ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/06/2013 BUILDING SURVEY DATE

Size: px
Start display at page:

Download "ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/06/2013 BUILDING SURVEY DATE"

Transcription

1 WEST GREEN STREET URBANA, ILLINOIS SYSTEM CONDITION INDEX.810 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 18,640,900 OFFICE BUILDING GROSS SQUARE FEET 175,513 NUMBER OF BUILDING STORIES 4 BUILDING SURVEY DATE CANNON DESIGN: Tim Morriss (M), Amanda Buchheit (E) ORIGINAL YEAR OF CONSTRUCTION /06/2013 B U I L D I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y TRADE E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR ($) GOOD ($) (5-10 YEARS) (10-20 YEARS) POOR ($) (1-5 YEARS) EXCELLENT ($) (20+ YEARS) TOTAL ($) $/GSF PERCENT OF BUILDING TOTAL (%) MECHANICAL 9,752, , , ,500 10,755, PLUMBING 3,051, , ,200 3,577, FIRE PROTECTION 70, , , ELECTRICAL 2,049, , ,000 3,083, COMMUNICATIONS 173, , , TOTAL % OF TOTAL 15,096,700 1,002,300 1,207,100 1,334,700 18,640, NO CRITICAL ITEMS IDENTIFIED FOR THIS BUILDING NOTE: Cost Estimates are Construction Costs are in 2013 dollars to Replace in Kind unless otherwise noted PAGE 1

2 PAGE 2

3 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y SYSTEM/COMPONENT CHILLED WATER SYSTEM Chilled Water Piping Departmental Units Chilled Water Piping Lab 336 Process Chilled Water Piping from Campus Loop PROCESS COOLING SYSTEM Liebert Unit (Rm. 106H) Liebert Unit (serves unknown room) STEAM AND CONDENSTATE SYSTEM Steam and Condensate piping HEATING HOT WATER SYSTEM Heating Hot Water for Departmental Units HEAT EXCHANGER Heat Exchanger for Departmental AHUs SUPPLY AIR SYSTEM Supply Air Ductwork POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 67,200 67,200 52,700 52, , ,400 21,600 21,600 23,700 23,700 2,101,300 2,101,300 67,800 67,800 21,400 21,400 4,545,500 4,545, PAGE 3

4 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y AIR HANDLER TOILET EXHAUST SYSTEM LABORATORY EXHAUST SYSTEM SYSTEM/COMPONENT 58.AHU1 58.AHU10 58.AHU11 58.AHU12 58.AHU13 58.AHU14 58.AHU2 58.AHU3 58.AHU4 58.AHU5 58.AHU6 58.AHU7 58.AHU8 58.AHU9 D.AHU1 (Laser Lab) D.AHU2 (Laser Lab) D.AHU3 D.AHU4A D.AHU4B Two Small Split DX Systems Toilet Exhaust Laboratory Exhaust POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 293, , , ,900 83,100 83,100 52,000 52,000 98,800 98,800 98,800 98, , , , , , , , , , , , , , , , ,400 62,700 62,700 62,700 62,700 62,700 62,700 47,700 47,700 43,600 43,600 33,000 33,000 6,200 6, , , PAGE 4

5 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y NATURAL GAS SYSTEM HVAC CONTROLS SYSTEM SYSTEM/COMPONENT Natural Gas HVAC Controls MECHANICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 223, ,800 32,400 32,400 9,752, , , ,500 10,755, PAGE 5

6 Text6 C H I L L E D W A T E R P I P I N G D E P A R T M E N T A L U N I T S A S S E S S M E N T D A T A Item ID Description Department units D.AHU1, D.AHU2, and the process chilled water system serving Labs 336 and 336A are served by a chilled water loop that uses a plate-and-frame heat exchanger that is located in Penthouse Rm Overall Condition Date Installed 1/1/2003 Manufacturer Model Number This chilled water loop is a remnant of a previous air-cooled chiller system. The air-cooled chiller was essentially abandoned when the building was added to the campus chilled water system. The system used an outside DX condensing unit that was connected to an indoor evaporator/chiller unit. The outside DX condensing unit is now abandoned, and the indoor evaporator/chiller unit is now abandoned except for the duplex inline pumps and pumping package components. These duplex inline pumps are still used to circulate the chilled water piping loop for the departmental units. When the building was added to the campus chilled water system the plate-and-frame heat exchanger was added to allow the campus chilled water system to serve this chilled water loop. The pumps Good Remaining Useful Life 20 Years Nominal Useful Life: 30 Years Replacement Cost $67,200 Pumps: Bell & Gossett; Heat Exchanger: Alfa Laval Heat Exchanger: M6-FG Serial Number Heat Exchanger: Size/Capacity Voltage Process: degrees F Pump: 208V / 1 phase PAGE 6

7 Text6 C H I L L E D W A T E R P I P I N G D E P A R T M E N T A L U N I T S S U R V E Y P H O T O G R A P H S Heat Exchanger and associated piping in penthouse Rm.503. The chilled water supply and return to the departmental units D.AHU1 and D.AHU2 penetrates the floor. Campus chilled water is coming from above. Heat Exchanger in penthouse Rm Evaporator/chiller unit in penthouse Rm This unit is abandoned (including the two chilled water buffer tanks seen behind the unit) except for the pumping package (pumps are red in color). One pump was operating at time of survey. The Trane DX condensing unit that served the departmental unit chilled water loop is now abandoned PAGE 7

8 Text6 C H I L L E D W A T E R P I P I N G L A B P R O C E S S A S S E S S M E N T D A T A Item ID Description The labs in rooms 336 and 336A are served by a process chilled water system. The labs have valved connections for chilled water supply and return. This chilled water system is served by a small heat exchanger located in room 334A (adjacent to D.AHU2) with a small pumping package that has a simplex pump. This simplex pump was recently replaced. Overall Condition Date Installed 1/1/2003 Manufacturer HP/kW The heat exchanger uses chilled water from the same chilled water piping loop that serves D.AHU2 (this larger chilled water piping loop uses a plate-and-frame heat exchanger located in the penthouse that is also tied to the campus chilled water loop). Good Remaining Useful Life 20 Years Nominal Useful Life: 30 Years Size/Capacity Voltage Pump: Grundfos Pump: 1.5 HP Replacement Cost $52,700 Process: degrees F Pump: 208V / 1 phase PAGE 8

9 Text6 C H I L L E D W A T E R P I P I N G L A B P R O C E S S S U R V E Y P H O T O G R A P H S Lab process chilled water pump, expansion tank, and valving. Lab Process chilled water supply and return piping can be seen on the far wall (near bottom center of photo) PAGE 9

10 Text6 C H I L L E D W A T E R P I P I N G F R O M C A M P U S L O O P A S S E S S M E N T D A T A Item ID Description The building is served by what appears to be a 10 chilled water supply and return line from the campus chilled water loop. These pipes enter the building on the south side of the basement Mechanical Room 10. This piping serves the chilled water cooling coils in the air handlers (located in the basement and the penthouse), chilled water cooling coils in three of the four departmental air handlers, a chilled water cooling coil in one Liebert unit for Laser Labs #2 and #3, a process chilled water system for Labs 336 and 336A, and one of the helium recovery compressors located in basement Rm. 71. There may be other lab process functions not seen on existing drawings or at time of survey. There are no chilled water pumps. The piping from the campus chilled water loop was installed around 2002 (the absorption chiller was demolished). This newer piping ties into the existing piping. A large portion of the chilled water piping in the building is 1962 original, but there also appears to have been significant new piping installed at the time of the connection to the campus chilled water loop. Some of this piping inside the building is available for future use. The cooling tower that served the absorption chiller is abandoned-in-place on the enclosed area of the roof. The age of the original 1962 piping means that this system is classified as being in poor condition. The chilled water is metered. Overall Condition Poor Date Installed 1/1/1962 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity 10 supply and return from the campus system Material Steel pipe Replacement Cost $298,400 Comments The older canvas-style insulation on the 1962 original piping may possibly contain asbestos PAGE 10

11 Text6 C H I L L E D W A T E R P I P I N G F R O M C A M P U S L O O P S U R V E Y P H O T O G R A P H S Chilled water piping entry into the building, at the south end of basement Mechanical Room 10. Newer chilled water piping mains (from campus system) tie into 1962 original chilled water piping mains, in basement Mechanical Room 10. Abandoned cooling tower on roof. Newer hot water heating (white insulation) and chilled water cooling (black insulation) taps for unspecified future use, at room 334A PAGE 11

12 Text6 L I E B E R T U N I T ( R M H ) A S S E S S M E N T D A T A Item ID Description This Liebert unit serves the new laser labs in rooms 106J and 106K. Each room has an electric heating coil in the supply air ductwork serving each room. These Liebert units normally serve computer server rooms, but this unit is serving a lab. This unit does not appear to have any provisions for outside air ventilation (Liebert units are not designed to condition outdoor air). This unit (with the electric duct heaters) is the only HVAC system for these two rooms. It is not supplemental cooling. This unit has a chilled water cooling coil, and an integral steam-generating humidifier. The chilled water appears to be from the building/campus chilled water loop. Overall Condition Date Installed 1/1/2009 Equipment Tag Manufacturer Model Number Comments The supply air ductwork for these labs is fabric duct, designed to provide a very even airflow distribution across this room. Excellent Remaining Useful Life 21 Years Nominal Useful Life: 30 Years Size/Capacity Voltage CRU-1 Liebert Replacement Cost $21,600 Challenger BU036C-CA0S 3 tons nominal cooling capacity, 1500 cfm 208V / 3 phase The control of the Liebert unit and the downstream electric duct heaters must be watched, to insure that these pieces of equipment don t fight each other (simultaneous heating and cooling) PAGE 12

