Asset Detail Report. by Asset Name. February 28, 2012

Size: px
Start display at page:

Download "Asset Detail Report. by Asset Name. February 28, 2012"

Transcription

1 February 28, 2012

2 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-FAUQUIER CAMPUS Asset Number: 0000 Asset Name: Modular Buildings 1-6 (Classrooms & Offices) STATISTICS FCI Cost: 49,169 FCI: 0.08 Total Requirements Cost : 49,169 RI: 0.08 Current Replacement Value 604,601 Address College St. Size 7,200 SF Address 2 - Year Constructed 2005 City Warrenton Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect N/A Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 5B Type Building Use Academic Last Inspection Date :00:00 Functional Use - PHOTO Modular Buildings 1-6 (Classrooms & Offices) - ASSET DESCRIPTION ARCHITECTURAL Modular Buildings 1-6 (Classrooms and Offices) is located at 6480 College Street, Warrenton, VA 20187, on the Fauquier Campus of Lord Fairfax Community College. This one (1) story 7,200 SF modular buildings were originally constructed in 2005 and installed on site in The asset consists of six (6) double-wide, pre-finished modular structures with connected walking platform. The building houses additional classrooms (Modular Buildings #1-5) and offices (Modular Building #6) for the college. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 5B Unsprinklered. REQUIREMENTS Page 1 of 3

3 Requirement Name Prime System Category Priority Action Date Cost Carpeting - Tile Renewal C3020-Floor Finishes of assm't date 01/11/ ,674 D5092-Emergency Emergency Battery Pack Lights Renewal Light and Power Systems of assm't date 02/27/2015 4,495 Total 49,169 Page 2 of 3

4 REPLACEMENT VALUE A-Substructure Spread Footings - No Basement 9,527 B1014-Ramps Accessible Ramps - Exterior - Wood 3,118 B1015-Exterior Stairs and Fire Escapes Exterior Stairs - Wood 864 B2010-Exterior Walls Metal Paneled Walls 44,640 B2010-Exterior Walls Vinyl Siding 10,440 B2020-Exterior Windows Aluminum Windows 14,055 B2030-Exterior Doors Door Assembly - 3 x 7 Wood 19,648 B30-Roofing Gutters and Downspouts - Aluminum 2,691 B30-Roofing Metal Roofing 42,595 C1010-Partitions Demountable Partitions - Vinyl Faced 69,579 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 28,799 C3020-Floor Finishes Carpeting - Tile 35,739 C3020-Floor Finishes VCT 790 C3030-Ceiling Finishes ACT System - Hi-Strength 35,496 D3050-Terminal and Package Units Thru-Wall Units - Cooling w/electric Heat 56,739 D40-Fire Protection Fire Extinguishers - Dry Chem 209 D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 208Y/120V 17,053 D5022-Lighting Equipment Lighting Fixtures - Light Density 17,652 D5033-Telephone Systems Telephone System - Light Density 10,872 D5039-Local Area Networks LAN System - Light Density 13,104 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 3,596 D5092-Emergency Light and Power Systems Exit Signs - Low Density 1,837 F1010-Special Structures Pre-Fabricated Buildings - Mobile Trailers 134,190 G2049-Miscellaneous Structures Wooden Decks - Treated and Composite 31,367 Subtotal 604,600 Overhead Cost Description Cost Total Replacement Value 604,600 Page 3 of 3

5 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-FAUQUIER CAMPUS Asset Name: Paul and Sheila Wolk Hall (Main Building) Asset Number: 0B01 STATISTICS FCI Cost: 1,176,372 FCI: 0.11 Total Requirements Cost : 1,183,086 RI: 0.11 Current Replacement Value 11,053,585 Address College St. Size 57,376 SF Address 2 - Year Constructed 1999 City Warrenton Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Sverdrup Facilities, Inc. Ownership Agency Owned Historical Category None Floors 2 Construction Type IBC - Type 2B Type Building Use Academic Last Inspection Date :30:00 Functional Use - PHOTO Paul and Sheila Wolk Hall (Main Building) - ASSET DESCRIPTION ARCHITECTURAL The Paul and Sheila Wolk Hall or known as the Main Building is located at 6480 College Street, Warrenton, VA 20187, on the Fauquier Campus of Lord Fairfax Community College. This two (2) story 57,376 SF building was originally constructed in The building houses classrooms, computer lab, chemistry classroom/lab, biology classroom/lab, nursing classroom/lab, bookstore, library and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 2B Fully Sprinklered. REQUIREMENTS Page 1 of 6

6 Requirement Name Prime System Category Priority Action Date Cost Adhered Membrane (EPDM) Single-Ply Renewal B30-Roofing Carpeting Renewal C3020-Floor Finishes of assm't date 01/11/ , Within mos. of assm't date 01/11/ ,063 DX Split System Renewal D3030-Cooling Generating Systems of assm't date 02/27/2016 3,117 D5092-Emergency Emergency Battery Pack Lights Renewal Light and Power Systems of assm't date 02/27/ ,824 D5092-Emergency Exit Signs - High Density Renewal Light and Power Systems of assm't date 02/27/ ,750 Exterior Doors - Aged Paint Finish B2030-Exterior Doors Appearance 3 - Within mos. of assm't date 01/11/2014 2,324 Exterior Guard Rails - Aged Paint Finish G2041-Fences and Gates Appearance 3 - Within mos. of assm't date 01/11/2014 2,372 Exterior Paving - Missing Concrete G2030-Pedestrian Paving Capacity/Design of assm't date 01/11/2018 6,715 Exterior Walls - Cracked and Stained CMU B2010-Exterior Walls Appearance 2 - Within 12 mos of assm't date 01/11/ ,866 LAN System - Heavy Density Renewal D5039-Local Area Networks 3 - Within mos. of assm't date 02/27/ ,073 Metal Roof Trim - Aged Paint Finish B30-Roofing Reliability 2 - Within 12 mos of assm't date 01/11/2013 9,880 Plumbing - Sanitary Waste Issues D2030-Sanitary Waste Repair/Replace (Unreliable) 2 - Within 12 mos of assm't date 01/11/ ,286 Plumbing - Secondary Roof Drainage Improperly Installed D2030-Sanitary Waste Repair/Replace (Unreliable) 2 - Within 12 mos of assm't date 01/11/2013 8,092 Plumbing - Water Closet Issues D2010-Plumbing Fixtures Repair/Replace (Unreliable) date) 01/11/ ,805 Security System Renewal D5038-Security and Detection Systems of assm't date 02/27/ ,976 Water Heater - Gas Renewal D2020-Domestic Water Distribution 3 - Within mos. of assm't date 02/27/ ,479 Total 1,183,087 Page 2 of 6

7 REPLACEMENT VALUE A-Substructure A-Substructure Foundation Wall and Footings - No Basement 85,093 Foundation Wall and Footings 16-Ft - Full Basement 122,333 A-Substructure Grade Beams - Average 373,128 A-Substructure Structural Slab on Grade - Non Industrial 186,446 B10-Superstructure Superstructure - Multi Story - Steel 1,315,087 B1015-Exterior Stairs and Fire Escapes Exterior Stairs - Concrete 878 B2010-Exterior Walls CMU - Split-Face 395,278 B2015-Balcony Walls and Handrails Metal Pipe Railings 14,750 B2016-Exterior Soffits Painted GWB Soffits 6,961 B2020-Exterior Windows Aluminum Windows 156,569 B2020-Exterior Windows Curtain Wall System 270,310 B2030-Exterior Doors Automatic Openers - Single 16,096 B2030-Exterior Doors Door Assembly - 3 x 7 HM 20,223 B2030-Exterior Doors Door Assembly - 3 x 7 Storefront 6,709 B2030-Exterior Doors Door Assembly - 6 x 7 HM 11,327 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 20,980 B30-Roofing Adhered Membrane (EPDM) Single-Ply 149,972 B30-Roofing Metal Roofing 215,244 B3022-Roof Hatches Roof Hatches 2,399 C1010-Partitions CMU Block Walls - Plain 249,275 C1010-Partitions Folding Partitions 116,026 C1010-Partitions GWB Partitions on Furring 17,125 C1010-Partitions GWB Walls - Standard (Non-Painted) 88,707 C1010-Partitions Windows/Storefront Partitions 16,117 C1020-Interior Doors Automatic Openers - Single 32,193 C1020-Interior Doors Overhead/Rolling Grilles 7,106 C1020-Interior Doors Swinging Doors - 3 x 7 Glazed Wd 65,150 C1020-Interior Doors Swinging Doors - 3 x 7 HM 18,550 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 3,355 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 422,384 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 HM 10,371 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 Wd 32,597 C1030-Fittings Restroom Accessories 37,332 Page 3 of 6

