1 Ministry of the Environment and Climate Change Safe Drinking Water Branch 3232 White Oak Road, 3 rd Floor London ON N6E L8 Tel (59) Fax (59) Ministère de l Environnement et de l Action en matière de changement climatique Direction du contrôle de la qualité de l eau potable Bureau du district de London 3 e étage 3232, chemin White Oak London (Ontario) N6E L8 Tel (59) August 7, 207 File no. PE PS C8 540 The Township of Perth South 3204 Perth Road 22 St. Pauls, Ontario N0L J0 Attention: Mr. Ken Bettles, Director of Public Works Re: St. Pauls Drinking Water System Inspection Report (Water Work # ) Inspection conducted on June 06, 207 Dear Mr. Ken Bettles, The enclosed Drinking Water Inspection Report outlines non-compliance, if any, with Ministry legislation, and policies for the above noted water system. Violations noted in this report, if any, have been evaluated based on community risk. These violations will be monitored for compliance with the minimum standards for drinking water in Ontario as set forth under the Safe Drinking Water Act and associated regulations. Where risk is deemed to be high and/or compliance is an ongoing concern, violations will be forwarded to this Ministry s Investigation and Enforcement Branch. In order to measure individual inspection results, the Ministry has established an inspection compliance risk framework based on the principles of the Inspection, Investigation & Enforcement (II&E) Secretariat and advice of internal/external risk experts. The Inspection Summary Rating Record (IRR) provides the Ministry, the system owner and the local Public Health Units with a summarized quantitative measure of the drinking water system s annual inspection and regulated water quality testing performance. Section 9 of the Safe Drinking Water Act (Standard of Care) creates a number of obligations for individuals who exercise decision-making authority over municipal drinking water systems. Please be aware that the Ministry has encouraged such individuals, particularly municipal councillors, to take steps to be better informed about the drinking water systems over which they have decisionmaking authority. These steps could include asking for a copy of this inspection report and a review of its findings. Further information about Section 9 can be found in Taking Care of Your Drinking Water: A guide for members of municipal council found under Resources on the Drinking Water Ontario website at

2 Please note the attached IRR methodology memo describing how the risk rating model has improved to better reflect the health related and administrative non-compliance found in an inspection report. IRR ratings are published (for the previous inspection year) in the Ministry s Chief Drinking Water Inspector s Annual Report. If you have any questions or concerns regarding the rating, please contact Scott Milne, Acting Drinking Water Program Supervisor, at (59) If you have any questions regarding the report, please feel free to call me at (59) Yours truly, Jim Miller Provincial Officer London District Office jim.w.miller@ontario.ca cc. Ontario Clean Water Agency Perth District Health Unit Upper Thames River Conservation Authority

3 Ministry of the Environment and Climate Change Inspection Report Site Number: Inspection Number: -F6SNZ Date of Inspection: Jun 06, 207 Inspected By: Jim Miller

4 Ministry of the Environment Drinking Water System Inspection Report Table of Contents Table of Contents Owner Information... 2 Inspection Details... 2 Inspection Summary... 4 SMRS Introduction... 4 SMRS Source... 4 SMRS Capacity Assessment... 5 SMRS Treatment Processes... 5 SMRS Treatment Process Monitoring... 6 SMRS Operations Manuals... 7 SMRS Logbooks... 8 SMRS Security... 8 SMRS Certification and Training... 8 SMRS Water Quality Monitoring... 8 SMRS Water Quality Assessment... 0 SMRS Reporting and Corrective Actions... SMRS Other Inspection Findings... Non Compliance with Regulatory Requirements and Actions Required... 2 Summary of Recommendations and Best Practice Issues... 5 Signatures... 6 Inspection Audit Sample Results... Appendix A Stakeholder References Appendix B Inspection Rating Record and Inspection Risk Methodology... Appendix C

5 Ministry of the Environment and Climate Change Inspection Report OWNER INFORMATION: Company Name: PERTH SOUTH, THE CORPORATION OF THE TOWNSHIP OF Street Number: 3204 Unit Identifier: Street Name: PERTH ROAD 22 Road City: ST. PAUL'S Province: ON Postal Code: N0K V0 CONTACT INFORMATION Type: Owner Contact Name: Ken Bettles Phone: (59) Fax: (59) Title: Director of Public Works Type: Owner Name: Rebecca Clothier Phone: (59) Fax: (59) Title: Treasurer/Deputy Clerk Type: Owner Name: Tim Ivanyshyn Phone: (59) Fax: (59) Title: Chief Administrative Officer Type: Operating Authority Name: Marcel Misuraca Phone: (59) Fax: (59) Title: Senior Operations Manager Type: Operating Authority Name: Renee Hornick Phone: (59) Fax: (59) Title: Process Compliance Technician INSPECTION DETAILS: Site Name: Site Address: 3204 ROAD 22 RD ST. PAULS ON N0K V0 County/District: Perth South MOECC District/Area Office: London District Health Unit: PERTH DISTRICT HEALTH UNIT Conservation Authority: MNR Office: Category: Small Municipal Residential Site Number: Inspection Type: Unannounced Inspection Number: -F6SNZ Date of Inspection: Jun 06, 207 Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 2 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

