13-08 Dome venting- 5th floor walkway structural capacity
|
|
- Brice Blair
- 5 years ago
- Views:
Transcription
1 13-08 Dome venting- 5th floor walkway structural capacity Analyzed File: Walkway framing section from iam Autodesk Inventor Version: 2012 SP2 (Build , 219) Creation Date: Simulation Author: Summary: 7/30/2013, 4:25 PM S.Bauman A Structural Analysis of the 5th floor walkway to determine load capacity. Request from outside vendor performing contract work to use man-lift on walkway platform for installation and assembly of dome vent units. Reference drawings: The drawing below gives dimensions for the location of the elevation 13,784 73/4, the individual segments that make up the walkway, and specifics on structural members. The designed live load defined in the drawing is 100PSF.
2
3 Figure 1: _CFHT Dome walkway framing section and details by SNC After verifying the drawing above with the as built configuration and construction of the dome inconsistencies were found. The callouts for the structural members that make up each walkway segment were incorrect, C4 x 5.4 TYP underlined in yellow below, was not used for the construction of the walkway. How the as-built details differ from the drawing will be identified below in actual photos, the remaining details in figure 2 below seem consistent.
4 Figure 2: Close-up view of walkway framing plan Section B-B enlarged from the above drawing: The section below shows a detail of the 5 th floor walkway. Each segment is arrayed around the inside of the dome at 7.5 degrees (typical).
5
6 Figure 3: Section B-B After verifying the drawings above with the as built configuration and construction of the dome the following inconsistencies were found. In Figure 5 below one can see that the support beams for the walkway are W4 x 13 not C4 x 5.4 TYP as identified in the drawings. W4 x 13 Figure 4: Walkway main support beam, W4 X 13 (typical) The member highlighted below in yellow shows a support for the walkway. It is welded at an angle from the bottom of the W4 x 13 wide flange beam to the vertical rib member of the dome skeletal structure. The callout in the drawing is incorrect, instead a hollow tube, indentified in the yellow highlighted oval, shows the 2 STD pipe with.158 wall thickness, instead of the called out L 2 ½ x 2 ½ x ¼ angle bar.
7 Figure 5: Section A-A and detail 7, 8, 9 The support beam that spans the width of the platform segment between the Wide flange beams is a L4 x 4 x ¼ L angle and not a C4 x 5.4 TYP as depicted in the drawing. There also is not a structural beam at the termination of the platform where the railing is located.
8 L4 x 4 x ¼ 2 STD round tube,.158 wall Figure 4: Walkway plate support beam, L4 X 4 X 1/4 (typical) The photo below shows the ¼ steel checkered plate which is positioned on top of the wide flange beams, not show in the drawing is the 4 lip (toe kicks) on each side of the walkway plate. There is not s C4 x 5.4 beam positioned between the wide flange beams.
9 ¼ checkered plate TYP Figure 5: Walkway platform surface plate, ¼ thick plate all around (typ) Project Info (iproperties) Summary Title Subject Dome Venting 5ht floor structural walkway capacity
10 Author S.Bauman Manager D.Salmon Company CFHT Category Engineering verification Project Part Number Walkway framing section from Description Project Designer Engineer S.Bauman Status Design Status WorkInProgress Physical Mass Area Volume Center of Gravity lbmass in^ in^3 x= in y= in z= in Note: Physical values could be different from Physical values used by FEA reported below. Simulation:1 General objective and settings: Design Objective Single Point Simulation Type Static Analysis Last Modification Date 7/30/2013, 4:16 PM Detect and Eliminate Rigid Body Modes No Separate Stresses Across Contact Surfaces No Motion Loads Analysis No Advanced settings: Avg. Element Size (fraction of model diameter) 0.1
11 Min. Element Size (fraction of avg. size) 0.2 Grading Factor 1.5 Max. Turn Angle Create Curved Mesh Elements Use part based measure for Assembly mesh Material(s) Name General Stress Steel Mass Density Yield Strength 60 deg No Yes lbmass/in^ psi Ultimate Tensile Strength psi Young's Modulus Poisson's Ratio Shear Modulus Expansion Coefficient ksi 0.3 ul 0 ksi ul/f Stress Thermal Thermal Conductivity btu/( ft hr f ) Part Name(s) Specific Heat btu/( lbmass f ) AISC - W 4x ipt AISC - W 4x ipt Walking surface.ipt AISC - L 4 x 4 x 1_4-70 JLG 1930ES wheel footprint.ipt JLG 1930ES half wheel footprint.ipt Operating conditions Summary: The two highlighted areas below show the pressure applied to the walkway platform model from the wheels of the JLG 1930ES scissor lift. The load below is the worst case where the lift is placed on two portions of the walkway, directly at the center of the segment where the most bending and deflection takes place due to the load of the lift. The details for the JLG 1930ES lift can be found in the appendix. The following information was used for the analysis: JLG 1930ES weight: Lbs Personal weight (max platform weight capacity): 500lbs Total weight of lift: 3, Load per wheel: 812.4lbs Wheel size: 12.5 O.D. x 4 wide
12 Area of wheel on steel platform: 4 wide wheel x 2 effective wheel contact surface = 8 in^2 Pressure:1 Load Type Pressure Magnitude psi Selected Face(s) Gravity Load Type Gravity Magnitude in/s^2
13 Vector X Vector Y Vector Z in/s^ in/s^ in/s^2 Selected Face(s) Fixed Constraint:1 Constraint Type Fixed Constraint The platform is constrained at the end of the wide flange beam where it ties into the vertical rib structure of the dome skeletal structure.