13 Text6 L I E B E R T U N I T ( R M H ) S U R V E Y P H O T O G R A P H S Supply air fabric ductwork in Rm. 106K (New Laser Lab #3). Liebert unit. Piping connections at Liebert unit PAGE 13

14 Text6 L I E B E R T U N I T ( S E R V E S U N K N O W N R O O M ) A S S E S S M E N T D A T A Item ID Description There is a Liebert condensing unit on the roof of the penthouse. This unit does not appear on any of the existing drawings. Possibly it serves Rm The nameplate for the condensing unit is not legible. But the unit is was operating at the time of survey. The refrigerant lines appear to run down into the penthouse and into one of the pipe and duct chases. This unit probably does not exceed 3 tons nominal cooling capacity. Overall Condition Fair Date Installed 1/1/1990 Remaining Useful Life 7 Years Nominal Useful Life: 30 Years Manufacturer Liebert Voltage 208V / 1 phase Replacement Cost $23,700 Text6 L I E B E R T U N I T ( S E R V E S U N K N O W N R O O M ) S U R V E Y P H O T O G R A P H S Liebert condensing unit on roof. Condensing unit nameplate. Condensing unit fan PAGE 14

15 Text6 S T E A M A N D C O N D E N S A T E P I P I N G A S S E S S M E N T D A T A Item ID Description The building is served by the campus steam system. The steam system provides heating to the building via the perimeter heating system and the steam heating coils typically located in the supply air ductwork immediately downstream of the air handling units (in the penthouse and basement room 18). There is no heating hot water other than three of the four departmental air handlers. The steam system also provides domestic hot water to the building, via a steam-to-hot water heat exchanger assembly in the basement. The steam system at one time did serve an absorption chiller in the basement, but in approximately 2002 the building was added to the campus chilled water system. The labs do not appear to use steam for any process purposes. The supply air distribution system uses a dual-duct system, so there does not appear to be any zone heating coils. Overall Condition Date Installed 1/1/1959 Material Comments The building appears to be served by a 10 medium pressure steam line. This line would have been sized to accommodate the absorption chiller in the basement. The building is also served by a 2 pumped condensate return line. These lines all enter the building at the southeast corner of basement Mechanical Room 10. The vacuum and pumped condensate receivers (both duplex) are also in Rm. 10. The vacuum condensate receiver also appears to serve the perimeter radiation (fin tube and convectors), and this receiver pumps into the pumped condensate receiver. The overall condensate return is metered. There are additional condensate receivers in basement Mechanical Room 10 (serving the AHUs in this room) and penthouse Mechanical Room 501 (serving the steam-to-hot-water heat exchanger for the departmental AHUs). Most of the steam and condensate piping and equipment in the building appear to be 1959 and 1962 original construction. Steam traps appear to be well maintained in the building and the system is not blowing steam. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Steel piping Replacement Cost $2,101, medium pressure steam supply, 2 pumped condensate return The older canvas style insulation seen on the steam and condensate return piping may possibly contain asbestos PAGE 15

16 Text6 S T E A M A N D C O N D E N S A T E P I P I N G S U R V E Y P H O T O G R A P H S Steam main entrance in basement Mechanical Room 10 (at right) and associated steam distribution header. The steam lines that served the absorption chiller are valved off. Duplex pumped condensate receiver in basement Mechanical Room 10. Duplex vacuum condensate receiver in basement Mechanical Room 10. Duplex condensate receiver in penthouse Mechanical Room 501. This receiver serves the steam-to-hot-water heat exchanger that serves 3 of the 4 departmental AHUs PAGE 16

17 Text6 H E A T I N G H O T W A T E R F O R D E P A R T M E N T A L U N I T S A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/2008 Manufacturer Model Number Item ID HP/kW Three of the four departmental AHUs (D.AHU1, D.AHU2, and D.AHU3) are served by a hot water heating loop (in either a preheat coil at the AHU or zone heating coils downstream of the AHU) that is tied to a steam-to-hot water heat exchanger located in penthouse Mechanical Room 501. This heat exchanger is fed by the campus steam system. The hot water pumping package is also located in Mechanical Room 501, adjacent to the heat exchanger. The system uses duplex inline pumps. The pumps are on variable-frequency drives (VFD s). Excellent Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Size/Capacity Voltage Replacement Cost $67,800 Pumps: Bell & Gossett Size BF Pumps: 60 gpm each (only one pump runs at any given time) Pumps: 3hp each Pumps: 208V / 3 phase PAGE 17

18 Text6 H E A T I N G H O T W A T E R F O R D E P A R T M E N T A L U N I T S S U R V E Y P H O T O G R A P H S Pumping package (duplex pumps, expansion tank, hot water storage tank) at heat exchanger in penthouse Mechanical Room 501. VFDs for hot water heating pumps, in penthouse Mechanical Room 501. Hot water heating piping where it enters one of the two main pipe and duct chase in penthouse Mechanical Room 501. Hot water heating (white insulation) taps for future use, in room 334A PAGE 18

19 Text6 H E A T E X C H A N G E R F O R D E P A R T M E N T A L A H U S A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/2008 Manufacturer Model Number Item ID Three of the four departmental AHUs (D.AHU1, D.AHU2, and D.AHU3) are served by a hot water heating loop (in either a preheat coil at the AHU or zone heating coils downstream of the AHU) that is tied to a steam-to-hot water heat exchanger located in penthouse Mechanical Room 501. This heat exchanger is fed by the campus steam system. This heat exchanger is newer, installed in Excellent Remaining Useful Life 30 Years Nominal Useful Life: 35 Years Bell & Gossett Replacement Cost $21,400 SU (shell and tube) Serial Number PAGE 19

20 Text6 H E A T E X C H A N G E R F O R D E P A R T M E N T A L A H U S S U R V E Y P H O T O G R A P H S Heat exchanger, in penthouse Mechanical Room 501. Pumping package (duplex pumps, expansion tank, hot water storage tank) near heat exchanger in penthouse Mechanical Room 501. Condensate receiver for heat exchanger, in penthouse Mechanical Room 501. Heat exchanger and condensate trap, in penthouse Mechanical Room PAGE 20

21 Text6 S U P P L Y A I R D U C T W O R K A S S E S S M E N T D A T A Item ID Description There has been no complete renovation of the building supply and return air ductwork system since the building was constructed in 1959 and The two main lecture halls have had their ductwork replaced, and there have been several major lab renovations with new ductwork over the years, but there is still a significant amount of original ductwork in the building. Overall Condition Date Installed 1/1/1959 Material Comments The supply air system is a dual-duct system, tied to zone damper boxes that mix the warm and cold airstreams to achieve occupant comfort. The supply air system is constant volume (not VAV), even though there are zone-level damper systems. The original pneumatic dual-duct boxes are in very poor condition and replacement parts can no longer be obtained. Some original boxes have permanently failed and have been modified with a manual sliding metal damper on one of the two ducts, to allow some manual control of the supply air temperature. Supply air and return air from the penthouse air handlers is routed down to the occupied floors through two different building shafts. The 1959/1962 original supply and return air ductwork is internally lined. Given the age of this lining it has deteriorated and the fibers will flake off into the supply airstream and can possibly contaminate the lab spaces. In many spaces the supply air diffusers have been covered with a filter batt. See the pictures below for an example of what these filter batts look like after they are removed. Per interview with the building personnel, some of the existing ductwork mains are undersized for the renovated labs they are feeding. The entire building appears to be air conditioned. There are no window AC units in this building. The laser labs use a fabric-type supply air duct to provide a very even (draft-free) airflow distribution in the room. This fabric-type ductwork typically has a 10- to 15-year useful life. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $4,545,500 Galvanized steel sheet metal Replacement of the internally-lined ductwork is considered a top priority by the building personnel. Correcting the issue of original ductwork mains being undersized for some of the renovated labs, along with replacing the original dual-duct boxes, are also considered top priorities. Some original ductwork has external canvas-type insulation. This insulation or canvas jacket may possibly contain asbestos PAGE 21

22 Text6 S U P P L Y A I R D U C T W O R K S U R V E Y P H O T O G R A P H S Typical dual-duct zone damper box and supply grille. The filter batt covering the supply air grille has become dirty due to the deteriorated ductwork lining. A used filter batt that was previously used to cover a supply air diffuser. A typical supply air diffuser and return air grille in one of the 1st floor classrooms. Newer ductwork and a newer dual-duct zone damper box in a renovated 1st floor lab space PAGE 22

23 Text A H U 1 A S S E S S M E N T D A T A Item ID Description 58.AHU1 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1959 Equipment Tag S-1 and E-1 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located on the east side of the building and serves labs and offices on the east face of the 1st, 2nd, 3rd, and 4th floors. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 18,000 cfm Replacement Cost $293,200 Supply fan: 30 HP, Return fan: 5 HP 208V / 3 phase PAGE 23

24 Text A H U 1 S U R V E Y P H O T O G R A P H S 58.AHU1. Return/exhaust fan E-1. Supply air ductwork above 58.AHU1. The ductwork splits to serve the dual-duct system. Overhead supply air ductwork from 58.AHU1. The steam heating coil serves the warm side ductwork PAGE 24