6 Ministry of the Environment and Climate Change Inspection Report Date of Previous Inspection: COMPONENTS DESCRIPTION Site (Name): MOE DWS Mapping Type: DWS Mapping Point Sub Type: Site (Name): WELL Type: Source Sub Type: Ground Comments: As per Drinking Water Works Permit , the well is a 70.4 m deep drilled groundwater well with a 50 mm steel casing to a depth of 45. m, located approximately 2 m outside the Township Municipal Building, equipped with a submersible pump rated at 26 L/min. Site (Name): TREATED WATER Type: Treated Water POE Sub Type: Pumphouse Comments: As per Drinking Water Works Permit : A well pumphouse located within the municipal building, housing the treatment and control facilities, and ultraviolet (UV) system as a primary disinfectant consisting of: - three (3) UV reactors, each equipped with two (2) UV lamps rated to provide a minimum dosage of 40 mj/cm² at a capacity of 3 L/min., complete with flow control valve (restrictor), solenoid actuated isolation valves and associated appurtenances; -iron sequestering system consisting of two (2) chemical metering pumps ( duty, off-line standby) rated at 0.47 L/hr. of sodium silicate solution discharging into the well pump header, complete with one () 00 L solution tank in containment tub; - one () 20 L hypochlorite solution tank (standby) in containment tub; - one () free chlorine residual analyzer at treated water header, complete with autodialer alarm system; -vent pipe from hypochlorite solution tank to external of building, complete with mesh screen; -one () natural gas fired emergency generator rated at 5 kilowatts with manual transfer switch and external connection for emergency power -well pump header and appurtenances; -raw and treated water sampling taps; -a 38 mm diameter flowmeter with shut off valves and bypass -pressure relief valve and blow-off valve; and -electrical panel. Site (Name): DISTRIBUTION (WATER INSPECTIONS) Type: Other Sub Type: Other Comments: The distribution system has 35 service connections with no hydrants for approximately 90 residents. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 3 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

7 Ministry of the Environment and Climate Change Inspection Report INSPECTION SUMMARY: Introduction The primary focus of this inspection is to confirm compliance with Ministry of the Environment and Climate Change (MOECC) legislation as well as evaluating conformance with ministry drinking water related policies and guidelines during the inspection period. The ministry utilizes a comprehensive, multi-barrier approach in the inspection of water systems that focuses on the source, treatment and distribution components as well as management practices. This drinking water system is subject to the legislative requirements of the Safe Drinking Water Act, 2002 (SDWA) and regulations made therein, including Ontario Regulation 70/03, "Drinking Water Systems" (O.Reg. 70/03). This inspection has been conducted pursuant to Section 8 of the SDWA. This report is based on a "focused" inspection of the system. Although the inspection involved fewer activities than those normally undertaken in a detailed inspection, it contained critical elements required to assess key compliance issues. This system was chosen for a focused inspection because the system's performance met the ministry's criteria, most importantly that there were no deficiencies as identified in O.Reg. 72/03 over the past 3 years. The undertaking of a focused inspection at this drinking water system does not ensure that a similar type of inspection will be conducted at any point in the future. This inspection report does not suggest that all applicable legislation and regulations were evaluated. It remains the responsibility of the owner to ensure compliance with all applicable legislative and regulatory requirements. Water Inspector's Jim Miller and Tyler Kelly conducted an unannounced physical inspection of the St. Paul's Drinking Water System, Water Works # on June 6, 207. This inspection covers the period from April 30, 206 to May 3, 207. Documents reviewed in association with this report include but are not limited to: ) Ministry of the Environment and Climate Change Drinking Water Works Permit # Issue Number: 3, dated April 2, 206; 2) Ministry of the Environment and Climate Change Municipal Drinking Water Licence # Issue Number: 2, dated April 2, 206; 3) Ministry of the Environment and Climate Change Permit To Take Water # WJ9U dated May 2, 200. This report also includes a review and assessment of compliance and operating practices in relation to the following Acts and Regulations: ) Safe Drinking Water Act, 2002; 2) Drinking Water Systems Regulation, (Ontario Regulation 70/03); 3) Ontario Drinking-Water Quality Standards (Ontario Regulation 69/03); 4) Ontario Water Resources Act, 990 and associated regulations; 5) Certification of Drinking-Water System Operators and Water Quality Analysts (Ontario Regulation 28/04). Other operational documents maintained by the owner/operating authority for the period April 30, 206 through May 3, 207 were also reviewed in conjunction with this inspection. Source The owner was maintaining the production well(s) in a manner sufficient to prevent entry into the well of Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 4 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