14 Selected Face(s) Contacts (Bonded) Name Bonded:1 Bonded:2 Bonded:4 Bonded:5 Part Name(s) AISC - W 4x :1 Walking surface:1 AISC - W 4x :2 Walking surface:1 Walking surface:1 JLG 1930ES wheel footprint:1 Walking surface:1 JLG 1930ES wheel footprint:1
15 Bonded:6 Bonded:10 Bonded:11 Bonded:13 Bonded:14 Bonded:15 Bonded:16 Results Walking surface:1 JLG 1930ES wheel footprint:1 Walking surface:1 JLG 1930ES half wheel footprint:1 Walking surface:1 JLG 1930ES half wheel footprint:1 AISC - W 4x :1 AISC - L 2.5 x 2.5 x 1_4-70:1 AISC - W 4x :2 AISC - L 4 x 4 x 1_4-70:1 Walking surface:1 AISC - L 4 x 4 x 1_4-70:1 Walking surface:1 AISC - L 4 x 4 x 1_4-70:1 Reaction Force and Moment on Constraints Reaction Force Reaction Moment Constraint Name Magnitude Component (X,Y,Z) Magnitude Component (X,Y,Z) 0 lbforce lbforce ft Fixed Constraint: lbforce lbforce lbforce ft 0 lbforce ft Result Summary Name Minimum Maximum Volume Mass Von Mises Stress in^ lbmass 1st Principal Stress ksi 3rd Principal Stress ksi ksi ksi 0 lbforce 0 lbforce ft ksi ksi Displacement 0 in in Safety Factor ul 15 ul X Displacement Y Displacement Z Displacement in in in in in in Contact Pressure 0 ksi ksi Contact Pressure X ksi Contact Pressure Y ksi Contact Pressure Z ksi ksi ksi ksi
16 Figures The greatest stress found was at the center of the platform at the wheel loading location closest to the railing. This makes sense since it is the furthest supported edge in the platform. Von Mises Stress 1st Principal Stress
17 3rd Principal Stress
18 Displacement The largest displacement the platform sees from loading of the lift is 0.24 inches of deflection downward.
19 Safety Factor
20 X Displacement
21 Y Displacement
22 Z Displacement
23 Contact Pressure
24 Contact Pressure X
25 Contact Pressure Y
26 Contact Pressure Z
27 C:\VaultProdWorkspace\CFHT DESIGNS\10-19 OBSERVATORY BUILDING\11 ARCHITECTURAL AND STRUCTURAL\11-04 FLOORING\Walkway framing section from iam
JPods, LLC. Cost Estimate. Structural Support Systems. for 12/08/06 SHEET N 1 OF 16 CALC N
1 OF 16 12/08/06 Cost Estimate of Structural Support Systems for JPods, LLC 2 OF 16 TABLE OF CONTENTS SUBJECT: PAGE 1. Purpose.. 3 2. Methodology. 3. 3. Assumptions. 4 4. Input Data... 5 5. Loading Combinations
More informationE APPENDIX. The following problems are intended for solution using finite element. Problems for Computer Solution E.1 CHAPTER 3
E APPENDIX Problems for Computer Solution The following problems are intended for solution using finite element analysis software. In general, the problems associated with Chapters 3, 4, and 9 can be solved
More informationSET PROJECT STRUCTURAL ANALYSIS OF A TROUGH MODULE STRUCTURE, IN OPERATION AND EMERGENCY Luca Massidda
SET PROJECT STRUCTURAL ANALYSIS OF A TROUGH MODULE STRUCTURE, IN OPERATION AND EMERGENCY Luca Massidda Table of Contents Introduction... 2 Finite element analysis... 3 Model description... 3 Mirrors...