25 Text A H U 1 0 A S S E S S M E N T D A T A Item ID Description 58.AHU10 is a packaged multizone air handler located in the basement Fan Room 10. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit, and return/exhaust fan is a floor-mounted utility-set type fan. The cooling coil and heating coil are integral to the unit. This AHU appears to have been replaced around The return/exhaust fan appears to be original. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback purposes. The AHU is otherwise constant volume. This AHU serves the 1st floor classrooms and lecture rooms, Rms. 136, 137, 139, 143, 144, 147, and 158. Each classrooms is served by its own zone at the AHU. Overall Condition Fair Date Installed 1/1/1990 Remaining Useful Life 10 Years Nominal Useful Life: 30 Years Equipment Tag S-10 and E-10 Manufacturer Temtrol Size/Capacity 9600 cfm HP/kW Supply fan: 5 HP, Return fan: 2 HP Voltage 208V / 3 phase Material Galvanized Steel Replacement Cost $122, PAGE 25

26 Text A H U 1 0 S U R V E Y P H O T O G R A P H S 58.AHU10. Chilled water piping (black insulation) and steam heating piping (white insulation) at coil connections to 58.AHU10. VFD for S-10. Return/exhaust fan E PAGE 26

27 Text A H U 1 1 A S S E S S M E N T D A T A Item ID Description 58.AHU11 is a single-zone packaged air handler located in the basement Fan Room 10. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit, and return/exhaust fan is a floor-mounted utility-set type fan. The cooling coil is integral to the unit, but the steam heating coil appears to be in the supply air ductwork above the unit. Most components of this air handler appear to be 1959 original construction. The chilled water coil was apparently replaced in Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback purposes. The AHU is otherwise constant volume. This AHU serves the 1st floor Lecture Room A, Rm Overall Condition Poor Date Installed 1/1/1959 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Equipment Tag S-11 and E-11 Manufacturer Trane Model Number Climate Changer, Type 17 Serial Number Size/Capacity 8,250 cfm HP/kW Supply fan: 5 HP, Return fan: 1.5 HP Voltage 208V / 3 phase Material Galvanized Steel Replacement Cost $83, PAGE 27

28 Text A H U 1 1 S U R V E Y P H O T O G R A P H S 59.AHU11. Return/exhaust fan E-11. VFDs for S-11 and E-11. Chilled water piping connections (black insulation) and steam heating piping connections (white insulation) at 59.AHU PAGE 28

29 Text A H U 1 2 A S S E S S M E N T D A T A Item ID Description 58.AHU12 is a single-zone packaged air handler located in the basement Fan Room 10. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit, and return/exhaust fan is a floor-mounted utility-set type fan. The cooling coil is integral to the unit, but the steam heating coil appears to be in the supply air ductwork above the unit. This AHU appears to have been replaced around The return/exhaust fan appears to be original but was apparently refurbished in Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback purposes. The AHU is otherwise constant volume. This AHU serves the 1st floor Lecture Room B, Rm Overall Condition Good Date Installed 1/1/2000 Remaining Useful Life 15 Years Nominal Useful Life: 30 Years Equipment Tag S-12 and E-12 Manufacturer York Model Number Climate Changer, Type 17 Size/Capacity 5060 cfm HP/kW Supply fan: 3 HP, Return fan: 1 HP Voltage 208V / 3 phase Material Galvanized Steel Replacement Cost $52, PAGE 29

30 Text A H U 1 2 S U R V E Y P H O T O G R A P H S 59.AHU12. Return/exhaust fan E-12. VFDs for S-12 and E-12, at left. Chilled water piping connections (black insulation) and steam heating piping connections (white insulation, to steam coil overhead) at 59.AHU PAGE 30

31 Text A H U 1 3 A S S E S S M E N T D A T A Item ID Description At the time of survey 58.AHU13 had been completely removed, leaving the south half of the 1st floor lobby (which serves as a student commons and study area) without air conditioning or ventilation (some heat would be provided by the perimeter fin-tube). This AHU would normally be located in basement Mechanical Room 10. The building facility director/manager said that there is a project in work to replace this AHU. The older variable-frequency drives (VFDs) that served this AHU located on the wall in Rm. 10, and may be used again for the new AHU. This AHU serves a single zone, the south half of the 1st floor main lobby (58.AHU14 serves the north half), as a constant volume unit. Overall Condition Poor Date Installed 1/1/2013 Remaining Useful Life TBD Nominal Useful Life: 30 Years Equipment Tag S-13 and E-13 Size/Capacity 9500 cfm Replacement Cost $98, PAGE 31

32 Text A H U 1 3 S U R V E Y P H O T O G R A P H S Return and relief air duct connections for 58.AHU13. Supply air and outside air intake duct connections for 58.AHU13. VFDs for S-13 and E-13, at right. These VFDs are not currently in use PAGE 32

33 Text A H U 1 4 A S S E S S M E N T D A T A Item ID Description 58.AHU14 is a single-zone packaged air handler located in the basement Fan Room 10. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit, and return/exhaust fan is a floor-mounted utility-set type fan. The cooling coil is integral to the unit, but the steam heating coil appears to be in the supply air ductwork above the unit. Most components of this AHU appear to be 1959 original construction. The chilled water cooling coil was apparently replaced in Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback purposes. The AHU is otherwise constant volume. This AHU serves a single zone, the north half of the 1st floor main lobby (58.AHU14 serves the south half), as a constant volume unit. Overall Condition Poor Date Installed 1/1/1959 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Equipment Tag S-14 and E-14 Manufacturer Trane Model Number Climate Changer Type 21 Serial Number Size/Capacity 9500 cfm HP/kW Supply fan: 5 HP, Return fan: 3 HP Voltage 208V / 3 phase Material Galvanized Steel Replacement Cost $98, PAGE 33

34 Text A H U 1 4 S U R V E Y P H O T O G R A P H S 58.AHU14. Chilled water piping (black insulation) and steam heating piping (white insulation, to steam heating coil in supply air ductwork overhead) at 58.AHU14. VFDs for S-14 and E-14, center and at left. Return/exhaust fan E PAGE 34

35 Text A H U 2 A S S E S S M E N T D A T A Item ID Description 58.AHU2 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1959 Equipment Tag S-2 and E-2 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU serves labs and offices on the south face of the east (1959) half of the building, on the 1st, 2nd, 3rd, and 4th floors. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 13,600 cfm Replacement Cost $220,100 Supply fan: 25 HP, Return fan: 3 HP 208V / 3 phase PAGE 35

36 Text A H U 2 S U R V E Y P H O T O G R A P H S 58.AHU2. Return/exhaust fan E-2. Supply air ductwork above 58.AHU2. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for supply fan S-2, at left PAGE 36

37 Text A H U 3 A S S E S S M E N T D A T A Item ID Description 58.AHU3 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1959 Equipment Tag S-3 and E-3 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around Although this AHU is located in the east half of the building, it serves labs and offices on the south face of the west (1962) half of the building, on the 1st, 2nd, 3rd, and 4th floors, and in the basement. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 10,350 cfm Replacement Cost $168,700 Supply fan: 20 HP, Return fan: 3 HP 208V / 3 phase PAGE 37

38 Text A H U 3 S U R V E Y P H O T O G R A P H S 58.AHU3. Return/exhaust fan E-3. Supply air ductwork above 58.AHU3. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. Chilled water cooling coil connections at 58.AHU PAGE 38

39 Text A H U 4 A S S E S S M E N T D A T A Item ID Description 58.AHU4 is a built-up air handler located in the penthouse Fan Room 503. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1962 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1962 Equipment Tag S-4 and E-4 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located in the west half of the building, it serves labs and offices on the west face of the building, on the 2nd, 3rd, and 4th floors. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 20,770 cfm Replacement Cost $338,500 Supply fan: 40 HP, Return fan: 5 HP 208V / 3 phase PAGE 39

40 Text A H U 4 S U R V E Y P H O T O G R A P H S 58.AHU4. Return/exhaust fan E-4. Supply air ductwork above 58.AHU4. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for supply fan S PAGE 40

41 Text A H U 5 A S S E S S M E N T D A T A Item ID Description 58.AHU5 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1959 Equipment Tag S-5 and E-5 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around Although this AHU is located in the east half of the building, it serves labs and offices on the north face of the west (1962) half of the building, on the 1st, 2nd, 3rd, and 4th floors, plus several rooms in the west half of the basement. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 14,400 cfm Replacement Cost $234,700 Supply fan: 25 HP, Return fan: 3 HP 208V / 3 phase PAGE 41

42 Text A H U 5 S U R V E Y P H O T O G R A P H S 58.AHU5. Return/exhaust fan E-5, and associated VFD. Supply air ductwork above 58.AHU5. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for supply fan S-5, at right PAGE 42

43 Text A H U 6 A S S E S S M E N T D A T A Item ID Description 58.AHU6 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1959 Equipment Tag S-6 and E-6 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located in the east half of the building and it serves labs and offices on the north face of the east (1959) half of the building, on the 1st, 2nd, 3rd, and 4th floors, and possibly one room in the west half of the basement. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 16,100 cfm Replacement Cost $262,400 Supply fan: 25 HP, Return fan: 3 HP 208V / 3 phase PAGE 43

44 Text A H U 6 S U R V E Y P H O T O G R A P H S 58.AHU6. Return/exhaust fan E-6. Supply air ductwork above 58.AHU6. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for supply fan S-6, at right PAGE 44

45 Text A H U 7 A S S E S S M E N T D A T A Item ID Description 58.AHU7 is a built-up air handler located in the penthouse Fan Room 501. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1959 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located in the east half of the building and it serves interior labs and offices in the east (1959) half of the building, on the 1st, 2nd, 3rd, and 4th floors. Overall Condition Poor Date Installed 1/1/1959 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Equipment Tag S-7 and E-7 Size/Capacity 15,000 cfm HP/kW Supply fan: 25 HP, Return fan: 3 HP Voltage 208V / 3 phase Replacement Cost $244, PAGE 45

