1 SECTION PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting a bid for the work of this SECTION SCOPE OF WORK A. Furnish and install the following, as shown on the Drawings and/or specified herein. 1. Continuous membrane air barrier on new exterior wall and soffit construction including all necessary primers, sealants, etc. necessary to continuously seal the wall air and vapor barrier to adjacent construction (windows, doors, roof, etc.). 2. Repair wall and floor air and vapor barriers damaged by the work of other trades. B. This subcontractor shall furnish, install and maintain in safe, adequate condition all staging and scaffolding that are necessary for the proper execution of the work of this section RELATED WORK SPECIFIED ELSEWHERE A. The following related work is to be performed under the designated SECTIONS: 1. Construction of masonry back up walls, compressible joint fillers in masonry, and membrane flashing in masonry walls and installing rigid wall insulation in exterior masonry veneer walls: SECTION MASONRY. 2. Compressible joint fillers in cast-in-place concrete, and underslab moisture barrier and insulation: SECTION CAST-IN-PLACE CONCRETE. 3. Wood blocking and back up construction at soffits, fascias, and roof edges: SECTION ROUGH CARPENTRY. 4. Roof vapor retarder, metal and membrane flashings, and sealants in conjunction with roofing: SECTION ROOFING AND FLASHING

2 1.04 SUBMITTALS 5. Metal framing, wall insulation installation, panels, flashings and internal sealants at prefinished metal wall and soffit panel system: SECTION PREFORMED CLADDING. 6. Internal sealants in conjunction and with metal window systems: SECTION METAL WINDOWS. 7. Below grade dampproofing of basement walls: SECTION WATERPROOFING, DAMPPROOFING, AND CAULKING. 8. Gypsum board/metal stud exterior wall construction: SECTION GYPSUM WALL BOARD. A. Submit the following samples in accordance with the provisions of SECTION SUBMITTALS. 1. Joint bead material - 12 inch length. 2. Sealants and caulking materials, 3-inch strips of each specified type, in all available colors for selection by the Architect, applied to pieces of hardboard. 3. Air Barrier not less than 6 by 12 inches of each type. B. Include, with samples submission, complete manufacturer's specifications, installation instructions and application data, and duplicate copies of certifications of compliance to the designated Standards and Specifications set forth herein for all material, together with supporting test data and chemical composition of each material. Written approval of the Architect must be obtained for all samples and data before delivering any material to the project. C. Manufacturer's data - Submit to the Architect copies of manufacturer's specifications and installation and application instructions for all herein specified, certified test results, recommendations for sealing penetrations and perimeters, and other data as may be required. D. Contractorʼs Review-accompanying approval request, submit to the Architect written statement signed by the Sub-contractor, stating that the Architectʼs drawings and specifications for materials herein specified have been reviewed with an agent or the manufacturer of the primary materials and that he is in agreement that the selected systems and all other materials herein specified are proper, compatible and adequate for the application shown, and the conditions and details are not in conflict with the respective warranties. Show by copy of transmittal from that copy of statement that has been transmitted to respective manufacturers

3 E. Shop Drawings for Air Barrier Membrane Mockup: Submit shop drawings for mockup indicating size of mockup, details of construction, and expansion and control joints. Include relationship with adjacent materials, sequence of installation and materials and methods for sealing penetrations. Obtain approval of shop drawings prior to construction of mockup. Revise to show changes necessary to obtain approval of mockup. F. Shop Drawings: In accordance with SECTION ENERGY CODE REQUIREMENTS, submit dew point analysis of wall and roof assemblies and shop drawings indicating details of construction, including expansion and control joints. Include relationship with adjacent materials, sequence of installation and materials and methods for sealing penetrations. At a minimum, shop drawings shall include details of the following connections, as applicable to the project: 1. Foundation and walls. 2. Walls and windows or doors. 3. Different wall systems. 4. Wall and roof. 5. Walls, floor and roof across construction, control and expansion joints. 6. Walls, floors and roof to utility, pipe and duct penetrations. G. Qualifications of Installer: Submit qualifications of firm installing air barrier membrane materials, including name and qualifications of supervisor for this project, and including name and location of three projects where similar work was performed by both firm and supervisor. H. Mockups of Air Barrier Membrane Installation: Designate an area of the building to integrate the air barrier into the exterior wall as a mockup for approval by the Architect. Mockup shall show connection between wall and roof, and wall and window assembly. Mockup shall use actual air barrier membrane materials. Provide several mockups if necessary to include the various conditions. Remove mockup assemblies that are not approved. Rebuild mockups which are not approved at no additional cost to the Owner AIR BARRIER PRECONSTRUCTION CONFERENCE A. Preconstruction conference prior to the commencement of any construction work, a preconstruction conference shall be held as specified under SECTION ENERY CODE REQUIREMENTS. B. After approval of all materials and prior to installation, a air barrier preconstruction conference shall be held at the job site. In attendance shall be (1) Architect, (2) General Contractor, (3) Air Barrier Sub-contractor, and (4) Manufacturerʼs representative. C. The parties shall review Drawings, specifications and approved materials. Correct conflicts, if any, between approvals and specification requirements. Examine job site conditions, including inspection of substrate, material labels and methods of storing materials. Review installation procedures, scheduling and temperature requirements, and establish protection methods for finished waterproofing from other trades