More informationPage 1 of 46 Exam 1. Exam 1 Past Exam Problems without Solutions NAME: Given Formulae: Law of Cosines: C. Law of Sines:
NAME: EXAM 1 PAST PROBLEMS WITHOUT SOLUTIONS 100 points Tuesday, September 26, 2017, 7pm to 9:30 You are allowed to use a calculator and drawing equipment, only. Formulae provided 2.5 hour time limit This
More informationES230 Strength of Materials Exam 6 - Compilation Prof. Kurtz, ES230 STRENGTH OF MATERIALS Exam 6 Wednesday, April 26, 2017, 7pm
Given Formulae Bending M/EI = 1/ = -y/ =My/I = E Beam Shear Stress = VQ/It q = VQ/I q = F/s Torsion I = ( /4)r 4 for a solid, circular shape of radius r Pressure Vessels hoop = Pr/t long = Pr/2t ES230
More informationCHAPTER III DYNAMIC BEHAVIOR OF A LABORATORY SPECIMEN
CHAPTER III DYNAMIC BEHAVIOR OF A LABORATORY SPECIMEN To address the vibration response of a long span deck floor system, an experiment using a specimen that resembles the conditions found in the in-situ
More informationJames Hauck 1 and Christine Moe 2
3479 Beam-over-Column Bracing Requirements in Continuous Steel Frame Buildings James Hauck 1 and Christine Moe 2 1 Associate Principal, Wiss, Janney, Elstner Associates, Inc., 10 South LaSalle Street,
More informationSAMPLE TC6K Elevator Design Summary. Order No PO-47201
SAMPLE TC6K Elevator Design Summary 900 RR 620 S., Ste C206 Austin TX 78734 (512) 266-6200 voice (512) 266-6210 fax SAMPLE CCR TC6K Elevator Design Summary - Elevator System Design Parameters Nominal Height
More informationStructural Engineering, Mechanics, and Materials. Preliminary Exam - Structural Design
Fall Semester 2018 Preliminary Exam - Structural Design A small building is located in downtown Berkeley. The structural system, either structural steel or reinforced concrete, comprises gravity framing
More informationADAPT-PTRC 2016 Getting Started Tutorial ADAPT-PT mode
ADAPT-PTRC 2016 Getting Started Tutorial ADAPT-PT mode Update: August 2016 Copyright ADAPT Corporation all rights reserved ADAPT-PT/RC 2016-Tutorial- 1 This ADAPT-PTRC 2016 Getting Started Tutorial is
More informationADAPT-PT 2010 Tutorial Idealization of Design Strip in ADAPT-PT
ADAPT-PT 2010 Tutorial Idealization of Design Strip in ADAPT-PT Update: April 2010 Copyright ADAPT Corporation all rights reserved ADAPT-PT 2010-Tutorial- 1 Main Toolbar Menu Bar View Toolbar Structure
More informationPro-Con Structural Study for Alternative Floor Systems October 27, 2004
Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive
More informationTECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania
TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering
More informationSTRUCTURAL STEEL FRAMING
SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical
More informationAPPENDIX B. LOAD FRAME. This Appendix will describe the philosophy in the design and operation of the loading system.
