1 SECTION FLASHING AND SHEET METAL PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: Provide all flashing and sheet metal not specifically described in other Sections of these Specifications but required to prevent penetration of water through exterior shell of building. Scope of Work shall be as shown on the Drawings: B. Related work described elsewhere: 1. Selective Demolition Section Adhered PVC Roofing System Section Sealants and Caulking Section QUALITY ASSURANCE A. Standards: Comply with standards specified in this Section. B. Qualification of manufacturer: Prefabricated products used in the work of this Section shall be produced by manufacturers regularly engaged in manufacture of similar items and with a history of successful production acceptable to the Owner. C. Qualification of installers: Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this Section SUBMITTALS A. General: Comply with provisions of General Conditions. B. Manufacturer's data: Within ten (10) calendar days after receipt of the Notice to Proceed, submit: 1. Complete materials list of all items proposed to be furnished and installed under this Section indicating amount, gauge and/or weight, dimensions, and type. 2. Manufacturer's specifications and other data required to demonstrate compliance with the specified requirements. 3. The manufacturer's recommended installation procedures and the shop drawings, when approved by the Owner, will become the basis for inspecting and accepting or rejecting actual installation procedures used on the Work PRODUCT HANDLING A. Protection: Use all means necessary to protect materials of this Section before, during, and after installation and to protect installed work and materials of all other trades. B. Replacements: In the event of damage, immediately make all repairs and replacements necessary to the approval of the Owner and at no additional cost the Owner. 1.5 PERFORMANCE REQUIREMENTS A. General: Install sheet metal flashing and trim to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failing, rattling, leaking, and fastener disengagement. FLASHING AND SHEET METAL SECTION

2 B. Fabricate and install roof edge flashing according to ANSI/SPRI ES-1. C. Thermal Movements: Provide sheet metal flashing and trim that allow for thermal movement to prevent buckling, opening joints, hole elongation, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Provide clips that resist rotation and avoid shear stress as a result of sheet metal and trim thermal movements. Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss. D. Water Infiltration: Provide sheet metal flashing and trim that do not allow water infiltration to building interior. PART 2 - PRODUCTS 2.01 DESIGN A. Standard commercial items may be used for flashing, trim, and reglets, provided all such items meet or exceed the quality standards specified herein. B. Quality standards: In addition to complying with all pertinent codes and regulations, comply with all pertinent recommendations contained in "Architectural Sheet Metal Manual," current edition of the Sheet Metal and Air Conditioning Contractors National Association COUNTER FLASHING A. Provide min. 4 counter flashing at all vertical flashing locations. B. New counter flashing metal shall match the existing metal which it is to be in contact with (.040 mil finish aluminum,.018 stainless steel, 26 gauge galvanized and/or 16 oz copper). If there is no existing metal to match, new counter flashing shall be 26 gauge galvalume with a Kynar (or approved equal) finish. C. Counter flashing cleats, where required, shall be a minimum one gage heavier than the counter flashing material PITCH POCKETS A. Material for pitch pockets for EPDM Roof Systems shall be manufacturer s approved pitch pocket dam material. B. Where manufacturer s components can not be used, material for pitch pockets shall be 16 oz. copper. All joints shall be soldered prior to the installation of stripping/flashing materials. Provide a sample of a 4x4 pitch pocket with the project submittals prior to job start. C. Hoods for pitch pockets shall be 16 oz. copper. All joints shall be soldered. New hoods shall be required at all pitch pan locations. Provide a sample of a pitch pocket hood with the project submittals prior to job start METAL EDGE / FASCIA A. Pre-manufactured metal edge / fascia shall be 24 gauge galvalume with a Kynar (or approved equal) finish. Back-up plates shall be of equal or greater thickness material. Finish shall be minimum 70% Kynar fluorocarbon coating. B. Color shall be selected by the Owner from manufacturer s full range of colors. FLASHING AND SHEET METAL SECTION

