1 LIMITED AHERA/NESHAP ASBESTOS INSPECTION AND LEAD PAINT CHIP REPORT 309 E STREET ANDERSON, SC CLIENT: City of Anderson Department of Economic and Community Development 401 South Main Street Anderson, SC LOCATION: 390 E Street Anderson, South Carolina DATE OF INSPECTION: February 22, 2018 DATE OF REPORT: March 14, 2018 PREPARED BY: Robert L. Smith Environmental Branch Manager SUMMIT Engineering, Laboratory & Testing, P.C. (SUMMIT) 3575 Centre Circle Fort Mill, South Carolina SUMMIT Job No

2 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, 2018 LIMITED AHERA/NESHAP ASBESTOS INSPECTION AND LEAD PAINT CHIP REPORT 309 E STREET ANDERSON, SC SECTION TABLE OF CONTENTS PAGE TABLE OF CONTENTS... i LIST OF APPENDICES... i 1.0 REPORT CERTIFICATION EXECUTIVE SUMMARY SUSPECT MATERIAL Window Glazing... Error! Bookmark not defined. 3.2 Roofing SUSPECT LEAD PAINT CHIPS Exterior House Exterior Window CONCLUSIONS AND RECOMMENDATIONS... 4 LIST OF APPENDICES A B C Analytical Results Asbestos Inspector s Licenses Summit Documentation C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx i

3 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, REPORT CERTIFICATION SUMMIT is pleased to provide environmental consulting services for City of Anderson. Please contact this office at with any questions or comments regarding the findings submitted in this report. This document, entitled AHERA/NESHAP Asbestos Inspection Report, was prepared for City of Anderson and the South Carolina Department of Health and Environmental Control (SCDHEC) with sound practices and procedures and in accordance with Asbestos Hazard Emergency Response Act (AHERA), Title II of the Toxic Substance Control Act (TSCA), SCDHEC Regulation , 40 CFR 61, and 40 CFR 763 for Asbestos Containing Materials (ACM) guidance. The results obtained by the work documented in this report fulfill the requirements of federal, state, and local regulations regarding Asbestos Containing Materials. 3/14/2018 Robert L. Smith Date South Carolina DHEC Asbestos Building Inspector BI-0045 Exp. 9/07/2018 Asbestos Air Monitor AS Exp. 9/07/2018 Asbestos AHERA Supervisor SA Exp. 11/07/18 Asbestos Project Designer PD Exp. 09/06/18 Asbestos Management Planner MP Exp. 09/08/18 C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx 1

4 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, EXECUTIVE SUMMARY On February 22, 2018, SUMMIT performed a Limited AHERA/NESHAP Asbestos Inspection and paint chip sampling for the structure at 309 E Street in Anderson, South Carolina. This inspection was limited to the window glazing, and roofing shingles due to the unsafe condition of the structure. It is assumed that there are asbestos containing materials in this location and will be tested when found during demolition. The purpose of this inspection was to investigate available records for the specification of asbestos containing material (ACM), inspect the structures for suspect materials, sample and analyze suspect materials to test for asbestos, and assess the condition and location of the ACM and other characteristics of the structures. No records were available for review to determine the date the structures were built or the type of materials used during the construction. A homogeneous material is a material that appears to be uniform when properties such as age, color, and texture are compared. There were two (2) homogeneous suspect materials observed on the structure. The homogeneous areas are described in detail in section 3.0 of this report. Asbestos containing material (ACM) was not identified in during the course of this limited inspection out of the materials SUMMIT could access. SUMMIT is assuming that there is the possibility of more suspect materials inside that could not gain access to. The window glazing material is located on the window panes of the structure. The glazing material is currently in damaged condition with a potential for future damage. The material is non-friable and is classified as a miscellaneous material. The material was sampled and the results indicated that the material is classified as Asbestos Containing Material (ACM). The window glazing material contains 2% Chrysotile and there is approximately 8 windows containing this material. The sample analysis of the material is enclosed in Appendix A. A detailed map showing the locations of the sampling locations can be found in SUMMIT Documentation. 3.0 SUSPECT MATERIAL WG Window Glazing The window glazing material is located on the window panes of the structure. The glazing material is currently in damaged condition with a potential for future damage. The material is non-friable and is classified as a miscellaneous material. The material was sampled and the results indicated that the material is not classified as Asbestos Containing Material (ACM). The sample analysis of the material is enclosed in Appendix A. A detailed map showing the locations of the sampling locations can be found in SUMMIT Documentation. C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx 2