46 Text A H U 7 S U R V E Y P H O T O G R A P H S 58.AHU7. Return/exhaust fan E-7, with associated VFD at left. Cooling coil inside 58.AHU7. Supply fan S-7, inside 58.AHU PAGE 46

47 Text A H U 8 A S S E S S M E N T D A T A Item ID Description 58.AHU8 is a built-up air handler located in the penthouse Fan Room 503. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1962 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1962 Equipment Tag S-8 and E-8 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located in the west half of the building and it serves interior labs and offices in the west (1959) half of the building, on the 1st, 2nd, 3rd, and 4th floors, and one lab in the basement. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 12,800 cfm Replacement Cost $208,600 Supply fan: 25 HP, Return fan: 3 HP 208V / 3 phase PAGE 47

48 Text A H U 8 S U R V E Y P H O T O G R A P H S 58.AHU8. Return/exhaust fan E-8, with associated VFD at right. Supply air ductwork above 58.AHU8. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for supply fan S PAGE 48

49 Text A H U 9 A S S E S S M E N T D A T A Item ID Description 58.AHU9 is a built-up air handler located in the penthouse Fan Room 503. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan is integral to the unit (a double-width, double-inlet base-mounted fan), and return/exhaust fan is a floor-mounted utility-set type fan (single-width, single-inlet). Most components of this air handler appear to be 1962 original construction, but the chilled water cooling coil was apparently replaced in 2001, and the steam heating coil appears to have been replaced within the past 5-10 years, possibly at the same time as the cooling coil. Overall Condition Date Installed 1/1/1962 Equipment Tag S-9 and E-9 HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. There is no other steam heating coil inside the AHU. The original chilled water coil was located downstream of the ductwork split, but was removed. The chilled water coil installed in 2001 is at the main air handler (a full-face coil; no bypass). Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and night setback. The AHU is otherwise constant volume. This AHU draws outside ventilation air through louvers in the side walls of the penthouse. This AHU also discharges relief/exhaust air through louvers in the side walls of the penthouse. This building was constructed in two phases, with the east half of the building constructed around 1959 and the west half of the building constructed around This AHU is located in the west half of the building and it serves interior labs and offices in the west (1959) half of the building, on the 1st, 2nd, 3rd, and 4th floors, and one lab in the basement. The exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage 15,300 cfm Replacement Cost $249,400 Supply fan: 25 HP, Return fan: 3 HP 208V / 3 phase PAGE 49

50 Text A H U 9 S U R V E Y P H O T O G R A P H S 58.AHU9. Return/exhaust fan E-9. Supply air ductwork above 58.AHU9. The ductwork splits to serve the dual-duct system. The steam heating coil can be seen in the upper duct. VFD for return fan E-9, at left PAGE 50

51 Text6 D. A H U 1 ( L A S E R L A B ) A S S E S S M E N T D A T A Item ID Description D.AHU1 serves lab rooms 362 and 362A to provide a tightly controlled thermal environment in these rooms. The AHU is located in room 362B. These rooms could not be accessed. This AHU has a chilled water cooling coil that is integral to the AHU and a single hot water (or possibly steam) heating coil in the downstream ductwork. The system appears to be constant volume (not VAV). This AHU does not appear to provide any outside air ventilation (recirculation only). The unit has 95% efficient cartridge filters, with 30% prefilters. The return air grilles appear to be mounted low to the floor to provide an even airflow in the room. This AHU uses chilled water from a plate-and-frame heat exchanger located in penthouse Fan Room 503 above. Overall Condition Good Date Installed 1/1/2002 Remaining Useful Life 20 Years Nominal Useful Life: 30 Years Size/Capacity 2500 cfm HP/kW 1.5 HP Voltage 208V / 3 phase Replacement Cost $62, PAGE 51

52 Text6 D. A H U 2 ( L A S E R L A B ) A S S E S S M E N T D A T A Item ID Description D.AHU2 serves lab rooms 336 and 336A (known as the Laser Lab) to provide a tightly controlled thermal environment in these rooms. The AHU is located in room 334A. This AHU has a chilled water cooling coil that is integral to the AHU and hot water heating coils in the downstream ductwork for each of the 2 zones served. The system appears to be constant volume (not VAV). This system uses fabric ductwork in the two lab spaces to provide an even distribution of supply air, without drafts. This AHU does not appear to provide any outside air ventilation (recirculation only). The unit has 95% efficient filters, with 30% prefilters. Overall Condition Date Installed 1/1/2008 Equipment Tag Manufacturer HP/kW This AHU uses chilled water from a plate-and-frame heat exchanger located in penthouse Fan Room 503 above. This AHU uses hot water that appears to be taken from the same hot water piping loop that serves D.AHU3 in RM. 332 (existing drawings are unclear). Excellent Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Serial Number 2532 Size/Capacity Voltage AHU-332/334 Air Flow Equipment 1800 cfm 10 HP 208V / 3 phase Replacement Cost $62, PAGE 52

53 Text6 D. A H U 2 ( L A S E R L A B ) S U R V E Y P H O T O G R A P H S D.AHU2. D.AHU2. D.AHU2. Fabric duct at ceiling in Rm PAGE 53

54 Text6 D. A H U 3 A S S E S S M E N T D A T A Description Overall Condition Item ID Date Installed 1/1/2000 D.AHU3 appears to serve lab rooms 332, 334, and 334B, but this AHU may no longer be in use. These rooms were not accessed, and existing drawings are not clear. This AHU appears to use a DX cooling coil and was possibly served by a condensing unit located on the penthouse roof. A possible candidate for the condensing unit on the roof is disconnected (see photos). Good Remaining Useful Life 17 Years Nominal Useful Life: 30 Years Voltage 208V / 3 phase Replacement Cost $62,700 Text6 D. A H U 3 S U R V E Y P H O T O G R A P H S Disconnected condensing unit on roof may (or may not) be tied to D.AHU PAGE 54

55 Text6 D. A H U 4 A A S S E S S M E N T D A T A Item ID Description D.AHU4A is a Liebert Computer Room Air-Conditioning (CRAC) unit serving Room 458 (along with D.AHU4B), which is apparently a computer server room. This room could not be accessed, and existing drawings do not show this unit. Overall Condition Date Installed 1/1/2002 Manufacturer Model Number This is a DX split system. The Liebert condenser is located on the roof at the penthouse level, in the open area that houses the (abandoned) cooling tower. The refrigerant lines run into the Penthouse before dropping down into room 458. Good Remaining Useful Life 19 Years Nominal Useful Life: 30 Years Serial Number Voltage Liebert Replacement Cost $47,700 Condenser: DCDF165LY Condenser: 0208C54781 Condenser: 208V / 1 phase PAGE 55

56 Text6 D. A H U 4 A S U R V E Y P H O T O G R A P H S Condenser for D.AHU4A (center unit with 2 fans). Refrigerant lines (at top center of picture), enter the penthouse before dropping down to Room PAGE 56

57 Text6 D. A H U 4 B A S S E S S M E N T D A T A Item ID Description D.AHU4B is a modular air handler located in the penthouse Fan Room 503. There doesn t appear to be any existing drawings for this AHU. This AHU appears to be a cooling-only supplemental AHU that exclusively serves room 458, which is located directly below this unit. The AHU has a DX cooling coil and integral supply air fan, but does not appear to have a return fan. The AHU does not appear to have an outside air intake, so it likely provides recirculation-only supplemental cooling to the Rm. 458 lab space. This AHU is still in use, and there are signs on the disconnects warning that it should not be turned off. Room 458 could not be accessed, but the building systems manual indicates that it is a server room. Overall Condition Date Installed 1/1/1977 Equipment Tag Manufacturer Model Number There is a floor-mounted DX compressor unit and a ducted condenser unit located in Fan Room 503 near this AHU. This DX system serves the cooling coil in D.AHU4B. The compressor on the compressor unit appears to have been replaced around The ducted condenser unit includes an integral fan to draw air from the fan room across the condenser coil. The air discharge is ducted straight up through the roof of the penthouse to a gooseneck discharge. The AHU is not original 1962 construction. The installation date is estimated at 1977 based on the condensing unit serial number and the overall appearance of the equipment. This would make this AHU and the associated condenser (the compressor unit may be newer) more than 30 years old, and thus considered to be in poor condition. The exterior of this AHU is insulated with a material that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage AHU-458 Replacement Cost $43,600 Compressor and Condenser Unit: Dunham-Bush Compressor: LSCU cfm 208V / 3 phase PAGE 57

58 Text6 D. A H U 4 B S U R V E Y P H O T O G R A P H S D.AHU4B, with refrigerant piping running above. DX cooling coil connections at D.AHU4B. Floor-mounted compressor for DX cooling coil for D.AHU4B. Ducted condenser unit for DX cooling system for D.AHU4B PAGE 58

59 Text6 T W O S M A L L S P L I T D X S Y S T E M S A S S E S S M E N T D A T A Item ID Description There are two split system air conditioning systems that appear to be in use. These units do not appear on any drawings. The spaces served were not accessed. These units are identified by their associated condensing units, which are found on the roof. Overall Condition Date Installed 1/1/ A condensing unit serves Room 222. This condensing unit appears to have 2 or 3 tons of nominal cooling capacity (nameplate is obscured). Manufacturer is Goodman. This unit is located in the roof area next to the (abandoned) cooling tower, and next to the condensing unit serving Room 428. The refrigerant lines for this unit run into the penthouse and down a vertical pipe and ductwork chase. The disconnect for this unit was in the off position at time of survey. This unit may no longer be used, possibly since the building was added to the campus chilled water loop. 2. A condensing unit serves Room 428. This condensing unit appears to have 4 tons nominal cooling capacity. Serial number is Manufacturer is Goodman. This unit is located in the roof area next to the (abandoned) cooling tower, and next to the condensing unit serving Room 222. The refrigerant lines for this unit run into the penthouse and down a vertical pipe and ductwork chase. The disconnect for this unit was in the off position at time of survey. This unit may no longer be used, possibly since the building was added to the campus chilled water loop. There are likewise two small condensing units on the roof of the penthouse. The refrigerant lines for these units have been disconnected. Excellent Remaining Useful Life 24 Years Nominal Useful Life: 30 Years Voltage 208V / 1 phase Replacement Cost $33, PAGE 59

