FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT424 4 Inch Thick Ready Traps Page 1 of 3
|
|
- Candace Carter
- 5 years ago
- Views:
Transcription
1 FOR: Ready Acoustics LLC Sound Absorption Test Elk River, MN RAL -A ON: RT424 4 Inch Thick Ready Traps Page 1 of 3 CONDUCTED: 25 May 2006 TEST METHOD The test method conformed explicitly with the requirements of the ASTM Standard Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method: ASTM C423-02a and E Riverbank Acoustical Laboratories has been accredited by the U.S. Department of Commerce, National Institute of Standards and Technology (NIST) under the National Voluntary Laboratory Accreditation Program (NVLAP) for this test procedure (NVLAP Lab Code: ). A description of the measuring procedure and room qualifications is available separately. DESCRIPTION OF THE SPECIMEN The test specimen was designated by the manufacturer as RT424 4 inch thick Ready Traps. The specimen consisted of eight (8) units. Each unit as measured was nominally 610 mm (24 in.) wide by 1.22 m (48 in.) long and 102 mm (4 in.) thick. The specimen was tested in the laboratory's 292 m 3 (10,311 ft 3 ) test chamber. The manufacturer's description of the specimen was as follows: Each unit consisted of 2 pieces of 2 inch thick Owens Corning insulation 703, 3 PCF wrapped in polyester acoustical stretched suede. A visual inspection verified the manufacturer's description of the specimen. The weight of the entire specimen as measured was 29 kg (64.25 lbs), an average of 3.6 kg (8 lbs) per panel. The room temperature at the time of the test was 22ºC (71ºF) and 64±2% relative humidity. MOUNTING J Seven panels were distributed about the test chamber as follows: Three units each on the south and north walls and one unit on the west wall. Respective to each wall surface the panels were located at a 45º angle supported at both the wall and floor with the long dimension of the panel parallel to the wall-floor intersection. The panels were located nominally 203 mm (8 in.) apart. An eighth panel was located at a nominal 45º angle in the southwest corner of the room. The panel was suspended vertically with bottom edge hanging 622 mm (24.5 in.) from the test room floor. The sides of the face of the panel were butted against the south and west wall surfaces.
2 Ready Acoustics LLC RAL -A May 2006 Page 2 of 3 TEST RESULTS 1/3 Octave Center Frequency (Hz) Absorption Sabins/Unit Total Absorption In Sabins ** ** ** ** ** ** Tested by Approved by Marc Sciaky David L. Moyer Senior Technician Laboratory Manager
3 SOUND ABSORPTION REPORT RAL-A Page 3 of 3
4 1512 S. Batavia Avenue Geneva, Illinois Ph: Fax Founded in 1918 by Wallace Clement Sabine Appendix to Sound Absorption Test: RAL -A Attachment No. of Pages Specimen Mounting Details 1 Specimen Mounting Room Layout 1 Extended Frequencies 1 Measurement Uncertainty 1
5 Mounting Detail TEST NUMBER: TEST DATE: CLIENT: DESIGNATION: DIMENSIONS: NUMBER OF UNITS: RAL -A MAY 25, 2006 Ready Acoustics LLC RT424 4 Inch Thick Ready Traps 24" x 48" x 4" 8 3 specimens each on the south and north wall with nominal 8 spacing between specimens. 1 specimen on west wall. 1 specimen in the southwest corner vertically oriented with bottom edge a nominal 24.5 above test room floor [nominal 18 above 6.5 floor ledge]. All specimens 45 degree angle to wall with the backside long axis edges resting against the test room wall / floor. See figures 1 & 2 below. Figure 1 Figure 2 ADDITIONAL INFORMATION IS PROVIDED ON THE ATTACHED FLOOR DIAGRAM PAGE RALA Appendix Page 1 of 4
6 RALA Appendix Page 2 of 4