5 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, 2018 R Roofing The roofing shingles material is located on the roof, is currently in damaged condition and nonfriable with a low potential for disturbance. The material is classified as miscellaneous material. The roofing was sampled and is not classified as Asbestos Containing Material (ACM). The sample analysis is enclosed in Appendix A. A detailed map showing the sampling locations can be found in SUMMIT Documentation. 4.0 SUSPECT LEAD PAINT CHIP SUMMIT performed Lead-Based Paint Chip sampling for the structure located at 805 Beachwood Ave. in Anderson, South Carolina. The paint was sampled on the exterior of the house. The data collected is located in Appendix A. On February 18, 2018 SUMMIT personnel collected one (1) paint chip samples from the exterior portions of the house located at 309 E Street in Anderson, SC. LP White Exterior Paint Results The paint chip samples: Gray-Wood lead concentrations of: 7.6% by weight which is above the federal lead-based paint standard of 0.5% by weight. SUMMIT has determined that the exterior paint sampled is classified as Lead-Based Paint (LBP). 4.2 White Exterior Windows The paint chip samples: White-Wood lead concentrations of: 0.079% by weight which is below the federal lead-based paint standard of 0.5% by weight. SUMMIT has determined that the exterior paint sampled is not classified as Lead-Based Paint (LBP). This report is only intended for OSHA and disposal of lead-based paint demolition debris, not for HUD. 5.0 CONCLUSIONS AND RECOMMENDATIONS On February 22, 2018, SUMMIT performed a Limited AHERA/NESHAP Asbestos Inspection and paint chip sampling for the structure at 309 E Street in Anderson, South Carolina. This inspection was limited to the window glazing, and roofing shingles due to the unsafe condition of the structure. It is assumed that there are asbestos containing materials in this location and will be tested when found during demolition. C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx 3

6 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, 2018 Asbestos containing material (ACM) was not identified in during the course of this limited inspection out of the materials SUMMIT could access. SUMMIT is assuming that there is the possibility of more suspect materials inside that could not gain access to. Federal OSHA Standard 26 CFR has specific requirements relating to employee protection and notification during construction projects (including demolition and renovation projects) involving ACM as well as materials containing trace levels of asbestos which apply to this project. SUMMIT recommends complying with applicable OSHA regulations, which would include notifying the demolition contractor of the presence of asbestos. If the structure is to be renovated or demolished, a copy of this report and a notification of demolition or renovation forms must be submitted to The North Carolina Department of Health and Human Services (NC DHHS) Health Hazards Control Unit at least ten working days prior to these activities taking place. Bidders are responsible for their own calculations and estimates of quantities. Actual quantities may be more or less than indicated. Though every effort was made to examine wall cavities and other areas for pipe insulation, spray-applied or trowel applied surfacing material or other miscellaneous materials and other Presumed Asbestos Containing Material (PACM), this survey and report only deals with accessible areas of the building. There may be additional inaccessible areas above ceiling, behind walls and below floors that become evident during demolition or renovation activities. If suspect materials are found, additional asbestos testing may be required. C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx 4

7 Limited AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, S.C. March 14, 2018 APPENDIX A ANALYTICAL RESULTS C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Report E Street Anderson, SC.docx