APPENDIX B. LOAD FRAME This Appendix will describe the philosophy in the design and operation of the loading system. LOAD FRAME The large-scale gusset plate testing required a unique loading fixture. A
More informationADAPT Floor Pro 2009/2010 Tutorial Export Design Strip to ADAPT PT or ADAPT RC
ADAPT Floor Pro 2009/2010 Tutorial Export Design Strip to ADAPT PT or ADAPT RC Update: May 2010 Copyright ADAPT Corporation all rights reserved ADAPT PT 2010/RC 2010 to ADAPT Floor Pro 2009/2010 Strip
More informationSteel Design Guide Series. Steel and Composite Beams with. Web Openings
Steel Design Guide Series Steel and Composite Beams with Web Openings Steel Design Guide Series Steel and Composite Beams with Web Openings Design of Steel and Composite Beams with Web Openings David Darwin
More informationAnti-fatigue Performance Analysis on Steel Crane Beam
Sensors & Transducers 2013 by IFSA http://www.sensorsportal.com Anti-fatigue Performance Analysis on Steel Crane Beam Yuanmin Xie College of Machinery and Automation, Wuhan University of Science and Technology,
More informationAnalysis and Design of One-way Slab System (Part-I)
Lecture-02 Analysis and Design of One-way Slab System (Part-I) By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Topics Addressed Concrete Floor Systems Analysis and
More informationTHE EFFECTS OF FRAME DEFORMATION ON WELDED GUSSET PLATES FOR DIAGONAL BRACING ELEMENTS LOADED IN TENSION
Advanced Steel Construction Vol. 8, No. 4, pp. 398-421 (2012) 398 THE EFFECTS OF FRAME DEFORMATION ON WELDED GUSSET PLATES FOR DIAGONAL BRACING ELEMENTS LOADED IN TENSION J. Kent Hsiao 1,*, Donald W. Tempinson
More informationPIP STF05521 Details for Angle Railings for Walking and Working Surfaces
TECHNICAL CORRECTION January 2017 Structural PIP STF05521 Details for Angle Railings for Walking and Working Surfaces PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of
More informationANSYS CALCULATIONS REPORT Outer Vessel Ansys outer vessel Sylvain ANTOINE Amaury PORHIEL - Rev C
SUMMARY 1. REVISION RECORD... 2 2. ABSTRACT... 2 3. FEA Software... 2 4. USER S DESIGN SPECIFICATION... 2 5. FEA MODEL GEOMETRY AND MESHING... 3 6. FEA MODEL CONTACT AND BOUNDARIES CONDITIONS... 4 7. FEA
More informationDECK DAMAGE AND PENETRATIONS
DECK DAMAGE AND PENETRATIONS Prepared By Richard B. Heagler, P.E. SDI CONSULTANT Copyright 1987 (Rev. 2000) All rights reserved P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648
More informationStructural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity
System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm
More informationMulti-Story Solid Tilt-Up Wall Panel Analysis and Design (ACI 551)
Multi-Story Solid Tilt-Up Wall Panel Analysis and Design (ACI 551) Span 1 Span 2 Span 3 Span 4 Reinforced Concrete Multi-Story Tilt-Up Wall Panel Analysis (ACI 551) Tilt-up is form of construction with
More informationDesign of Blowout Preventer Lifting Frame
www.daoe-journal.org Development and Applications of Oceanic Engineering (DAOE) Volume 2 Issue 4, November 2013 Design of Blowout Preventer Lifting Frame Krishna Baireddy *1 Former Student of Ocean Engineering
More informationGRATING PRODUCTS. PROGrid and PROGrate
GRATING PRODUCTS PROGrid and PROGrate PROGrid and PROGrate Grating Products CONTENTS GRATING PRODUCTS 4 PROGrid Molded Grating 10 PROGrid High Capacity Molded Grating 12 PROGrate Pultruded Grating ACCESSORIES
More informationStructural Breadth. Cathedral Place Milwaukee, WI Steven Puchek Senior Thesis Project. Relationship with Thesis Project.
Structural Breadth The structural breadth for this thesis was chosen late in development as a response to the use of a seemingly exorbitant cantilever at the ground floor of the building s lobby. Fully
More informationVOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)
DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,
More informationUses of Abaqus/Standard in Failure Analysis
Uses of Abaqus/Standard in Failure Analysis Matthew T. Kenner, P.E., John A. Wilkinson, P.E., Michael E. Stevenson, Ph.D., P.E., and Michael D. Hayes, Ph.D., P.E. Engineering Systems Inc. www.esi-website.com
More informationSoftware Verification
EXAMPLE 9 ACI Handbook Two-Way Slab Example 2 PROBLEM DESCRIPTION The two-way slab system arranged three-by-three is shown in Figure 9-1. The slab consists of nine 6.5-inch-thick 20-foot 24-foot panels.
More informationDesign of a Beam Structure for Failure Prevention at Critical Loading Conditions
International Academic Institute for Science and Technology International Academic Journal of Innovative Research Vol. 3, No. 10, 2016, pp. 32-44. ISSN 2454-390X International Academic Journal of Innovative
More informationProject ULA 120D Snow-0 Seis-IV
ULA Geometry Module Specification Sub-Array Configuration ULA Totals # Rows: 4 Column N-S Length (in): 6 # SubArrays: N-S Dim (in): 40 N-S Spacing (in): 0.25 # Columns: 5 Array E-W Dimension (in): 326
More information1.02 SYSTEM DESCRIPTION
1 OF 7 MODULAR MEZZANINES GUIDE SPECIFICATIONS FOR PART 1 - GENERAL 1.01 RELATED WORK A. SECTION 03 30 00: Cast in Place Concrete (and Concrete Finishing) 1. The area where mezzanine is installed shall
More informationLa Jolla Commons Office Tower. Appendix Slides. Architecture Breadth. Dual Systems Check. Lateral System. Shear Wall Modeling. Verification.