8 C1030-Fittings Toilet Partitions 34,221 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 25,486 C20-Stairs Guard Rails 6,146 C20-Stairs Stairs - Learning Resource Center 17,904 C20-Stairs Stairs - Student Center 15,680 C3010-Wall Finishes Acoustical Wall Panels 19,061 C3010-Wall Finishes Ceramic Wall Tile 44,765 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 80,544 C3010-Wall Finishes Raised Wood Paneling 72,936 C3020-Floor Finishes Carpeting 177,650 C3020-Floor Finishes Ceramic Floor Tile 19,500 C3020-Floor Finishes Concrete - Painted or Sealed 2,160 C3020-Floor Finishes Quarry Tile 14,634 C3020-Floor Finishes Stone Finish 46,194 C3020-Floor Finishes Terrazzo 140,836 C3020-Floor Finishes VCT 20,183 C3030-Ceiling Finishes ACT System - Standard 142,450 C3030-Ceiling Finishes GWB Taped and Finished 17,232 C3030-Ceiling Finishes Metal Paneled System 4,426 C3030-Ceiling Finishes Painted Finish on Steel Structures 8,628 D1010-Elevators and Lifts Hydraulic Passenger Elev, Economy 59,547 D1011-Passenger Elevators Elevator Cab Finishes - Passenger 15,744 D2010-Plumbing Fixtures Custodial/Utility Sinks 4,580 D2010-Plumbing Fixtures Emergency Eyewash and Shower Units 1,500 D2010-Plumbing Fixtures Kitchenette Sinks 2,854 D2010-Plumbing Fixtures Laboratory Sinks 36,902 D2010-Plumbing Fixtures Restroom Fixtures, Std Density, Avg Qual 55,282 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 6,946 D2020-Domestic Water Distribution Water Dist Complete - Average 149,220 D2020-Domestic Water Distribution Water Heater - Gas 27,214 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 94,334 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 75,890 D2090-Other Plumbing Systems Compressed Air Distribution 13,727 D2090-Other Plumbing Systems Lab Acid Waste System - Polypropylene 7,826 Page 4 of 6

9 D2090-Other Plumbing Systems Natural Gas Distribution for Building 29,759 D2090-Other Plumbing Systems Natural Gas Distribution for Lab 11,938 D3020-Heat Generating Systems Boiler - Gas-Fired - Average 85,941 D3030-Cooling Generating Systems Chiller - Air Cooled ,129 D3030-Cooling Generating Systems Chiller - Air Cooled ,129 D3030-Cooling Generating Systems DX Split System 2,494 D3040-Distribution Systems D3040-Distribution Systems Central AHU - Const Volume w/distribution 35,412 Central AHU - VAV System w/distribution 1,031,005 D3040-Distribution Systems Exhaust System - Kitchen - Commercial 36,093 D3040-Distribution Systems Four Pipe Distribution System w/pump 740,092 D3040-Distribution Systems Fume Hood and Exhaust System 30,664 D3040-Distribution Systems General Building Exhaust 28,952 D3040-Distribution Systems Restroom Exhaust System 16,392 D3050-Terminal and Package Units Unit Heaters 36,319 D3060-Controls and Instrumentation DDC System 197,729 D40-Fire Protection Fire Extinguishers - Dry Chem w/cabinet 1,530 D40-Fire Protection Wet Sprinkler System - Light Hazard wo/pump 232,108 D5010-Electrical Service and Distribution Distribution System - Heavy Capacity 479,409 D5010-Electrical Service and Distribution Feeder - Heavy Service 195,592 D5010-Electrical Service and Distribution Switchgear - Heavy Duty 35,214 D5012-Low Tension Service and Dist. D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V 183,927 Main Electrical Service A 208Y/120V 40,401 D5020-Lighting and Branch Wiring Lighting, exterior flood, pair 802 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 190,488 D5022-Lighting Equipment Lighting Fixtures - Heavy Density 227,686 D5033-Telephone Systems Telephone System - High Density 173,849 D5038-Security and Detection Systems Security System 213,581 D5039-Local Area Networks LAN System - Heavy Density 207,127 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 13,892 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 28,659 D5092-Emergency Light and Power Systems Exit Signs - High Density 35,800 Page 5 of 6

10 E-Equipment and Furnishings Fixed Casework -Institutional 32,292 E-Equipment and Furnishings Laboratory Equipment - College 120,336 E10-Equipment Access Ladder 1,920 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 26,040 G2040-Site Development Retaining Wall - Concrete Masonry Unit 26,127 G2040-Site Development Retaining Walls - Concrete 45,481 Subtotal 11,053,582 Overhead Cost Description Cost Total Replacement Value 11,053,582 Page 6 of 6

11 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-FAUQUIER CAMPUS Asset Name: The Barn Building Asset Number: 0B02 STATISTICS FCI Cost: 24,425 FCI: 0.05 Total Requirements Cost : 24,425 RI: 0.05 Current Replacement Value 527,849 Address College St. Size 3,200 SF Address 2 - Year Constructed 1999 City Warrenton Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Sverdrup Facilities, Inc. Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 3B Type Building Use Academic Last Inspection Date :00:00 Functional Use - PHOTO The Barn Building - ASSET DESCRIPTION ARCHITECTURAL The Barn Building is located at 6480 College Street, Warrenton, VA 20187, on the Fauquier Campus of Lord Fairfax Community College. This one (1) story 3,200 SF building was originally constructed as a dairy barn before World War II and was completely rebuilt in The building houses an assembly hall for the college plus associated building support spaces. The building s primary occupancy is classified as Group A-3, Assembly and its primary construction type per the 2006 IBC is Type 3B Unsprinklered. REQUIREMENTS Page 1 of 4

12 Requirement Name Prime System Category Priority Action Date Cost Carpeting Renewal C3020-Floor Finishes of assm't date 01/11/ ,981 D5092-Emergency Exit Signs - Low Density Renewal Light and Power Systems of assm't date 02/27/2015 1,021 Exterior Walls - Cracked CMU B2010-Exterior Walls Appearance 2 - Within 12 mos of assm't date 01/11/2013 1,110 Pedestrian Pavement - Cracked Concrete G2030-Pedestrian Paving Appearance 3 - Within mos. of assm't date 01/11/2014 1,986 Plumbing - Water Closet Issues D2010-Plumbing Fixtures Repair/Replace (Unreliable) date) 01/11/2012 1,079 Water Heater - Electric Renewal D2020-Domestic Water Distribution 3 - Within mos. of assm't date 02/27/2014 2,249 Total 24,426 Page 2 of 4