8 Asbestos Laboratory Report Prepared for SUMMIT Engineering, Laboratory & Testing, P.C. Project: 309 E Street Summit #: Date Analyzed: 2/23/2018 Date Reported: 2/23/2018 Total Samples Analyzed: 10 # Samples >1% Asbestos: 0 Method of Analysis: EPA 600 / R93 / 116 Page 1 of 3

9 Summit Laboratories 3575 Centre Circle, Fort Mill, SC Phone: (704) Summit Order: Robert Smith SUMMIT Engineering, Laboratory & Testing, P.C Centre Circle Drive Fort Mill, SC Date Received: 2/23/2018 Date Analyzed: 2/23/2018 Date Reported: 2/23/2018 Project : 309 E Street Asbestos Sample ID Description Appearance % Fibrous % Non-Fibrous % Asbestos WG-1 Test Report: Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method using Polarized Light Microscopy WG R-1-White Shingle R-1-Gray Shingle A R-1-Tan Shingle B R-1-Felt C R-2-White Shingle R-2-Gray Shingle A R-2-Tan Shingle B R-2-Felt C Window Glazing Window Glazing Roofing Roofing Roofing Roofing Roofing Roofing Roofing Roofing Gray,Tan Non-fibrous Homogeneous Gray,Tan Non-fibrous Homogeneous Black,White Fibrous Homogeneous Black,Gray Fibrous Homogeneous Black,Tan Fibrous Homogeneous Black Fibrous Homogeneous Black,White Fibrous Homogeneous Black,Gray Fibrous Homogeneous Black,Tan Fibrous Homogeneous Black Fibrous Homogeneous Non-Asbestos 100% Non-fibrous (other) 100% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 50% Cellulose 50% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 5% Glass 95% Non-fibrous (other) 50% Cellulose 50% Non-fibrous (other) Analyst(s): Chris Estes Page 2 of 3

10 METHOD: EPA 600 / R93 / 116 For samples easily separated into homogeneous layers, each component will be analyzed separately. The sample may not be representative of the larger material in question. Interpretation and use of test results are the responsibility of the client. Due to the limitations of the EPA 600 Method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles, mastic and roofing can be difficult to analyze by PLM. Reanalysis by Transmission Electron Microscopy (TEM) to verify results of <1% or None Detect for these materials is recommended. This sheet may not be reproduced except with permission from Summit Laboratories. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Analyst(s): Chris Estes Approved By: Michael Zavislak, Approved Signatory NVLAP Lab Code Summit Laboratories, 3575 Centre Circle, Fort Mill, SC 29715, Phone: (704) Page 3 of 3 This is the last page of the report

11

12

13 Customer: Summit Engineering, Laboratory & Testing, P.C Centre Circle Drive Fort Mill, SC Project: 309 E Street Bulk Asbestos Analysis by Transmission Electron Microscopy Semi-Quantitative Chatfield SOP Rev. 1 Attn: Robert Smith Lab Order ID: Analysis ID: Date Received: Date Reported: _TB 2/27/2018 3/6/2018 Sample ID Lab Sample ID Description Lab Notes Organic Acid Sol. Asbestos (Wt. %) (Wt. %) (Wt. %) LCL-UCL (Wt. %) WG-3 Window glazing 11% 88% TBS_1 R-3-A Roofing (white shingle, gray shingle, tan shingle, felt) 35% TBS_2 white shingle R-3-B Roofing (white shingle, gray shingle, tan shingle, felt) 20.% TBS_5 gray shingle R-3-C Roofing (white shingle, gray shingle, tan shingle, felt) 19% TBS_4 tan shingle R-3-D Roofing (white shingle, gray shingle, tan shingle, felt) 78% TBS_3 felt Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Ired Gulley (5) T-F-010 r15 1/15/2018 tem_ Analyst Approved Signatory Scientific Analytical Institute, Inc Dundas Dr. Greensboro, NC (336) Page 1 of 1

