FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT424 4 Inch Thick Ready Traps Page 1 of 3

Size: px
Start display at page:

Download "FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT424 4 Inch Thick Ready Traps Page 1 of 3"

Transcription

1 FOR: Ready Acoustics LLC Sound Absorption Test Elk River, MN RAL -A ON: RT424 4 Inch Thick Ready Traps Page 1 of 3 CONDUCTED: 25 May 2006 TEST METHOD The test method conformed explicitly with the requirements of the ASTM Standard Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method: ASTM C423-02a and E Riverbank Acoustical Laboratories has been accredited by the U.S. Department of Commerce, National Institute of Standards and Technology (NIST) under the National Voluntary Laboratory Accreditation Program (NVLAP) for this test procedure (NVLAP Lab Code: ). A description of the measuring procedure and room qualifications is available separately. DESCRIPTION OF THE SPECIMEN The test specimen was designated by the manufacturer as RT424 4 inch thick Ready Traps. The specimen consisted of eight (8) units. Each unit as measured was nominally 610 mm (24 in.) wide by 1.22 m (48 in.) long and 102 mm (4 in.) thick. The specimen was tested in the laboratory's 292 m 3 (10,311 ft 3 ) test chamber. The manufacturer's description of the specimen was as follows: Each unit consisted of 2 pieces of 2 inch thick Owens Corning insulation 703, 3 PCF wrapped in polyester acoustical stretched suede. A visual inspection verified the manufacturer's description of the specimen. The weight of the entire specimen as measured was 29 kg (64.25 lbs), an average of 3.6 kg (8 lbs) per panel. The room temperature at the time of the test was 22ºC (71ºF) and 64±2% relative humidity. MOUNTING J Seven panels were distributed about the test chamber as follows: Three units each on the south and north walls and one unit on the west wall. Respective to each wall surface the panels were located at a 45º angle supported at both the wall and floor with the long dimension of the panel parallel to the wall-floor intersection. The panels were located nominally 203 mm (8 in.) apart. An eighth panel was located at a nominal 45º angle in the southwest corner of the room. The panel was suspended vertically with bottom edge hanging 622 mm (24.5 in.) from the test room floor. The sides of the face of the panel were butted against the south and west wall surfaces.

2 Ready Acoustics LLC RAL -A May 2006 Page 2 of 3 TEST RESULTS 1/3 Octave Center Frequency (Hz) Absorption Sabins/Unit Total Absorption In Sabins ** ** ** ** ** ** Tested by Approved by Marc Sciaky David L. Moyer Senior Technician Laboratory Manager

3 SOUND ABSORPTION REPORT RAL-A Page 3 of 3

4 1512 S. Batavia Avenue Geneva, Illinois Ph: Fax Founded in 1918 by Wallace Clement Sabine Appendix to Sound Absorption Test: RAL -A Attachment No. of Pages Specimen Mounting Details 1 Specimen Mounting Room Layout 1 Extended Frequencies 1 Measurement Uncertainty 1

5 Mounting Detail TEST NUMBER: TEST DATE: CLIENT: DESIGNATION: DIMENSIONS: NUMBER OF UNITS: RAL -A MAY 25, 2006 Ready Acoustics LLC RT424 4 Inch Thick Ready Traps 24" x 48" x 4" 8 3 specimens each on the south and north wall with nominal 8 spacing between specimens. 1 specimen on west wall. 1 specimen in the southwest corner vertically oriented with bottom edge a nominal 24.5 above test room floor [nominal 18 above 6.5 floor ledge]. All specimens 45 degree angle to wall with the backside long axis edges resting against the test room wall / floor. See figures 1 & 2 below. Figure 1 Figure 2 ADDITIONAL INFORMATION IS PROVIDED ON THE ATTACHED FLOOR DIAGRAM PAGE RALA Appendix Page 1 of 4

6 RALA Appendix Page 2 of 4

7 FOR: Ready Acoustics LLC An Appendix To Elk River, MN RAL-A ON: RT424 4 Inch Thick Ready Traps CONDUCTED: 25 May 2006 SUBJECT: Additional Frequency Data for Absorption Testing As requested by the client, sound absorption values were calculated at additional test frequencies. Although the measurements were made in accordance with the procedures described in ASTM C423-02a, they do not qualify as part of the standard. Since the results are representative of the test environment only, they are unofficial and intended for research and development guidelines rather than for commercial purposes. The sound absorption values at additional frequencies were as follows: RAL-A /3 Octave Center Absorption Total Absorption (Hz) Sabins/Unit Sabins RALA Appendix Page 3 of 4