8 Ministry of the Environment and Climate Change Inspection Report Source surface water and other foreign materials. At the time of the physical inspection, the well was in good condition equipped with a commercially manufactured watertight, vermin-proof well cap, complete with a screened air vent. The casing height was greater than 40 cm above the ground surface and signs of surface water pooling were not noted. Also, a review of the raw water quality does not indicate influence from surface water or other foreign material. In addition, the owner/operating authority has prepared a Well Inspection and Maintenance Plan to ensure the well is maintained in a secured state. Measures were in place to protect the groundwater and/or GUDI source in accordance with any the Municipal Drinking Water Licence and Drinking Water Works Permit issued under Part V of the SDWA. The Operations and Maintenance Manual includes a Well Inspection and Maintenance Plan as required by Schedule B, Section 6, of the Municipal Drinking Water License # issue # 2 issued on April 2, 206. The plan defines the schedule for inspections and maintenance procedures on the production Well. A remedial action plan is also defined for situations where an inspection indicates non-compliance with respect to regulatory requirements. Capacity Assessment There was sufficient monitoring of flow as required by the Municipal Drinking Water Licence or Drinking Water Works Permit issued under Part V of the SDWA. Schedule C, Section 2.0 of the Municipal Drinking Water Licence issue # 2 issued on April 2, 206 for the St. Pauls Drinking Water System states that the following flow rates must be measured and recorded: ) The flow rate and daily volume of treated water that flows from the treatment system to the distribution system and; 2) The flow rate and daily volume of water that flows into the treatment system. St. Pauls Drinking Water System has one () treated flow meter. The flow meter records the amount of treated flow prior to entering the distribution systems. The flow meter records the average, maximum, and minimum flow rate in every five minute period to the data logger. The owner was in compliance with the conditions associated with maximum flow rate or the rated capacity conditions in the Municipal Drinking Water Licence issued under Part V of the SDWA. Schedule C, Section.0 (.) of the Municipal Drinking Water Licence Issue # 2 issued on April 2, 206 for the St. Pauls Drinking Water System states that the maximum daily volume of treated water entering the distribution system shall not exceed m3/day. Documentation provided by the operating authority indicates that the daily capacity was not exceeded during the inspection period. Treatment Processes The owner had ensured that all equipment was installed in accordance with Schedule A and Schedule C of the Drinking Water Works Permit. During the physical inspection all equipment was installed in accordance with the Drinking Water Works Permit , issue # 3, issued on April 2, 206. During the inspection, it was noted that the following equipment was not properly connected to the drinking water system in accordance with Schedule A and Schedule C of the Drinking Water Works Permit. The owner/operating authority shall ensure the following equipment is properly connected upon completion of the planned equipment upgrades in 207 to the drinking water system. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 5 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

9 Ministry of the Environment and Climate Change Inspection Report Treatment Processes ) The one () standby Sodium Hypochlorite chemical feed pump required by Drinking Water Works Permit was not connected to a power source, therefore making it offline. The Drinking Water Works Permit requires one () duty and one () standby Sodium Hypochlorite chemical feed pumps. Standby equipment is considered to be equipment that can be made duty by the manual act of switching over (flipping an on/off switch) or an automatic switch over of equipment initiated by a signal from a monitoring system. 2) During the inspection there was only one () duty Sodium Silicate chemical feed pump at the drinking water system. The Drinking Water Works Permit requires one () duty and one () offline Sodium Silicate chemical feed pumps. Records indicated that the treatment equipment was operated in a manner that achieved the design capabilities required under Ontario Regulation 70/03 or a Drinking Water Works Permit and/or Municipal Drinking Water Licence issued under Part V of the SDWA at all times that water was being supplied to consumers. The St. Pauls Drinking Water System utilizes UV for primary disinfection, and sodium hypochlorite for secondary disinfection of the groundwater supply. A review of the data provided by the operating authority indicates that the UV disinfection units and sodium hypochlorite injection system is operated in a manner that achieves disinfection requirements. Records confirmed that the water treatment equipment which provides chlorination or chloramination for secondary disinfection purposes was operated so that at all times and all locations in the distribution system the chlorine residual was never less than 0 mg/l free or 0.25 mg/l combined. Documentation provided by the operating authority indicates that during the inspection period the free chlorine residuals were greater than 0 mg/l in the distribution system. The primary disinfection equipment was equipped with alarms or shut-off mechanisms that satisfied the standards described in Section -6 () of Schedule of Ontario Regulation 70/03. The St. Pauls Drinking Water System uses three (3) Hallett 30 UV Pure to achieve primary disinfection. Each Hallett 30 UV Pure is equipped with an automatic shut-off valve that will cease the flow of water to the distribution system if the UV units malfunction, loses power or is not providing a disinfection dose of 40 mj/cm2. The UV units are also equipped with an auto-dialer alarm system that contacts the operator on call to notify them of the issue. Treatment Process Monitoring The secondary disinfectant residual was measured as required for the distribution system. In accordance with Ontario Regulation 70/03 Schedule 7-2 (5), the owner/operating authority shall ensure that at least 2 distribution samples are collected and immediately tested for free chlorine residual. Ontario Regulation 70/03 Schedule 7-2 (6), states that at least one of the distribution samples shall be taken 48 hours after and during the same week as, one of the other distribution samples. Records provided from the operating authority indicate that the St. Pauls Drinking Water System collected and tested for free chlorine residual within the frequency stated in Ontario Regulation 70/03 Schedule 7-2 (6). Operators were examining continuous monitoring test results and they were examining the results within 72 hours of the test. The operators examine the continuous monitoring data on a daily basis. All continuous monitoring data during the inspection period was reviewed within 72 hours. All continuous monitoring equipment utilized for sampling and testing required by O. Reg.70/03, or Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 6 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