4 D. Pre-Construction Meeting: After approval of mockup shop drawings, but prior to construction of mockup, convene a meeting with representatives of materials to be incorporated in the mockup and installers of mockup. Agenda shall include sequence and details of construction to ensure continuity of air barrier. E. Pre-Installation Meeting: Convene a pre-installation meeting a minimum of one week prior to commencing work of this section. Attendees shall include representatives of air barrier manufacturer, exterior wall installers and project superintendent. Agenda shall include the following: 1. Review of approved submittals. 2. Review of mockups. 3. Coordination with sequence of installation with adjacent materials. 4. Schedule for subsequent work covering air barrier. 5. Procedures for quality assurance GUARANTEE AND BONDS A. Silicone Sealant Systems 1. Manufacturer for the work of this SECTION shall review the Contract Documents, Shop Drawings and inspect the installation, and upon approval issue a standard twenty (20) year warranty QUALITY ASSURANCE A. The Subcontractor shall, for all materials and systems specified herein, submit a letter from each respective manufacturer certifying this Subcontractor is an authorized applicator PERFORMANCE REQUIREMENTS A. Commonwealth of Massachusetts Building Code Requirements: The intent of this specification is to require compliance with the 2009 IECC and 780 CMR 13. B. Code 780 CMR , Air Barriers: The building envelope shall be designed and constructed with a continuous air barrier to control air leakage into or out of the conditioned space. An air barrier shall also be provided with interior partitions between conditioned space and space designed to maintain temperature or humidity levels which differ from those in the conditioned space by more than 50 percent of the difference between the conditioned space and design ambient conditions. The air barrier shall have the following characteristics: 1. It must be continuous, with all joints made air-tight. 2. It shall have an air permeability not to exceed cubic feet per minute per square foot under a pressure differential of 0.3 in. water

5 3. It shall be capable of withstanding positive and negative design wind, fan and stack pressures on the envelope without damage or displacement, and shall transfer the load to the structure. It shall not displace adjacent materials under full load. 4. It shall be durable or maintainable. 5. The air barrier shall be joined in an air-tight and flexible manner to the air barrier material of adjacent systems, allowing for the relative movement of systems due to thermal and moisture variations and creep. Connection shall be made between: a. Foundations and walls. b. Walls and windows or doors. c. Different wall systems. d. Wall and roof. e. Wall and roof over unconditioned space. f. Walls, floor and roof across construction, control and expansion joints. g. Walls, floors and roof to utility, pipe and duct penetrations. C. Code 780 CMR , Air Barrier Penetrations: All penetrations of the air barrier and paths of air infiltration/exfiltration shall be made air-tight. D. Design Intent: Air barrier membrane shall be located, constructed and flashed to perform as an air and water barrier to discharge to the outside any incidental condensation or water penetration. Air barrier membrane shall accommodate movements of building materials by providing expansion and control joints as required, with appropriate air seal materials at such locations, changes in substrate and perimeter conditions PRODUCT DELIVERY, STORAGE AND HANDLING A. Each container must bear an unbroken seal, test number, and label of the manufacturer upon delivery to the site. Failure to comply with these requirements shall be sufficient cause for rejection of the material in question by the Architect and his requiring its removal from the site. New materials conforming to said requirements, shall be promptly furnished at no additional cost JOB CONDITIONS A. Weather conditions must be dry and of the proper temperature during application operations. Surfaces receiving work of this SECTION must be absolutely dry and dust free. All joints receiving sealants and caulking materials shall be subject to the approval of the materials manufacturer for proper use of the specified materials. B. Adjacent surfaces must be protected from damaged work performed under this SECTION

