1 Client: Manufacturing place: Test subject: Name: ENERGON HELLAS G.N. KYTINOS & SIA O.E. Address: Arethousis 44, Halkida, GREECE Manufacturer s name: ENERGON HELLAS G.N. KYTINOS & SIA O.E. Address: Arethousis 44, Halkida, GREECE Factory s name: ENERGON HELLAS G.N. KYTINOS & SIA O.E. Address: Arethousis 44, Halkida, GREECE Product: Inverter air source heat pump Type: AXAI-15 Test specification: EN : 2011 clause 4 Technical Report No Rev. 00 Dated Purpose of examination: EN :2011 Test according to the test specification Client s requirements of test conditions (see page 8) Test result: See page 3-7 This technical report may only be quoted in full. Any use for advertising purposes must be granted in writing. This report is the result of a single examination of the object in question and is not generally applicable evaluation of the quality of other products in regular production. Page: 1 of 8

2 1 Description of the test subject 1.1 Function Manufacturer s specification for intended use: The appliance is inverter air source heat pump used for heating or cooling the water. 1.2 Technical Data Model : AXAI-15 Rated Voltage (V) : Rated Frequency (Hz) : Inverter air source heat pump Rated Power (W) 4400W for outdoor unit : (heating) 54W A for indoor unit Protection Class : Class I; Class II; Class III Protection Against Moisture : IPX4 for outdoor unit IPX1 for indoor unit Construction : Stationary Portable Hand-held Open-frame Supply connection : Non detachable cord Permanent connection to fixed wiring Appliance inlet Operation mode continuous operation; Intermittent operation; Short time operation; Rated capacity (ml), if any Weight (kg) : 103 for outdoor unit 35 for indoor unit 2 Order 2.1 Date of Purchase Order, Customer s Reference Receipt of Test Sample, Location , Axen Heating Technologies Limited Address: No.32, Shilian Road, Shiqi Town, Panyu Distrcit, Guangzhou, China 2.3 Date of Testing to Location of Testing Axen Heating Technologies Limited Address: No.32, Shilian Road, Shiqi Town, Panyu Distrcit, Guangzhou, China Page: 2 of 8

3 3 Test Results Table 1: test result at A-7/W30: Model : AXAI-15 Compressor built-in : Frequency setting Mode : DA150S1C-20FZ and PA240X2CS-4KU1 85Hz Heating Test method Calorimeter test method Indoor air ehthalpy test method Water enthalpy method Test condition Measured ambient temperture Atmospheric pressure kpa - Test Voltage V Test frequency Hz 50 Total current A 14.2 Total power input (P T ) W 3952 Effective power input (P E ) W 3955 Air inlet evaporator temperature, DB/WB C -6.7/-7.7 Air outlet evaporator temperature, DB/WB C - Air inlet condenser temperature, DB/WB C - Air outlet condenser temperature, DB/WB C - For duct connection External/internal static pressure difference Pa - Volume flow rate m 3 /h - Indoor water inlet temperature C 30.0 Indoor water outlet temperature C 34.6 Indoor water volume flow m 3 /h 1.69 Pressure difference kpa 75.2 Outdoor water inlet temperture C - Outdoor water outlet temperture C - Outdoor water volume flow m 3 /h - Total heating capacity (P H ) W 8969 Coefficient of performance (COP) W/W 2.23 DB/WB outdoor ( C) -7.0/-8.0 DB/WB outdoor ( C) -6.7/-7.7 Page: 3 of 8

4 Table 2: test result at A2/W30: Model : AXAI-15 Compressor built-in : Frequency setting: Mode : DA150S1C-20FZ and PA240X2CS-4KU1 85Hz Heating Test method Calorimeter test method Indoor air ehthalpy test method Water enthalpy method Test condition Measured ambient temperture Atmospheric pressure kpa - Test Voltage V Test frequency Hz 50 Total current A 13.7 Total power input (P T ) W 3578 Effective power input (P E ) W 3385 Air inlet evaporator temperature, DB/WB C 2.3/1.3 Air outlet evaporator temperature, DB/WB C - Air inlet condenser temperature, DB/WB C - Air outlet condenser temperature, DB/WB C - For duct connection External/internal static pressure difference Pa - Volume flow rate m 3 /h - Indoor water inlet temperature C 30.0 Indoor water outlet temperature C 34.6 Indoor water volume flow m 3 /h 2.13 Pressure difference kpa 77.3 Outdoor water inlet temperture C - Outdoor water outlet temperture C - Outdoor water volume flow m 3 /h - Total heating capacity (P H ) W Coefficient of performance (COP) W/W 4.13 DB/WB outdoor ( C) 2.0/1.0 DB/WB outdoor ( C) 2.3/1.3 Page: 4 of 8