60 Text6 T W O S M A L L S P L I T D X S Y S T E M S S U R V E Y P H O T O G R A P H S Condensing unit serving Rm. 428 (foreground) and unit serving Rm Note that both disconnects are in the off position PAGE 60

61 Text6 T O I L E T E X H A U S T A S S E S S M E N T D A T A Item ID Description E-16 appears to be the one main toilet exhaust fan, per existing drawings. This fan appears to be original 1959 construction (with a newer motor). The exhaust fan is a belt-driven base-mounted centrifugal fan (single-inlet, single-width), located in penthouse Mechanical Room 501. Per existing drawings this is the only toilet exhaust fan in the building. The fan and its flex connections appear to have been reasonably well maintained. Overall Condition Date Installed 1/1/1959 Equipment Tag Fan E-16 Manufacturer HP/kW This exhaust fan discharges through a sidewall louver located in the roof area (that has walls but no roof) that contains the cooling tower. The first floor restrooms have been renovated and increased in size to meet ADA requirements. The existing toilet exhaust fan is undersized for these larger toilet rooms. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage New York Blower 3000 cfm 3/4 HP Replacement Cost $6, V / 3 phase PAGE 61

62 Text6 T O I L E T E X H A U S T S U R V E Y P H O T O G R A P H S Toilet exhaust fan E-16, in penthouse Mechanical Room 501. Toilet exhaust louver (top center of photo) in roof area that contains the cooling tower. Exhaust grille and ductwork in basement Toilet Room PAGE 62

63 Text6 L A B O R A T O R Y E X H A U S T A S S E S S M E N T D A T A Item ID Description This building has far fewer lab exhaust fans than the Seitz MRL next door. This building has 11 exhaust fans serving fume hoods. The fans serve one or two hoods each. These fans appear to operate as constant volume. There is no provision for heat recovery from any lab exhaust system. The lab exhaust fans are mostly roof-mounted fans. EF-24 is a base-mounted fan located in the penthouse. Most of the fans were replaced in the 1990s, but a few are original construction. E-17 (nameplate missing) is mounted on the roof of the penthouse, appears to be from about 1990 (original fan was in penthouse), has an extended discharge for dilution, and appears to be operational. This fan serves a fume hood in Rm. 434 or 434A. E-18 (Chicago Blower, size 122, S/N ) is mounted on the roof next to the penthouse, appears to be original 1962 construction, does not have an extended discharge, and has been maintained and appears to be operational. This fan appears to serve a fume hood in Rm. 451A. E-19 (GP Fan, Size 12, S/N F ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge, and appears to be operational. This fan serves hoods in Rm. 461 and Rm E-20 (GP Fan, Size 12, S/N F ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge and appears to be operational. This fan serves a hood in Rm E-21 (GP Fan, size 12, S/N F ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge and appears to be operational. This fan serves two hoods in Rm E-22 (GP Fan, size 12, S/N F ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge and appears to be operational. This fan serves hoods in Rm. 475 and Rm E-23 (GP Fan, size 12, S/N F ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge and appears to be operational. This fan serves a hood in Rm E-24 (New York Blower) is mounted on the floor of the penthouse, is original 1959 construction, discharges through a sidewall louver, and appears to be out of service (or may just have been off at time of survey). This fan serves or served a hood or hoods in Rm E-26 (GP Fan, Size 122, S/N G ) is mounted on the roof next to the penthouse, was replaced in 1990, has an extended discharge, but is disconnected and not operational. This fan serves a hood or hoods in Rm E-27 (Greenheck, model 12-BISW II, S/N 99I24117) is apparently a newer fan on the roof of the penthouse, was installed or replaced around 1999, has an extended discharge, and is operational. This fan serves a fume hood in Rm. 120A. E-28 (nameplate missing) is mounted on the roof next to the penthouse, appears to be original 1959 construction, and does not appear to be operational and does not appear to be maintained like the other operational fans. This fan serves or served hoods in Rm. 383A and Rm. 383B PAGE 63

64 Overall Condition Date Installed 1/1/1990 Equipment Tag Manufacturer HP/kW Comments Fair Remaining Useful Life 5 Years Nominal Useful Life: 30 Years Size/Capacity Voltage Varies, see description varies 600 to 1200 cfm 3/4hp to 1-1/2hp Replacement Cost $305,400 Typical: 208V / 3 phase No transite exhaust duct (a material that possibly contains asbestos) was seen in this building, but it has frequently been seen in other lab buildings of this vintage. Transite exhaust duct may be present here in areas not accessed PAGE 64

65 Text6 L A B O R A T O R Y E X H A U S T S U R V E Y P H O T O G R A P H S EF-18 on roof next to penthouse. Left to right: EF-19, EF-20, EF-26, EF-21, and EF-22 on the north side of the roof, next to the penthouse. EF-26 (foreground) and EF-21 (background). EF-23 (left) and EF-28 (right) on roof next to penthouse. EF-28 does not appear to be working PAGE 65

66 Text6 N A T U R A L G A S A S S E S S M E N T D A T A Item ID Description A natural gas service enters the building at the south end of basement Mechanical Room 10 and serves most or all lab spaces. The gas piping has been replaced when labs have been renovated, but a significant amount of this piping is still original 1959 or 1962 construction and thus considered to be in poor condition. The gas service does not appear to serve any other equipment other than the lab processes. Overall Condition Date Installed 1/1/1959 Material Comments The gas meter is located at the south end of basement Mechanical Room 10, where the service enters the building. A valve and regulator are located outside at the south side of the building. The gas service to the building appears to be at a higher pressure (possibly 1 psig or 14 water column) than the building service, and this pressure is regulated down outside the building. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Size/Capacity Black iron pipe Replacement Cost $223,800 Main is 3 pipe (low pressure) The gas meter is described as being well oversized for the amount of natural gas that actually gets used. The gas meter should ideally be replaced with a smaller gas meter, as this apparently results in a smaller baseline utility fee PAGE 66

67 Text6 N A T U R A L G A S S U R V E Y P H O T O G R A P H S Gas piping and (oversized) meter at south end of basement Mechanical Room 10. Gas service valve and regulator at the south side of the building. The smaller pipe at the valve suggests that the gas service is supplied at a higher pressure that is then regulated down before it enters the building. Newer natural gas piping (unlabeled black pipe) in 1st floor renovated lab. Natural gas turret (blue cap) in 1st floor renovated lab PAGE 67

68 Text6 H V A C C O N T R O L S A S S E S S M E N T D A T A Item ID Description HVAC controls in the building are a mixture of the original pneumatic controls, MACS electro-mechanical controls, and modern DDC controls that have been added over the years when areas have been renovated. The air handlers appear to have limited BAS control through a combination of MACS and DDC control. Overall Condition Date Installed 1/1/1959 Manufacturer Comments Original dual-duct zone damper boxes use pneumatic thermostats. The original pneumatic controls are in poor condition and in some cases are no longer functional. Parts for the original pneumatic zone damper boxes are apparently no longer available and in some cases manual sliding dampers have been added to the dual-duct boxes. The air compressor for the HVAC control system is located in basement Mechanical Room 10. This duplex air compressor is a newer installation and is in good condition. This is apparently the only air compressor serving the pneumatic control system. Poor Remaining Useful Life Exceeded Nominal Useful Life: 18 Years Invensys Replacement Cost $32,400 In interviews with building personnel about this building, replacement of the older controls systems with new DDC controls is listed as one of the highest priorities for this building PAGE 68

69 Text6 H V A C C O N T R O L S S U R V E Y P H O T O G R A P H S Pneumatic thermostat in 1st floor classroom. This duplex air compressor in basement Mechanical Room 10 appears to serve the controls system. Pneumatic actuators at multi-zone AHU in basement fan Rm. 18. DDC thermostat in renovated 1st floor lab space PAGE 69

70 Text106 P L U M B I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DOMESTIC COLD WATER SYSTEM DOMESTIC HOT WATER SYSTEM HEATER PLUMBING FIXTURES SYSTEM SANITARY WASTE AND VENT SYSTEM STORM DRAINAGE SYSTEM SUB-SOIL DRAINAGE SYSTEM COMPRESSED-AIR VACUUM NITROGEN SYSTEM OTHER PIPED GAS SYSTEM/COMPONENT Domestic Cold Water Domestic Hot Water Domestic Hot Water Heater Plumbing Fixtures Sanitary, Waste, and Vent Storm Drainage Subsoil Drainage Compressed Air (for labs) Vacuum Nitrogen Helium Recovery Piping PLUMBING TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 392, , , ,700 53,900 53, , , , , , , , , , , , ,200 28,500 28, , ,800 3,051, , ,200 3,577, PAGE 70