3 C. Continuous cleat shall be of equal thickness and material as the metal edge. D. All metal edges shall be in compliance with ANSI/SPRI ES FLOW THROUGH OVERFLOW SCUPPER A. Pre-manufactured overflow scupper shall be designed to work with the new pre-manufactured metal edge. B. Color shall be selected by the Owner from manufacturer s full range of colors GUTTERS AND DOWNSPOUTS A. Materials for new gutters and downspouts shall be 24 gauge galvalume with a Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating. Color shall be selected by the Owner from manufacturer s full range of colors. B. Gutter profile: 6 box style C. Downspout size: 4 x4 D. Material for new hidden gutter straps shall be 2 x 18 gauge galvalume with Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating and shall match the selected gutter color. E. Material for new gutter hangers shall be 2 x 18 gauge galvalume with Kynar (or approved equal) finish. Finish shall be minimum 70% Kynar fluorocarbon coating and shall match the selected gutter color OTHER MATERIALS A. All other materials, not specifically described but required for a complete and proper installation of the work of this Section, shall be new, first quality of their respective kinds, and as selected by the Contractor subject to the approval of the Owner FABRICATION, GENERAL A. Sheet Metal Fabrication Standard: Fabricate sheet metal flashing and trim to comply with recommendations of SMACNA s Architectural Sheet Metal Manual that apply to the design, dimensions, metal, and other characteristics of the item indicated. B. Comply with details shown to fabricate sheet metal flashing and trim that fit substrates and result in waterproof and weather-resistant performance once installed. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal. C. Form exposed sheet metal Work that is without excessive oil canning, buckling, and tool marks and that is true to line and levels indicated, with exposed edges folded back to form hems. D. Seams: Fabricate nonmoving seams in sheet metal with flat-lock seams. Tin edges to be seamed, form seams, and solder. E. Expansion Provisions: Space movement joints at maximum of 10 feet with no joints allowed within 12 inches of corner or intersection. Where lapped or bayonet-type expansion provisions in Work cannot be used or would not be sufficiently weatherproof and waterproof, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant (concealed within joints). See details. FLASHING AND SHEET METAL SECTION

4 F. Sealed Joints: Form non-expansion, but movable, joints in metal to accommodate elastomeric sealant to comply with SMACNA standards. G. Separate metal from non-compatible metal or corrosive substrates by coating concealed surfaces at locations of contact with asphalt mastic or other permanent separation as recommended by manufacturer. H. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of sheet metal exposed to public view. I. Fabricate cleats and attachment devices from same material as sheet metal component being anchored or form compatible, non-corrosive metal recommended by sheet metal manufacturer. Size shall be as recommended by SMACNA manual or sheet metal manufacturer for application but never less than thickness of metal being secured. PART 3 - EXECUTION 3.01 INSPECTION A. Examine the areas and conditions under which work of this Section will be installed. Correct conditions detrimental to the proper and timely completion of the Work. Do not proceed until unsatisfactory conditions have been corrected WORKMANSHIP A. General: 1. Form all sheet metal accurately and to the dimensions and shapes required, finishing all molded and broken surfaces with true, sharp, and straight lines and angles and, where intercepting other members, soldering securely. 2. Unless otherwise specifically permitted by the Owner, turn all exposed edges back 13 mm (1/2"). B Weatherproofing: 1. Finish watertight and weathertight where so required. 2. Make all lock seam work flat and true to line. Make all lock seam and lap seams, when soldered, at least 13 mm (1/2") wide. 3. Make all flat and lap seams in direction of flow. 4. Counter flashing at curbs shall be lapped a minimum of 4" and riveted, and sloped from the penetration to arrest water from laying on the detail. C. Nailing: 3.03 EMBEDMENT 1. Whenever possible, secure metal by means of clips or cleats without nailing through the metal. 2. In general, space all screws not more than 20cm (8") apart, where exposed to the weather, and use neoprene washers. 3. For nailing into brick, use drilled plugholes and plugs. A. Prime metal flanges on all metal components top and bottom with required primer prior to installation. FLASHING AND SHEET METAL SECTION

5 B. Embed all metal in connection with roofs in a solid bed of sealant, using materials and methods described in these Specifications or other materials approved in advance by the Owner. END OF SECTION FLASHING AND SHEET METAL SECTION

Hawthorne Fire Station Repairs Section Page 1 of 8

Hawthorne Fire Station Repairs Section Page 1 of 8 Hawthorne Fire Station Repairs Section 07620 Page 1 of 8 SECTION 07620 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Architectural Wall Products Guide Specifications

Architectural Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is

More information

SECTION C. Water Infiltration: Provide manufactured cupolas and dormers that do not allow water infiltration to cupola and dormer interiors.