13 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 26,522 A-Substructure Structural Slab on Grade - Non Industrial 17,536 B10-Superstructure Superstructure - Multi Story - Wood 26,896 B2010-Exterior Walls CMU - Split-Face 47,862 B2010-Exterior Walls Wood Walls - Siding 12,339 B2020-Exterior Windows Aluminum Windows 5,258 B2030-Exterior Doors Door Assembly - 3 x 7 HM 5,778 B2030-Exterior Doors Door Assembly - 6 x 7 HM 5,664 B2030-Exterior Doors Door Assembly - 6 x 7 HM - Sliders 5,664 B30-Roofing Metal Roofing 128,205 C1010-Partitions GWB Partitions on Furring 5,068 C1010-Partitions GWB Walls - Standard (Non-Painted) 12,375 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 12,000 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 Wd 9,313 C1030-Fittings Restroom Accessories 2,082 C1030-Fittings Toilet Partitions 1,909 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 341 C3010-Wall Finishes Ceramic Wall Tile 13,264 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 6,641 C3020-Floor Finishes Carpeting 13,585 C3020-Floor Finishes Ceramic Floor Tile 3,656 C3020-Floor Finishes Concrete - Painted or Sealed 180 C3030-Ceiling Finishes GWB Taped and Finished 2,154 C3030-Ceiling Finishes Painted Finish on Wood Structures 2,214 D2010-Plumbing Fixtures Restroom Fixtures, Std Density, Avg Qual 7,783 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 1,907 D2020-Domestic Water Distribution Water Dist Complete - Average 8,322 D2020-Domestic Water Distribution Water Heater - Electric 2,008 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 5,261 D3040-Distribution Systems Barn Ceiling Fans 3,900 D3040-Distribution Systems Central AHU - VAV System w/distribution 53,328 D3040-Distribution Systems Four Pipe Distribution System 4,635 Page 3 of 4

14 D3040-Distribution Systems General Building Exhaust 4,868 D3040-Distribution Systems Restroom Exhaust System 4,564 D3050-Terminal and Package Units Unit Heaters 3,772 D3060-Controls and Instrumentation DDC System 6,268 D40-Fire Protection Fire Extinguishers - Dry Chem w/cabinet 171 D5010-Electrical Service and Distribution Feeder - Light Service 2,129 D5012-Low Tension Service and Dist. D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V 10,258 Main Electrical Service A 208Y/120V 12,653 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 10,624 D5022-Lighting Equipment Lighting Fixtures - Light Density 7,845 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 1,550 D5092-Emergency Light and Power Systems Exit Signs - Low Density 817 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 8,680 Subtotal 527,849 Overhead Cost Description Cost Total Replacement Value 527,849 Page 4 of 4

15 Agency: Virginia Community College System (VCCS) Asset Name: Alson H. Smith Hall Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: STATISTICS FCI Cost: 262,268 FCI: 0.09 Total Requirements Cost : 276,620 RI: 0.10 Current Replacement Value 2,796,437 Address Skirmisher Lane Size 16,154 SF Address 2 - Year Constructed 1984 City Middletown Year Renovated 2010 State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Howard Shockey & Sons, Inc. Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 2B Type Building Use Academic Last Inspection Date :30:00 Functional Use - PHOTO Alson H. Smith Hall - ASSET DESCRIPTION ARCHITECTURAL The Alson H. Smith Hall is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This one (1) story 16,154 SF building was originally constructed in 1984 and renovated in The building houses the classroom space, theatre, vocational training, seminar and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group B, Business with a secondary occupancy of Group A-3, Assembly and its primary construction type per the 2006 IBC is Type 2B Fully Sprinklered. REQUIREMENTS Page 1 of 5

16 Requirement Name Prime System Category Priority Action Date Cost ACT System - Standard - Older Renewal C3030-Ceiling Finishes Ceramic Floor Tile Renewal C3020-Floor Finishes of assm't date 01/11/ ,390 of assm't date 01/11/2015 8,963 Domestic Water Distribution - Backflow Prevention Lacking D2020-Domestic Water Distribution Grandfathered Code 5 - Does Not Meet Current Codes / Standards - 4,291 D5092-Emergency Emergency Battery Pack Lights Renewal Light and Power Systems 3 - Within mos. of assm't date 01/11/2014 8,878 Exterior Walls - Aged Caulk Joints B2010-Exterior Walls Reliability Fire Protection - Sprinkler Backflow Prevention Lacking D40-Fire Protection Grandfathered Code date) 01/11/2012 6, Does Not Meet Current Codes / Standards - 10,062 General Building Exhaust Renewal D3040-Distribution Systems date) 01/11/ ,558 HVAC Electric Controls - Average Renewal D3060-Controls and Instrumentation date) 01/11/ ,745 Lighting, Exterior Wall Pack Renewal D5020-Lighting and Branch Wiring date) 01/11/2012 1,935 Pedestrian Pavement - Cracked Concrete G2030-Pedestrian Paving Appearance 2 - Within 12 mos of assm't date 01/11/2013 4,164 Restroom Exhaust System w/roof Fan Renewal D3040-Distribution Systems date) 01/11/2012 6,995 Rooftop Unitary AC - Cooling w/gas Heat Renewal D3050-Terminal and Package Units date) 01/11/ ,554 Unit Heaters - Gas Renewal D3050-Terminal and Package Units date) 01/11/2012 1,982 Water Coolers, Wall-Mounted Renewal D2010-Plumbing Fixtures date) 01/11/2012 4,585 Total 276,621 Page 2 of 5

17 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 82,707 A-Substructure Grade Beams - Average 167,553 A-Substructure Structural Slab on Grade - Non Industrial 86,747 B10-Superstructure Floor joists, 2"x6", 24" OC, includes subfloor 1,990 B10-Superstructure Single-Story Superstructure 332,934 B2010-Exterior Walls Brick Walls 239,986 B2010-Exterior Walls Metal Paneled Walls 1,406 B2010-Exterior Walls Precast Concrete Panels 18,282 B2016-Exterior Soffits Painted Plaster Soffits 378 B2020-Exterior Windows Aluminum Windows - Newer 6,527 B2020-Exterior Windows Aluminum Windows - Older 77,671 B2030-Exterior Doors Automatic Openers - Pair 24,603 B2030-Exterior Doors Door Assembly - 3 x 7 HM 5,835 B2030-Exterior Doors Door Assembly - 6 x 7 HM - Newer 11,438 B2030-Exterior Doors Door Assembly - 6 x 7 HM - Older 5,719 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 25,669 B2030-Exterior Doors Overhead Doors (Electrically Operated) 4,051 B30-Roofing Adhered Membrane (EPDM) Single-Ply 90,307 B3022-Roof Hatches Roof Hatch 1,198 C1010-Partitions CMU Block Walls - Plain 162,321 C1010-Partitions GWB Walls - Standard (Non-Painted) 14,442 C1010-Partitions Windows/Storefront Partitions 10,273 C1020-Interior Doors Automatic Openers - Single 15,931 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 3,296 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 60,339 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 Wd 65,559 C1030-Fittings Restroom Accessories 10,412 C1030-Fittings Toilet Partitions 8,174 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 7,079 C3010-Wall Finishes Ceramic Wall Tile 13,539 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 39,600 C3020-Floor Finishes Carpeting - Tile 3,252 Page 3 of 5

18 C3020-Floor Finishes Ceramic Floor Tile 5,976 C3020-Floor Finishes Concrete - Painted or Sealed 5,250 C3020-Floor Finishes VCT 15,226 C3020-Floor Finishes Vinyl Sheet Goods 19,740 C3020-Floor Finishes Wood Flooring 10,859 C3030-Ceiling Finishes ACT System - Standard - Newer 9,672 C3030-Ceiling Finishes ACT System - Standard - Older 17,112 D2010-Plumbing Fixtures Custodial/Utility Sinks 1,264 D2010-Plumbing Fixtures Restroom Fixtures, Std Density, Avg Qual 17,208 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 3,668 D2010-Plumbing Fixtures Work/Exam/Scrub Sinks 16,682 D2020-Domestic Water Distribution Water Dist Complete - Average 42,847 D2020-Domestic Water Distribution Water Heater - Gas 4,757 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 27,408 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 22,032 D2090-Other Plumbing Systems Compressed Air Distribution 9,439 D2090-Other Plumbing Systems Dental Air Compressor 11,480 D2090-Other Plumbing Systems Dental Vacuum Pump (Each) 52,086 D2090-Other Plumbing Systems Natural Gas Distribution for Building 25,089 D3040-Distribution Systems General Building Exhaust 12,446 D3040-Distribution Systems Restroom Exhaust System w/roof Fan 5,596 D3040-Distribution Systems Welding Exhaust 31,294 D3050-Terminal and Package Units Rooftop Unitary AC - Cooling w/gas Heat 133,244 D3050-Terminal and Package Units Unit Heaters - Gas 1,769 D3060-Controls and Instrumentation HVAC Electric Controls - Average 11,796 D40-Fire Protection Fire Extinguishers, Dry Chem 421 D40-Fire Protection Wet Sprinkler System - Light Hazard wo/pump 66,820 D5010-Electrical Service and Distribution Distribution System - Medium Capacity 87,550 D5010-Electrical Service and Distribution Feeder - Average Service 19,542 D5010-Electrical Service and Distribution Switchgear - Average Duty 6,372 D5012-Low Tension Service and Dist. D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V 65,681 Main Electrical Service A 480Y/277V 44,622 D5020-Lighting and Branch Wiring Lighting, Exterior Wall Pack 1,548 Page 4 of 5