6 PART 2 PRODUCTS 2.01 MATERIALS REQUIREMENTS A. Deliver each material in manufacturer's unopened container or bundles, fully identified with brand, type, grade, class, and all other qualifying information. B. Storage of Materials - Store all materials in properly protected and dry storage facilities until ready for use. Installation of wet or damp materials will not be accepted. Do not use materials which have been damaged in any manner. C. Protect work from damage during construction period so that it will be without indication of abuse or damage at time of acceptance. D. Protect the building from damage resulting from spillage, dripping, and dropping of materials. Repair and restore other work damaged during roofing operations. E. Prevent waterproofing materials from running into the drains, clogging rain water conductors. F. Take all necessary precautions against fire and other hazards, during delivery, storage, and installation of inflammable adhesives, solvents, and other materials specified herein. Comply with local ordinances and fire regulations in the installation of hazardous materials specified or required under this SECTION SELF-ADHERING AIR AND VAPOR BARRIER MEMBRANES A. Self-Adhering Air and Vapor Barrier Membrane: Self-adhering, self-sealing membrane consisting of a 36 mil self-adhering rubberized ashalt membrane laminated to a 4 mil high density polyethylene film as follows: 1. To establish a standard of quality, design and function required, specifications are based on CCW-705 Membrane by Carlisle Coatings and Waterproofing, Inc., in widths as required by job conditions. 2. Similar membranes by Grace (Permabarrier), WR Meadows (Meadows Air Shield) or other manufacturers will be considered as an equal upon receipt of adequate supporting data. B. Transition Materials: To provide an air barrier between the membrane and adjacent materials, provide transition materials consisting of extruded low-modulus silicone sheet and silicone sealant designed to adhere to polyethylene side of membrane and adjacent material. Provide the following materials as acceptable to the manufacturer of the air barrier membrane: 1. Cleaning Agent; Toluene. 2. Silicone Sheet: SIL-SPAN Preformed Silicone Profiles by Pecora or ULTRASPAN Weatherstripping by General Electric. Provide preformed corners. 3. Silicone Sealant: Dow 790 Silicone Sealant or Pecora 864 Silicone Sealant. 4. Carlisle Window and Door Flashing

7 2.03 LIQUID APPLIED AIR AND VAPOR BARRIER MEMBRANES A. Liquid Applied Air and Vapor Barrier Membrane: Roller or spray applied, waterbased rubberized asphalt emulsion applied in a single 40 mil coat to gypsum based sheathing, wood, concrete and concrete masonry unit surfaces as follows: 1. Barriseal by Carlisle Coatings and Waterproofing, Inc. or approved equal, in roller or spray grades as required by job conditions. B. Accessory Products: To provide an air barrier between the membrane and adjacent materials, provide the following materials as acceptable to the manufacturer of the membrane manufacturer: 1. Surface Primer: Shall be CCW-702 Solvent-Based Primer, CCW-AWP Water-Based primer or CCW-CAV-Grip. 2. Detail Membrane: CCW-705 TWF, CCW-Barriseal, DCH Reinforcing Fabric CCW-W/D Flashing or PRE-KLEENED EPDM. 3. Mastic: Shall be CCW-704 Mastic. 4. Sealants: Shall be CCW-703 Vertical Grade Liquiseal membrane, PT-304 one component or CCW-201 two component Polyurethane Sealant

8 PART 3 EXECUTION 3.01 SELF-ADHERING AND LIQUID APPLIED AIR BARRIER MEMBRANES A. System Selection The air vapor barrier subcontractor shall select either a selfadhering or liquid applied barrier based upon the particular installation conditions and substrates in order to meet the system performance required by the Massachusetts Energy Conservation Code. B. Clean substrate surfaces to receive air barrier membrane in accordance with manufacturerʼs instructions. Apply primer if recommended by manufacturer. C. Strictly comply with air barrier membrane manufacturerʼs printed instructions, approved submittals and the following: 1. Apply materials within manufacturerʼs requirements for temperature and weather conditions. 2. Do not apply to wet or frozen substrates. 3. Do not allow contamination with dust or dirt. 4. Seal completely at edges, perimeter and penetrations. D. Protect installed work from damage due to harmful weather exposures, physical abuse, and other causes. E. Provide temporary protection over air barrier membrane if materials covering air barrier membrane will not be installed within manufacturerʼs recommended time limit for exposure. F. Repair damage to air barrier membrane caused by construction activities or subsequent work prior to covering CLEANING A. Clean all surfaces of adjacent surfaces which have been marked or soiled by the work of this SECTION, removing all excess mastics, sealants, and caulking materials there from. Use only cleaning materials and solvents which will not damage the surfaces in any way. END OF SECTION

