EVH-660D. Miami-Dade Qualified Wind-Driven Rain Louver. Application and Design. Standard Construction. Options (at additional cost)

Size: px
Start display at page:

Download "EVH-660D. Miami-Dade Qualified Wind-Driven Rain Louver. Application and Design. Standard Construction. Options (at additional cost)"

Transcription

1 Application and Design Miami-Dade Qualified Wind-Driven Rain Louver EVH-0D Florida Product Approval No.: EVH-0D is a Florida Product Approved and Miami-Dade Qualified stationary vertical blade wind driven rain extruded aluminum louver designed to protect air intake and exhaust openings in building exterior walls. EVH-0D is tested in accordance with AMCA 500-L Air Performance, Water Penetration and Wind Driven Rain. EVH-0D is tested in accordance with AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and Enhanced Protection, Missile Level E). EVH-0D is tested in accordance with AMCA 550 Test Method for High Velocity Wind Driven Rain Resistant Louvers. EVH-0D is licensed to bear the AMCA seal allowing design professionals to select and apply with confidence. EVH-0D is tested and qualified per the following Florida test protocols: TAS 201 (Large Missile Impact), TAS 202 (Uniform Static Air Pressure), TAS 203 (Cyclic Wind Loading) and TAS 100A (Wind Driven Rain). Per Miami-Dade EVH-0D may be installed in locations where the room behind the louver is NOT designed to drain water penetrating into the room or the room will house non-water resistant or water proof equipment components or supplies. Standard Construction Frame Heavy gauge extruded 03T5 aluminum, in. x in. nominal wall thickness Blades Vertical rain resistant design, heavy gauge extruded 03T5 aluminum, 0.03 in. nominal wall thickness, positioned on approximately 0.75 in. centers Construction..... Mechanically fastened Birdscreen /4 in. x flattened expanded aluminum removable frame, inside mount (rear) Finish Mill Anchor Clips..... Heavy gauge extruded aluminum, mill finish, continuous mounting angels (head and sill only) Minimum Rough Opening Size in. W x 12 in. H Maximum Rough Opening Size.... Unlimited W x 120 1/2 in. H Maximum Rough Opening Single Section Size /2 in. W x 120 1/2 in. H Options (at additional cost) A variety of bird and insect screens Blank-off panels Extended sill Filter racks Flanged frame Security bars Factory attached VCD-40 damper A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel Kynar *Width and height dimensions furnished approximately 1/2 inch under size. NOTE: Lifting lugs will be shipped with all units over 10 sq. ft.

2 PERFORMANCE DATA Wind-Driven Rain Performance 75 mm/h (3 in./hr) Rainfall & 13 m/s (29 mph) Wind Velocity Ventilation Air Core Free Area Velocity Velocity Water Penetration Discharge Loss Coefficient Class (Intake) = mm/h (8 in./hr) Rainfall & 22 m/s (50 mph) Wind Velocity Ventilation Air Core Free Area Velocity Velocity Water Penetration (fpm) (m/s) (fpm) (m/s) Effective Class (fpm) (m/s) (fpm) (m/s) Effective Class 0.0 (0) 0.0 (0) A 0.0 (0) 0.0 (0) A 0.9 (185) 0.5 (98) A 0.9 (185) 0.5 (98) A 1.9 (371) 1.0 (197) A 1.9 (371) 1.0 (197) A 2.8 (55) 1.5 (295) A 2.8 (55) 1.5 (295) A 3.8 (742) 2.0 (394) A 3.8 (742) 2.0 (394) A 4.7 (927) 2.5 (492) A 4.7 (927) 2.5 (492) A 5.7 (1113) 3.0 (591) A 5.7 (1113) 3.0 (591) A. (1298) 3.5 (89) A. (1298) 3.5 (89) A 7.5 (1483) 4.0 (787) A 7.5 (1483) 4.0 (787) A 8.5 (19) 4.5 (88) A 8.5 (19) 4.5 (88) A 9.4 (1852) 5.0 (983) A 9.4 (185) 5.0 (985) A Weather louvers shall be classified by their ability to reject simulated rain. The table shows different classifications based on the maximum simulated rain penetration per square meter (square feet) of louver. Water penetration rating at a given louver face velocity is determined by the water penetration while the louver is subjected to a selected simulated rainfall rate and wind velocity. EVH-0D Florida Product Approval No.: Greenheck Fan Corporation certifies that the EVH-0D louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance, water penetration, and winddriven rain ratings. Greenheck Fan Corporation certifies that the EVH-0D louvers shown herein are approved to bear the AMCA Listing Label. The Ratings shown are based on tests and procedures performaned in accordance with AMCA Publications and comply with the requirements of the AMCA Listing Label Program. The AMCA Listing Label applies to Wind Borne Debris Impact Resistant and High Velocity Rain Resistant Louvers. Discharge Loss Coefficient Classifications Class Discharge Loss Coefficient Wind-driven Rain Penetration Classes and Above Class Effectiveness to A 1 to to B to 0.95 Airflow Resistance (Standard Air lb/ft 3 ) and Below C to 0.80 Water Penetration Test Size 48 in. x 48 in. Test Duration of 15 min. D Below 0.80 Model EVH-0D resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information. (Test Figure ) The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through 0.01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of water penetration for Model EVH-0D is above 1250 fpm free area velocity. These performance ratings do not guarantee a louver to be weather-proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.