8 FOR: Ready Acoustics LLC An Appendix To Elk River, MN RAL-A ON: RT424 4 Inch Thick Ready Traps CONDUCTED: 25 May 2006 SUBJECT: Additional Measurement Uncertainty Data As requested by the client, the uncertainties of the measured sound absorption values were calculated and are presented below. The absorption of the test specimen contains the combined uncertainties of the two room absorptions: the absorption of the empty room and the absorption of the room containing the test specimen. For the total number of 80 decays conducted for both the empty room and the room containing the test specimen, the standard deviation of the decay time was determined and used with the appropriate t-distribution factor and the mean to derive the 95% confidence limits. The uncertainties were combined using the usual "root-sum-of-squares" method. Room uncertainties are used internally for quality control purposes although these uncertainties are not established as criteria for conducting the test. More information regarding room qualifications, reproducibility, R, and repeatability, r, can be found in the current ASTM C423 standard. 1/3 Octave Center Frequency Absorption Per Unit Total Absorption (Hz) (Sabins) (Sabins) % Uncertainty With 95% Confidence RALA Appendix Page 4 of 4

FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT426 6 Inch Thick Ready Traps Page 1 of 3

FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT426 6 Inch Thick Ready Traps Page 1 of 3 FOR: Ready Acoustics LLC Sound Absorption Test Elk River, MN RAL -A06-143 ON: RT426 6 Inch Thick Ready Traps Page 1 of 3 CONDUCTED: 25 May 2006 TEST METHOD The test method conformed explicitly with the

More information

CONDUCTED: 28 November 2012 Page 1 of 5

CONDUCTED: 28 November 2012 Page 1 of 5 FOR: Guayaquil, Ecuador Sound Absorption CONDUCTED: 28 November 2012 Page 1 of 5 ON: Acoustical Panels TEST METHOD The test method conformed explicitly with the requirements of the ASTM Standard Test Method

More information

CONDUCTED: Page 1 of 6

CONDUCTED: Page 1 of 6 FOR: Auralex Acoustics, Inc. Indianapolis, IN. Sound Absorption CONDUCTED: 2014-11-18 Page 1 of 6 ON: Deep 6 Bass Trap Panel TEST METHOD The test method conformed explicitly with the requirements of the

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Owatonna, MN. Sound Absorption CONDUCTED: 2014-12-16 Page 1 of 6 ON: Large Motorized Enclosure - Retractable Drapery - Outer Fabric is 22oz. Encore Velour - 4" Airspace - Inner Fabric is Quilted Material

More information

CONDUCTED: 1 August 2013 Page 1 of 7. ON: #22 - N3 Web Perforated Metal Deck pcf Fiberglass 3.25"x3" - 2" Poly ISO Board

CONDUCTED: 1 August 2013 Page 1 of 7. ON: #22 - N3 Web Perforated Metal Deck pcf Fiberglass 3.25x3 - 2 Poly ISO Board FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 1 August 2013 Page 1 of 7 ON: #22 - N3 Web Perforated Metal Deck - 0.75pcf Fiberglass 3.25"x3" - 2" Poly ISO Board TEST METHOD The test

More information

CONDUCTED: 21 August 2013 Page 1 of 7. ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25"x1.5" over 2" Poly ISO Board

CONDUCTED: 21 August 2013 Page 1 of 7. ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25x1.5 over 2 Poly ISO Board FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 21 August 2013 Page 1 of 7 ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25"x1.5" over 2" Poly ISO Board TEST

More information

CONDUCTED: Page 1 of 6

CONDUCTED: Page 1 of 6 FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-07 Page 1 of 6 ON: 2.0 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Plain Fiberglass - 2" Rigid Fiberglass

More information

CONDUCTED: 26 November 2013 Page 1 of 6

CONDUCTED: 26 November 2013 Page 1 of 6 FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Audimute Isolé Plus External Barrier Sheet TEST METHOD The test method conformed explicitly with the

More information

CONDUCTED: Page 1 of 6

CONDUCTED: Page 1 of 6 FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-21 Page 1 of 6 ON: 3.5 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Encapsulated Fiberglass - 2" Rigid

More information

CONDUCTED: 26 November 2013 Page 1 of 6

CONDUCTED: 26 November 2013 Page 1 of 6 FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Rigid eco-c-tex 2' x 2' Ice Cube Audimute Acoustic Coating TEST METHOD The test method conformed explicitly

More information

CONDUCTED: 19 August 2013 Page 1 of 7. ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25" x 1.5" over 2" Poly ISO Board

CONDUCTED: 19 August 2013 Page 1 of 7. ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25 x 1.5 over 2 Poly ISO Board FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 19 August 2013 Page 1 of 7 ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25" x 1.5" over 2" Poly ISO Board TEST METHOD The test method conformed

