum of 4" and riveted, and sloped from the penetration to arrest water from laying on the detail. C. Nailing: 3.03 EMBEDMENT 1. Whenever possible, secure metal by means of clips or cleats without nailing through the metal. 2. In general, space all screws not more than 20cm (8") apart, where exposed to the weather, and use neoprene washers. 3. For nailing into brick, use drilled plugholes and plugs. A. Prime metal flanges on all metal components top and bottom with required primer prior to installation. FLASHING AND SHEET METAL SECTION
5 B. Embed all metal in connection with roofs in a solid bed of sealant, using materials and methods described in these Specifications or other materials approved in advance by the Owner. END OF SECTION FLASHING AND SHEET METAL SECTION
Hawthorne Fire Station Repairs Section Page 1 of 8
Hawthorne Fire Station Repairs Section 07620 Page 1 of 8 SECTION 07620 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationSECTION ROOF SPECIALTIES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationArchitectural Wall Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is
More informationSECTION C. Water Infiltration: Provide manufactured cupolas and dormers that do not allow water infiltration to cupola and dormer interiors.
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Manufactured exterior cupolas. 2. Manufactured dormers. 3. Historical locomotive weather Vane. 1.2 PERFORMANCE REQUIREMENTS A. General:
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification
More informationPASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017
SECTION 07620 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationC. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations.
ms1505 SECTION 07 60 00 - Page 1 PART 1 GENERAL 1.01 SECTION INCLUDES A. Coping flashing and cleats. B. Counterflashings at roof edge. C. Counterflashings at roof-mounted mechanical equipment, vent stacks,
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationDISVISON 8: DOORS, WINDOWS AND GLASS SECTION 07600: SHEET METAL FLASHING AND TRIM
DISVISON 8: DOORS, WINDOWS AND GLASS SECTION 07600: SHEET METAL FLASHING AND TRIM Allentown, PA - Plant Expansion PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Flashings and counterflashings, gutters
More informationSECTION COPPER STANDING SEAM ROOFING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 61 16 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph as required and
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationA. Provide all labor, equipment, and materials fabricate and install the following. 2. Counterflashings over bituminous base flashing.
SECTION 076200 - FLASHING AND SHEET METAL PART 1 GENERAL 1.1 SECTION INCLUDES: A. Provide all labor, equipment, and materials fabricate and install the following. 1. Edge strip and flashing. 2. Counterflashings
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationSECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION.
SECTION 074213 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting
More informationSECTION MANUFACTURED ROOF EXPANSION JOINTS
SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationIce Rink Renovation & New Clubhouse
SECTION 074243- METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationStudent Services & Classroom Addition
SECTION 074243 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSHEET METAL FLASHING AND TRIM
SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationUniversity of Louisville February 22, 2017 Papa John s Cardinal Stadium -North Expansion Bid Package No. 5 Louisville, Kentucky
SECTION 076200 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationSheet Metal Flashing and Trim
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 076200 - Sheet
More informationProject Name Project # Project Information
SECTION 074229.00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationSECTION ROOF MOUNTED ATTIC EXHAUST VENT
SECTION 07 72 00 ROOF MOUNTED ATTIC EXHAUST VENT **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular
More informationSECTION METAL ROOF AND SOFFIT PANELS
Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for
More informationEMBRY RIDDLE PRESCOTT SECTION METAL COMPOSITE MATERIAL WALL PANELS
SECTION 074213.23 - WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION STANDING-SEAM METAL ROOF PANEL
SECTION 074113 -STANDING-SEAM METAL ROOF PANEL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSECTION TURBINE VENTILATORS
SECTION 07 72 00 TURBINE VENTILATORS **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular project.
More information1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights
1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights These 1 Exam Prep tabs are based on the 2012 Sheet Metal and Air Conditioning Contractors' National Association, Inc., seventh edition.
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 074213 - INSULATED METAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION METAL COMPOSITE MATERIAL WALL PANELS
SECTION 074213.23 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
Project Name: Jefferson City Jaycees Fairgrounds Main Building Roof Replacement Project Site Address: 1445 Fairgrounds Road, Jefferson City, MO 65109 Project Contact: Randy Weaver Project Contact phone
More informationMETAL COMPOSITE MATERIAL WALL PANELS
MasterSpec Full Length 1 of 10 SECTION 074213.23 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes metal composite material wall panels. 1.2 PREINSTALLATION MEETINGS
More informationAddendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE
SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,
More information1. Include similar Samples of trim and accessories involving color selection.
SECTION 074116- INSULATED METAL ROOF PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTECHNICAL INFORMATION
TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories
More informationCS-100 Guide Specifications
MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification
More informationSECTION (07620) - SHEET METAL FLASHING AND TRIM
SECTION 07 62 00 (07620) - SHEET METAL FLASHING AND TRIM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Flashing at Roof, Windows, Doors, and other locations as shown on Drawings. 2. Roof Drainage
More informationSECTION STANDING SEAM METAL ROOFING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 41 13 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Use for roofing sloped 1 in 4 (3 in/ft) or greater. 3. Delete between // // if not applicable
More information1. Rough Carpentry for wood nailers, cants, curbs, and blocking and for wood-based, structural-use roof deck and walls: Division 6.