SECTION SELF-ADHERING SHEET FLASHING

SECTION SELF-ADHERING SHEET FLASHING MANUFACTURER S GUIDE SPECIFICATIONS SECTION 076526 SELF-ADHERING SHEET FLASHING 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 604129 03.24.15 Carlisle, Flexphalt, Sure-Seal and CAV-GRIP

More information

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the

More information

A. Section includes fluid applied, vapor permeable membrane air barriers.

A. Section includes fluid applied, vapor permeable membrane air barriers. Master Construction Specifications Insert Project Name SECTION 072726 FLUID APPLIED MEMBRANE AIR BARRIERS PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied, vapor permeable membrane air barriers.

More information

SECTION SUPERGREEN LAM (LIQUID-APPLIED MEMBRANE AIR/VAPOR BARRIER SYSTEM)

SECTION SUPERGREEN LAM (LIQUID-APPLIED MEMBRANE AIR/VAPOR BARRIER SYSTEM) SECTION 07260 SUPERGREEN LAM (LIQUID-APPLIED MEMBRANE AIR/VAPOR BARRIER SYSTEM) PART 1 GENERAL 1.1 SECTION INCLUDES This section includes the following: 1. Materials and installation methods for peel-and-stick

More information

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE PART 1 - GENERAL 1.1 SUMMARY SECTION 07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit

More information

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION PREFORMED CLADDING. A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 074213 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Part A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION SINGLE-PLY ROOFING SYSTEM

SECTION SINGLE-PLY ROOFING SYSTEM PART 1 - GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals required to provide single-ply adhered roofing system. 1.02 COORDINATION A. The Contractor

More information

SECTION SELF-ADHERING SHEET MEMBRANE WATERPROOFING

SECTION SELF-ADHERING SHEET MEMBRANE WATERPROOFING SECTION 07 13 26 PART 1 - GENERAL 1.1 SUMMARY A. Scope: 1. Apply waterproofing to: a. Exterior of walls below grade: 1) Waterproofing shall include exterior of walls surrounding elevator pits and sumps.

More information

Insulation manufacturer to submit dew point analysis free of charge for typical wall section. Analysis by:

Insulation manufacturer to submit dew point analysis free of charge for typical wall section. Analysis by: PACE REPRESENTATIVES INC. 50 Redfield Street Boston MA 02122 www.pacerepresentatives.com 617-342-7072 PRE JOB AIR BARRIER/EXTERIOR WALL INSULATION MEETING CHECK LIST 1.01 Date: Insulation manufacturer

More information

SECTION DAMPPROOFING AND WATERPROOFING

SECTION DAMPPROOFING AND WATERPROOFING SECTION 07100 DAMPPROOFING AND WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Sheet Membrane Waterproofing 2. Under-Slab-On-Grade Vapor Retarder B. Related Sections: 1. Section 03300

More information

SECTION (07100) - DAMPPROOFING AND WATERPROOFING

SECTION (07100) - DAMPPROOFING AND WATERPROOFING SECTION 07 10 00 (07100) - DAMPPROOFING AND WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Sheet Membrane Waterproofing 2. Under-Slab-On-Grade Vapor Barrier B. Related Sections: 1.02

More information

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SECTION 07 30 05.01 SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SPEC WRITERS NOTE: This specification includes materials and installation procedures for SlopeShield SA Self-Adhered Water-Resistive Vapor

More information

Guide Specification for the OSI QUAD Window and Door Flashing System

Guide Specification for the OSI QUAD Window and Door Flashing System Henkel Corporation 26235 First Avenue Westlake, OH 1-866-591-2178 www.ositough.com Guide Specification for the OSI QUAD Window and Door Flashing System Specifier Note: The purpose of this guide specification

More information

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulation, membrane roofing, base flashings roofing membrane accessories joints, and counter flashings.