More information

CONDUCTED: Page 1 of 6

CONDUCTED: Page 1 of 6 FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-07 Page 1 of 6 ON: 2.0 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Encapsulated Fiberglass - 2" Poly

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: St. Louis, MO. Sound Absorption CONDUCTED: 2015-04-08 Page 1 of 7 ON: Acoustical Wrapped Panel(AWP) - 2 Inch Truetone with Polyester Svelte Face TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

CONDUCTED: 26 February 2014 Page 1 of 6

CONDUCTED: 26 February 2014 Page 1 of 6 FOR: Phoneix, AZ. Sound Absorption CONDUCTED: 26 February 2014 Page 1 of 6 ON: #46 - B36 Web Perforated Metal Deck - Plain 0.75pcf Fiberglass 2.375"x1.5" Over 0.5" DensDeck over 2"Poly ISO Board TEST METHOD

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Indianapolis, IN. Sound Absorption CONDUCTED: 2015-11-05 Page 1 of 7 ON: Studio 6 Foam Panel TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-09-09 Page 1 of 7 ON: D-GIK (24"x48" panels) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute

More information

CONDUCTED: 26 February 2014 Page 1 of 6

CONDUCTED: 26 February 2014 Page 1 of 6 FOR: Phoenix, AZ. Sound Absorption CONDUCTED: 26 February 2014 Page 1 of 6 ON: #43 - N24 Web Perforated Metal Deck - Plain 0.75pcf Fiberglass 2.375"x3" Over 0.5" DensDeck over 2"Poly ISO Board TEST METHOD

More information

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-28 Page 1 of 9 ON: BioMontage Panels, Pole Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 8 ON: R_1 76778 D01-0445B EFSL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 9 ON: R_1 76437 11634-12A EFFL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: AcoustiMac, LLC Tampa, FL. Sound Absorption CONDUCTED: 2015-09-14 Page 1 of 9 ON: Sound Lock/Space Divider/Partition - Wood Framed Sound Proofing Panel - Fabric Both Sides TEST METHOD Riverbank Acoustical

More information

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-25 Page 1 of 9 ON: BioMontage Panels - Reindeer Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of

More information

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Sustainable Poplar Bark

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Sustainable Poplar Bark CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-27 Page 1 of 9 ON: BioMontage Panels, Sustainable Poplar Bark TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Elgin, IL Sound Absorption CONDUCTED: 2016-05-31 Page 1 of 7 ON: Rigid PET felt board TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute

More information

KINETICS NOISE CONTROL TEST REPORT #AT001073

KINETICS NOISE CONTROL TEST REPORT #AT001073 KINETICS NOISE CONTROL TEST REPORT #AT001073 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 63 TESTING AGENCY & REPORT NUMBER: o RIVERBANK ACOUSTICAL LABORATORIES o RAL TL06-048

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: St. Louis, MO. Sound Absorption CONDUCTED: 2015-02-19 Page 1 of 7 ON: 1" Truetone Acoustical Wrapped Panels (On 1/8" Spacers) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S.

More information

A L I O N Technical Center. Test Report. SPONSOR: a-light Architectural Lighting

A L I O N Technical Center. Test Report. SPONSOR: a-light Architectural Lighting SPONSOR: Oceanside, CA Sound Absorption CONDUCTED: 2019-03-06 Page 1 of 7 ON: ABH-4', spaced 48 in. on center, 21.5 in. from test surface TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Beachwood, OH Sound Absorption CONDUCTED: 2016-06-29 Page 1 of 7 ON: eco-c-tex (1" nominal thickness) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Lebanon, PA Sound Transmission Loss CONDUCTED: 2017-07-12 Page 1 of 9 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-045 STC 56 IIC 73 CONSTRUCTION Carpet and Pad 3/4 T&G OSB Subfloor 11-1/4" Deep Open Web Truss @ 24" OC R-11

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-15 Page 1 of 7 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

DIRECT FIX TO STEEL STUD Toll Free (866) RAL Assembly STC 58

DIRECT FIX TO STEEL STUD Toll Free (866) RAL Assembly STC 58 WALL ASSEMBLY DIRECT FIX TO STEEL STUD Toll Free (866) 774-2100 WWW.PAC-INTL.COM RAL 05-013 Assembly STC 58 58 STC RAL 05-013 STC CONSTRUCTION * 1 layer 5/8" Gypsum * 3-5/8" Steel Stud at 24" oc. * R-19