19 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 46,847 D5022-Lighting Equipment Lighting Fixtures - Average Density 42,753 D5033-Telephone Systems Telephone System - Average Density 33,923 D5039-Local Area Networks LAN System - Average Density 39,981 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 7,298 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 7,102 D5092-Emergency Light and Power Systems Exit Signs - Average Density 6,044 E-Equipment and Furnishings Fixed Casework - Institutional 20,895 E-Equipment and Furnishings Theater And Stage Equipment 153,451 E-Equipment and Furnishings Theater Curtains - Electrically Operated 11,341 E10-Equipment Access Ladder 1,520 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 19,566 Subtotal 2,796,435 Overhead Cost Description Cost Total Replacement Value 2,796,435 Page 5 of 5

20 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: Asset Name: Corron Community Development Center STATISTICS FCI Cost: 0 FCI: 0.00 Total Requirements Cost : 0 RI: 0.00 Current Replacement Value 5,714,987 Address Skirmisher Lane Size 30,490 SF Address 2 - Year Constructed 2010 City Middletown Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Burt, Hill Ownership Agency Owned Historical Category None Floors 2 Construction Type IBC - Type 2B Type Building Use Academic/Research Last Inspection Date :00:00 Functional Use - PHOTO Corron Community Development Center - ASSET DESCRIPTION ARCHITECTURAL The Corron Community Development Center is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This two (2) story 30,490 SF building and was constructed in The building houses classroom space, conference room, conference center and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group B, Business with a secondary occupancy of Group A-3, Assembly and its primary construction type per the 2006 IBC is Type 2B Fully Sprinklered. REQUIREMENTS Page 1 of 5

21 Requirement Name Prime System Category Priority Action Date Cost Total 0 Page 2 of 5

22 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 63,082 A-Substructure Grade Beams - Average 158,125 A-Substructure Structural Slab on Grade - Non Industrial 81,866 B10-Superstructure Superstructure - Multi Story - Steel 729,809 B2010-Exterior Walls Brick Walls 368,220 B2010-Exterior Walls Metal Paneled Walls 28,128 B2010-Exterior Walls Metal Screen Walls 29,546 B2020-Exterior Windows Curtain Wall System 903,600 B2030-Exterior Doors Automatic Openers - Single 21,242 B2030-Exterior Doors Door Assembly - 3 x 7 HM 8,752 B2030-Exterior Doors Door Assembly - 3 x 7 Storefront 6,593 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 20,535 B2030-Exterior Doors Overhead Rolling Doors - Manual Operation 2,601 B30-Roofing Single-Ply Membrane 77,146 B3022-Roof Hatches Roof Hatch 1,198 C1010-Partitions CMU Block Walls - Plain 36,180 C1010-Partitions Folding Partitions 168,858 C1010-Partitions GWB Partitions on Furring 21,210 C1010-Partitions GWB Walls - Standard (Non-Painted) 79,680 C1010-Partitions Windows/Storefront Partitions 25,682 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 13,185 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 149,641 C1020-Interior Doors Swinging Doors - 6 x 7 Storefront 15,401 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 56,194 C1030-Fittings Restroom Accessories 19,651 C1030-Fittings Toilet Partitions 33,414 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 13,361 C20-Stairs Stairs - Average 37,823 C3010-Wall Finishes Acoustical Wall Panels 12,864 C3010-Wall Finishes Ceramic Wall Tile 27,106 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 50,160 C3010-Wall Finishes Raised Wood Paneling 53,160 Page 3 of 5

23 C3020-Floor Finishes Carpeting 113,820 C3020-Floor Finishes Ceramic Floor Tile 14,785 C3020-Floor Finishes Concrete - Painted or Sealed 850 C3020-Floor Finishes Quarry Tile 6,578 C3020-Floor Finishes Rubber Tile 85,750 C3020-Floor Finishes Terrazzo 14,921 C3020-Floor Finishes VCT 2,648 C3030-Ceiling Finishes ACT System - Standard 100,440 C3030-Ceiling Finishes GWB Taped and Finished 5,852 D1010-Elevators and Lifts Hydraulic Passenger Elev, Economy 58,809 D2010-Plumbing Fixtures Custodial/Utility Sinks 1,419 D2010-Plumbing Fixtures Kitchenette Sink 1,749 D2010-Plumbing Fixtures Restroom Fixtures 23,670 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 923 D2020-Domestic Water Distribution Water Dist Complete - Average 80,871 D2020-Domestic Water Distribution Water Heater - Gas 22,231 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 51,732 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 20,793 D2090-Other Plumbing Systems Dental Vacuum Pump (Each) 52,086 D2090-Other Plumbing Systems Natural Gas Distribution for Building 47,355 D3020-Heat Generating Systems Boiler HW, Gas Fired 101,921 D3030-Cooling Generating Systems Chiller - Air Cooled - York 155,334 D3040-Distribution Systems Central AHU - VAV System w/distribution 537,948 D3040-Distribution Systems General Building Exhaust 11,672 D3040-Distribution Systems Restroom Exhaust System 3,109 D3060-Controls and Instrumentation DDC System, Average 27,912 D40-Fire Protection Fire Extinguishers, Dry Chem 794 D40-Fire Protection Wet Sprinkler System - Light Hazard w/o Pump 126,121 D5010-Electrical Service and Distribution Distribution System - Medium Capacity 165,248 D5010-Electrical Service and Distribution Feeder - Average Service 36,884 D5010-Electrical Service and Distribution Switchgear Amp 277/480V 43,270 D5020-Lighting and Branch Wiring Exterior Lighting 6,328 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 88,421 D5022-Lighting Equipment Lighting Fixtures - Average Density 80,695 Page 4 of 5

24 D5033-Telephone Systems Telephone System - Average Density 64,029 D5035-Television Systems Television Systems - Coaxial Connectivity 6,627 D5036-Clock and Program Systems Clock System - Light Density 14,794 D5038-Security and Detection Systems Security System - CCTV 13,231 D5039-Local Area Networks LAN System - Average Density 75,463 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 6,888 D5092-Emergency Light and Power Systems Emergency Generator - Average 350KW 56,715 D5092-Emergency Light and Power Systems Exit Signs - Average Density 11,408 E-Equipment and Furnishings Fixed Casework - Institutional 33,431 E-Equipment and Furnishings Kitchen Cabinets 3,605 E10-Equipment Access Ladder 2,280 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 19,566 Subtotal 5,714,989 Overhead Cost Description Cost Total Replacement Value 5,714,989 Page 5 of 5