SECTION C. Water Infiltration: Provide manufactured cupolas and dormers that do not allow water infiltration to cupola and dormer interiors. PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Manufactured exterior cupolas. 2. Manufactured dormers. 3. Historical locomotive weather Vane. 1.2 PERFORMANCE REQUIREMENTS A. General:

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 07620 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

C. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations.

C. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations. ms1505 SECTION 07 60 00 - Page 1 PART 1 GENERAL 1.01 SECTION INCLUDES A. Coping flashing and cleats. B. Counterflashings at roof edge. C. Counterflashings at roof-mounted mechanical equipment, vent stacks,

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

DISVISON 8: DOORS, WINDOWS AND GLASS SECTION 07600: SHEET METAL FLASHING AND TRIM

DISVISON 8: DOORS, WINDOWS AND GLASS SECTION 07600: SHEET METAL FLASHING AND TRIM DISVISON 8: DOORS, WINDOWS AND GLASS SECTION 07600: SHEET METAL FLASHING AND TRIM Allentown, PA - Plant Expansion PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Flashings and counterflashings, gutters

More information

SECTION COPPER STANDING SEAM ROOFING

SECTION COPPER STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 61 16 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph as required and

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

A. Provide all labor, equipment, and materials fabricate and install the following. 2. Counterflashings over bituminous base flashing.

A. Provide all labor, equipment, and materials fabricate and install the following. 2. Counterflashings over bituminous base flashing. SECTION 076200 - FLASHING AND SHEET METAL PART 1 GENERAL 1.1 SECTION INCLUDES: A. Provide all labor, equipment, and materials fabricate and install the following. 1. Edge strip and flashing. 2. Counterflashings

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used

More information

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 074213 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 074243- METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 074243 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SHEET METAL FLASHING AND TRIM

SHEET METAL FLASHING AND TRIM SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

University of Louisville February 22, 2017 Papa John s Cardinal Stadium -North Expansion Bid Package No. 5 Louisville, Kentucky

University of Louisville February 22, 2017 Papa John s Cardinal Stadium -North Expansion Bid Package No. 5 Louisville, Kentucky SECTION 076200 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Sheet Metal Flashing and Trim

Sheet Metal Flashing and Trim University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 076200 - Sheet

More information

Project Name Project # Project Information

Project Name Project # Project Information SECTION 074229.00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

SECTION ROOF MOUNTED ATTIC EXHAUST VENT

SECTION ROOF MOUNTED ATTIC EXHAUST VENT SECTION 07 72 00 ROOF MOUNTED ATTIC EXHAUST VENT **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular

More information

SECTION METAL ROOF AND SOFFIT PANELS

SECTION METAL ROOF AND SOFFIT PANELS Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for

More information

EMBRY RIDDLE PRESCOTT SECTION METAL COMPOSITE MATERIAL WALL PANELS

EMBRY RIDDLE PRESCOTT SECTION METAL COMPOSITE MATERIAL WALL PANELS SECTION 074213.23 - WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION STANDING-SEAM METAL ROOF PANEL

SECTION STANDING-SEAM METAL ROOF PANEL SECTION 074113 -STANDING-SEAM METAL ROOF PANEL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION TURBINE VENTILATORS

SECTION TURBINE VENTILATORS SECTION 07 72 00 TURBINE VENTILATORS **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular project.

More information

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights 1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights These 1 Exam Prep tabs are based on the 2012 Sheet Metal and Air Conditioning Contractors' National Association, Inc., seventh edition.

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 074213 - INSULATED METAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION METAL COMPOSITE MATERIAL WALL PANELS

SECTION METAL COMPOSITE MATERIAL WALL PANELS SECTION 074213.23 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING

SECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING Project Name: Jefferson City Jaycees Fairgrounds Main Building Roof Replacement Project Site Address: 1445 Fairgrounds Road, Jefferson City, MO 65109 Project Contact: Randy Weaver Project Contact phone

More information

METAL COMPOSITE MATERIAL WALL PANELS

METAL COMPOSITE MATERIAL WALL PANELS MasterSpec Full Length 1 of 10 SECTION 074213.23 - METAL COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes metal composite material wall panels. 1.2 PREINSTALLATION MEETINGS

More information

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,

More information

1. Include similar Samples of trim and accessories involving color selection.

1. Include similar Samples of trim and accessories involving color selection. SECTION 074116- INSULATED METAL ROOF PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

CS-100 Guide Specifications

CS-100 Guide Specifications MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification

More information

SECTION (07620) - SHEET METAL FLASHING AND TRIM

SECTION (07620) - SHEET METAL FLASHING AND TRIM SECTION 07 62 00 (07620) - SHEET METAL FLASHING AND TRIM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Flashing at Roof, Windows, Doors, and other locations as shown on Drawings. 2. Roof Drainage

More information

SECTION STANDING SEAM METAL ROOFING

SECTION STANDING SEAM METAL ROOFING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 41 13 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Use for roofing sloped 1 in 4 (3 in/ft) or greater. 3. Delete between // // if not applicable

More information

1. Rough Carpentry for wood nailers, cants, curbs, and blocking and for wood-based, structural-use roof deck and walls: Division 6.

1. Rough Carpentry for wood nailers, cants, curbs, and blocking and for wood-based, structural-use roof deck and walls: Division 6. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: SECTION 076200 - SHEET METAL FLASHING AND TRIM 1. Provide all labor, equipment, and materials fabricate and install the following: a. Pre-manufactured

More information

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION 075000 ROOFING SYSTEMS PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. ASTM American Society

More information

SECTION ELECTRICAL POWER ATTIC EXHAUST VENTILATOR

SECTION ELECTRICAL POWER ATTIC EXHAUST VENTILATOR SECTION 07 72 00 ELECTRICAL POWER ATTIC EXHAUST VENTILATOR **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to delete

More information

Tuscaloosa Police Station

Tuscaloosa Police Station Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK

More information

DIVISION 7: MOISTURE PROTECTION SECTION 07417: INSULATED METAL PANELS

DIVISION 7: MOISTURE PROTECTION SECTION 07417: INSULATED METAL PANELS DIVISION 7: MOISTURE PROTECTION SECTION 07417: INSULATED METAL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels.

SECTION ALUMINUM COMPOSITE MATERIAL WALL PANELS. A. Section includes aluminum composite material wall panels. 1/11 SECTION 074213.23 - ALUMINUM COMPOSITE MATERIAL WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes aluminum composite material wall panels. 1.2 PRE-INSTALLATION MEETINGS A. Pre-installation

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION

DIVISION 7 THERMAL AND MOISTURE PROTECTION DIVISION 7 THERMAL AND MOISTURE PROTECTION UCSC Campus Standards Handbook Waterproofing Standards 07100 1 SECTION 07100: WATERPROOFING STANDARDS A. Guarantee 1. Provide a guarantee on Contractor's letterhead

More information

SECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011

SECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 SECTION 07553 ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Elastomeric roofing membrane (EPDM), conventional application at low slope roof

More information

Guide Specifications ADP Series SECTION SHEET METAL ROOFING

Guide Specifications ADP Series SECTION SHEET METAL ROOFING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sheet metal roofing panels, metal trim, accessories, fasteners, closures, and sealants. [Specifier Note: Edit paragraph below to suit project requirements.]

More information

A. Section includes custom-fabricated, standing-seam sheet metal roofing.

A. Section includes custom-fabricated, standing-seam sheet metal roofing. SECTION 076100 - SHEET METAL ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NRM-7000 Guide Specifications

NRM-7000 Guide Specifications NRM-7000 Guide Specifications MANUFACTURER www.nuraymetals.com sales@nuraymetals.com 800-700-7228 SECTION 07 411 PREFORMED ROOF & WALL PANELS PART 1 - GENERAL 1.1 SUMMARY A. Section includes complete system

More information

SECTION FLASHING AND SHEET METAL

SECTION FLASHING AND SHEET METAL SECTION 07600 FLASHING AND SHEET METAL ****** **** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: See MDCPS Design Criteria for flashing condition requirements. ****** **** **** *** ** * **

More information

SECTION SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS

SECTION SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS SECTION 07410 SEM-LOK - PREFORMED STANDING SEAM ROOF PANELS # Specifier: Notation (#) means that text following is a specifier s note or sample. PART 1 - GENERAL 1.01 Description # Specifier: Do not alter

More information

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208 Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan

More information

Metal Roof Panels

Metal Roof Panels University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal

More information

SECTION VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS

SECTION VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS SECTION 07410 VERTI-LOK - PREFORMED STANDING SEAM ROOF PANELS # Specifier: Notation (#) means that text following is a specifier s note or sample. PART 1 - GENERAL 1.01 Description # Specifier: Do not