More information

FOR: LATICRETE International, Inc. Impact Sound Transmission Test

FOR: LATICRETE International, Inc. Impact Sound Transmission Test FOR: LATICRETE International, Inc. Impact Sound Transmission Test Bethany, CT ON: Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs with Insulated

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Beachwood, OH Impact Sound Transmission CONDUCTED: 2017-11-15 Page 1 of 8 ON: LVT flooring over Peacemaker Soundproofing Underlayment over 8" Concrete Slab No Ceiling TEST METHOD Riverbank Acoustical

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-22 Page 1 of 8 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 Over 3.5" R-13 Fiberglass TEST METHOD Riverbank Acoustical

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-20 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1B Silicone Compression Seal System - Double Installation in

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-14 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1C Silicone Compression Seal System - Double Installation in

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 8 ON: KNM-100B Limp Mass Vinyl TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-044 STC 54 IIC 52 CONSTRUCTION Hardwood Flooring 1/16" Foam Underlayment 3/4 T&G OSB Subfloor 11-1/4" Deep

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: AcoustiMac, LLC Tampa, FL. Sound Transmission Loss CONDUCTED: 2015-09-14 Page 1 of 8 ON: Sound Lock (Window+Door Sound Proofing Panel) Fabric Wrapped Panel - Wood Backing - Wood Frame TEST METHOD

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 9 ON: KNM-100AL Limp Mass Vinyl with Reinforced Aluminum Foil Face TEST METHOD Riverbank Acoustical Laboratories is accredited by

More information

Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008

Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008 FOR: LATICRETE International, Inc. Bethany, CT Floor Covering Impact Reduction Test ON: Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs Page

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN08-016 CONSTRUCTION Sheet Vinyl 1/2 Wood Underlayment 5/8 Plywood Subfloor (*L513 3/4 Ply) 2" X 10" Solid Wood Joist

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Bethany, CT. Impact Sound Transmission CONDUCTED: 2015-09-11 Page 1 of 7 ON: 5/16 inch Porcelain Tile - Fracture Ban 40 Peel and Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit with Absorbar Impact Absorption Muntins + Absorbud Impact Absorption Intersects TEST METHOD Riverbank

More information

ACOUSTICAL LABORATORIES

ACOUSTICAL LABORATORIES An AL IO N Technical Center RIVERBANK.ALIONSCIENCE.COM FOR: Tampa, FL Sound Transmission Loss CONDUCTED: Page 1 of 10 ON: Dbl. metal std. wall, 18 ga. 6"studs 24"oc, 2" Air gap, Dbl lyr 5/8" Type X (Sor.)

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Bethany, CT. Impact Sound Transmission CONDUCTED: 2015-07-30 Page 1 of 8 ON: 5/16 inch Porcelain Tile - Fracture Ban 90 Peel & Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Bethany, CT. Sound Transmission Loss CONDUCTED: 2015-09-11 Page 1 of 7 ON: 5/16 inch Porcelain Tile - Fracture Ban 40 Peel and Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Denver, Colorado Impact Sound Transmission RAL-IN16-035 CONDUCTED: 2016-11-01 Page 1 of 7 ON: Porcelain Tile flooring - Thinset Mortar - Whisper Mat underlayment - 8 inch Concrete Slabs - No Ceiling

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Cambridge, Ontario. Sound Transmission Loss CONDUCTED: 2015-04-15 Page 1 of 8 ON: dbnr Nois-eNvelope Panel A4 (Perforations Face Source) TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test

FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO

More information

FLOOR CEILING ASSEMBLY

FLOOR CEILING ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN09-012 Toll Free (866) 774-2100 WWW.PAC-INTL.COM Fire Resistance Ratings CONSTRUCTION 3/8" HARDWOOD FLOORING VAPOR BARRIER 3/4 LT WT CONCRETE

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB TYPE: Acoustic Baffles Sample ID Number & Sample Description D9015.01 Series/Model 9100AB REVRB,

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System TYPE: Upholstered Panel Summary of Test Results Sample ID Number & Sample Description 1/3 Octave

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB TYPE: Acoustical Wall Panel Summary of Test Results Sample ID Number & Sample Description D9013.01

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES TYPE: Acoustic Panels Summary of Test Results Data File No. 1/3 Octave Sound Absorption

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4 Weltless. TYPE: Stretch Fabric Wall System ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless TYPE: Stretch Fabric Wall System Summary of Test Results Sample ID Number & Sample Description 1/3

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1 FABRI TACK ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK TYPE: Tackable Acoustic Core Material with Guilford of Maine FR 701 Fabric Sample ID Number & Sample

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4 Fabri Trak ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak TYPE: Upholstered Panel System with 1-1/4" Fabri Tack Summary of Test Results Sample ID Number