25 Agency: Virginia Community College System (VCCS) Asset Name: Facility Operations Center Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: STATISTICS FCI Cost: 12,236 FCI: 0.02 Total Requirements Cost : 12,236 RI: 0.02 Current Replacement Value 492,047 Address Skirmisher Lane Size 5,200 SF Address 2 - Year Constructed 2005 City Middletown Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Chou & Associates Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 2B Type Building Use Maintenance Last Inspection Date :00:00 Functional Use - PHOTO Facility Operations Center - ASSET DESCRIPTION ARCHITECTURAL The Facility Operations Center is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This one (1) story 5,200 SF building was originally constructed in The building houses the maintenance and facilities shop, warehouse and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 2B Unprinklered. REQUIREMENTS Page 1 of 4

26 Requirement Name Prime System Category Priority Action Date Cost D5092-Emergency Emergency Battery Pack Lights Renewal Light and Power Systems of assm't date 02/22/2015 2,858 Emergency Eyewash - Blocked Access D2010-Plumbing Fixtures Life Safety date) 01/11/ D5092-Emergency Exit Signs - Low Density Renewal Light and Power Systems of assm't date 02/22/2015 1,459 Telephone System - Light Density Renewal D5033-Telephone Systems of assm't date 02/22/2015 7,735 Total 12,236 Page 2 of 4

27 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 32,442 A-Substructure Structural Slab on Grade - Light Industrial 37,492 B10-Superstructure Single-Story Superstructure 39,156 B2010-Exterior Walls Brick Walls 37,158 B2010-Exterior Walls Metal Paneled Walls 13,840 B2020-Exterior Windows Aluminum Windows 3,590 B2030-Exterior Doors Door Assembly - 3 x 7 HM 14,587 B2030-Exterior Doors Overhead Doors (Electrically Operated) 7,840 B30-Roofing Gutters and Downspouts - Aluminum 2,074 B30-Roofing Metal Roofing 42,405 C1010-Partitions CMU Block Walls - Plain 7,069 C1010-Partitions GWB Partitions on Furring 6,717 C1010-Partitions GWB Walls - Standard (Non-Painted) 5,976 C1010-Partitions Windows/Storefront Partitions 1,027 C1020-Interior Doors Swinging Doors - 3 x 7 HM 26,705 C1030-Fittings Restroom Accessories 2,577 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 1,139 C3010-Wall Finishes Ceramic Wall Tile 2,436 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 7,069 C3020-Floor Finishes Concrete - Painted or Sealed 4,080 C3020-Floor Finishes VCT 1,324 C3030-Ceiling Finishes ACT System - Standard 2,604 C3030-Ceiling Finishes Batt Insulation - Vinyl Faced 5,082 D2010-Plumbing Fixtures Emergency Eyewash and Shower Units 2,451 D2010-Plumbing Fixtures Restroom Fixtures 6,227 D2010-Plumbing Fixtures Work Sink 1,795 D2020-Domestic Water Distribution Water Dist Complete - Average 13,792 D2020-Domestic Water Distribution Water Heater - Gas - Residential - 30 Gal 2,486 D2030-Sanitary Waste Sanitary Waste - Pumped Disch 25,416 D2090-Other Plumbing Systems Natural Gas Distribution 5,234 D3030-Cooling Generating Systems DX Split Systems 15,061 D3040-Distribution Systems General Building Exhaust 15,487 Page 3 of 4

28 D3040-Distribution Systems Restroom Exhaust System w/roof Fan 607 D3050-Terminal and Package Units Unit Heaters - Electric 3,520 D3050-Terminal and Package Units Unit Heaters - Gas Fired 8,425 D40-Fire Protection Fire Extinguishers - Dry Chem 135 D5010-Electrical Service and Distribution Distribution System - Light Capacity 17,785 D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 208Y/120V 11,139 D5020-Lighting and Branch Wiring Lighting, exterior flood, pair 372 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 15,080 D5022-Lighting Equipment Lighting Fixtures - Light Density 11,219 D5033-Telephone Systems Telephone System - Light Density 7,280 D5039-Local Area Networks LAN System - Light Density 8,632 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 2,286 D5092-Emergency Light and Power Systems Exit Signs - Low Density 1,167 E-Equipment and Furnishings Fixed Casework - Average 3,366 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 8,696 Subtotal 492,047 Overhead Cost Description Cost Total Replacement Value 492,047 Page 4 of 4

29 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: Asset Name: Fairfax Hall (Academic & Administration Building) STATISTICS FCI Cost: 2,993,464 FCI: 0.41 Total Requirements Cost : 3,355,541 RI: 0.46 Current Replacement Value 7,277,607 Address Skirmisher Lane Size 60,223 SF Address 2 - Year Constructed 1969 City Middletown Year Renovated 1989 State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Lyles, Bissett, Carlisle & Wolff Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 2B Type Building Use Academic Last Inspection Date :00:00 Functional Use - PHOTO Exterior View - Main Elevation - ASSET DESCRIPTION ARCHITECTURAL The Fairfax Hall (Academic and Administration Building) is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This one (1) story 60,223 SF building was originally constructed in 1969 and expanded the Student Center in The building is connected to the Paul Wolk Library on the south side. The facility houses the main reception, classrooms, pottery studio, paining studio, bookstore, student lounges and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 2B Partially Sprinklered. REQUIREMENTS Page 1 of 8

30 Requirement Name Prime System Category Priority Action Date Cost ACT System - Standard - Older Renewal C3030-Ceiling Finishes ADA - Handrails Missing (Lecture Hall 140) - Accessibility of assm't date 01/11/ , Does Not Meet Current Codes / Standards - 2, Does Not Meet ADA - Non-Compliant Service Counters E-Equipment and Furnishings Accessibility Current Codes / Standards - 4,306 Aluminum Windows - Older Renewal B2020-Exterior Windows date) 01/11/ ,486 Branch Wiring - Equipment & Devices Renewal D5021-Branch Wiring Devices of assm't date 02/22/ ,308 Carpeting - Older Renewal C3020-Floor Finishes Ceramic Floor Tile Renewal C3020-Floor Finishes 3 - Within mos. of assm't date 01/11/ ,950 of assm't date 01/11/ ,561 Custodial/Utility Sinks Renewal D2010-Plumbing Fixtures date) 01/11/2012 5,916 DDC System, Average Renewal D3060-Controls and Instrumentation date) 01/11/ ,915 Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V Renewal D5012-Low Tension Service and Dist. date) 02/22/ ,079 Distribution System - Medium Capacity Renewal D5010-Electrical Service and Distribution date) 02/22/ ,991 DX Split System Renewal D3030-Cooling Generating Systems 2 - Within 12 mos of assm't date 02/22/2013 7,947 Electric Heat Renewal D3050-Terminal and Package Units date) 01/11/ ,977 Electrical Panelboard - Inadequate Directory D5010-Electrical Service and Distribution Building Code date) 01/11/2012 3,145 D5092-Emergency Exit Signs - Average Density Renewal Light and Power Systems of assm't date 02/22/ ,165 Exterior Walls - Aged and Stained Brick B2010-Exterior Walls Appearance 2 - Within 12 mos of assm't date 01/11/ ,378 Page 2 of 8

31 Requirement Name Prime System Category Priority Action Date Cost Exterior Walls - Aged Caulk Joints B2010-Exterior Walls date) 01/11/2012 8,206 Feeders Renewal D5010-Electrical Service and Distribution date) 02/22/ ,066 Fire Protection - Insufficient Sprinkler Coverage D40-Fire Protection Mission Fire Protection - Sprinkler Backflow Prevention Lacking D40-Fire Protection Grandfathered Code of assm't date 01/11/ , Does Not Meet Current Codes / Standards - 10,062 General Building Exhaust Renewal D3040-Distribution Systems date) 01/11/ ,903 Interior Doors - Electrical Room Doors Non-Compliant C1020-Interior Doors Life Safety date) 01/11/2012 7,058 LAN System - Average Density Renewal D5039-Local Area Networks of assm't date 02/22/ ,368 Life Safety: Firestopping Lacking C1010-Partitions Life Safety date) 01/11/2012 3,758 Lighting Fixtures - Average Density Renewal D5022-Lighting Equipment 3 - Within mos. of assm't date 01/11/ ,234 Lighting, exterior flood, pair Renewal D5020-Lighting and Branch Wiring date) 01/11/ Main Electrical Service A 480Y/277V Renewal D5012-Low Tension Service and Dist. date) 02/22/ ,049 Natural Gas Distribution for Lab Renewal D2090-Other Plumbing Systems date) 01/11/ ,706 Pedestrian Pavement - Cracked Concrete G2030-Pedestrian Paving Appearance 2 - Within 12 mos of assm't date 01/11/2013 3, Does Not Meet Plumbing - Non-Code Compliant Sink Install D2010-Plumbing Fixtures Building Code Current Codes / Standards - 2,762 Restroom Exhaust System w/roof Fan Renewal D3040-Distribution Systems date) 01/11/ ,853 Page 3 of 8