5 Table 3: test result at A7/W30: Model : AXAI-15 Compressor built-in : Frequency setting Mode : DA150S1C-20FZ and PA240X2CS-4KU1 85Hz Heating Test method Calorimeter test method Indoor air ehthalpy test method Water enthalpy method Test condition Measured ambient temperture Atmospheric pressure kpa - Test Voltage V Test frequency Hz 50 Total current A 14.8 Total power input (P T ) W 3578 Effective power input (P E ) W 3385 Air inlet evaporator temperature, DB/WB C 7.0/6.0 Air outlet evaporator temperature, DB/WB C - Air inlet condenser temperature, DB/WB C - Air outlet condenser temperature, DB/WB C - For duct connection External/internal static pressure difference Pa - Volume flow rate m 3 /h - Indoor water inlet temperature C 30.0 Indoor water outlet temperature C 35.4 Indoor water volume flow m 3 /h 2.13 Pressure difference kpa 80.3 Outdoor water inlet temperture C - Outdoor water outlet temperture C - Outdoor water volume flow m 3 /h - Total heating capacity (P H ) W Coefficient of performance (COP) W/W 4.13 DB/WB outdoor ( C) 7.0/6.0 DB/WB outdoor ( C) 7.0/6.0 Page: 5 of 8

6 Table 4: test result at A7/W40: Model : AXAI-15 Compressor built-in : Frequency setting Mode : DA150S1C-20FZ and PA240X2CS-4KU1 85Hz Heating Test method Calorimeter test method Indoor air ehthalpy test method Water enthalpy method Test condition Measured ambient temperture Atmospheric pressure kpa - Test Voltage V Test frequency Hz 50 Total current A 17.2 Total power input (P T ) W 4096 Effective power input (P E ) W 4108 Air inlet evaporator temperature, DB/WB C 7.1/6.0 Air outlet evaporator temperature, DB/WB C - Air inlet condenser temperature, DB/WB C - Air outlet condenser temperature, DB/WB C - For duct connection External/internal static pressure difference Pa - Volume flow rate m 3 /h - Indoor water inlet temperature C 40.0 Indoor water outlet temperature C 45.0 Indoor water volume flow m 3 /h 2.29 Pressure difference kpa 83.9 Outdoor water inlet temperture C - Outdoor water outlet temperture C - Outdoor water volume flow m 3 /h - Total heating capacity (P H ) W Coefficient of performance (COP) W/W 3.19 DB/WB outdoor ( C) 7.0/6.0 DB/WB outdoor ( C) 7.1/6.0 Page: 6 of 8

7 Table 5: test result at A7/W50: Model : AXAI-15 Compressor built-in : Frequency setting Mode : DA150S1C-20FZ and PA240X2CS-4KU1 85Hz Heating Test method Calorimeter test method Indoor air ehthalpy test method Water enthalpy method Test condition Measured ambient temperture Atmospheric pressure kpa - Test Voltage V Test frequency Hz 50 Total current A 19.2 Total power input (P T ) W 4524 Effective power input (P E ) W 4431 Air inlet evaporator temperature, DB/WB C 7.0/6.0 Air outlet evaporator temperature, DB/WB C - Air inlet condenser temperature, DB/WB C - Air outlet condenser temperature, DB/WB C - For duct connection External/internal static pressure difference Pa - Volume flow rate m 3 /h - Indoor water inlet temperature C 50.0 Indoor water outlet temperature C 54.8 Indoor water volume flow m 3 /h 2.39 Pressure difference kpa 76.2 Outdoor water inlet temperture C - Outdoor water outlet temperture C - Outdoor water volume flow m 3 /h - Total heating capacity (P H ) W Coefficient of performance (COP) W/W 2.40 DB/WB outdoor ( C) 7.0/6.0 DB/WB outdoor ( C) 7.0/6.0 Page: 7 of 8