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan TYPE: Ceiling System Summary of Test Results Sample ID Number & Sample Description C8714.01 Series/Model

More information

Why Reported Acoustic Performance Can Vary Between Panel Manufacturers

Why Reported Acoustic Performance Can Vary Between Panel Manufacturers Why Reported Acoustic Performance Can Vary Between Panel Manufacturers Typical Industry Standard Acoustic Panel Components The industry standard fiberglass acoustic insulation is a nominal 6-7 PCF density

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM. RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT 9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON 1000 SERIES SKU 1113-6 CROSS PIECE WOOD GRILLES WITH FIBERGLASS DUCT LINER REPORT NUMBER H5145.04-303-11

More information

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON OMNIASCREEN, ROLLER SHADE FABRIC REPORT NUMBER I7377.01-113-11-R0 TEST DATE 08/14/18 ISSUE DATE 09/04/18

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

INTRODUCTION SPECIMEN DESCRIPTION

INTRODUCTION SPECIMEN DESCRIPTION INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel E7002.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to DFB SALES Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel Type: Absorption Panel Summary of Test Results Data File

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6# G9534.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6# TYPE: 1" (25.4 mm) Thick Acoustical Fiberglass Summary of Test

More information

BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT

BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON BENETTIMOSS WALL PANELS REPORT NUMBER H6047.01-303-11 R0 TEST DATE 10/20/17 ISSUE DATE 11/13/17 RECORD

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using

More information

KINETICS NOISE CONTROL TEST REPORT #AT001052

KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

Intertek Testing Services

Intertek Testing Services Intertek Testing Services 3933 U.S. Rt. 11 Cortland, NY 13045-0950 Phone: 607-75~-6711 Fax: 607-758-6506 Intertek Testing Services For The Scope of Accreditation Job No. 3034879 January 15, 2003 REPORT

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

Intertek Testing Services

Intertek Testing Services Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A

More information

Acoustical Data kraft paper softwall + softblock modular system

Acoustical Data kraft paper softwall + softblock modular system Acoustical Data kraft paper softwall + softblock modular system molo design, ltd 1470 Venables Street Vancouver, B.C. Canada V5L 2G7 t +1 604 696 2501 f +1 604 685 0342 info@molodesign.com www.molodesign.com

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON A 2" NOVAWALL SQUARE EDGE SYSTEM REPORT NUMBER H8708.02-113-11-R0 TEST DATE 12/28/17 ISSUE

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC

More information

Roomtmove 3/9 Church Road MAddington WA 6109

Roomtmove 3/9 Church Road MAddington WA 6109 Report ALA 14-084-1 Measurement of the Sound Absorption in a Reverberation Room ENDUROPANEL 40/10 Perf 18mm slotted ply Tested to AS / ISO 354-2006 Revision 1 Roomtmove 3/9 Church Road MAddington WA 6109

More information

Rose Brand Acoustical Test Report for: 54" IFR 32 oz. Royale. 100% Fullness Pleated Panel

Rose Brand Acoustical Test Report for: 54 IFR 32 oz. Royale. 100% Fullness Pleated Panel Rose Brand Acoustical Test Report for: 54" IFR 32 oz. Royale 100% Fullness Pleated Panel customerservicerosebrand.com 800.223.1624 NÊCwøg Acoustical Testing TESTING SEßVICES ACÍ}USTICAT. FIRE. STRUCTURAI.

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source

More information

Rose Brand Acoustical Test Report for: 62" IFR 15 oz. Encore. 100% Fullness Pleated Panel

Rose Brand Acoustical Test Report for: 62 IFR 15 oz. Encore. 100% Fullness Pleated Panel Rose Brand Acoustical Test Report for: 62" IFR 15 oz. Encore 100% Fullness Pleated Panel customerservice@rosebrand.com 800.223.1624 NGC'o@@ê Acoustical Testing TESTING SEßVICES ACl]USTICAL. FIRE. STRUCTIJRAI-.

More information

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 FOR THE SCOPE OF LAB CODE 100402-0. Order No. 100667931 Date: May 23, 2012 REPORT NO. 100667931CRT-001a SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION

More information

Rose Brand Acoustical Test Report for: Rhapsody Fabric Panels

Rose Brand Acoustical Test Report for: Rhapsody Fabric Panels Rose Brand Acoustical Test Report for: Rhapsody Fabric Panels customerservicerosebrand.com 800.223.1624 NGCøøg TESTING SERVICES AC0USTICAt. FIR[. STRIJCIURAL. Al' A[YTlCAt'. ß{v Lab Code 2OO29l Page I

More information