7 FOR: Ready Acoustics LLC An Appendix To Elk River, MN RAL-A ON: RT424 4 Inch Thick Ready Traps CONDUCTED: 25 May 2006 SUBJECT: Additional Frequency Data for Absorption Testing As requested by the client, sound absorption values were calculated at additional test frequencies. Although the measurements were made in accordance with the procedures described in ASTM C423-02a, they do not qualify as part of the standard. Since the results are representative of the test environment only, they are unofficial and intended for research and development guidelines rather than for commercial purposes. The sound absorption values at additional frequencies were as follows: RAL-A /3 Octave Center Absorption Total Absorption (Hz) Sabins/Unit Sabins RALA Appendix Page 3 of 4
8 FOR: Ready Acoustics LLC An Appendix To Elk River, MN RAL-A ON: RT424 4 Inch Thick Ready Traps CONDUCTED: 25 May 2006 SUBJECT: Additional Measurement Uncertainty Data As requested by the client, the uncertainties of the measured sound absorption values were calculated and are presented below. The absorption of the test specimen contains the combined uncertainties of the two room absorptions: the absorption of the empty room and the absorption of the room containing the test specimen. For the total number of 80 decays conducted for both the empty room and the room containing the test specimen, the standard deviation of the decay time was determined and used with the appropriate t-distribution factor and the mean to derive the 95% confidence limits. The uncertainties were combined using the usual "root-sum-of-squares" method. Room uncertainties are used internally for quality control purposes although these uncertainties are not established as criteria for conducting the test. More information regarding room qualifications, reproducibility, R, and repeatability, r, can be found in the current ASTM C423 standard. 1/3 Octave Center Frequency Absorption Per Unit Total Absorption (Hz) (Sabins) (Sabins) % Uncertainty With 95% Confidence RALA Appendix Page 4 of 4
FOR: Ready Acoustics LLC Sound Absorption Test. ON: RT426 6 Inch Thick Ready Traps Page 1 of 3
FOR: Ready Acoustics LLC Sound Absorption Test Elk River, MN RAL -A06-143 ON: RT426 6 Inch Thick Ready Traps Page 1 of 3 CONDUCTED: 25 May 2006 TEST METHOD The test method conformed explicitly with the
More informationCONDUCTED: 28 November 2012 Page 1 of 5
FOR: Guayaquil, Ecuador Sound Absorption CONDUCTED: 28 November 2012 Page 1 of 5 ON: Acoustical Panels TEST METHOD The test method conformed explicitly with the requirements of the ASTM Standard Test Method
More informationCONDUCTED: Page 1 of 6
FOR: Auralex Acoustics, Inc. Indianapolis, IN. Sound Absorption CONDUCTED: 2014-11-18 Page 1 of 6 ON: Deep 6 Bass Trap Panel TEST METHOD The test method conformed explicitly with the requirements of the
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Owatonna, MN. Sound Absorption CONDUCTED: 2014-12-16 Page 1 of 6 ON: Large Motorized Enclosure - Retractable Drapery - Outer Fabric is 22oz. Encore Velour - 4" Airspace - Inner Fabric is Quilted Material
More informationCONDUCTED: 1 August 2013 Page 1 of 7. ON: #22 - N3 Web Perforated Metal Deck pcf Fiberglass 3.25"x3" - 2" Poly ISO Board
FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 1 August 2013 Page 1 of 7 ON: #22 - N3 Web Perforated Metal Deck - 0.75pcf Fiberglass 3.25"x3" - 2" Poly ISO Board TEST METHOD The test
More informationCONDUCTED: 21 August 2013 Page 1 of 7. ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25"x1.5" over 2" Poly ISO Board
FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 21 August 2013 Page 1 of 7 ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25"x1.5" over 2" Poly ISO Board TEST
More informationCONDUCTED: Page 1 of 6
FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-07 Page 1 of 6 ON: 2.0 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Plain Fiberglass - 2" Rigid Fiberglass
More informationCONDUCTED: 26 November 2013 Page 1 of 6
FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Audimute Isolé Plus External Barrier Sheet TEST METHOD The test method conformed explicitly with the
More informationCONDUCTED: Page 1 of 6
FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-21 Page 1 of 6 ON: 3.5 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Encapsulated Fiberglass - 2" Rigid