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: SECTION 076200 - SHEET METAL FLASHING AND TRIM 1. Provide all labor, equipment, and materials fabricate and install the following: a. Pre-manufactured
More informationWVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION
075000 ROOFING SYSTEMS PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. ASTM American Society
More informationSECTION ELECTRICAL POWER ATTIC EXHAUST VENTILATOR
SECTION 07 72 00 ELECTRICAL POWER ATTIC EXHAUST VENTILATOR **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to delete
More informationTuscaloosa Police Station
Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK
More informationDIVISION 7: MOISTURE PROTECTION SECTION 07417: INSULATED METAL PANELS
DIVISION 7: MOISTURE PROTECTION SECTION 07417: INSULATED METAL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels.
1/11 SECTION 074213.23 - ALUMINUM COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes aluminum composite material wall panels. 1.2 PRE-INSTALLATION MEETINGS A. Pre-installation
More informationDIVISION 7 THERMAL AND MOISTURE PROTECTION
DIVISION 7 THERMAL AND MOISTURE PROTECTION UCSC Campus Standards Handbook Waterproofing Standards 07100 1 SECTION 07100: WATERPROOFING STANDARDS A. Guarantee 1. Provide a guarantee on Contractor's letterhead
More informationSECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011
SECTION 07553 ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Elastomeric roofing membrane (EPDM), conventional application at low slope roof
More informationGuide Specifications ADP Series SECTION SHEET METAL ROOFING
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sheet metal roofing panels, metal trim, accessories, fasteners, closures, and sealants. [Specifier Note: Edit paragraph below to suit project requirements.]
More informationA. Section includes custom-fabricated, standing-seam sheet metal roofing.
SECTION 076100 - SHEET METAL ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationNRM-7000 Guide Specifications
NRM-7000 Guide Specifications MANUFACTURER www.nuraymetals.com sales@nuraymetals.com 800-700-7228 SECTION 07 411 PREFORMED ROOF & WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes complete system
More informationSECTION FLASHING AND SHEET METAL
SECTION 07600 FLASHING AND SHEET METAL ****** **** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: See MDCPS Design Criteria for flashing condition requirements. ****** **** **** *** ** * **
More informationSECTION SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS
SECTION 07410 SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS # Specifier: Notation (#) means that text following is a specifier s note or sample. PART 1 - GENERAL 1.01 Description # Specifier: Do not alter
More informationRoof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan
More informationMetal Roof Panels
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal
More informationSECTION VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS
SECTION 07410 VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS # Specifier: Notation (#) means that text following is a specifier s note or sample. PART 1 - GENERAL 1.01 Description # Specifier: Do not
More informationSpecifications for FL-100 Soffit Panel
Union Corrugating Company Specifications for FL-100 Soffit Panel SECTION 07410 METAL SOFFIT PANELS PART 1 GENERAL 1.1 DESCRIPTON A. Section Includes: 1. Preformed metal soffit panel system 2. Associated
More informationSECTION ROOF SPECIALTIES
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 07 71 00 ROOF SPECIALTIES SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the
More informationDL-200. Specifications
DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01
More informationSSL-175. Specifications
SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES
More informationSECTION 07530CP EPDM MEMBRANE ROOFING
PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION SHEET MEMBRANE ROOFING
SECTION 07610 SHEET MEMBRANE ROOFING PART I - GENERAL 1.01 DESCRIPTION A. Work of this Section shall include all materials and installation necessary to provide Sheet Metal Roofing as shown and detailed
More informationADDENDUM TO BID DOCUMENTS SCCD RFP: # Vacaville Classroom Building (Annex) Renovation. Date: 11/16/2017
Vacaville Classroom Annex Renovation Documents #18-005 ADDENDUM TO BID DOCUMENTS ADDENDUM #02 SCCD RFP: #18 005 Project: Vacaville Classroom Building (Annex) Renovation Date: 11/16/2017 Addendum # 02 The
More informationSECTION METAL BUILDING SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 13 34 19 1. Use this section only for NCA projects. 2. Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable
More informationLight-Metal Roof Edge, Raised
NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED
More informationMagnolia Transit Center Expansion SECTION METAL SOFFIT PANELS
Magnolia Transit Center Expansion 07416-1 SECTION 07416 METAL SOFFIT PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide
More informationRAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012
SECTION 10200 - LOUVERS AND VENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016
PART 1: GENERAL 1.01 Scope Of Standard 1.02 Reference Standards 1.03 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for
More informationSECTION (10705) EXTERIOR SUN CONTROL DEVICES
10 71 13 SECTION (10705) EXTERIOR SUN CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationRevised Jan-15 Sheet Metal Flashing
PART 1 - GENERAL 1.1 SCOPE OF STANDARD A. This standard provides general guidance concerning the specific preferences of Texas State University for Standing Sheet Metal Roofing. B. Texas State University
More informationC. Jointing of Exterior Vertical Surfaces. Section D. The Secretary of the US Department of the Interior s Standards for Rehabilitation.