32 Requirement Name Prime System Category Priority Action Date Cost Rooftop Unitary AC - Cooling w/gas Heat Renewal D3050-Terminal and Package Units date) 01/11/ ,988 Switchgear Renewal D5010-Electrical Service and Distribution date) 02/22/ ,696 Telephone System - Average Density Renewal D5033-Telephone Systems of assm't date 02/22/ ,373 Total 3,355,541 Page 4 of 8

33 REPLACEMENT VALUE A-Substructure A-Substructure Foundation Wall and Footings - No Basement - Addition 10,013 Foundation Wall and Footings - No Basement - Original 140,182 A-Substructure Grade Beams - Average 583,988 A-Substructure A-Substructure Structural Slab on Grade - Non Industrial - Addition 21,050 Structural Slab on Grade - Non Industrial - Original 302,347 B10-Superstructure Single-Story Superstructure - Addition 29,518 B10-Superstructure Single-Story Superstructure - Original 423,962 B1014-Ramps Accessible Ramps - Exterior Concrete 26,071 B1014-Ramps Accessible Ramps - Interior Concrete 22,812 B1015-Exterior Stairs and Fire Escapes Exterior Stairs - Concrete 1,497 B2010-Exterior Walls Brick Walls 328,399 B2010-Exterior Walls Metal Paneled Walls - Addition 11,720 B2010-Exterior Walls Metal Paneled Walls - Original 16,408 B2010-Exterior Walls Precast Concrete Panels 27,215 B2016-Exterior Soffits Painted Plaster Soffits 7,108 B2020-Exterior Windows Aluminum Windows - Mid 63,965 B2020-Exterior Windows Aluminum Windows - Newer 13,054 B2020-Exterior Windows Aluminum Windows - Older 93,989 B2030-Exterior Doors Automatic Openers - Single 15,931 B2030-Exterior Doors Door Assembly - 3 x 7 HM 11,670 B2030-Exterior Doors Door Assembly - 3 x 7 Storefront 29,666 B2030-Exterior Doors Door Assembly - 6 x 7 HM 5,719 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 30,803 B2030-Exterior Doors Overhead Doors (Electrically Operated) 8,101 B30-Roofing Adhered Membrane (EPDM) Single-Ply 336,670 B3022-Roof Hatches Roof Hatch 1,198 C1010-Partitions Brick Walls 44,880 C1010-Partitions CMU Block Walls - Plain 337,680 C1010-Partitions Folding Partitions 40,026 C1010-Partitions GWB Partitions on Furring 2,121 C1010-Partitions GWB Walls - Standard (Non-Painted) 26,892 C1010-Partitions Windows/Storefront Partitions 46,228 Page 5 of 8

34 C1020-Interior Doors Automatic Openers - Single 15,931 C1020-Interior Doors Overhead/Rolling Grilles 10,807 C1020-Interior Doors Swinging Doors - 3 x 7 HM 21,364 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 19,778 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 470,644 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 HM 10,450 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 Wd 28,097 C1030-Fittings Restroom Accessories 38,815 C1030-Fittings Toilet Partitions 30,474 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 26,390 C20-Stairs Interior Stairs - Concrete - Newer 1,670 C20-Stairs Interior Stairs - Concrete - Older 2,505 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 80,784 C3020-Floor Finishes Access Computer Room Flooring System 51,563 C3020-Floor Finishes Carpeting - Newer 97,560 C3020-Floor Finishes Carpeting - Older 97,560 C3020-Floor Finishes Ceramic Floor Tile 17,249 C3020-Floor Finishes Concrete - Painted or Sealed 3,400 C3020-Floor Finishes Epoxy Flooring 6,482 C3020-Floor Finishes VCT - Newer 20,191 C3020-Floor Finishes VCT - Older 37,072 C3030-Ceiling Finishes ACT System - Standard - Newer 35,712 C3030-Ceiling Finishes ACT System - Standard - Older 170,376 C3030-Ceiling Finishes GWB Taped and Finished 9,576 D2010-Plumbing Fixtures Custodial/Utility Sinks 4,733 D2010-Plumbing Fixtures Emergency Eyewash and Shower Units 4,962 D2010-Plumbing Fixtures Restroom Fixtures 67,664 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted ,823 D2010-Plumbing Fixtures Work/Exam/Kitchen Sinks 11,685 D2020-Domestic Water Distribution Water Dist Complete - Average 159,735 D2020-Domestic Water Distribution Water Heater - Gas 5,783 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 102,180 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 82,138 D2090-Other Plumbing Systems Lab Acid Waste System 26,607 Page 6 of 8

35 D2090-Other Plumbing Systems Natural Gas Distribution for Building 93,534 D2090-Other Plumbing Systems Natural Gas Distribution for Lab 18,965 D3030-Cooling Generating Systems DX Split System 6,358 D3040-Distribution Systems Fume Hood and Exhaust System 45,795 D3040-Distribution Systems General Building Exhaust 101,522 D3040-Distribution Systems Restroom Exhaust System w/roof Fan 23,882 D3050-Terminal and Package Units Electric Heat 31,230 D3050-Terminal and Package Units D3050-Terminal and Package Units Rooftop Unitary AC - Cooling w/gas Heat ,390 Rooftop Unitary AC - Cooling w/gas Heat ,254 D3060-Controls and Instrumentation DDC System, Average 55,132 D40-Fire Protection Fire Extinguishers, Dry Chem 1,568 D40-Fire Protection Wet Sprinkler System - Light Hazard w/opump 23,291 D5010-Electrical Service and Distribution Distribution System - Medium Capacity 326,393 D5010-Electrical Service and Distribution Feeders 72,853 D5010-Electrical Service and Distribution Switchgear 23,757 D5012-Low Tension Service and Dist. D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V 244,863 Main Electrical Service A 480Y/277V 107,239 D5020-Lighting and Branch Wiring Lighting, exterior flood, pair 744 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 174,647 D5022-Lighting Equipment Lighting Fixtures - Average Density 159,387 D5033-Telephone Systems Telephone System - Average Density 126,468 D5039-Local Area Networks LAN System - Average Density 149,052 D5091-Grounding Systems Lightning Protection Systems - Bldg Over 75' 38,371 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 26,478 D5092-Emergency Light and Power Systems Emergency Generator - Average 250KW 65,936 D5092-Emergency Light and Power Systems Exit Signs - Average Density 22,532 E-Equipment and Furnishings Fixed Casework - Institutional 25,073 E-Equipment and Furnishings Fixed Seating 21,281 E-Equipment and Furnishings Kitchen Cabinets 7,209 E10-Equipment Access Ladder 2,280 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 43,480 Page 7 of 8