Appendix Slides Architecture Breadth Dual Systems Check Shear Wall Modeling Lateral System Verification Model Verification Vibrations Analysis Architecture Breadth 198 8 La Jolla Commons Office Tower Floor-to-Ceiling
More informationFinite element checking of flange connection in integral hoisting of flare stack
International Conference on Advanced Electronic Science and Technology (AEST 2016) Finite element checking of flange connection in integral hoisting of flare stack Xuanyu Sheng1,a, Hongzhi Zhang2 and You
More informationHow to Design a Singly Reinforced Concrete Beam
Time Required: 45 minutes Materials: -Engineering Paper -Calculator -Pencil -Straight Edge Design For Flexural Limit State How to Design a Singly Reinforced Concrete Beam Goal: ΦMn > Mu Strength Reduction
More informationENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa - UL2-D10-E10
ENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa UL2D10E10 November 16, 2016 AMPS Project Number: 20160200 Designed in compliance with: 2014 Florida Building Code 5th Edition with 2016 Supplements
More informationUS Composites User Guide and Theoretical Background
US Composites User Guide and Theoretical Background US Composites User Guide and Theoretical Background All information in this document is subject to modification without prior notice. No part of this
More informationInvestigation for the Removal of Steel Tie Rods in a Historic Segmental Arch Floor
Investigation for the Removal of Steel Tie Rods in a Historic Segmental Arch Floor J. Lan 1, R. Gilsanz 2, and M. Lo 3 1 Gilsanz Murray Steficek, LLP, 129 West 27 th St., 5 th Floor, New York, NY 10001
More informationNonlinear Redundancy Analysis of Truss Bridges
Nonlinear Redundancy Analysis of Truss Bridges Analysis Report Dr. Michel Ghosn Ph.D. Graziano Fiorillo The City College of New York / CUNY SEPTEMBER 2013 Acknowledgments This section describes the redundancy
More informationMODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications
MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications Mar/2008 v1.0 SECTION 02255 HYDRAULICLY DRIVEN STEEL UNDERPINNING PILES PART 1 GENERAL 1.01 SCOPE OF WORK The work shall
More informationBrent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan
Structural Design: Goals: The original design of 200 Minuteman Drive was dictated largely by Brickstone Properties, the building s owner. The new design of 200 Minuteman Drive, with additional floors,
More informationStructural Characteristics of New Composite Girder Bridge Using Rolled Steel H-Section
Proc. Schl. Eng. Tokai Tokai Univ., Univ., Ser. ESer. E 41 (2016) (2016) - 31-37 Structural Characteristics of New Composite Girder Bridge Using Rolled Steel H-Section by Mohammad Hamid ELMY *1 and Shunichi
More informationOffice Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari
Office Building-G Thesis Proposal Structural Option December 10, 2010 Table of Contents Executive Summary... 3 Introduction... 4 Gravity System...4 Lateral System:...6 Foundation System:...6 Problem Statement...
More informationCouncil on Tall Buildings
Structure Design of Sino Steel (Tianjin) International Plaza Xueyi Fu, Group Chief Engineer, China Construction Design International 1 1 Brief of Project 2 Location: Tianjin Xiangluowan Business District
More informationEffect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis
Effect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis Zasiah Tafheem 1, A.S.M Rubaiat Nahid 2, Tanzeelur Rahman
More information1.02 SYSTEM DESCRIPTION
1 OF 7 MODULAR MEZZANINES GUIDE SPECIFICATIONS FOR PART 1 - GENERAL 1.01 RELATED WORK A. SECTION 03 30 00: Cast in Place Concrete (and Concrete Finishing) 1. The area where mezzanine is installed shall
More informationMOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS
MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF
More information.1 American Institute of Steel Construction (AISC) Specifications for Steel Buildings AISC
05 12 00 STRUCTURAL STEEL FRAMING Page 1 of 3 1 General 1.1 SECTION INCLUDES.1 Structural steel framing and support members 1.2 RELATED SECTIONS.1 Section 05 50 00 Metal Fabrications 1.3 REFERENCES.1 American
More informationCrossroads at Westfields Building II
Crossroads at Westfields Building II Chantilly, Va STEPHEN LUMPP Structural option Faculty Consultant: Dr. Andres Lepage Technical Report 2 EXECUTIVE SUMMARY This report is a study of alternate floor systems
More informationSTAINLESS STEEL SHEETS