71 Text6 D O M E S T I C C O L D W A T E R A S S E S S M E N T D A T A Item ID Description A 6 domestic cold water line (cast iron) enters the south side of the basement Mechanical Room 10. This service feeds the fire protection (standpipe) system and the domestic cold water system. There has been overall major renovation of the domestic cold water piping since its 1959 and 1962 original installation. Sections have been replaced on an as-needed basis due to leaks, and significant areas have had piping replaced due to a major lab renovation. Due to the age of the original piping it is considered to be in poor condition. Overall Condition Date Installed 1/1/1959 Material Comments There is no booster pump. No major issues with this system have been reported. This system supplies water to the labs in the building. There is no separate nonpotable water system for lab use. Older emergency shower stations in the building appear to use cold water only, not tempered. Emergency shower stations in renovated lab areas use tempered water. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $392,700 6 water service, serving domestic cold water and fire protection galvanized steel, cast iron, ductile iron, with some newer copper Piping insulation on the original domestic water piping may contain asbestos PAGE 71

72 Text6 D O M E S T I C C O L D W A T E R S U R V E Y P H O T O G R A P H S Water meters for domestic water service, in basement Mechanical Room 10. Blue paint on the ground at the south side of the building indicates the route of the domestic cold water service. Newer domestic cold water piping in renovated 1st floor lab PAGE 72

73 Text6 D O M E S T I C H O T W A T E R A S S E S S M E N T D A T A Description Domestic hot water is supplied to the building from two steam-to-hot water heat exchangers and one storage tank, located in basement Mechanical Room 10. There are two hot water recirculation pumps. There is a 2 hot water supply to the building and a 1-1/2 recirculation line. There has been no major renovation of the domestic hot water piping since its 1959 and 1962 original installation. Sections have been replaced on an as-needed basis due to leaks, and significant areas have had piping replaced due to a major lab renovation. Due to the age of the original piping it is considered to be in poor condition. Overall Condition Item ID Date Installed 1/1/1959 Material Comments No other major issues with this system have been reported. This system apparently supplies hot water to the labs in the building. There is no separate nonpotable hot water system for lab use. Older emergency shower stations in the building appear to use cold water only, not tempered. Emergency shower stations in renovated lab areas use tempered water. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $381,700 2 HWS and 1-1/2 HWR (probably) galvanized steel with some newer copper The piping insulation on the original piping may contain asbestos PAGE 73

74 Text6 D O M E S T I C H O T W A T E R S U R V E Y P H O T O G R A P H S Domestic hot water recirculation pumps, at water heater in basement Mechanical Room 10. Domestic water piping in a renovated 1st floor lab. The domestic cold and domestic hot water system tie together at a tempering valve (lower right) to serve an emergency eyewash station PAGE 74

75 Text6 D O M E S T I C H O T W A T E R H E A T E R A S S E S S M E N T D A T A Item ID Description The basement Mechanical Room 10 contains a domestic hot water heater that uses two steam-to-hot water heat exchangers to create hot water. This water heater is a packaged unit, with the two heat exchangers located at the sides of the storage tank. There are two hot water recirculation pumps, and the building has a hot water recirculation piping system. The pumps and the steam control valves have been replaced, but the tank and heat exchangers are possibly 1959 originals. Based on the age of this equipment it is considered to be in poor condition. This water heater supplies hot water to the labs. There is no separate non-potable water system for the labs. The water heater has a dedicated duplex condensate pump that is 1959 original. Overall Condition Poor Date Installed 1/1/1959 Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Manufacturer Stover Serial Number A-3163 Size/Capacity Tank: 300 gallons, Pumps: 10 gpm each HP/kW Pumps: 1/6 HP each. Voltage Pumps: 120V / 1 phase Replacement Cost $53,900 Comments The water heater is covered with an insulation material that may possibly contain asbestos PAGE 75

76 Text6 D O M E S T I C H O T W A T E R H E A T E R S U R V E Y P H O T O G R A P H S Hot water heater in basement Mechanical Room 10. The two heat exchangers are located at the sides of the large storage tank. Hot water recirculation pumps. Duplex condensate receiver for the water heater. Hot water heater in basement Mechanical Room 10. The two heat exchangers are located at the sides of the large storage tank PAGE 76

77 Text6 P L U M B I N G F I X T U R E S A S S E S S M E N T D A T A Item ID Description Most plumbing fixtures appear to be 1959 original installation. Toilets and urinals appear to use flush valves, some are sensor-type (touchless), and some are not. Some older urinals seen in the basement use a foot-operated flush valve that is located in the wall under the urinal. The 1st floor restrooms have been or are being renovated to accommodate the handicapped and have some new fixtures. Overall Condition Date Installed 1/1/1959 Older (original) emergency showers in the building appear to use cold water only. Emergency showers in newer (renovated) labs use tempered water. Older (original) emergency shower stations do not appear to have a floor drain. Newer (renovated) labs with emergency showers appear to have a floor drain. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Replacement Cost $473, PAGE 77

78 Text6 P L U M B I N G F I X T U R E S S U R V E Y P H O T O G R A P H S Urinals in 1st floor mens restroom use sensor-type flush valves. These urinals in the basement restroom use a footoperated flush valve. Water fountain. ADA toilet in restroom on 1st floor PAGE 78

79 Text6 S A N I T A R Y, W A S T E, A N D V E N T A S S E S S M E N T D A T A Item ID Description There has been no major renovation of the sanitary, waste, and vent piping since original 1959 and 1962 construction. Sanitary waste exits on the north side of the building, through one 8 cast iron sanitary line (which runs overhead in the basement and which serves the 1st, 2nd, 3rd, and 4th floors plus the penthouse) and one 4 cast iron sanitary line (which runs overhead in the basement and serves the ejector pit discharge that serves the basement). These two sanitary lines tie together at a manhole outside the building. Overall Condition Date Installed 1/1/1959 Material Existing drawings show that there is no specific distinction made between waste stack and lab stack. Waste from the labs and nearby restrooms tie together into a single stack. In other lab buildings lab stacks are kept separate from waste stacks and the lab stacks are made with Durion piping. There does appear to be a few sections of Duriorn piping in use in this building, serving waste from rooms labeled as Chemistry Labs. These short sections of Duriron piping are used only up to the point where a restroom or other branch waste line ties into the Duriron line (apparently the piping gets washed down by the other waste and Duriron was no longer considered necessary). Per building personnel, some sections of cast iron sanitary or vent piping may have been replaced with PVC as-needed due to leaks or lab reconfigurations. Any replacement of Duriron piping would has been made with acid-resistant plastic piping. There is a duplex ejector pit in the middle of basement Mechanical Room 10. All basement sanitary waste appears to tie into this ejector pit. The pumps and controls (but not the actual pit) of the ejector pit appear to have been replaced within the past 20 years. Emergency shower stations in the building typically do not have a floor drain. The emergency showers in some of the renovated labs have floor drains. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $795,500 One 8 sanitary exit and one 4 sanitary exit Mostly cast iron, some PVC and some Duriron PAGE 79

80 Text6 S A N I T A R Y, W A S T E, A N D V E N T S U R V E Y P H O T O G R A P H S Duplex ejector pit in basement Mechanical Room 10 Floor drain in mechanical Fan Room 18. Waste piping (hub and spigot) near emergency shower in renovated 1st floor lab. Floor drain in penthouse Mechanical Room PAGE 80

81 Text6 S T O R M D R A I N A G E A S S E S S M E N T D A T A Item ID Description The building has a flat roof and uses roof drains. These roof drains are tie together in the basement (with overhead piping) into a 10 storm drainage discharge and a 12 storm drainage discharge. Both of these pipes exit the north side of the building and discharge into Boneyard Creek. The discharge from the sump pit in the basement mechanical room (which serves the subsoil drainage system) ties into the basement downspout piping system. Overall Condition Date Installed 1/1/1959 Material There are no secondary roof drains. This system is nearly all original piping and is considered to be in poor condition due to the age of the piping. Otherwise, with recent improvements to Boneyard Creek, storm drainage and potential flooding is not considered to be a major concern. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Drain tile Replacement Cost $570, PAGE 81

82 Text6 S T O R M D R A I N A G E S U R V E Y P H O T O G R A P H S Roof drain, in enclosed area where the cooling tower is located. Roof drains (and plumbing vents) on roof next to penthouse. 10 storm drain discharge into Boneyard Creek. Boneyard Creek, with Loomis Physics Lab to the right PAGE 82

83 Text6 S U B S O I L D R A I N A G E A S S E S S M E N T D A T A Item ID Description The building has a drain tile system that runs under the basement level of the building, including around the perimeter of the building. These drain tile lines tie together at a sump pit at the south end of basement mechanical room 10. There are approximately 19 rod-out basins (with an 18 dia. cover) for the drain tile systems. These basins are located around the basement level. The rod-out basins are not regularly opened for rod-out maintenance. There are also some cleanouts in the basement floor that serve the drain tile system. Overall Condition Date Installed 1/1/1959 Material The duplex sump pit in basement Mechanical Room 10 ties into the downspout drain system that runs overhead in the basement, which runs straight north in basement Mechanical Room 10 to ultimately empty into Boneyard Creek. Flooding is not considered a major concern for this building, mostly due to the availability of nearby Boneyard Creek for stormwater drainage. The sump pit appears to be original 1959 construction, but is otherwise appears to be maintained. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Drain tile Replacement Cost $109, PAGE 83

84 Text6 S U B S O I L D R A I N A G E S U R V E Y P H O T O G R A P H S Sump pit in basement mechanical room storm drain discharge into Boneyard Creek PAGE 84