More information

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants.

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants. Section 07 42 13 Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants. 1.2 RELATED SECTIONS A. Section 06112 - Framing

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

SECTION MODIFIED BITUMINOUS SHEET AIR BARRIERS

SECTION MODIFIED BITUMINOUS SHEET AIR BARRIERS MANUFACTURER S GUIDE SPECIFICATIONS SECTION 072713 MODIFIED BITUMINOUS SHEET AIR BARRIERS 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 601737 05.22.13 Carlisle, Pre-Kleened and Sure-Seal

More information

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013) SECTION 07 27 20 FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013) PART 1 GENERAL 1.01 SECTION INCLUDES A. Materials and installation methods supplementing a one-component

More information

SECTION JOINT SEALERS 1.03 THIS SECTION INCLUDES JOINT SEALERS FOR THE FOLLOWING LOCATIONS:

SECTION JOINT SEALERS 1.03 THIS SECTION INCLUDES JOINT SEALERS FOR THE FOLLOWING LOCATIONS: PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 07900 - A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

SECTION FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER

SECTION FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER PART 1 - GENERAL 1.01 SUMMARY SECTION 07 65 00 FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER A. Section includes through wall masonry flashing system components for installation over sheathing where spray

More information

MODIFIED BITUMINOUS SHEET AIR / VAPOUR BARRIERS SELF ADHESIVE

MODIFIED BITUMINOUS SHEET AIR / VAPOUR BARRIERS SELF ADHESIVE Page 1 of 8 MODIFIED BITUMINOUS SHEET AIR / VAPOUR BARRIERS SELF ADHESIVE SOPRASEAL STICK 1100 T FOR A COMPLETE DESCRIPTION OF PRODUCTS AND APPLICABLE STANDARDS, PLEASE REFER TO THE TECHNICAL DATA SHEETS

More information

SECTION JOINT SEALANTS. A. Preparation of substrate surfaces to receive sealants.

SECTION JOINT SEALANTS. A. Preparation of substrate surfaces to receive sealants. SECTION 07910 JOINT SEALANTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Preparation of substrate surfaces to receive sealants. B. Furnish and install joint sealants and backing for the following locations:

More information

University of New Hampshire Scholars' Repository

University of New Hampshire Scholars' Repository University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 075423 - TPO

More information

RECOMMENDED DESIGN SPECIFICATION

RECOMMENDED DESIGN SPECIFICATION RECOMMENDED DESIGN SPECIFICATION SILICONE COATED SPF ROOFING 1 General 1.1 Section Includes A. Silicone coated SPF roofing system, including substrate board, roof insulation boards, foam insulation materials,

More information

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage

More information

PART 2 - AIR BARRIERS SELF-ADHESIVE

PART 2 - AIR BARRIERS SELF-ADHESIVE Part 1 - General 1.1 General.1 Related Documents: Provisions established within General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and the Drawings are collectively

More information

SECTION INJECTED or CAVITY-FILL POLYURETHANE FOAM (IPF)

SECTION INJECTED or CAVITY-FILL POLYURETHANE FOAM (IPF) SECTION 07200 INJECTED or CAVITY-FILL POLYURETHANE FOAM (IPF) Specifier Note: This specification is provided as guidelines for your use. Please review before publishing. PART 1.00 - GENERAL 1.01 DESCRIPTION:

More information

ABAA SPECIFICATION FOR MEDIUM-DENSITY CLOSED-CELL SPRAY POLYURETHANE FOAM AIR BARRIER SECTION 07263

ABAA SPECIFICATION FOR MEDIUM-DENSITY CLOSED-CELL SPRAY POLYURETHANE FOAM AIR BARRIER SECTION 07263 ABAA SPECIFICATION FOR SECTION 07263 PART 1 - GENERAL 1.1 SECTION INCLUDES A. This Section specifies a spray polyurethane foam air barrier in exterior wall assemblies. SPEC NOTE: COORDINATE RELATED WORK

More information

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013) SECTION 07 27 20 FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013) PART 1 GENERAL 1.01 SECTION INCLUDES A. Materials and installation methods supplementing a one-component