STAINLESS & NICKEL ALLOY CHATHAM STEEL CORPORATION 59 STAINLESS STEEL SHEETS TYPE 04, 04L, 6, 6L No. 2B Finish Cold Rolled, Annealed *No. 2D Finish No. Finish Polished One Side No. 4 Finish Polished One
More informationExecutive Summary. Greg Kochalski. JW Marriott, Grand Rapids, MI
Executive Summary JW Marriott, Grand Rapids, MI November 21, 2006 Greg Kochalski Structural Advisor: Boothby The JW Marriott is a 24 story hotel currently under construction in Grand Rapids, Michigan and
More informationName: 1 FOR ANY AISC DESIGN AIDS: YOU MUST SPECIFY THE TABLE USED. CE311 Fall 2017 Exam 3 11/16/2017. ASD Load Combinations: LRFD Load Combinations:
CE 311 Celebration of Knowledge 3 100 points November 16, 2017, 7pm to 9:30pm YOU MUST CITE ANY AISC DESIGN AIDS USED You are allowed to have the AISC manual, and a calculator. Given Formulae: Live Load
More informationCHAPTER 6 FINITE ELEMENT ANALYSIS
105 CHAPTER 6 FINITE ELEMENT ANALYSIS 6.1 INTRODUCTION Several theoretical approaches are considered to analyze the yielding and buckling failure modes of castellated beams. Elastic Finite Element Analysis
More information30 kip/ft (Dead load) 5 ft. 20 ft
UNIVERSITY OF CALIFORNIA, BERKELEY Dept. of Civil and Environmental Engineering Spring Semester 2017 Structural Engineering, Mechanics and Materials Ph.D. Preliminary Examination: Design Consider the frame
More informationPACIFIC SHORING, LLC ALUMINUM SHORING PRODUCTS ALUMINUM S-PANEL SHIELDS. TABULATED DATA Effective April 01, 2014
1 ALUMINUM S-PANEL SHIELDS Effective April 01, 2014 PSH 265 Roberts Avenue Santa Rosa, Ca. 95407 (707) 575-9014 Construction Engineering Resource 1837 Wright Street Santa Rosa, Ca. 95404 jmtengr2@aol.com
More informationSpecial edition paper
Retrofit Reinforcement Method for H-section Steel Beams Using Longitudinal Web Stiffeners Tsutomu Hoshikawa* The purpose of this study is to investigate how longitudinal stiffener plates can improve plastic
More informationPanduit Corporation Tinley Park, Illinois. Outset and Inset Cabinets Seismic Load Rating and Anchorage Design
Panduit Corporation Tinley Park, Illinois Outset and Inset Cabinets Seismic Load Rating and Anchorage Design February 13, 2013 Degenkolb Job Number B2439007.00 www.degenkolb.com 500 Degenkolb Engineers
More informationSTRUCTURAL ANALYSIS OF 200 MPH WIND RATED ALUMASHIELD UPGRADE OPTION FOR OD, 2OD, & 3OD ENCLOSURES
STRUCTURAL ANALYSIS OF 200 MPH WIND RATED ALUMASHIELD UPGRADE OPTION FOR OD, 2OD, & 3OD ENCLOSURES Prepared for: Michael Mahorney DDB Unlimited, Inc. 2301 S. HWY. 77 Pauls Valley, OK 73075 USA Telephone:
More informationSoftware Verification
EXAMPLE 15 Wall Object Behavior - Static Lateral Loads Analysis Problem Description This example analyzes a series of wall configurations to evaluate the behavior of the shell object with wall section
More informationStress-Laminated / Steel T-Beam Bridge System
Stress-Laminated / Steel T-Beam Bridge System David A. Apple and Clinton Woodward, New Mexico State University Abstract The stress-laminated timber bridge deck has been successfully used for short span
More informationHow Loads Are Distributed
LOAD DISTRIBUTION 1 LOAD DISTRIBUTION This section illustrate how load will transmit from the deck to the stringers. Determining the fraction of load carried by a loaded member and the remainder distributed
More informationCantilevered Rail System
Knight Global's Cantilevered Rail Systems are designed to eliminate the need for a four post floor structure system. It provides an alternative to workstations with minimal floor space. A wide range of
More informationSECTION Permanent Grandstands PART 1 GENERAL 1.1 RELATED DOCUMENTS
SECTION 13125 Permanent Grandstands PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections,
More informationTechnical Report #1. Matthew R Peyton
Technical Report #1 This Document is Technical Report #1 for 5th year senior thesis in the Architectural Engineering Departments at The Pennsylvania State University. This Report will include structural
More informationE-Beam HD. Cold-Formed Insulated Composite Structural Elements. Engineering/Analysis Report
E-Beam HD Cold-Formed Insulated Composite Structural Elements Engineering/Analysis Report February 2012 Engineering/Analysis Report February 2012 Prepared for: 309 Noble Cliff Langley, WA 98260 Prepared
More informationMASONRY WALL DATA: Wall Height = ft. Nominal Wall Thickness = 8.00 in. Depth to c.g. Steel, Wall = 3.81 in.