10 Ministry of the Environment and Climate Change Inspection Report Treatment Process Monitoring Municipal Drinking Water Licence or Drinking Water Works Permit or order, were equipped with alarms or shut-off mechanisms that satisfy the standards described in Schedule 6. The St. Pauls Drinking Water System utilizes one () free chlorine analyzer to monitor treated secondary disinfection. The analyzer will alarm through the auto dialer, which will contact the operator on call. The alarm set points are: Low: 0.65 mg/l High:.50 mg/l All continuous analysers were not calibrated, maintained, and operated, in accordance with the manufacturer's instructions or the regulation. Schedule E, of the Municipal Drinking Water Licence Issue # 2 issued on April 2, 206 for the St. Pauls Drinking Water System states the requirements for the UV disinfection sensor checks and calibration. The owner/operating authority shall ensure the following is being conducted: ) Duty UV sensors shall be checked on at least a monthly basis against a reference UV sensor or at the frequency as otherwise recommended by the UV equipment manufacturer; 2) When comparing a duty UV sensor to a reference UV sensor, the calibration ratio (intensity measured with the duty UV sensor/intensity measured with the reference UV sensor) shall be less than or equal to.2; 3) If the calibration ratio is greater than.2, the duty UV sensor shall be replaced with a calibrated UV sensor or a UV sensor correction factor shall be applied while the problem with the UV sensor is being resolved; 4) Reference UV sensors shall be checked against a Master Reference Assembly at a minimum frequency of once every three years or on a more frequent basis depending upon the recommendations of the equipment manufacturer. Records provided by the operating authority indicated that the UV units have not been properly checked and calibrated as recommended by the UV equipment manufacturer (UV Pure) and as per the Municipal Drinking Water Licence during the inspection period. Also during the physical inspection a sensor check was performed by the operating authority using a Hallett Diagnostic Tool. The Hallett Diagnostic Tool was used to determine the transmittance and intensity of the duty UV sensor, but not checked against a reference UV sensor. All other continuous analysers were calibrated, maintained, and operated, in accordance with the manufacturer's instructions or the regulation. Operations Manuals The operations and maintenance manuals contained plans, drawings and process descriptions sufficient for the safe and efficient operation of the system. The operating authority provided an up-to-date copy of the St. Pauls Drinking Water System operations and maintenance manuals. The manuals contains plans, drawings and process descriptions sufficient for the safe and efficient operation of the subsystem as required by Ontario Regulation 28/04, s. 28. The operations and maintenance manuals met the requirements of the Drinking Water Works Permit and Municipal Drinking Water Licence issued under Part V of the SDWA. Schedule B, Section 6.0 of the Municipal Drinking Water Licence Issue # 2 issued on April 2, 206 for the St. Pauls Drinking Water System states the minimal requirements of documents to be maintained in the operations and maintenance manual. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 7 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