8 4 Remark 5 Documentation Attachment No.1: 6 pages of photo documentation Attachment No.2: 2 pages of nameplate Attachment No.3: 1 page of test equipment list 6 Summary 1. According to the client s requirements, heating capacity test at below conditions were considered in this report: Code Ambient temperature ( C ) Water temperature ( C ) Test voltage Dry bulb Wet bulb Inlet Outlet A-7/W V, 50Hz A2/W V, 50Hz A7/W V, 50Hz A7/W V, 50Hz A7/W V, 50Hz 2. Water enthalpy method was adopted in this report. 3. The tests were performed according to EN :2011. Jiangsu TÜV Product Service Ltd. TÜV SÜD Group Engineer: Dennis Deng Technical Report checked: Eric Yang Page: 8 of 8

9 Attachment No.1 Photo documentations Model: AXAI -15 Front view for outdoor unit Back view for outdoor unit Page: 1 of 6

10 Attachment No.1 Front view for indoor unit Back view for indoor unit Page: 2 of 6

11 Attachment No.1 Internal view for outdoor unit Internal view for indoor unit Page: 3 of 6

12 Attachment No.1 Fan motor view Compressor I view Page: 4 of 6

13 Attachment No.1 Compressor II view Water pump view Page: 5 of 6

14 Attachment No.1 Controller view Page: 6 of 6

15 Attachment No.2 Label of the appliance Copy of marking plate Inverter air source heat pump Model Name AXAI-15 (indoor unit) Heating Cooling Capacity* kw Power input* kw EER* / COP* W/W Rated voltage / frequency V/Hz /50 Rated Power input W 54 (+4000**) 54 Rated Current A 0.4 (+17.4**) 0.4 Max. water outlet temp. C 55 Rated water flow rate m³/h 2.3 Permissible water pressure MPa 0.6 Net weight kg 35 Net dimension mm 609x450x250 Sound pressure level db (A) 29 Unit protection class IP IPX1 * Capacity and power input based on the following conditions: - Heating: Water Inlet/Outlet temperature 30 C /35 C. Outdoor air dry bulb/wet bulb temperature 7 C /6 C - Cooling: Water Inlet/Outlet temperature 23 C /18 C, Outdoor air dry bulb temperature 35 C. ** Related to the supplementary heater. ENERGON HELLAS G.N. KYTINOS & SIA O.E. Arethousis 44, Halkida, GREECE Page: 1 of 2

16 Attachment No.2 Inverter air source heat pump Model Name AXAI-15 (outdoor unit) Heating Cooling Capacity* kw Power input* kw EER* / COP* W/W Rated voltage / frequency V/Hz / 50 Rated Power input W Rated Current A Capacity adjustable range kw Refrigerant type/charge kg R410A / 3.0 Permissible refrigerant pressure MPa 1.3 / 4.2 suction / discharge Net weight kg 103 Net dimension mm 963x1250x342 Sound pressure level db (A) 52 Unit protection class IP IPX4 * Capacity and power input based on the following conditions: - Heating: Water Inlet/Outlet temperature 30 C /35 C. Outdoor air dry bulb/wet bulb temperature 7 C /6 C - Cooling: Water Inlet/Outlet temperature 23 C /18 C. Outdoor air dry bulb temperature 35 C ENERGON HELLAS G.N. KYTINOS & SIA O.E. Arethousis 44, Halkida, GREECE Page: 2 of 2

17 Attachment No.3 Test Equipment List Equipment ID No. Model Brand/Manufacturer Calibration due date Tape measure MC09 LD-385W LAND AC source Supply JJ JINGJIU Performance measuring chamber Multi-function digital power meter SB HP GUANGZHOU PINXIN ZW ZW3432B QINGZHI Temperature recorder MY HP34972 AGILENT Platinum resistance -- PT-100 YINUO Pressure transmitter GZ MPa MICRO SENSOR Water flow meter LDY-25S Shanghai Guanghua Page: 1 of 1