TIME: 10:49 AM Page: 1 DESIGN METHOD : ACI 530-99: Working Stress Design MASONRY MATERIAL : Hollow Core Concrete Masonry Units MORTAR TYPE : Type S MORTAR MATERIAL : Portland Cement Lime Mortar BLOCK PLACEMENT
More informationSTRESS ANALYSIS OF A 46-INCH REACTOR FEED/EFFLUENT EXCHANGER
STRESS ANALYSIS OF A 46-INCH REACTOR FEED/EFFLUENT EXCHANGER Chris Alexander Stress Engineering Services, Inc. Houston, Texas John Jagodzinski Brown Fintube Houston, Texas Richard Biel, P.E. Stress Engineering
More informationOVERALL STRUCTURAL SYSTEM
EXECUTIVE SUMMARY The at the Pittsburgh International Airport, PA, is a 275,000 square foot multi-use building located directly adjacent to the airport s landside terminal. The building consists of an
More informationModeling Component Assembly of a Bearing Using Abaqus
Modeling Component Assembly of a Bearing Using Abaqus Bisen Lin, Ph.D., P.E. and Michael W. Guillot, Ph.D., P.E. Stress Engineering Services, Inc. Abstract: Assembly process of a bearing considered in
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 05 5117 ALTERNATING TREAD STEEL STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationICC-ES Evaluation Report
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1042 Reissued February 1, 2011 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION:
More informationCVEN 483. Structural System Overview
CVEN 483 Structural System Overview Dr. J. Bracci Fall 2001 Semester Presentation Overview 1. Building system primary function 2. Types of load 3. Building materials 4. Structural members 5. Structural
More informationEarthquake Analysis for Cryogenic Components of NPDG Liquid Hydrogen Target
Earthquake Analysis for Cryogenic Components of NPDG Liquid Hydrogen Target at SNS, Oak Ridge. TN Prepared by: Walt Fox, CEEM, Indiana University, 7 15 2010 (Revised 10 15 2010, 2 nd Revision 1 21 2011)
More informationSPECIFICATIONS FOR THE CONSTRUCTION OF NEW PASSENGER EQUIPMENT CARS PREFACE
SPECIFICATIONS FOR THE CONSTRUCTION OF NEW PASSENGER EQUIPMENT CARS Standard ADOPTED 1939; ADVANCED TO STANDARD, 1945. PREFACE The specifications have been prepared on the basis that they will be used
More informationTable of Contents. What's New in GRAITEC Advance BIM Designers 2019 R2 UPDATES... 4 IMPROVEMENTS & CORRECTIONS... 6
What's New 2019 R2 Table of Contents UPDATES... 4 NEW VERSION OF THE ITALIAN CODE NTC 2018... 4 Modification of load coefficients for non-structural permanent loads... 4 New concrete class available...
More informationCONCRETE TECHNOLOGY CORPORATION
PRECAST, PRESTRESSED HOLLOW CORE SLABS DESIGN CRITERIA & SPAN-LOAD CHARTS FOR STORM WATER DETENTION VAULT LIDS (CHARTS REVISED /18/08) Introduction Design Criteria for Development of the Span-Load Charts
More informationRajan s Book Chapter 3: Structural Design Fundamentals
Rajan s Book Chapter 3: Structural Design Fundamentals What is Design? Design a process by which an acceptable solution is obtained. -- Feasible solution is acceptable, but desirable to have a minimum
More informationStandard Installation Fire Damper Models: 119, 119(F), 119(SS), D19
Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the
More informationStatic Structural Analysis of Sandwich Structural Panel using ANSYS
IJIRST International Journal for Innovative Research in Science & Technology Volume 4 Issue 2 July 2017 ISSN (online): 2349-6010 Static Structural Analysis of Sandwich Structural Panel using ANSYS Anjan
More informationDynaform Fiberglass Structural Shapes. Design Guide. High Performance Composite Solutions. Corrosion Resistant. Fire Retardant.