11 Ministry of the Environment and Climate Change Inspection Report Operations Manuals The operations and maintenance manual for the St. Pauls Drinking Water System contained all required documentation, with the exemption of procedures for UV checks and calibrations as stated in Schedule E of the Municipal Drinking Water Licence. The owner/operating authority shall develop a procedure in accordance with the Municipal Drinking Water Licence and the UV equipment manufacture recommendations for UV checks and calibrations upon completion of the planned equipment upgrades in 207 to the drinking water system. Logbooks Records or other record keeping mechanisms confirmed that operational testing not performed by continuous monitoring equipment was being done by a certified operator, water quality analyst, or person who suffices the requirements of O. Reg. 70/ All log records regarding Ontario Regulation 70/ reviewed during the inspection period, identified the names of all operators of the facility and their respective signatures and/or initials. It should be noted that any entries in the log must be identified by the person making the entry in the logs. An example of this is if multiple operators make entries in the log. If this occurs, those persons must clearly identify who made the entry (i.e. by signature or initial). Security The owner had provided security measures to protect components of the drinking water system. During the physical inspection a visual security assessment was conducted. The pumphouse/treatment facility is securely locked and is visited on a daily basis by the operating authority. Only the operating authority and owner have key access to the facility. Certification and Training The overall responsible operator had been designated for each subsystem. At the time of inspection, the overall responsible operator designated for the St. Pauls Drinking Water System was found to have certification equal or greater than the classification level of the system. The St. Pauls Drinking Water System is categorized as a Limited Ground Water System, issued on June 23, 998. Operators in charge had been designated for all subsystems which comprised the drinking-water system. An operator in charge was designated for the St. Pauls Drinking Water System at all times. The operator in charge had the valid level of certification required under Ontario Regulation 28/04 to operate the St. Pauls Drinking Water System as an operator in charge. All operators possessed the required certification. All operators possessed at the minimum a valid limited subsurface operators certificate as required under Ontario Regulation 28/04. Only certified operators made adjustments to the treatment equipment. Documentation provided from the operating authority for the inspection period indicated that adjustments to the water treatment equipment was only carried out by certified operators. Water Quality Monitoring All microbiological water quality monitoring requirements for distribution samples prescribed by legislation were being met. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 8 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

12 Ministry of the Environment and Climate Change Inspection Report Water Quality Monitoring In accordance with Ontario Regulation 70/03 Schedule -2, the operating authority of the St. Pauls Drinking Water System obtained at least one distribution sample every two weeks. Each sample was analyzed for E. coli, total coliform, and general bacterial population expressed as colony counts on a heterotrophic plate count (HPC). All distribution microbiological sample results during the inspection period were in compliance with Ontario Regulation 69/03. All inorganic water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-2 (3), the owner and operating authority shall ensure that inorganics samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Records indicate that the St. Pauls Drinking Water System collected and tested the parameters listed in Schedule 23 of Ontario Regulation 70/03 on June 29, 20, then on January, 206, which is 54 months and 3 days between sampling dates. Therefore, the owner and operating authority failed to collect and test for inorganic parameters 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). All sample results show that the treated water is within acceptable limits stated in Ontario Regulation 69/03. All organic water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-4 (3), the owner and operating authority shall ensure that organics samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Records indicate that the St. Pauls Drinking Water System collected and tested the parameters listed in Schedule 24 (organics) of Ontario Regulation 70/03 on June 29, 20, then on January, 206, which is 54 months and 3 days between sampling dates. Therefore, the owner and operating authority failed to collect and test for organic parameters 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). All sample results show that the treated water is within acceptable limits stated in Ontario Regulation 69/03. All haloacetic acid water quality monitoring requirements prescribed by legislation are being conducted within the required frequency and at the required location. In accordance with Ontario Regulation 70/03 Schedule 3-6., the owner and operating authority shall ensure that at least one distribution water sample that is likely to have an elevated potential for the formation of Haloacetic acids is collected and tested for Haloacetic acids each calendar quarter. Haloacetic Acid monitoring was completed on the following dates during the inspection period: January 3, 207, and April 3, 207. The samples were collected at the community centre, which is the furthest non-residential sample point in the distribution system. All trihalomethane water quality monitoring requirements prescribed by legislation were conducted within the required frequency and at the required location. In accordance with Ontario Regulation 70/03 Schedule 3-6, the owner and operating authority shall ensure that at least one distribution water sample that is likely to have an elevated potential for the formation of Trihalomethanes is collected and tested for Trihalomethanes each calendar quarter. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 9 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