More information

DIVISION 7 MARFLEX 5000 FLUID APPLIED AIR & VAPOR BARRIER - 3 PART SPEC 07262

DIVISION 7 MARFLEX 5000 FLUID APPLIED AIR & VAPOR BARRIER - 3 PART SPEC 07262 Marflex Building Solutions 6866 Chrisman Lane / Middletown, OH 45042 Phone: (800) 498-1411 / Phone: (513) 422-7285 Fax: (513) 422-7282 E-mail: technicalsupport@mar-flex.com www.mar-flex.com This specification

More information

SECTION FLUID-APPLIED WATERPROOFING

SECTION FLUID-APPLIED WATERPROOFING SECTION 07140 FLUID-APPLIED WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied rubberized asphalt and/or elastomeric membrane waterproofing; and surface dusting and/or protective

More information

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL 13686.00 SECTIONAL OVERHEAD DOORS 083613-1 1.1 RELATED DOCUMENTS SECTION 083613 - SECTIONAL OVERHEAD DOORS PART 1 GENERAL A. Drawings and general provisions of Contract, including General and Supplementary

More information

(Project Location) (your firm's name)

(Project Location) (your firm's name) SECTION 07 21 00 THERMAL INSULATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including the Conditions of the Contract and Division 01 Specification Sections

More information

Architectural Wall Products Guide Specifications

Architectural Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is

More information

SECTION FLUID APPLIED VAPOR PERMEABLE AIR BARRIER MEMBRANE

SECTION FLUID APPLIED VAPOR PERMEABLE AIR BARRIER MEMBRANE SECTION 07 27 26.01 FLUID APPLIED VAPOR PERMEABLE AIR BARRIER MEMBRANE SIKA SPECIFICATION NOTE: This guide specification includes test methods, materials and installation procedures for an air barrier

More information

SECTION AIR / MOISTURE / VAPOR BARRIERS 1

SECTION AIR / MOISTURE / VAPOR BARRIERS 1 SECTION 07 27 06 - AIR / MOISTURE / VAPOR BARRIERS 1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following for Contractor s choice: 1. Self-adhering modified bituminous sheet air barriers,

More information

National Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ].

National Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ]. National Master Specification (NMS) Section 07 21 16 BLANKET INSULATION Publisher: Spex.ca Page 1 Approved: 2014-12-31 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section [ ]. 1.2 REFERENCES.1 CSA Group.1

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Masonry

More information

FirstEnergy Program Overview

FirstEnergy Program Overview FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping 1 General 1.1 The bidding requirements, contracting requirements, and applicable parts of Division 1 - General Requirements, as listed in the Table of Contents, shall be included in and made a part of

More information

SECTION GENERAL REQUIREMENTS PART 1 - GENERAL I 1 GENERAL REQUIRMENTS

SECTION GENERAL REQUIREMENTS PART 1 - GENERAL I 1 GENERAL REQUIRMENTS SECTION 01 00 00 GENERAL REQUIREMENTS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Summary of Work: 1. General 2. Contract. B. Contract Considerations: 1. Schedule of values. 2. Applications for payment. 3.

More information

WeatherSmart Air Barrier Installation Guide

WeatherSmart Air Barrier Installation Guide WeatherSmart Air Barrier Installation Guide 1 The intent of this document is to provide a guide for the installation of WeatherSmart as both a Weather Resistive Barrier (W.R.B.) and an Air Barrier Material

More information

PART 6 - INSULATED WALL SYSTEMS

PART 6 - INSULATED WALL SYSTEMS System Summary This specification details the materials and installation of foamed plastic sheathing exterior to the metal stud structure. The joints and transitions are taped to facilitate an air barrier

More information

Perm-A-Barrier VPS (Vapor Permeable Sheet)

Perm-A-Barrier VPS (Vapor Permeable Sheet) VPS (Vapor Permeable Sheet) Self-adhering vapor permeable air barrier membrane Product Description VPS (Vapor Permeable Sheet) is a vapor permeable air barrier membrane consisting of a proprietary breathable

More information

SRP-AirOutshield UV Issued:

SRP-AirOutshield UV Issued: SECTION 07276: SRP-AirOutshield UV Ultra Violet (UV) resistant, Vapour Permeable Air Barrier Underlayment and Sheathing Membrane Guide Specification This specification is a guide only and may need editing