85 Text6 C O M P R E S S E D A I R ( F O R L A B S ) A S S E S S M E N T D A T A Item ID Description All labs in the building appear to have compressed air service. There appears to be two air simplex air compressors that are tied together and use a common receiver. Both air compressors are located in this building is in the basement Mechanical Room 10. Overall Condition Date Installed 1/1/1959 Material The older and larger air compressor is an older simplex model, from This air compressor is in poor condition and appears to constantly leak oil onto the floor. This air compressor appears to have a filter and dryer system that provides air at a higher quality than typical shop air or air used for temperature control. The smaller and newer air simplex compressor appears to tie to the receiver of the older compressor. Renovated lab areas have newer compressed air piping, but a large portion of the compressed air piping in this building appears to be original 1959 or 1962 construction and is considered to be in poor condition. This air compressor system is probably capable of serving as a backup to the air compressor for the temperature control system. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $245,300 Copper and iron pipe PAGE 85

86 Text6 C O M P R E S S E D A I R ( F O R L A B S ) S U R V E Y P H O T O G R A P H S Older simplex air compressor for labs, in basement Mechanical Room 10. Filter/dryer assembly for the older air compressor for the labs. Newer simplex air compressor for labs, in basement Mechanical Room 10. Compressed air turret (orange-cap) in renovated lab area on 1st floor PAGE 86

87 Text6 V A C U U M A S S E S S M E N T D A T A Item ID Description A newer vacuum piping system has been installed in phases in recent years to serve most of the labs. This system appears to be designed for the exhaust of smaller lab vacuum pumps. The small, electrically-driven vacuum pumps used in the labs have exhaust air that may contain oil droplets. This vacuum system is designed to accept gases only. There are no provisions for separation of liquids or solids in the airstream. This system is served by a newer vacuum pump unit located in basement Mechanical Room 10. Overall Condition Excellent Date Installed 1/1/2010 Remaining Useful Life 27 Years Nominal Useful Life: 30 Years Manufacturer Busch Model Number RCU100 E Serial Number E36994 Material Copper and plastic piping Replacement Cost $302, PAGE 87

88 Text6 V A C U U M S U R V E Y P H O T O G R A P H S Vacuum pump and receiver in basement Mechanical Room 10. Vacuum turrets (yellow caps) in a 1st floor renovated lab. Vacuum pump and receiver in basement Mechanical Room PAGE 88

89 Text6 N I T R O G E N A S S E S S M E N T D A T A Item ID Description A piped gaseous nitrogen supply originates from a liquid nitrogen tank located outside at the northeast corner of the building. This tank feeds the Loomis Physics Building and typically does not feed the gaseous nitrogen system serving Seitz Materials Research Lab, the Superconductivity Center, and the Engineering Sciences Building. The Loomis gaseous nitrogen system can be tied into the other system by operating a manual valve, as a piping connection crosses the bridge/link between Loomis and Seitz. Nitrogen at higher pressure may be provided in some labs using gas cylinders. Most labs in the building appear to be served by this system. The installation date for this system is unclear, based on existing drawings. It does not appear on the original 1959 construction drawings. Overall Condition Poor Date Installed 01/01/1985 Remaining Useful Life 2 Years Nominal Useful Life: 30 Years Material Copper Replacement Cost $28, PAGE 89

90 Text6 N I T R O G E N S U R V E Y P H O T O G R A P H S Liquid nitrogen tank at northeast corner of building. Liquid nitrogen tank at northeast corner of building, as seen from overhead. Note the ice buildup at the left end of the tank. Nitrogen piping at renovated 1st floor lab. Fume hood, with gaseous nitrogen system connection PAGE 90

91 Text6 H E L I U M R E C O V E R Y P I P I N G A S S E S S M E N T D A T A Item ID Description The labs in this building have a helium recovery system. This is a system of metered piping to allow liquid helium (used for cooling lab experiments) to be reclaimed in gaseous form and recycled for future use. The helium recovery piping for this building, as well as the helium recovery piping system that runs from Engineering Sciences Building, through the Superconductivity Center, and through the Seitz Materials Research Lab (and across the bridge/link) all tie to this building. The helium reclamation and liquefier systems are located in room this building. Overall Condition Date Installed 1/1/1988 Material The first step in helium recover is compressing the low-pressure used helium back to high pressure for storage. The compressor system is located in basement Storage Room 71 and consists of two compressors, an older model (installation date unknown) and a newer model (2012). These compressors appear to be aircooled and compress the helium to a high-pressure gaseous state for storage in either the eight tanks on the roof or some of the tanks located at grade near the northeast corner of the building. The liquefier system is also located in basement Storage Room 71. This unit compresses the gaseous helium to a liquid, which apparently is piped up to 1st floor Rm. 175 for storage in dewars. This unit uses the building chilled water system and a compact heat exchanger (with a small condenser water loop using small duplex pumps) to reject the heat that must be removed from the helium as part of the process. The recovery piping system does not have a suction pump; rather it relies on the pressure of the helium gas that is discharged into the piping to transport the gas to the Loomis Physics Lab. There is also a system of inflatable gas bags connected to the piping that allows the system to store gaseous helium at times when the reclamation system (which compresses the gaseous helium for storage in high pressure tanks) can t keep up. There is a large bag in basement Storage Room 71. There are meters that measure the amount of gaseous helium recovered. These meters are located high on the wall, typically in a storage room or a corridor, and look like natural gas meters. These meters keep track of how much helium is recovered, as projects/departments are charged for how much helium is used (not recovered). Helium supply is not piped. Liquid helium is transported into this building in dewars, from Loomis Physics Lab room 175, for use in experiments. Not all helium used in lab experiments is recovered. The system is ultimately replenished by the tanks of high-pressure helium located on a trailer outside the northeast corner of the building. Several different piping materials appear to be in use for this system: copper (sweat), PVC, and braided-jacket flex hoses. The piping in Loomis was apparently replaced in Good Remaining Useful Life 15 Years Nominal Useful Life: 40 Years Replacement Cost $223,800 Copper and possibly some PVC PAGE 91

92 Text6 H E L I U M R E C O V E R Y P I P I N G S U R V E Y P H O T O G R A P H S New helium compressor in the foreground, in basement Storage Room 71. An older model (apparently still in use) is in the background. Helium liquefier in basement Storage Room gaseous (pressurized) helium storage tanks on the roof. Liquid helium dewar (silver tank) at filling equipment located in Rm PAGE 92

93 Text106 F I R E P R O T E C T I O N D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y FIRE ALARM SYSTEM STANDPIPE SYSTEM SYSTEM/COMPONENT Fire Alarm System Standpipes FIRE PROTECTION TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 342, ,600 70,200 70,200 70, , , PAGE 93

94 Text6 F I R E A L A R M S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/2000 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The main fire alarm panel is located in the north vestibule. Smoke detectors are installed throughout the building and in front of the elevators for elevator recall. Notification devices are installed in corridors, restrooms and labs, however, coverage is inadequate per current codes. An additional battery cabinet is located in the basement, directly below the main FACP. Fair Remaining Useful Life 7 Years Nominal Useful Life: 20 Years Serial Number Size/Capacity Voltage Not Applicable Siemens MXL Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Replacement Cost $342, PAGE 94

95 Text6 F I R E A L A R M S Y S T E M S U R V E Y P H O T O G R A P H S FACP Pull Station Smoke Detector Horn Strobe PAGE 95

96 Text6 S T A N D P I P E S A S S E S S M E N T D A T A Item ID Description The building does not have any sprinklers. The building has an older system of standpipes, with hose valve cabinets (without any hoses) that have 2-1/2 valves with 1-1/2 hose adapters attached. These hose valve cabinets are typically located in corridors and stairways. Due to the age of the piping this system is considered to be in fair condition. There is no fire pump. There is a 4 siamese fire dept. connection at the midpoint of the south face of the building. Overall Condition Date Installed 1/1/1959 Material Comments The system is served by the same cold water piping that feeds the domestic cold water system. A 6 water service enters basement Mechanical Room 10 on the south side of the building. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $70, /2 hose valves. Steel piping and ductile iron. Sprinklers are planned for this building, to be added piecemeal with each lab renovation PAGE 96

97 Text6 S T A N D P I P E S S U R V E Y P H O T O G R A P H S Standpipe in penthouse. Main standpipe valve (with tamper switch) in basement Mechanical Room 10. Siamese fire dept. connection, on the south side of the building. Typical standpipe hose valve cabinet PAGE 97

98 Text106 E L E C T R I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y MEDIUM VOLTAGE SYSTEM SUBSTATION LOW VOLTAGE SYSTEM EMERGENCY POWER SYSTEM GENERATOR INTERIOR LIGHTING EMERGENCY LIGHTING SYSTEM EXIT LIGHTING SYSTEM LIGHTING CONTROL SYSTEM EXTERIOR LIGHTING SYSTEM SYSTEM/COMPONENT Medium Voltage System Medium Voltage System - Substation Low Voltage System Emergency Power System Emergency Power System - Generator Interior Lighting System Emergency Lighting System Exit Lighting System Lighting Control System Exterior Lighting System ELECTRICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 508, , , ,400 1,002,200 1,002, , ,900 51,900 51, , ,600 57,500 57,500 25,500 25, , ,800 12,500 12,500 2,049, , ,000 3,083, PAGE 98

99 Text6 M E D I U M V O L T A G E S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1959 Equipment Tag Manufacturer Model Number Item ID HP/kW Material Two building services provide redundant electricity to the building. One service from the campus loop and one service from the Utility (Ameren). The double ended substation has a manual tie, where one end (feeder) is capable of supporting the entire building in the event of a loss of one power source. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity Not observed GE Not Applicable Not Applicable 600A Voltage 4,160V Not Applicable Not Applicable Replacement Cost $508, PAGE 99