13 Ministry of the Environment and Climate Change Inspection Report Water Quality Monitoring Trihalomethane monitoring was completed on the following dates during the inspection period: April 3, 206, July 4, 206, October 3, 206, January 3, 207, and April 3, 207. The samples were collected at the community centre, which is the furthest non-residential sample point in the distribution system. All sample results for this inspection period show that the distribution water is within acceptable limits for Trihalomethanes as listed in Ontario Regulation 69/03. All nitrate/nitrite water quality monitoring requirements prescribed by legislation were conducted within the required frequency for the DWS. In accordance with Ontario Regulation 70/03 Schedule 3-7, the owner and operating authority shall ensure that at least one treated water sample is collected and tested for Nitrate and Nitrite every three months. Nitrate and Nitrite monitoring was completed on the following dates during the inspection period: April 3, 206, July 4, 206, October 3, 206, January 3, 207, and April 3, 207. All sample results for this inspection period show that the distribution water is within acceptable limits for Nitrate and Nitrite as listed in Ontario Regulation 69/03. All sodium water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-8, the owner/operating authority shall ensure that Sodium samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Records indicate that the St. Pauls Drinking Water System collected and tested Sodium on January, 202 (23.0 mg/l) and reported the exceedance on January 6, 202. Since January, 202 no other Sodium exceedances have been reported, therefore the owner and operating authority failed to collect and test a Sodium sample 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). All fluoride water quality monitoring requirements prescribed by legislation were conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-9, the owner and operating authority shall ensure that at least one treated water sample is collected and tested for fluoride at least once every 60 months. Fluoride samples were collected on January, 206 with a result of.4 mg/l, therefore within the acceptable limit for Fluoride. Previously Fluoride was sampled on April 4, 204 with a result of.53 mg/l, which was reported on April 23, 204. As per Ontario Regulation 70/03 Schedule 3-9 and Schedule 6-. (7) the next required Fluoride sample shall be collected 90 days before or after April 4, 209. Records confirmed that chlorine residual tests were being conducted at the same time and at the same location that microbiological samples were obtained. Records submitted by the operating authority indicated that chlorine residuals are being collected at the same time and location as microbiological samples from the treatment plant and the water distribution system. The owner has fulfilled the requirements prescribed by Ontario Regulation 70/03 6-3() which requires a water sample be taken and tested for a microbiological parameter, the owner of the drinking water system and the operating authority for the system shall ensure that another sample is taken at the same time from the same location and is tested immediately for, (a) free chlorine residual, if the system provides chlorination and does not provide chloramination. Water Quality Assessment Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 0 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

14 Ministry of the Environment and Climate Change Inspection Report Records showed that all water sample results taken during the inspection review period did not exceed the values of tables, 2 and 3 of the Ontario Drinking Water Quality Standards (O.Reg. 69/03). There were no exceedances of the values of Tables, 2 and 3 of the Ontario Drinking Water Quality Standards (Ontario Regulation 69/03) during the inspection review period. Reporting & Corrective Actions Where required continuous monitoring equipment used for the monitoring of chlorine residual and/or turbidity triggered an alarm or an automatic shut-off, a qualified person responded in a timely manner and took appropriate actions. During the inspection period there were two alarms, which triggered the auto dialer to contact the operator on call. -September 24, Low chlorine alarm due to a signalling issue with the chlorine analyzer. -December 3, Low chlorine alarm due to a crack hose and clogged chlorine injector. All alarms were addressed within a reasonable time frame and appropriate actions were taken. Other Inspection Findings The following instance(s) of non-compliance were also noted during the inspection: ) As per Ontario Regulation 28/04 Section 27 (2) entries in the logs or other record-keeping mechanism shall be made chronologically. -On May 6, 206, a distribution chlorine residual was recorded into the daily rounds log sheet after the original date of the tested distribution chlorine residual. The operator transcribed the distribution chlorine residual from their personal log into the daily log sheet and made no comment regarding the late entry. The operators personal logs should be kept in a bound logbook with numbered pages. 2) As per Ontario Regulation 28/04 Section 27 (4) a person who makes an entry in a log or other record-keeping mechanism shall do so in a manner that permits the person to be unambiguously identified as the maker of the entry. -Numerous times during the inspection period entries were recorded in the alarm testing log with no operator identification recorded in the log. -As of May 3, 207, the operating authority revised the alarm testing log by adding an "Operator ID" column to ensure the operator making the entry can be identified. The following issues were also noted during the inspection: During the physical inspection, the exterior portion of the bypass discharge pipe did not have a screen installed. Installing a screen on the bypass discharge pipe is a recommended best management practice to prevent the entry of foreign material into the treatment system. The following items are noted as being relevant to the Drinking Water System: On June 6, 207, Jim Miller and Tyler Kelly collected SWIPENHANCED samples at the St. Pauls Drinking Water System. The samples were collected at the treated water sample tap within the St. Pauls pumphouse. The samples were sent from the MOECC London District Office via courier to the MOECC Lab located at 25 Resources Road, Etobicoke, Ontario, M9P 3V6 on June 6, 207 at approximately 5:00 hrs. On July 2, 207, the sample results were received and are located in appendix A of this report. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