More informationCONDUCTED: 26 November 2013 Page 1 of 6
FOR: Audimute Soundproofing Beachwood, OH Sound Absorption CONDUCTED: 26 November 2013 Page 1 of 6 ON: Rigid eco-c-tex 2' x 2' Ice Cube Audimute Acoustic Coating TEST METHOD The test method conformed explicitly
More informationCONDUCTED: 19 August 2013 Page 1 of 7. ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25" x 1.5" over 2" Poly ISO Board
FOR: Verco Decking, Inc. Phoenix, AZ Sound Absorption CONDUCTED: 19 August 2013 Page 1 of 7 ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25" x 1.5" over 2" Poly ISO Board TEST METHOD The test method conformed
More informationCONDUCTED: Page 1 of 6
FOR: Nucor / Vulcraft Group Norfolk, NE. Sound Absorption CONDUCTED: 2014-08-07 Page 1 of 6 ON: 2.0 DA 20 ga. Perforated Metal Deck (Plastic Mesh) Insulated with 3.0 pcf Encapsulated Fiberglass - 2" Poly
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: St. Louis, MO. Sound Absorption CONDUCTED: 2015-04-08 Page 1 of 7 ON: Acoustical Wrapped Panel(AWP) - 2 Inch Truetone with Polyester Svelte Face TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationCONDUCTED: 26 February 2014 Page 1 of 6
FOR: Phoneix, AZ. Sound Absorption CONDUCTED: 26 February 2014 Page 1 of 6 ON: #46 - B36 Web Perforated Metal Deck - Plain 0.75pcf Fiberglass 2.375"x1.5" Over 0.5" DensDeck over 2"Poly ISO Board TEST METHOD
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Indianapolis, IN. Sound Absorption CONDUCTED: 2015-11-05 Page 1 of 7 ON: Studio 6 Foam Panel TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-09-09 Page 1 of 7 ON: D-GIK (24"x48" panels) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute
More informationCONDUCTED: 26 February 2014 Page 1 of 6
FOR: Phoenix, AZ. Sound Absorption CONDUCTED: 26 February 2014 Page 1 of 6 ON: #43 - N24 Web Perforated Metal Deck - Plain 0.75pcf Fiberglass 2.375"x3" Over 0.5" DensDeck over 2"Poly ISO Board TEST METHOD
More informationA L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss
CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-28 Page 1 of 9 ON: BioMontage Panels, Pole Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,
More informationA L I O N Technical Center. Test Report
FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 8 ON: R_1 76778 D01-0445B EFSL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationA L I O N Technical Center. Test Report
FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 9 ON: R_1 76437 11634-12A EFFL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: AcoustiMac, LLC Tampa, FL. Sound Absorption CONDUCTED: 2015-09-14 Page 1 of 9 ON: Sound Lock/Space Divider/Partition - Wood Framed Sound Proofing Panel - Fabric Both Sides TEST METHOD Riverbank Acoustical
More informationA L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss
CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-25 Page 1 of 9 ON: BioMontage Panels - Reindeer Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of
More informationA L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Sustainable Poplar Bark
CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-27 Page 1 of 9 ON: BioMontage Panels, Sustainable Poplar Bark TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Elgin, IL Sound Absorption CONDUCTED: 2016-05-31 Page 1 of 7 ON: Rigid PET felt board TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute
More informationKINETICS NOISE CONTROL TEST REPORT #AT001073
KINETICS NOISE CONTROL TEST REPORT #AT001073 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 63 TESTING AGENCY & REPORT NUMBER: o RIVERBANK ACOUSTICAL LABORATORIES o RAL TL06-048
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: St. Louis, MO. Sound Absorption CONDUCTED: 2015-02-19 Page 1 of 7 ON: 1" Truetone Acoustical Wrapped Panels (On 1/8" Spacers) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S.