Design Guide Dynaform Fiberglass Structural Shapes Corrosion Resistant Fire Retardant Low Maintenance Light Weight Long Service Life High Performance Composite Solutions Coupon Properties - Structural
More informationStructural Redesign Gravity System
Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides
More informationStress Analysis of Fixed Site Series 6000 Antennas
Stress Analysis of Fixed Site Series 6000 Antennas 1.0 Introduction A Technical Application Note from Doppler Systems April 12, 2002 This stress analysis considers five different antenna configurations,
More informationBEHAVIOR OF INFILL MASONRY WALLS STRENGTHENED WITH FRP MATERIALS
BEHAVIOR OF INFILL MASONRY WALLS STRENGTHENED WITH FRP MATERIALS D.S. Lunn 1,2, V. Hariharan 1, G. Lucier 1, S.H. Rizkalla 1, and Z. Smith 3 1 North Carolina State University, Constructed Facilities Laboratory,
More informationTechnical Report #3. Matthew R Peyton
Technical Report #3 This Document is Technical Report #3 for 5th year senior thesis in the Architectural Engineering Departments at The Pennsylvania State University. In this report the existing reinforced
More informationTable of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5
WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 1 OCTOBER 5, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI Table of Contents Table of Contents
More informationFabricate and Install metal alternating tread stair assemblies in accordance with the requirements set forth in this section.
SECTION - ALTERNATING TREAD STEEL STAIRS PART 1 - GENERAL 1.1 SCOPE OF WORK Fabricate and Install metal alternating tread stair assemblies in accordance with the requirements set forth in this section.
More informationTests of R/C Beam-Column Joint with Variant Boundary Conditions and Irregular Details on Anchorage of Beam Bars
October 1-17, 8, Beijing, China Tests of R/C Beam-Column Joint with Variant Boundary Conditions and Irregular Details on Anchorage of Beam Bars F. Kusuhara 1 and H. Shiohara 1 Assistant Professor, Dept.
More informationVARIOUS TYPES OF SLABS
VARIOUS TYPES OF SLABS 1 CHOICE OF TYPE OF SLAB FLOOR The choice of type of slab for a particular floor depends on many factors. Economy of construction is obviously an important consideration, but this
More information9. VACUUM TANK 9. VACUUM TANK
9. VACUUM TANK This system constitutes the external part of the solenoid cryostat. The vacuum tank, made of stainless steel, is cantilevered from the central ring of the barrel yoke. It houses and supports
More informationCHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS
30 CHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS 3.1 INTRODUCTION There are numerous similarities between ferrocement and reinforced concrete. Both use similar matrix and reinforcement materials. They
More informationCalculating Stress & Strain from Experimental ODS Data
Calculating Stress & Strain from Experimental ODS Data Brian Schwarz, Shawn Richardson, Mark Richardson Vibrant Technology, Inc. Scotts Valley, CA Click here for the presentation ABSTRACT In this paper
More informationSTANDARDIZED STRUCTURES
Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The
More informationCIRCULAR TUBE COLUMNS IN HIGH STRENGTH STEEL Economical solutions for building frames
EUROSTEEL 014, September 10-1, 014, Naples, Italy CIRCULAR TUBE COLUMNS IN HIGH STRENGTH STEEL Economical solutions for building frames Van-Long Hoang a, Jean-Pierre Jaspart a, Jean-François Demonceau
More informationStructural Technical Report 1 Structural Concepts/ Structural Existing Conditions Report
Kelly M. Sadusky The Food Science Building Oct. 6, 2004 Professor Parfitt University Park, PA Structural Option Executive Summery: Structural Technical Report 1 Structural Concepts/ Structural Existing
More informationStructural Technical Report #2 Pro/Con Study of Alternate Floor Systems
Christopher McCune Structural Option Eight Tower Bridge Faculty Advisor: Dr. Hanagan October 31 st, 2005 Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems Executive Summary This technical
More informationExecutive Summary Building Description: Introduction... 13
Table of Contents Executive Summary... 2 Building Description:... 2 Report Summary:... 2 Introduction... 3 Building Description:... 3 Current Framing Layout... 4 Report Topics:... 4 Loads and Load Cases...
More informationTemecula Medical Center Temecula, CA
Temecula Medical Center Temecula, CA Technical Assignment #2 Sean F. Beville The Pennsylvania State University Architectural Engineering Structural Option Senior Thesis Project Student Advisor: Thomas
More informationRutgers University Law School Building Addition and Renovation Camden, NJ
Building Addition and Renovation Camden, NJ Technical Assignment 1 October 5, 2007 Nathan E. Reynolds Structural Option Senior Thesis The Pennsylvania State University Faculty Consultant: Professor M.
More information