15 Ministry of the Environment and Climate Change Inspection Report NON-COMPLIANCE WITH REGULATORY REQUIREMENTS AND ACTIONS REQUIRED This section provides a summary of all non-compliance with regulatory requirements identified during the inspection period, as well as actions required to address these issues. Further details pertaining to these items can be found in the body of the inspection report. All continuous analysers were not calibrated, maintained, and operated, in accordance with the manufacturer's instructions or the regulation. Schedule E, of the Municipal Drinking Water Licence Issue # 2 issued on April 2, 206 for the St. Pauls Drinking Water System states the requirements for the UV disinfection sensor checks and calibration. The owner/operating authority shall ensure the following is being conducted: ) Duty UV sensors shall be checked on at least a monthly basis against a reference UV sensor or at the frequency as otherwise recommended by the UV equipment manufacturer; 2) When comparing a duty UV sensor to a reference UV sensor, the calibration ratio (intensity measured with the duty UV sensor/intensity measured with the reference UV sensor) shall be less than or equal to.2; 3) If the calibration ratio is greater than.2, the duty UV sensor shall be replaced with a calibrated UV sensor or a UV sensor correction factor shall be applied while the problem with the UV sensor is being resolved; 4) Reference UV sensors shall be checked against a Master Reference Assembly at a minimum frequency of once every three years or on a more frequent basis depending upon the recommendations of the equipment manufacturer. Records provided by the operating authority indicated that the UV units have not been properly checked and calibrated as recommended by the UV equipment manufacturer (UV Pure) and as per the Municipal Drinking Water Licence during the inspection period. Also during the physical inspection a sensor check was performed by the operating authority using a Hallett Diagnostic Tool. The Hallett Diagnostic Tool was used to determine the transmittance and intensity of the duty UV sensor, but not checked against a reference UV sensor. Action(s) Required: In accordance with Schedule E, of the Municipal Drinking Water Licence Issue # 2 issued on April 2, 206 the owner/operating authority of the St. Pauls Drinking Water System shall ensure that duty UV sensor checks and calibrations are being conducted as recommended by the UV equipment manufacturer (UV Pure) and as per the Municipal Drinking Water Licence. The owner/operating authority shall provide a training session to the operators of the St. Pauls Drinking Water System on performing UV checks and calibrations as recommended by the UV manufacturer and the Municipal Drinking Water Licence. Documentation of training to the operators shall be submitted to Jim Miller of the Ministry of the Environment and Climate Change, London District Office by September 30, 207, to confirm that these items have been complied with. 2 All inorganic water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-2 (3), the owner and operating authority shall ensure that inorganics samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Records indicate that the St. Pauls Drinking Water System collected and tested the parameters listed in Schedule Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 2 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

16 Ministry of the Environment and Climate Change Inspection Report 23 of Ontario Regulation 70/03 on June 29, 20, then on January, 206, which is 54 months and 3 days between sampling dates. Therefore, the owner and operating authority failed to collect and test for inorganic parameters 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Action(s) Required: In accordance with Ontario Regulation 70/03, Schedule 3-2 (3), the owner/operating authority of the St. Pauls Drinking Water System shall ensure that a sample is taken and tested for every parameter set out in Schedule 23 of the regulation at least every 60 months as per the Ontario Regulation 70/03. The frequency of sampling and equipment checks as per Schedule 6-. (7) of Ontario Regulation 70/03 states "If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 60 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 60 month period for the purpose of being tested for that parameter is taken not more than 90 days before or after the fifth anniversary of the day a sample was taken for that purpose in the previous 60 month period." The owner/operating authority shall develop a sampling plan and review protocol to ensure compliance, and provide documentation (sample plan and protocol) to Jim Miller of the Ministry of the Environment and Climate Change, London District Office by August 3, 207, to confirm that this item has been complied with. 3 All organic water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-4 (3), the owner and operating authority shall ensure that organics samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Records indicate that the St. Pauls Drinking Water System collected and tested the parameters listed in Schedule 24 (organics) of Ontario Regulation 70/03 on June 29, 20, then on January, 206, which is 54 months and 3 days between sampling dates. Therefore, the owner and operating authority failed to collect and test for organic parameters 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Action(s) Required: In accordance with Ontario Regulation 70/03, Schedule 3-4 (3), the owner/operating authority of the St. Pauls Drinking Water System shall ensure that a sample is taken and tested for every parameter set out in Schedule 24 of the regulation at least every 60 months as per the Ontario Regulation 70/03. The frequency of sampling and equipment checks as per Schedule 6-. (7) of Ontario Regulation 70/03 states "If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 60 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 60 month period for the purpose of being tested for that parameter is taken not more than 90 days before or after the fifth anniversary of the day a sample was taken for that purpose in the previous 60 month period." The owner/operating authority shall develop a sampling plan and review protocol to ensure compliance, and provide documentation (sample plan and protocol) to Jim Miller of the Ministry of the Environment and Climate Change, London District Office by August 3, 207, to confirm that this item has been complied with. 4 All sodium water quality monitoring requirements prescribed by legislation were not conducted within the required frequency. In accordance with Ontario Regulation 70/03 Schedule 3-8, the owner/operating authority shall ensure that Sodium samples are collected and tested every 60 months with the frequency prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 3 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