More information

Specifications for FL-100 Soffit Panel

Specifications for FL-100 Soffit Panel Union Corrugating Company Specifications for FL-100 Soffit Panel SECTION 07410 METAL SOFFIT PANELS PART 1 GENERAL 1.1 DESCRIPTON A. Section Includes: 1. Preformed metal soffit panel system 2. Associated

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 07 71 00 ROOF SPECIALTIES SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

DL-200. Specifications

DL-200. Specifications DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01

More information

SSL-175. Specifications

SSL-175. Specifications SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION SHEET MEMBRANE ROOFING

SECTION SHEET MEMBRANE ROOFING SECTION 07610 SHEET MEMBRANE ROOFING PART I - GENERAL 1.01 DESCRIPTION A. Work of this Section shall include all materials and installation necessary to provide Sheet Metal Roofing as shown and detailed

More information

ADDENDUM TO BID DOCUMENTS SCCD RFP: # Vacaville Classroom Building (Annex) Renovation. Date: 11/16/2017

ADDENDUM TO BID DOCUMENTS SCCD RFP: # Vacaville Classroom Building (Annex) Renovation. Date: 11/16/2017 Vacaville Classroom Annex Renovation Documents #18-005 ADDENDUM TO BID DOCUMENTS ADDENDUM #02 SCCD RFP: #18 005 Project: Vacaville Classroom Building (Annex) Renovation Date: 11/16/2017 Addendum # 02 The

More information

SECTION METAL BUILDING SYSTEMS

SECTION METAL BUILDING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 13 34 19 1. Use this section only for NCA projects. 2. Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Light-Metal Roof Edge, Raised

Light-Metal Roof Edge, Raised NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED

More information

Magnolia Transit Center Expansion SECTION METAL SOFFIT PANELS

Magnolia Transit Center Expansion SECTION METAL SOFFIT PANELS Magnolia Transit Center Expansion 07416-1 SECTION 07416 METAL SOFFIT PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012 SECTION 10200 - LOUVERS AND VENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016 PART 1: GENERAL 1.01 Scope Of Standard 1.02 Reference Standards 1.03 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information

SECTION (10705) EXTERIOR SUN CONTROL DEVICES

SECTION (10705) EXTERIOR SUN CONTROL DEVICES 10 71 13 SECTION (10705) EXTERIOR SUN CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Revised Jan-15 Sheet Metal Flashing

Revised Jan-15 Sheet Metal Flashing PART 1 - GENERAL 1.1 SCOPE OF STANDARD A. This standard provides general guidance concerning the specific preferences of Texas State University for Standing Sheet Metal Roofing. B. Texas State University

More information

C. Jointing of Exterior Vertical Surfaces. Section D. The Secretary of the US Department of the Interior s Standards for Rehabilitation.

C. Jointing of Exterior Vertical Surfaces. Section D. The Secretary of the US Department of the Interior s Standards for Rehabilitation. PART 1: GENERAL 1.01 Scope Of Standard A. This standard provides general guidance concerning the specific preferences of the University of Texas at Austin for roofing systems. B. UT recognizes that project

More information

BENTONITE WATERPROOFING

BENTONITE WATERPROOFING SECTION 07 17 00 BENTONITE WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install bentonite waterproofing system where shown on the drawings, as specified herein, and as needed for a complete

More information

University of New Hampshire Scholars' Repository

University of New Hampshire Scholars' Repository University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 075423 - TPO

More information

SECTION ROOFING AND SIDING PANELS

SECTION ROOFING AND SIDING PANELS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 40 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

C. All roofs shall be installed according to manufacturers guidelines. Corrections due to workmanship shall be at contractors expense.

C. All roofs shall be installed according to manufacturers guidelines. Corrections due to workmanship shall be at contractors expense. PART 1: GENERAL 1.01 Scope Of Standard 1.03 Reference Standards 1.04 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information

SECTION METAL ROOFING MASTER SPECIFICATION

SECTION METAL ROOFING MASTER SPECIFICATION SECTION 07 41 13 METAL ROOFING MASTER SPECIFICATION PART I - GENERAL REQUIREMENTS 1.01 DESCRIPTION OF WORK: A. Section Includes: The extent of each type of preformed metal roofing panel as indicated on

More information

3. Roof Expansion Joints between New Building and Existing Building.

3. Roof Expansion Joints between New Building and Existing Building. SECTION 077200 - ROOF ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Amendments to General Conditions and Division 01 Specification