36 Subtotal 7,277,607 Overhead Cost Description Cost Total Replacement Value 7,277,607 Page 8 of 8

37 Agency: Virginia Community College System (VCCS) Asset Name: Paul Wolk Library Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: STATISTICS FCI Cost: 530,659 FCI: 0.13 Total Requirements Cost : 543,803 RI: 0.13 Current Replacement Value 4,181,838 Address Skirmisher Lane Size 27,430 SF Address 2 - Year Constructed 1995 City Middletown Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect Gauthier, Alvarado & Associates, Inc. Ownership Agency Owned Historical Category None Floors 1 Construction Type IBC - Type 2B Type Building Use Library Last Inspection Date :30:00 Functional Use - PHOTO Paul Wolk Library - ASSET DESCRIPTION ARCHITECTURAL The Paul Wolk Library Building is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This one (1) story 27,430 SF building was originally constructed in 1995 with a small expansion in The building is connected to the Fairfax Hall on the north side. The building houses the main library, Warren B. French, Jr. Telecommunications Center, student learning center, and offices for the college plus associated building support spaces. The building s primary occupancy is classified as Group A-3, Assembly and its primary construction type per the 2006 IBC is Type 2B Fully Sprinklered. REQUIREMENTS Page 1 of 5

38 Requirement Name Prime System Category Priority Action Date Cost 5 - Does Not Meet ADA - Non-Compliant Kitchen Casework E-Equipment and Furnishings Accessibility Current Codes / Standards - 3,082 Ballasted Membrane (EPDM) Single-Ply Renewal B30-Roofing Carpeting Renewal C3020-Floor Finishes of assm't date 01/11/ ,137 of assm't date 01/11/ ,825 DDC System, Average Renewal D3060-Controls and Instrumentation of assm't date 02/22/ ,389 D5092-Emergency Emergency Battery Pack Lights Renewal Light and Power Systems of assm't date 02/22/ ,075 D5092-Emergency Exit Signs - Average Density Renewal Light and Power Systems of assm't date 02/22/ ,828 Exterior Walls - Aged and Stained Brick B2010-Exterior Walls Appearance 2 - Within 12 mos of assm't date 01/11/2013 4,168 Exterior Windows - Failing Glass Seals B2020-Exterior Windows Reliability 2 - Within 12 mos of assm't date 01/11/ ,764 Fire Protection - Sprinkler Backflow Prevention Lacking D40-Fire Protection Grandfathered Code 5 - Does Not Meet Current Codes / Standards - 10,062 Lighting, exterior flood, pair Renewal D5020-Lighting and Branch Wiring of assm't date 02/22/ Metal Screen Walls - Framing Aged Paint Finish B2010-Exterior Walls Appearance 3 - Within mos. of assm't date 01/11/2014 1,715 Rooftop Unitary AC - Cooling w/gas Heat Renewal D3050-Terminal and Package Units date) 01/11/ ,013 Water Coolers, Wall-Mounted Renewal D2010-Plumbing Fixtures of assm't date 02/22/2015 1,038 Water Heater - Electric Renewal D2020-Domestic Water Distribution date) 02/22/2012 5,242 Total 543,803 Page 2 of 5

39 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 91,218 A-Substructure Grade Beams - Average 284,511 A-Substructure Structural Slab on Grade - Non Industrial 147,299 B10-Superstructure Single-Story Superstructure 565,332 B1014-Ramps Ramps - Exterior Concrete 20,368 B1015-Exterior Stairs and Fire Escapes Exterior Stairs - Concrete 1,596 B2010-Exterior Walls Brick Walls 291,006 B2010-Exterior Walls Metal Paneled Walls 105,480 B2010-Exterior Walls Metal Screen Walls 10,744 B2016-Exterior Soffits Painted Plaster 5,178 B2020-Exterior Windows Aluminum Windows 95,294 B2030-Exterior Doors Automatic Openers - Single 37,173 B2030-Exterior Doors Door Assembly - 3 x 7 HM 2,917 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 46,204 B30-Roofing Ballasted Membrane (EPDM) Single-Ply 137,709 C1010-Partitions Brick Walls 48,960 C1010-Partitions CMU Block Walls - Plain 30,813 C1010-Partitions Demountable Partitions 13,370 C1010-Partitions Folding Partitions 38,722 C1010-Partitions GWB Partitions on Furring 17,330 C1010-Partitions GWB Walls - Standard (Non-Painted) 33,055 C1010-Partitions Windows/Storefront Partitions 64,410 C1020-Interior Doors Automatic Openers - Single 21,242 C1020-Interior Doors Swinging Doors - 3 x 7 HM 10,682 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 3,296 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 77,234 C1020-Interior Doors Swinging Doors - 6 x 7 Storefront 5,134 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 Glazed Wd 19,604 C1030-Fittings Restroom Accessories 17,679 C1030-Fittings Toilet Partitions 16,116 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 12,020 C3010-Wall Finishes Acoustical Wall Panels 6,432 C3010-Wall Finishes Ceramic Wall Tile 33,388 Page 3 of 5

40 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 23,994 C3020-Floor Finishes Carpeting 124,660 C3020-Floor Finishes Ceramic Floor Tile 11,089 C3020-Floor Finishes Glazed Brick 36,696 C3020-Floor Finishes VCT 3,310 C3030-Ceiling Finishes ACT System - Standard 87,420 C3030-Ceiling Finishes GWB Taped and Finished 10,108 D2010-Plumbing Fixtures Custodial/Utility Sinks 1,276 D2010-Plumbing Fixtures Kitchen Sink 1,574 D2010-Plumbing Fixtures Restroom Fixtures 21,294 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 830 D2020-Domestic Water Distribution Water Dist Complete - Average 26,524 D2020-Domestic Water Distribution Water Heater - Electric 4,680 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 46,540 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 37,412 D2040-Rain Water Drainage Roof Drainage - Secondary Drain - Add 7,482 D2090-Other Plumbing Systems Natural Gas Distribution for Building 15,531 D3040-Distribution Systems Central AHU - VAV System w/distribution 483,959 D3040-Distribution Systems General Building Exhaust 16,988 D3040-Distribution Systems Restroom Exhaust System 5,594 D3050-Terminal and Package Units Electric Heat 8,517 D3050-Terminal and Package Units Rooftop Unitary AC - Cooling w/gas Heat 92,811 D3060-Controls and Instrumentation DDC System, Average 25,111 D40-Fire Protection Fire Extinguishers, Dry Chem 714 D40-Fire Protection Wet Sprinkler System - Light Hazard wo/pump 113,463 D5010-Electrical Service and Distribution Distribution System - Medium Capacity 148,663 D5010-Electrical Service and Distribution Feeder - Average Service 33,182 D5010-Electrical Service and Distribution Switchgear - Average Duty 5,635 D5012-Low Tension Service and Dist. D5012-Low Tension Service and Dist. Distribution Equipment, Panelboards, and Feeders A 480Y/277V & 208Y/120V 80,989 Main Electrical Service A 208Y/120V 11,534 D5020-Lighting and Branch Wiring Lighting, exterior flood, pair 372 Page 4 of 5

41 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 79,547 D5022-Lighting Equipment Lighting Fixtures - Average Density 72,597 D5033-Telephone Systems Telephone System - Average Density 57,603 D5039-Local Area Networks LAN System - Average Density 67,889 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 12,393 D5092-Emergency Light and Power Systems Emergency Battery Pack Lights 12,060 D5092-Emergency Light and Power Systems Exit Signs - Average Density 10,263 E-Equipment and Furnishings Fixed Casework - Institutional 33,431 E-Equipment and Furnishings Kitchen Cabinets 4,326 E10-Equipment Access Ladder 1,824 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 30,436 Subtotal 4,181,837 Overhead Cost Description Cost Total Replacement Value 4,181,837 Page 5 of 5

42 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Number: Asset Name: Science and Health Professions Building STATISTICS FCI Cost: 5,193 FCI: 0.00 Total Requirements Cost : 6,212 RI: 0.00 Current Replacement Value 7,320,812 Address Skirmisher Lane Size 48,000 SF Address 2 - Year Constructed 2008 City Middletown Year Renovated - State/Province/Region VA Commission Date 08/25/2008 Zip/Postal Code Decommission Date - Architect Burt Hill Kosar Rittelmann Associates Ownership Agency Owned Historical Category None Floors 2 Construction Type IBC - Type 2B Type Building Use Academic/Research Last Inspection Date :00:00 Functional Use - PHOTO Science and Health Professions Building - ASSET DESCRIPTION ARCHITECTURAL The Science and Health Professions Building is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This two (2) story 48,000 SF building and was constructed in The building houses classrooms, offices, nursing and science labs, conference room and a facility mechanical room. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 2B fully sprinklered. REQUIREMENTS Page 1 of 5