More information

SECTION PENETRATION FIRESTOPPING PART 1- GENERAL PART 2- PRODUCTS 1.1 RELATED DOCUMENTS

SECTION PENETRATION FIRESTOPPING PART 1- GENERAL PART 2- PRODUCTS 1.1 RELATED DOCUMENTS SECTION 07 8413- PENETRATION FIRESTOPPING PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION Pactiv Building Products 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 Toll Free: (800) 241-4402 Web Site: www.green-guard.com SECTION 07210 THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS

More information

SECTION INSULATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION INSULATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 072100 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION STRUCTURAL INSULATED PANELS

SECTION STRUCTURAL INSULATED PANELS SECTION 06120 STRUCTURAL INSULATED PANELS Copyright 2011-2012 Korwall Industries, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural Insulated Roof Panels. B. Structural Insulated

More information

SELF-ADHERING SHEET WATERPROOFING

SELF-ADHERING SHEET WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY SECTION 07 13 26 SELF-ADHERING SHEET WATERPROOFING A. Furnish and install modified bituminous sheet waterproofing system where shown on the drawings, as specified herein, and

More information

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)

SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) SECTION 07412 COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof.

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof. DELTA -VENT S Vapor Permeable (Breathable) Roof Underlayment Division 7 Thermal and Moisture Protection PART 1 GENERAL 1.1 SUMMARY A. This Section provides information regarding vapor permeable roof underlayment

More information

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS SECTION 074233 EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING SECTION 07 14 16 CCW-MIRASEAL @ 120 mil thickness COLD FLUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting

More information

Product and System Specifications DuPont Flashing Systems

Product and System Specifications DuPont Flashing Systems DuPont Building Innovations March 2007 4417 Lancaster Pike Chestnut Run Plaza 721 Wilmington, DE 19805 1-800-448-9835 www.construction.tyvek.com Product and System Specifications DuPont Flashing Systems

More information

BENTONITE WATERPROOFING

BENTONITE WATERPROOFING SECTION 07 17 00 BENTONITE WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install bentonite waterproofing system where shown on the drawings, as specified herein, and as needed for a complete

More information

333-90TH STREET DALY CITY. CA ADDENDUM #1 CONTRACT BID DOCUMENTS FOR DOELGER SENIOR CENTER BOILER REPLACEMENT (101 LAKE MERCED BOULEVARD)

333-90TH STREET DALY CITY. CA ADDENDUM #1 CONTRACT BID DOCUMENTS FOR DOELGER SENIOR CENTER BOILER REPLACEMENT (101 LAKE MERCED BOULEVARD) CITY OF DALYCITY 333-90TH STREET DALY CITY. CA 9401 5-1895 PHONE: (650)99 1-8000 ADDENDUM #1 CONTRACT BID DOCUMENTS FOR DOELGER SENIOR CENTER BOILER REPLACEMENT (101 LAKE MERCED BOULEVARD) IN AND FOR THE

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 071326 - SELF-ADHERING SHEET WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Meet at Project site <insert number> days before starting installation.

A. Meet at Project site <insert number> days before starting installation. SECTION 074643 - COMPOSITION SIDING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Engineered wood cladding. 2. Soffit panels. 3. Trim and fascia. 4. Sealant. 5. Weather barrier. 6. Flashing. 1.2

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL

SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL Part 1. 1.1 Description General Conditions A. Scope of Work Provide all materials, labor and equipment required for the installation

More information

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS SECTION 08620 COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Mechanically attached system with thermoplastic roofing membrane. B. Insulation, flat and tapered. C. Flashings. D.

More information

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. SECTION 08625 METAL FRAMED SKYLIGHT PART 1 GENERAL 1.01 SECTION INCLUDES: A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. B. Fabrication

More information

FIRESTOPPING & SMOKE SEALS

FIRESTOPPING & SMOKE SEALS FIRESTOPPING & SMOKE SEALS SPECIFICATION SECTION 07860 1 General 1.1 SECTION INCLUDES.1 Comply with Division 1, General Requirements and Documents referred to therein..2 It is the intent of this section

More information

Architectural Roof and Wall Products Guide Specifications

Architectural Roof and Wall Products Guide Specifications Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification

More information

SECTION Arisfor WallGuard

SECTION Arisfor WallGuard 1.1 GENERAL A. is a three component polymerized cementitious protective coating that can be applied to a variety of vertical interior and exterior substrates including: stucco, exterior gypsum sheathing,

More information

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building May 8, 2017 ADDENDUM #1 IFB 17-082 Resin Floor System For Highway Department Central District Building Addendum #1 is being issued to offer an alternate resin flooring system. 096700 FLUID-APPLIED FLOORING

More information

[Project Name] Section [ ]

[Project Name] Section [ ] Page 1 PART 1 - GENERAL 1.1 SECTION INCLUDES 1.1.1 Design, labor, products, equipment and services necessary for interior/exterior Aluminum Facade System (AFS) work, in accordance with the Contract Documents.