More information

SECTION METAL ROOF PANELS

SECTION METAL ROOF PANELS SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof

More information

Section Sheet Metal Flashing and Trim

Section Sheet Metal Flashing and Trim ***** The Design Professional shall include the following PSFA requirements as noted and complete this section, edited as necessary with information for the specific project. Refer to the latest version

More information

ROOFING STUDY GUIDE ARCHITECTURAL SHEET METAL

ROOFING STUDY GUIDE ARCHITECTURAL SHEET METAL ROOFING STUDY GUIDE ARCHITECTURAL SHEET METAL PRACTICE TEST ONE 1. It is recommended that base fleshings be applied over a cant and be extended up the wall a minimum of. A. 6 inches B. 8 inches C. 10 inches

More information

* Other widths available upon request. 24 Gauge Galvalume - Standard Surface. Other gauges and aluminium available upon request.

* Other widths available upon request. 24 Gauge Galvalume - Standard Surface. Other gauges and aluminium available upon request. is a concealed fastener architectural standing seam roof panel. The panels are easily installed over decking, utilizing metal clips. panels are ideally suited for decorative mansard, fascia and roofs.

More information

SECTION FLASHING AND SHEET METAL

SECTION FLASHING AND SHEET METAL PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 60 00 1. Use section only for NCA projects. 2. Delete or edit text in // // if not applicable to project. Also delete any other paragraph not applicable in the

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

Section STRAIGHT BARREL MISSION ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY

Section STRAIGHT BARREL MISSION ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY This Guide Specification is intended to be used in preparation of specifications for a particular project, or as the basis for an office master specification. In either case, the Guide Specification must

More information

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>.

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>. SECTION 074213.23 METAL COMPOSITE MATERIAL WALL PANELS PART 1 GENERAL 1.1 SUMMARY A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary supports and anchors to structure,

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural roofing system of preformed steel panels. B. Fastening system. C. Factory finishing. D. Accessories and miscellaneous components.

More information

SLVHCS REPLACEMENT MEDICAL CENTER PROJECT EWP-6 Addendum 01 12/30/ /17/2012 SECTION FLASHING AND SHEET METAL PART 1 - GENERAL

SLVHCS REPLACEMENT MEDICAL CENTER PROJECT EWP-6 Addendum 01 12/30/ /17/2012 SECTION FLASHING AND SHEET METAL PART 1 - GENERAL SECTION 07 60 00 FLASHING AND SHEET METAL PART 1 - GENERAL 1.1 DESCRIPTION A. Formed sheet metal work for wall and roof flashing are specified in this section. B. Formed sheet metal work for wall and roof

More information

Roof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science

Roof Replacement. Notes: T-1 (Title Page) 709 Bull Street Columbia, South Carolina. University of South Carolina. Callcott Social Science Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details S1.0 Safety Anchor Plan Building 709 Bull Street Columbia, 1 10/13 T-1 (Title Page)

More information

SECTION STEEL BUILDING SYSTEMS

SECTION STEEL BUILDING SYSTEMS PART 1 - GENERAL 1.01 SECTION INCLUDES: SECTION 13120 - STEEL BUILDING SYSTEMS A. Pre-engineered building and components including the following: 1. Structural steel frame. 2. Roof covering system including

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

TYPICAL ROOF CONDITION LAYOUT

TYPICAL ROOF CONDITION LAYOUT FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 074243 - COMPOSITE WALL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 DEFINITIONS A. Aluminum Composite Wall

More information

Product Guide Specification

Product Guide Specification Umicore Building Products USA, Inc. January 2009 3600 Glenwood Ave., Suite 250 Raleigh, North Carolina 27612 Phone (919) 874-7173 Fax (919) 874-7140 Website www.vmzinc-us.com E-mail info@vmzinc-us.com

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

Fascia Systems. oofing 7.1

Fascia Systems. oofing 7.1 Systems oofing 7.1 TremLock TM A Pre-engineered, Non-Penetrating Metal Edge System oofing TremLock TM Pre-engineered, Non-penetrating Metal Edge System The TremLock is a pre-engineered, non-penetrating

More information

M.C.A. Superior Clay Roof Tile

M.C.A. Superior Clay Roof Tile This Guide Specification is intended to be used in preparation of specifications for a particular project, or as the basis for an office master specification. In either case, the Guide Specification must

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 076100 - SHEET METAL ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information