43 Requirement Name Prime System Category Priority Action Date Cost ADA - Non-Compliant Auto Door Opener Buttons B2030-Exterior Doors Accessibility 5 - Does Not Meet Current Codes / Standards - 1,020 Grounding - Main Water Line Not Grounded D5010-Electrical Service and Distribution Building Code date) 01/11/2012 3,151 Life Safety - Firestopping Lacking D5039-Local Area Networks Life Safety date) 01/11/2012 2,042 Total 6,213 Page 2 of 5

44 REPLACEMENT VALUE A-Substructure Foundation Wall and Footings - No Basement 72,094 A-Substructure Grade Beams - Average 248,934 A-Substructure Structural Slab on Grade - Non Industrial 128,880 B10-Superstructure Superstructure - Multi Story - Steel 1,148,928 B1015-Exterior Stairs and Fire Escapes Exterior Stairs - Concrete 712 B2010-Exterior Walls Brick Walls 364,670 B2014-Exterior Sun Control Devices Metal Canopies 34,502 B2020-Exterior Windows Aluminum Windows 162,653 B2020-Exterior Windows Curtain Wall System 503,004 B2030-Exterior Doors Automatic Openers - Pair 49,207 B2030-Exterior Doors Door Assembly - 3 x 7 HM 11,670 B2030-Exterior Doors Door Assembly - 6 x 7 HM 22,875 B2030-Exterior Doors Door Assembly - 6 x 7 Storefront 20,535 B30-Roofing Single-Ply Membrane 120,489 B3022-Roof Hatches Roof Hatch 1,198 C1010-Partitions CMU Block Walls - Plain 33,500 C1010-Partitions Folding Partitions 52,534 C1010-Partitions GWB Partitions on Furring 31,596 C1010-Partitions GWB Walls - Standard (Non-Painted) 99,600 C1010-Partitions Windows/Storefront Partitions 8,218 C1020-Interior Doors Swinging Doors - 3 x 7 HM 26,705 C1020-Interior Doors Swinging Doors - 3 x 7 Storefront 3,296 C1020-Interior Doors Swinging Doors - 3 x 7 Wd 156,881 C1020-Interior Doors Swinging Doors - 6 x 7 Storefront 20,535 C1020-Interior Doors Swinging Doors - Pair - 6 x 7 28,097 C1030-Fittings Restroom Accessories 30,937 C1030-Fittings Toilet Partitions 28,201 C1035-Identifying Devices Fittings: Signage (Room Numbering and Identification) 21,034 C20-Stairs Stairs - Average 67,932 C3010-Wall Finishes Ceramic Wall Tile 9,857 C3010-Wall Finishes Painted Finish - Average (1 Coat Prime - 2 Coats Finish) 64,598 C3020-Floor Finishes Carpeting 48,238 Page 3 of 5

45 C3020-Floor Finishes Concrete - Painted or Sealed 2,295 C3020-Floor Finishes Terrazzo 147,654 C3020-Floor Finishes VCT 87,715 C3030-Ceiling Finishes ACT System - Standard 165,540 C3030-Ceiling Finishes GWB Taped and Finished 4,788 C3030-Ceiling Finishes Metal Paneled System 5,208 D1010-Elevators and Lifts Hydraulic Passenger Elev 58,809 D2010-Plumbing Fixtures Custodial/Utility Sinks 2,234 D2010-Plumbing Fixtures Kitchenette Sink 2,754 D2010-Plumbing Fixtures Restroom Fixtures 37,263 D2010-Plumbing Fixtures Water Coolers, Wall-Mounted 1,453 D2020-Domestic Water Distribution Water Dist Complete - Average 127,315 D2020-Domestic Water Distribution Water Heater - Gas 22,231 D2030-Sanitary Waste Sanitary Waste - Gravity Disch - Average 81,441 D2040-Rain Water Drainage Roof Drainage - Gravity - Average 32,733 D2090-Other Plumbing Systems Dental Vacuum Pump (Each) 52,086 D2090-Other Plumbing Systems Natural Gas Distribution for Building 74,550 D3020-Heat Generating Systems Boiler HW, Gas Fired 101,921 D3030-Cooling Generating Systems Chiller - Air Cooled - York 155,334 D3040-Distribution Systems Central AHU - VAV System w/distribution 846,885 D3040-Distribution Systems General Building Exhaust 18,375 D3040-Distribution Systems Restroom Exhaust System 4,894 D3060-Controls and Instrumentation DDC System, Average 43,942 D40-Fire Protection Fire Extinguishers, Dry Chem 1,249 D40-Fire Protection Wet Sprinkler System - Light Hazard wo/pump 198,550 D5010-Electrical Service and Distribution Distribution System - Medium Capacity 260,147 D5010-Electrical Service and Distribution Feeder - Average Service 58,066 D5010-Electrical Service and Distribution Switchgear Amp 277/480V 43,270 D5020-Lighting and Branch Wiring Exterior Lighting 6,328 D5021-Branch Wiring Devices Branch Wiring - Equipment & Devices 139,200 D5022-Lighting Equipment Lighting Fixtures 127,037 D5033-Telephone Systems Telephone System 100,800 D5035-Television Systems Television Systems - Coaxial Connectivity 10,434 D5036-Clock and Program Systems Clock System - Light Density 23,290 Page 4 of 5

46 D5038-Security and Detection Systems Security System - CCTV 20,830 D5039-Local Area Networks LAN System - Average Density 118,800 D5091-Grounding Systems Lightning Protection Systems - Bldg Under 75' 10,843 D5092-Emergency Light and Power Systems Emergency Generator - Average 350KW 56,715 D5092-Emergency Light and Power Systems Exit Signs - Average Density 17,959 E-Equipment and Furnishings Fixed Casework - Institutional 100,294 E-Equipment and Furnishings Fixed Seating 20,762 E-Equipment and Furnishings Kitchen Cabinets 5,407 E-Equipment and Furnishings Laboratory Equipment - College 278,040 E10-Equipment Access Ladder 1,520 G2030-Pedestrian Paving Pedestrian Pavement - Concrete 21,740 Subtotal 7,320,811 Overhead Cost Description Cost Total Replacement Value 7,320,811 Page 5 of 5

47 Agency: Virginia Community College System (VCCS) Location: LORD FAIRFAX-MIDDLETOWN CAMPUS Asset Name: The Lodge (Modular Building) Asset Number: 298T02 STATISTICS FCI Cost: 6,113 FCI: 0.01 Total Requirements Cost : 6,113 RI: 0.01 Current Replacement Value 473,607 Address Skirmisher Lane Size 7,200 SF Address 2 - Year Constructed 2008 City Middletown Year Renovated - State/Province/Region VA Commission Date - Zip/Postal Code Decommission Date - Architect N/A Ownership Leased Historical Category None Floors 1 Construction Type IBC - Type 5B Type Building Use Academic Last Inspection Date :00:00 Functional Use - PHOTO Exterior View - Main Elevation - ASSET DESCRIPTION ARCHITECTURAL The Lodge (Modular Building) is located at 173 Skirmisher Lane, Middletown, VA 22645, on the Main Campus of Lord Fairfax Community College. This leased one (1) story 7,200 SF building was originally constructed and installed on site in The building is a single pre-finished modular structure with a combined ten (10) module single-wide trailer footprint. The building houses additional classrooms and offices for the college. The building s primary occupancy is classified as Group B, Business and its primary construction type per the 2006 IBC is Type 5B Unsprinklered. REQUIREMENTS Page 1 of 3