14 Company Contact Information Scientific Analytical Institute 4604 Dundas Dr. Greensboro, Ne Phone: Fax: Company: S G#t "":+ Contact: (L ~i'u:v1.f Address: ~ IAJ c )/ Phone 0: ~ 6?4'175" 17( Fax 0: :. ~ BillinglInvoice. Informa tion Turn Around Times Company : 5'u~~.4 90 Min Hours 0 Contact: 3 Hours 0 72 Hours 0 Address: 6 Hours 0 96 Hours 0 PO Number: Project Name!Number: ']01 G 12 Hours 0 ) 20 Hours ()([' 24 Hours Hours 0 Lab Use Only Lab Order ID: Client Code: Asbestos Test Types PLM EPA 600/R-93/116 (PLM) POSitive stop 0 PLM Point Count 400 (PT4) ~ PLM Point Count 1000 (PTM) 0 PCM NIOSH 7400-A Rules (PCM) 0 B Rules (PCB) D TWA (PTA)D TEM AHERA (AHE) 0 TEM Level J) (UI) 0 TEM NIOSH 7402 (TNI) 0 TEM Bulk Qualitative (TBL) 0 TEM Bulk Chatfield (TBS) TEM Bulk Quantitative (TBQ) ~ 110 TEM Wipe ASTM D6480-0S 0 TEM Microvac ASTM DS7SS-09 0 TEM Water EPA (TWI) 0' Other ~ - 0 SampleID# Description/Location Volume! Area Comments WG W ill6..qvu G-\~2.\ fl4 ~-3 ~~ ng (Wh\-~ s,\n~r"\i. \~ L--ro--\) S~ : "'" e. <J J(,~ <"'n :rv.\.e 0 ~C--\\-\l U -',, II, -'. --'-"...,~prea 'U.,-;-/. ' Reiected.n - Total # of Samples Daterrime

15 Customer: Summit Engineering, Laboratory & Testing, P.C Centre Circle Drive Fort Mill, SC Project: 309 E Street Analysis for Lead Concentration in Paint Chips by Flame Atomic Absorption Spectroscopy EPA SW B/6010C/7000B Attn: Robert Smith Lab Order ID: Analysis ID: _PBP Date Received: 2/27/2018 Date Reported: 3/5/2018 Sample ID Description Mass Concentration Concentration Lab Sample ID Lab Notes (g) (ppm) (% by weight) LP PBP_1 House paint ext % LP PBP_2 Window paint ext % Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA ELPAT program. ELPAT Laboratory ID: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Analytical uncertainty available upon request. The quality control samples run with the samples in this report have passed all EPA required specifications unless otherwise noted. RL: (Report Limit for an undiluted 50ml sample is 4µg Total Pb). L-F-021 r17 2/14/2020 pbrpt_4.0.01_pbp001 Daniel Olson (1) Melissa Ferrell (1) Analyst Laboratory Director Scientific Analytical Institute, Inc Dundas Dr. Greensboro, NC (336) Page 1 of 1

16 Scientific Analytical Institute Dundas Dr. Greensboro, He Phone: Fax: ~ab ~se Only //(Jr; J./9r5 qab prder ID: _.:...Its_1 Client Code: Company Name: I Address: ec f/1.;t(

17 AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, SC March 14, 2018 APPENDIX B INSPECTOR S LICENSES C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Appendix B.rtf

18

19 AHERA/NESHAP Asbestos Inspection and Lead Paint Chip SUMMIT Project No E Street, Anderson, SC March 14, 2018 APPENDIX C SUMMIT DOCUMENTATION C:\Users\rsmith\Desktop\City of Anderson\309 E Street\Appendix C.rtf

20 Figure 1 Site Location Map 309 E Street Anderson, SC SUMMIT ELT, PC Project: C:\Users\rsmith\Desktop\City of Anderson\309 E Street\R - Figure 1 Site Map.doc