More information

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING SECTION 07143 CCW-MIRASEAL @ 120 mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting

More information

DIVISION 7-THERMAL AND MOISTURE PROTECTION

DIVISION 7-THERMAL AND MOISTURE PROTECTION DIVISION 7 - THERMAL AND MOISTURE PROTECTION Page 1 of 28 07100 DAMPROOFING PART 1 GENERAL A. PREPARATION 1. Make all sub-surfaces free from material projections, dust, foreign materials, and any other

More information

SECTION METAL ROOF AND SOFFIT PANELS

SECTION METAL ROOF AND SOFFIT PANELS Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for

More information

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of

More information

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING SECTION 07 13 52 MODIFIED BITUMINOUS SHEET WATERPROOFING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior

More information

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior

More information

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING SECTION 07143 CCW-MIRASEAL @ 120 mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 061600 - SHEATHING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ReCote Finish System over Concrete

ReCote Finish System over Concrete Part 1 General 1.01 GENERAL A. The Master Wall ReCote Finish System for smooth precast and cast in place concrete consists of an acrylic primer and ReCote acrylic finish. When needed an acrylic modified

More information

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures. SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1

More information

LOG COLLEGE MIDDLE SCHOOL

LOG COLLEGE MIDDLE SCHOOL PART 1-GENERAL 1.1 SUMMARY A. This section includes the following: 1. Curb-mounted plastic glazed skylights. B. Refer to roofing system sections for roofing accessories to be built into the roofing system

More information

Architectural Roof Products Guide Specifications

Architectural Roof Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification

More information

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures. SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1

More information

A. Manufacturer: A firm that produces primary glass or fabricated glass as defined in referenced glazing publications.

A. Manufacturer: A firm that produces primary glass or fabricated glass as defined in referenced glazing publications. SECTION 08800 - GLAZING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier

BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier Backstop NT - Texture Specifications DRYVIT SYSTEMS CANADA MANUFACTURER S SPECIFICATION SECTION 07240 BACKSTOP NT -

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance www.epa.gov/iaq/moisture Foundations Issue Building foundations are vulnerable to moisture problems for a number of reasons, including: Water from rain and from plumbing leaks is drawn by gravity to foundations,

More information

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 13 52 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

SECTION FLUID-APPLIED WEATHER AND AIR BARRIER SYSTEM FOR VENTILATED CAVITY

SECTION FLUID-APPLIED WEATHER AND AIR BARRIER SYSTEM FOR VENTILATED CAVITY SECTION 07 27 27 FLUID-APPLIED WEATHER AND AIR BARRIER SYSTEM FOR VENTILATED CAVITY SPECIFIER NOTE: THIS SECTION IS INTENDED FOR A COMPLETE BUILDING ENVELOPE BARRIER APPLICATION, INCLUDING VENTILLATED

More information

SECTION BUILT-UP BITUMINOUS WATERPROOFING

SECTION BUILT-UP BITUMINOUS WATERPROOFING SECTION 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING SPEC WRITER NOTE: Delete any item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section

More information

A. Source Limitations: Obtain each type of building insulation through one source.

A. Source Limitations: Obtain each type of building insulation through one source. SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION FIRE RESISTIVE JOINT SYSTEMS

SECTION FIRE RESISTIVE JOINT SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 07 84 43 FIRE RESISTIVE JOINT SYSTEMS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Application Specification: GacoOnePass F1850

Application Specification: GacoOnePass F1850 Application Specification: GacoOnePass F1850 Two Pound Closed Cell Foam March 2017 Division: 07 21 19 GacoOnePass F1850 Closed-Cell Spray Polyurethane Foam Insulation GUIDE SPECIFICATION PART 1 GENERAL

More information

LOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS

LOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS SECTION 07.2419 - WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. EIFS-clad drainage-wall assemblies that are field applied over substrate.

More information