100 Text6 M E D I U M V O L T A G E S Y S T E M S U R V E Y P H O T O G R A P H S Medium Voltage Substation PAGE 100

101 Text6 M E D I U M V O L T A G E S Y S T E M - S U B S T A T I O N A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1959 Equipment Tag Manufacturer Model Number Item ID HP/kW Material Critical Issues A double ended substation provides power to the entire building. Two 750 KVA transformers step the voltage down to 120/208V. The unit is freestanding and located in room 10. The substation is fed from DC-2, with 65KAIC ratings. Breakers are drawout style. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity Not observed GE Not Applicable Not Applicable 600A Voltage 4,160V Not Applicable Not Applicable Replacement Cost $258,400 Water piping was noted to be running above the switchgear PAGE 101

102 Text6 M E D I U M V O L T A G E S Y S T E M - S U B S T A T I O N S U R V E Y P H O T O G R A P H S Medium Voltage Substation Water Piping above Substation PAGE 102

103 Text6 L O W V O L T A G E S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1959 Equipment Tag Manufacturer Model Number Item ID HP/kW Material From the 208V/120V low voltage side of the substation, several bus ducts provide power to various GE 208/120V panelboards located throughout electrical closets on every level of the building. Some of the 100A panelboards are located immediately inside the research labs near the door. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity Not Applicable GE Not Applicable Not Applicable Varies Not Applicable Voltage 208/120V Not Applicable Replacement Cost $1,002, PAGE 103

104 Text6 L O W V O L T A G E S Y S T E M S U R V E Y P H O T O G R A P H S Low Voltage Distribution at Substation Electrical Closets Disconnects/VFDs in Penthouse PAGE 104

105 Text6 E M E R G E N C Y P O W E R S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1994 Equipment Tag Manufacturer Model Number Item ID HP/kW Material A 125KW Diesel generator provides emergency power to lighting for the entire building. It also provides power to vacuum pumps, sump pumps and condensate pumps. The 400A, 208V open transition automatic switch supplies panel EM1 with normal load connection from the distribution panel in the main electrical room. Fair Remaining Useful Life 6 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Not Applicable Cummins Not Applicable Not Applicable 125KW Not Applicable Voltage 208/120V Not Applicable Replacement Cost $155, PAGE 105

106 Text6 E M E R G E N C Y P O W E R S Y S T E M S U R V E Y P H O T O G R A P H S Automatic transfer switch Generator PAGE 106

107 Text6 E M E R G E N C Y P O W E R S Y S T E M - G E N E R A T O R A S S E S S M E N T D A T A Description Overall Condition Date Installed 01/01/1994 Equipment Tag Item ID Manufacturer HP/kW Material A 125KW Diesel generator provides emergency power to lighting for the entire building. The 400A, 208V open transition automatic switch supplies panel EM with normal load connection from the distribution panel in the main electrical room. The generator contains a 300 gallon belly tank. Fair Remaining Useful Life 6 Years Nominal Useful Life: 25 Years Not Applicable Cummins Model Number OT 400 Serial Number Size/Capacity I KW Not Applicable Voltage 208/120V Not Applicable Replacement Cost $51, PAGE 107

108 Text6 E M E R G E N C Y P O W E R S Y S T E M - G E N E R A T O R S U R V E Y P H O T O G R A P H S Automatic transfer switch Generator PAGE 108

109 Text6 I N T E R I O R L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 4/22/2009 Equipment Tag Manufacturer Model Number HP/kW Material Recommendation Item ID The interior lighting consists of recessed 1x4 fluorescent troffers in the corridor and classrooms. Restroom lighting and lab lighting is direct pendant fluorescent luminaires. The large lecture hall utilize CFL downlights. Lighting levels appeared adequate in these spaces. In Room 10, mechanical room, the electrical substation does not have adequate lighting at the front of the gear. Levels in this area are very poor and consist of pendant lighting on the other side of the fenced area. Excellent Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Voltage 208/120V Not Applicable Replacement Cost $730,600 Add fluorescent lighting in front of substation for adequate light levels for maintenance PAGE 109

110 Text6 I N T E R I O R L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Corridor Lighting Lab Lighting Lobby Lighting Lecture Hall Lighting PAGE 110

111 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 4/22/2009 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The emergency generator provides emergency lighting circuits to select fixtures in the corridors. Emergency lighting units are supplemented in the lecture halls for emergency illumination. Excellent Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Voltage 208/120V Not Applicable Replacement Cost $57, PAGE 111

112 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Emergency Lighting Unit PAGE 112

113 Text6 E X I T L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Description Exit lighting through the building is LED and located at all corridor ends and stairwells. Overall Condition Excellent Date Installed 4/22/2009 Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Equipment Tag Not Applicable Manufacturer Not Applicable Model Number Not Applicable Serial Number Not Applicable Size/Capacity Not Applicable HP/kW Not Applicable Voltage 208/120V Material Not Applicable Replacement Cost $25, PAGE 113

114 Text6 E X I T L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Exit Light Fixture PAGE 114

115 Text6 L I G H T I N G C O N T R O L S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1963 Equipment Tag Manufacturer Model Number HP/kW Material Recommendation Item ID Lighting controls for the corridors, offices and restrooms are all keyed switches. Controls for labs are manual on/off switches. Occupancy sensors were observed in conference rooms. Poor Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Serial Number Size/Capacity Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Voltage 208/120V Not Applicable Replacement Cost $279,800 Recommend adding local occupancy sensors to offices and restrooms. Recommend installing a central system to control common spaces (corridor, lobby, stairwells, labs) PAGE 115

116 Text6 L I G H T I N G C O N T R O L S Y S T E M S U R V E Y P H O T O G R A P H S Keyed light switches Occupancy Sensor at Conference Room PAGE 116

117 Text6 E X T E R I O R L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Description Exterior luminaires are located in canopies over the exit doors and a much larger canopy on the north side of the building. Lamps are CFL. Overall Condition Excellent Date Installed 4/22/2009 Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Equipment Tag Not Applicable Manufacturer Not Applicable Model Number Not Applicable Serial Number Not Applicable Size/Capacity Not Applicable HP/kW Not Applicable Voltage 208/120V Material Not Applicable Replacement Cost $12, PAGE 117

118 Text6 E X T E R I O R L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Exterior Canopy Lighting Exterior Door Lighting PAGE 118

119 Text106 C O M M U N I C A T I O N S D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DATA SYSTEM SECURITY ACCESS CONTROL SYSTEM PAGING SYSTEM SYSTEM/COMPONENT Communication Infrastructure System Access Control System Rescue Assistance COMMUNICATIONS TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 638, , , ,700 40,100 40, , , , PAGE 119

120 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M A S S E S S M E N T D A T A Item ID Description The building is fed with 12 strands of single mode fiber and 800 copper pairs with each pair grounded and individually protected by a fuse/surge arrestor. Fiber and copper originate from Node #1. The building IDF is located in room B10 on the Basement level. Fiber distributes radially from the building IDF to hub rooms (telecommunication rooms) to within 100 meters of end-use equipment and lands at rack mounted fiber switch(es) within the hub room. Overall Condition Date Installed UIUC network upgrade complete (date range 2006 to 2012) Comments There are two hub rooms located within the building. Hub A located in room 38C on the Basement level feeds the lower portion of the building and Hub B located in room 220 on the Second Floor feeds the upper portion of the building. Typically, each hub room is equipped with free standing racks (one in Hub A and five at Hub B), wire management, overhead basket cable tray. Hub B has a dedicated electrical panel. The hub rooms have smoke detectors. Hub A does not have a dedicated cooling system, rather it is conditioned from the base building HVAC system. Hub B has a dedicated cooling system (Liebert Minimate, ceiling mounted) and a room exhaust fan. Both hub rooms have free standing plug in UPS modules. Outlet standards typically have 1"C stubbed to cable management. Wall mounted cable management/trough is installed in the corridors below the ceilings. Standard outlet consists of two network cables and two data jacks. Station cable typically consists of Cat 6e (Mohawk Advancenet). The building is typically equipped with WIFI throughout (coverage not noted). Good Remaining Useful Life 20 Years Nominal Useful Life: 20 Years Replacement Cost $638,300 Hub B has a free standing box fan aimed at the back of the equipment racks to provide additional air movement and cooling PAGE 120

121 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M S U R V E Y P H O T O G R A P H S Building 67 IDF Building 67 Hub Room Building 67 Data Rack Building 67 Corridor Cable Management PAGE 121

122 Text6 A C C E S S C O N T R O L S Y S T E M A S S E S S M E N T D A T A Item ID Description Card access control in this building consists of local keypads at the copy center, library and four labs. All keypads are battery operated. Overall Condition Poor Date Installed 1/1/1970 Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Equipment Tag Not Applicable Manufacturer Not Applicable Model Number Not Applicable Serial Number Not Applicable Size/Capacity Not Applicable HP/kW Not Applicable Voltage Not Applicable Material Not Applicable Replacement Cost $133, PAGE 122

123 Text6 A C C E S S C O N T R O L S Y S T E M S U R V E Y P H O T O G R A P H S Card Access Keypad PAGE 123

124 Text6 R E S C U E A S S I S T A N C E A S S E S S M E N T D A T A Item ID Description A rescue assistance two-way communication phone exists in the north stairwell of the building. Call station phones to facility shop on campus for monitoring. Overall Condition Poor Date Installed 1/1/1970 Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Equipment Tag Not Applicable Manufacturer Ramtech Model Number Not Applicable Serial Number Not Applicable Size/Capacity Not Applicable HP/kW Not Applicable Voltage Not Applicable Material Not Applicable Replacement Cost $40, PAGE 124

125 Text6 R E S C U E A S S I S T A N C E S U R V E Y P H O T O G R A P H S Rescue Call Station PAGE 125