3 PERFORMANCE DATA Free Area Chart (sq. ft.) Louver Height Inches Louver Width in Inches EVH-0D Florida Product Approval No.: Core Area Chart (sq. ft.) Louver Height Inches Louver Width in Inches

4 INSTALLATION DETAILS EVH-0D Florida Product Approval No.: Maximum Size and Installation Information Model EVH-0D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the installation instructions shown herein. Model EVH-0D is qualified for installation within concrete/masonry, steel stud, structural steel or wood framed building conditions. Model EVH-0D is structurally calculated to withstand positive and negative wind-loads up to 150 PSF. The maximum single section width is 48 in. The maximum single section height is 120 in. While the maximum section height is limited to 120 in., the width may be unlimited as multiple sections may be installed side by side in accordance with installation instructions. Minimum Rough Opening Size 12 in. W x 12 in. H Maximum Rough Opening Single Section Size 48 1/2 in. W x 120 1/2 in. H

5 PRODUCT DETAILS EVH-0D Florida Product Approval No.: Optional VCD-40 Control Damper

6 FASTENER CHART DESCRIPTION SUBSTRATE MINIMUM CONCRETE OR CMU ANCHORING 1/4" TAPCON SCREW FASTENER TABLE 1/4" TAPCON CONCRETE OR CMU (GROUT FILLED) EVH-0D Florida Product Approval No.: KSI CONCRETE OR KSI GROUT EDGE DISTANCE <MIN> 1 IN 1 1/2 IN 2 1/2 IN PENETRATION <MIN> LOUVER HEIGHT <IN> 1 3/4 IN >108 & >9 & >72 & 9 >48 & 72 4 >0 & 48 CONCRETE OR CMU ANCHORING 3/8" POWERS WEDGE BOLT FASTENER TABLE DESCRIPTION SUBSTRATE 3/8" POWERS WEDGE BOLT NORMAL WEIGHT CONCRETE CMU <1.5 KSI GROUT FILLED> " WIDE, GRADE N, TYPE II, MINIMUM 2.5 KSI LIGHT/MEDIUM/NORMAL WEIGHT CMU CONFORMING TO ASTM C90 EDGE DISTANCE <MIN> 2 IN 3 IN 4 1/2 IN 1 1/2 IN 2 IN PENETRATION <MIN> 2 1/8 IN 2 1/2 IN LOUVER HEIGHT <IN> >108 & NOT ALLOWED >72 & 108 NOT ALLOWED >3 & 72 >0 & 3 WOOD OR STEEL ANCHORING LAG SCREW, SCREW, & BOLT W/NUT FASTENER TABLE DESCRIPTION 3/8" LAG SCREW 1/4" LAG SCREW 1/4" 20 SCREW OR BOLT W/NUT SUBSTRATE WOOD STEEL MINIMUM EDGE DISTANCE <MIN> G /2 IN A3 STEEL OR Fy 3 KSI 1/2 IN PENETRATION <MIN> 2 3/4 IN 1 GA <0.0 IN> 3/1 IN LOUVER HEIGHT <IN> >84 & >0 & 84

7 OPTION DRAWINGS EVH-0D Florida Product Approval No.: FINISHES Finish Type Description/Application Color Selection Standard Warranty (Aluminum) 2-coat 70% KYNAR 500 /HYLAR 5000 AAMA 205 Dry film thickness 1.2 mil. (AKA: Duranar, Fluoropon, Trinar, Flouropolymer, Polyvinylidene Fluoride, PVDF2) Best. The premier finish for extruded aluminum. Tough, long-lasting coating has superior color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering. Standard Colors: Any of the 24 standard colors shown can be furnished in 70% or 50% KYNAR 500 /HYLAR 5000 or Baked Enamel. 10 Years (Consult Greenheck for availability of extended warranty) 2-coat 50% KYNAR 500 /HYLAR 5000 AAMA 204 Dry film thickness 1.2 mil. (AKA: Acroflur, Acrynar ) Baked Enamel AAMA 203 Dry film thickness 0.8 mil. (AKA: Acrabond Plus, Duracron ) Better. Tough, long-lasting coating has excellent color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering. Good. Provides good adhesion and resistance to weathering, corrosion and chemical stain. 2-Coat Mica: Greenheck offers 9 standard 2-coat Mica colors. Other colors are available. Consult Greenheck for possible extra cost when selecting non-standard colors or special finishes. 5 Years 1 Year Integral Color Anodize AA-M10C22A42 (>0.7 mil) Clear Anodize 215 R-1 AA-M10C22A41 (>0.7 mil) Clear Anodize 204 R-1 AA-M10C22A31 ( mil) Industrial coatings Mill Two-step anodizing is produced by following the normal anodizing step with a second, colorfast process. Clear, colorless and hard oxide aluminum coating that resists weathering and chemical attack. Clear, colorless and hard oxide aluminum coating that resists weathering and chemical attack. Light, Medium or Dark Bronze; Champagne; Black Clear Clear Greenheck offers a number of industrial coatings such as Hi-Pro Polyester, Epoxy, and Permatector. Consult a Greenheck Product Specialist for complete color and application information. Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is acceptable and there is no concern for color or color change. 5 years 5 years 1 Year Consult Greenheck Finishes meet or exceed AAMA 205, AAMA 204, and AAMA 203 requirements. Please consult for complete information on standard and extended paint warranties. Paint finish warranties are not applicable to steel products. n/a EVH-0D November 2017 Copyright 2017 Greenheck Fan Corporation Greenheck Fan Corporation reserves the right to make product changes without notice.