PART 1: GENERAL 1.01 Scope Of Standard A. This standard provides general guidance concerning the specific preferences of the University of Texas at Austin for roofing systems. B. UT recognizes that project
More informationBENTONITE WATERPROOFING
SECTION 07 17 00 BENTONITE WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install bentonite waterproofing system where shown on the drawings, as specified herein, and as needed for a complete
More informationUniversity of New Hampshire Scholars' Repository
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 075423 - TPO
More informationSECTION ROOFING AND SIDING PANELS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 40 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationC. All roofs shall be installed according to manufacturers guidelines. Corrections due to workmanship shall be at contractors expense.
PART 1: GENERAL 1.01 Scope Of Standard 1.03 Reference Standards 1.04 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for
More informationSECTION METAL ROOFING MASTER SPECIFICATION
SECTION 07 41 13 METAL ROOFING MASTER SPECIFICATION PART I - GENERAL REQUIREMENTS 1.01 DESCRIPTION OF WORK: A. Section Includes: The extent of each type of preformed metal roofing panel as indicated on
More information3. Roof Expansion Joints between New Building and Existing Building.
SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Amendments to General Conditions and Division 01 Specification
More informationSECTION METAL ROOF PANELS
SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof
More informationSection Sheet Metal Flashing and Trim
***** The Design Professional shall include the following PSFA requirements as noted and complete this section, edited as necessary with information for the specific project. Refer to the latest version
More informationROOFING STUDY GUIDE ARCHITECTURAL SHEET METAL
ROOFING STUDY GUIDE ARCHITECTURAL SHEET METAL PRACTICE TEST ONE 1. It is recommended that base fleshings be applied over a cant and be extended up the wall a minimum of. A. 6 inches B. 8 inches C. 10 inches
More information* Other widths available upon request. 24 Gauge Galvalume - Standard Surface. Other gauges and aluminium available upon request.
is a concealed fastener architectural standing seam roof panel. The panels are easily installed over decking, utilizing metal clips. panels are ideally suited for decorative mansard, fascia and roofs.
More informationSECTION FLASHING AND SHEET METAL
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 60 00 1. Use section only for NCA projects. 2. Delete or edit text in // // if not applicable to project. Also delete any other paragraph not applicable in the
More informationSHEET METAL ROOF TEST REPORT
SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA
More informationSection STRAIGHT BARREL MISSION ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY
This Guide Specification is intended to be used in preparation of specifications for a particular project, or as the basis for an office master specification. In either case, the Guide Specification must
More informationA. Pre-Installation Conference: Conduct conference at [project site] <insert location>.
SECTION 074213.23 METAL COMPOSITE MATERIAL WALL PANELS PART 1 GENERAL 1.1 SUMMARY A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary supports and anchors to structure,
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural roofing system of preformed steel panels. B. Fastening system. C. Factory finishing. D. Accessories and miscellaneous components.
More informationSLVHCS REPLACEMENT MEDICAL CENTER PROJECT EWP-6 Addendum 01 12/30/ /17/2012 SECTION FLASHING AND SHEET METAL PART 1 - GENERAL
SECTION 07 60 00 FLASHING AND SHEET METAL PART 1 - GENERAL 1.1 DESCRIPTION A. Formed sheet metal work for wall and roof flashing are specified in this section. B. Formed sheet metal work for wall and roof
More informationRoof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details S1.0 Safety Anchor Plan Building 709 Bull Street Columbia, 1 10/13 T-1 (Title Page)
More informationSECTION STEEL BUILDING SYSTEMS
PART 1 - GENERAL 1.01 SECTION INCLUDES: SECTION 13120 - STEEL BUILDING SYSTEMS A. Pre-engineered building and components including the following: 1. Structural steel frame. 2. Roof covering system including
More informationSECTION STAINLESS STEEL WALL PANELS
SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.
More informationTYPICAL ROOF CONDITION LAYOUT
FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 074243 - COMPOSITE WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 DEFINITIONS A. Aluminum Composite Wall
More informationProduct Guide Specification
Umicore Building Products USA, Inc. January 2009 3600 Glenwood Ave., Suite 250 Raleigh, North Carolina 27612 Phone (919) 874-7173 Fax (919) 874-7140 Website www.vmzinc-us.com E-mail info@vmzinc-us.com
More informationSECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM
PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.
More informationFascia Systems. oofing 7.1
Systems oofing 7.1 TremLock TM A Pre-engineered, Non-Penetrating Metal Edge System oofing TremLock TM Pre-engineered, Non-penetrating Metal Edge System The TremLock is a pre-engineered, non-penetrating
More informationM.C.A. Superior Clay Roof Tile
This Guide Specification is intended to be used in preparation of specifications for a particular project, or as the basis for an office master specification. In either case, the Guide Specification must
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 076100 - SHEET METAL ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information