More informationA L I O N Technical Center. Test Report. SPONSOR: a-light Architectural Lighting
SPONSOR: Oceanside, CA Sound Absorption CONDUCTED: 2019-03-06 Page 1 of 7 ON: ABH-4', spaced 48 in. on center, 21.5 in. from test surface TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Beachwood, OH Sound Absorption CONDUCTED: 2016-06-29 Page 1 of 7 ON: eco-c-tex (1" nominal thickness) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Sound Transmission Loss CONDUCTED: 2017-07-12 Page 1 of 9 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-045 STC 56 IIC 73 CONSTRUCTION Carpet and Pad 3/4 T&G OSB Subfloor 11-1/4" Deep Open Web Truss @ 24" OC R-11
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-15 Page 1 of 7 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationDIRECT FIX TO STEEL STUD Toll Free (866) RAL Assembly STC 58
WALL ASSEMBLY DIRECT FIX TO STEEL STUD Toll Free (866) 774-2100 WWW.PAC-INTL.COM RAL 05-013 Assembly STC 58 58 STC RAL 05-013 STC CONSTRUCTION * 1 layer 5/8" Gypsum * 3-5/8" Steel Stud at 24" oc. * R-19
More informationFOR: LATICRETE International, Inc. Impact Sound Transmission Test
FOR: LATICRETE International, Inc. Impact Sound Transmission Test Bethany, CT ON: Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs with Insulated
More informationA L I O N Technical Center. Test Report
FOR: Beachwood, OH Impact Sound Transmission CONDUCTED: 2017-11-15 Page 1 of 8 ON: LVT flooring over Peacemaker Soundproofing Underlayment over 8" Concrete Slab No Ceiling TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-22 Page 1 of 8 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 Over 3.5" R-13 Fiberglass TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-20 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1B Silicone Compression Seal System - Double Installation in
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-14 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1C Silicone Compression Seal System - Double Installation in
More informationA L I O N Technical Center. Test Report
FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 8 ON: KNM-100B Limp Mass Vinyl TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-044 STC 54 IIC 52 CONSTRUCTION Hardwood Flooring 1/16" Foam Underlayment 3/4 T&G OSB Subfloor 11-1/4" Deep
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: AcoustiMac, LLC Tampa, FL. Sound Transmission Loss CONDUCTED: 2015-09-14 Page 1 of 8 ON: Sound Lock (Window+Door Sound Proofing Panel) Fabric Wrapped Panel - Wood Backing - Wood Frame TEST METHOD
More informationA L I O N Technical Center. Test Report
FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 9 ON: KNM-100AL Limp Mass Vinyl with Reinforced Aluminum Foil Face TEST METHOD Riverbank Acoustical Laboratories is accredited by
More informationCeramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008
FOR: LATICRETE International, Inc. Bethany, CT Floor Covering Impact Reduction Test ON: Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs Page
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN08-016 CONSTRUCTION Sheet Vinyl 1/2 Wood Underlayment 5/8 Plywood Subfloor (*L513 3/4 Ply) 2" X 10" Solid Wood Joist
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Bethany, CT. Impact Sound Transmission CONDUCTED: 2015-09-11 Page 1 of 7 ON: 5/16 inch Porcelain Tile - Fracture Ban 40 Peel and Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit with Absorbar Impact Absorption Muntins + Absorbud Impact Absorption Intersects TEST METHOD Riverbank
More informationACOUSTICAL LABORATORIES
An AL IO N Technical Center RIVERBANK.ALIONSCIENCE.COM FOR: Tampa, FL Sound Transmission Loss CONDUCTED: Page 1 of 10 ON: Dbl. metal std. wall, 18 ga. 6"studs 24"oc, 2" Air gap, Dbl lyr 5/8" Type X (Sor.)
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Bethany, CT. Impact Sound Transmission CONDUCTED: 2015-07-30 Page 1 of 8 ON: 5/16 inch Porcelain Tile - Fracture Ban 90 Peel & Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Bethany, CT. Sound Transmission Loss CONDUCTED: 2015-09-11 Page 1 of 7 ON: 5/16 inch Porcelain Tile - Fracture Ban 40 Peel and Stick Membrane - 6 inch Concrete Slabs TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Denver, Colorado Impact Sound Transmission RAL-IN16-035 CONDUCTED: 2016-11-01 Page 1 of 7 ON: Porcelain Tile flooring - Thinset Mortar - Whisper Mat underlayment - 8 inch Concrete Slabs - No Ceiling
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Cambridge, Ontario. Sound Transmission Loss CONDUCTED: 2015-04-15 Page 1 of 8 ON: dbnr Nois-eNvelope Panel A4 (Perforations Face Source) TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationFOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test
FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO
More informationFLOOR CEILING ASSEMBLY
FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN09-012 Toll Free (866) 774-2100 WWW.PAC-INTL.COM Fire Resistance Ratings CONSTRUCTION 3/8" HARDWOOD FLOORING VAPOR BARRIER 3/4 LT WT CONCRETE
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB TYPE: Acoustic Baffles Sample ID Number & Sample Description D9015.01 Series/Model 9100AB REVRB,
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System TYPE: Upholstered Panel Summary of Test Results Sample ID Number & Sample Description 1/3 Octave
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB TYPE: Acoustical Wall Panel Summary of Test Results Sample ID Number & Sample Description D9013.01
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES TYPE: Acoustic Panels Summary of Test Results Data File No. 1/3 Octave Sound Absorption
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless TYPE: Stretch Fabric Wall System Summary of Test Results Sample ID Number & Sample Description 1/3
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK TYPE: Tackable Acoustic Core Material with Guilford of Maine FR 701 Fabric Sample ID Number & Sample
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak TYPE: Upholstered Panel System with 1-1/4" Fabri Tack Summary of Test Results Sample ID Number
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan TYPE: Ceiling System Summary of Test Results Sample ID Number & Sample Description C8714.01 Series/Model
More informationWhy Reported Acoustic Performance Can Vary Between Panel Manufacturers
Why Reported Acoustic Performance Can Vary Between Panel Manufacturers Typical Industry Standard Acoustic Panel Components The industry standard fiberglass acoustic insulation is a nominal 6-7 PCF density
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More information9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT
9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON 1000 SERIES SKU 1113-6 CROSS PIECE WOOD GRILLES WITH FIBERGLASS DUCT LINER REPORT NUMBER H5145.04-303-11
More informationROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT
ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON OMNIASCREEN, ROLLER SHADE FABRIC REPORT NUMBER I7377.01-113-11-R0 TEST DATE 08/14/18 ISSUE DATE 09/04/18
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationINTRODUCTION SPECIMEN DESCRIPTION
INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel
E7002.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to DFB SALES Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel Type: Absorption Panel Summary of Test Results Data File
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#
G9534.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6# TYPE: 1" (25.4 mm) Thick Acoustical Fiberglass Summary of Test
More informationBENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT
BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON BENETTIMOSS WALL PANELS REPORT NUMBER H6047.01-303-11 R0 TEST DATE 10/20/17 ISSUE DATE 11/13/17 RECORD
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationAAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window
AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using
More informationKINETICS NOISE CONTROL TEST REPORT #AT001052
KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationIntertek Testing Services
Intertek Testing Services 3933 U.S. Rt. 11 Cortland, NY 13045-0950 Phone: 607-75~-6711 Fax: 607-758-6506 Intertek Testing Services For The Scope of Accreditation Job No. 3034879 January 15, 2003 REPORT
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationIntertek Testing Services
Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A
More informationAcoustical Data kraft paper softwall + softblock modular system
Acoustical Data kraft paper softwall + softblock modular system molo design, ltd 1470 Venables Street Vancouver, B.C. Canada V5L 2G7 t +1 604 696 2501 f +1 604 685 0342 info@molodesign.com www.molodesign.com
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results
More informationNOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT
NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON A 2" NOVAWALL SQUARE EDGE SYSTEM REPORT NUMBER H8708.02-113-11-R0 TEST DATE 12/28/17 ISSUE
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC
More informationRoomtmove 3/9 Church Road MAddington WA 6109
Report ALA 14-084-1 Measurement of the Sound Absorption in a Reverberation Room ENDUROPANEL 40/10 Perf 18mm slotted ply Tested to AS / ISO 354-2006 Revision 1 Roomtmove 3/9 Church Road MAddington WA 6109
More informationRose Brand Acoustical Test Report for: 54" IFR 32 oz. Royale. 100% Fullness Pleated Panel
Rose Brand Acoustical Test Report for: 54" IFR 32 oz. Royale 100% Fullness Pleated Panel customerservicerosebrand.com 800.223.1624 NÊCwøg Acoustical Testing TESTING SEßVICES ACÍ}USTICAT. FIRE. STRUCTURAI.
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source
More informationRose Brand Acoustical Test Report for: 62" IFR 15 oz. Encore. 100% Fullness Pleated Panel
Rose Brand Acoustical Test Report for: 62" IFR 15 oz. Encore 100% Fullness Pleated Panel customerservice@rosebrand.com 800.223.1624 NGC'o@@ê Acoustical Testing TESTING SEßVICES ACl]USTICAL. FIRE. STRUCTIJRAI-.
More informationREPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045
REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 FOR THE SCOPE OF LAB CODE 100402-0. Order No. 100667931 Date: May 23, 2012 REPORT NO. 100667931CRT-001a SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION
More informationRose Brand Acoustical Test Report for: Rhapsody Fabric Panels
Rose Brand Acoustical Test Report for: Rhapsody Fabric Panels customerservicerosebrand.com 800.223.1624 NGCøøg TESTING SERVICES AC0USTICAt. FIR[. STRIJCIURAL. Al' A[YTlCAt'. ß{v Lab Code 2OO29l Page I
More information