17 Ministry of the Environment and Climate Change Inspection Report Records indicate that the St. Pauls Drinking Water System collected and tested Sodium on January, 202 (23.0 mg/l) and reported the exceedance on January 6, 202. Since January, 202 no other Sodium exceedances have been reported, therefore the owner and operating authority failed to collect and test a Sodium sample 90 days before or after the fifth anniversary of the last sample date as prescribed in Ontario Regulation 70/03 Schedule 6-. (7). Action(s) Required: In accordance with Ontario Regulation 70/03, Schedule 3-8, the owner/operating authority of the St. Pauls Drinking Water System shall ensure that a sample is taken and tested for Sodium at least every 60 months as per the Ontario Regulation 70/03. The frequency of sampling and equipment checks as per Schedule 6-. (7) of Ontario Regulation 70/03 states "If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 60 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 60 month period for the purpose of being tested for that parameter is taken not more than 90 days before or after the fifth anniversary of the day a sample was taken for that purpose in the previous 60 month period." The owner/operating Authority shall develop a sampling plan and review protocol to ensure compliance, and provide documentation (sample plan and protocol) to Jim Miller of the Ministry of the Environment and Climate Change, London District Office by August 3, 207 to confirm that this item has been complied with. 5 The following instance(s) of non-compliance were also noted during the inspection: ) As per Ontario Regulation 28/04 Section 27 (2) entries in the logs or other record-keeping mechanism shall be made chronologically. -On May 6, 206, a distribution chlorine residual was recorded into the daily rounds log sheet after the original date of the tested distribution chlorine residual. The operator transcribed the distribution chlorine residual from their personal log into the daily log sheet and made no comment regarding the late entry. The operators personal logs should be kept in a bound logbook with numbered pages. 2) As per Ontario Regulation 28/04 Section 27 (4) a person who makes an entry in a log or other record-keeping mechanism shall do so in a manner that permits the person to be unambiguously identified as the maker of the entry. -Numerous times during the inspection period entries were recorded in the alarm testing log with no operator identification recorded in the log. -As of May 3, 207, the operating authority revised the alarm testing log by adding an "Operator ID" column to ensure the operator making the entry can be identified. Action(s) Required: ) The owner/operating authority shall provide a training session to operators to ensure the operators are making entries in logs or other record-keeping mechanisms chorological order. Documentation of this training shall be provided to Jim Miller of the Ministry of the Environment and Climate Change, London District Office by September 30, 207, to confirm that this item has been complied with. 2) The owner/operating authority shall ensure that operators continue to properly identify entries into logs and other record-keeping mechanisms. No further actions are required. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 4 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

18 Ministry of the Environment and Climate Change Inspection Report SUMMARY OF RECOMMENDATIONS AND BEST PRACTICE ISSUES This section provides a summary of all recommendations and best practice issues identified during the inspection period. Details pertaining to these items can be found in the body of the inspection report. In the interest of continuous improvement in the interim, it is recommended that owners and operators develop an awareness of the following issues and consider measures to address them.. The following issues were also noted during the inspection: During the physical inspection, the exterior portion of the bypass discharge pipe did not have a screen installed. Installing a screen on the bypass discharge pipe is a recommended best management practice to prevent the entry of foreign material into the treatment system. Recommendation: As of June 7, 207, the operating authority installed a screen to the bypass discharge pipe. Photographs of the screened bypass discharge pipe were forwarded to Jim Miller of the Ministry of the Environment and Climate Change, London District Office. It is recommended that the operating authority periodically checks the integrity of the screen and replaces the screen if the integrity has been compromised. Report Generated for kellyty on 08/08/207 (dd/mm/yyyy) Page 5 of 6 Site #: Date of Inspection: 06/06/207 (dd/mm/yyyy)

19

20 Inspection Audit Sample Results Ministry of the Environment Drinking Water System Inspection Report Appendix A

21 APPENDIX TABLE AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF PARAMETERS EXCEEDING ODWQS Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units MC AO 2 3 OG SAMPLE # IRON / JUL-207 Page Module: d03_wb_swip.rdf

22 Shortforms: <T - A measurable trace amount; interpret with caution <W - No measurable response (zero) : < Reported value - No measurable response (zero) : < Reported value < - Actual result is less than reported value ND - Not detected!np - No appropriate procedure available NA - Result not available NS - Not sampled - Nanograms per litre - Micrograms per litre MG/L - Milligrams per litre 2-JUL-207 Page 2 Module: d03_wb_swip.rdf

23 Footnotes: Maximum Concentration as per O.Reg 69/03. 2 Aesthetic Objective. 3 Operational Guideline. 4 Includes alpha-chlordane, gamma-chlordane and Oxychlordane. 5 Includes p,p'-dde, o,p'-ddt, p,p'-ddd and p,p'ddt. a Total toxic equivalents when compared with 2,3,7,8,-TCDD (tetrachlorodibenzo-p-dioxin). b Where fluoride is added to drinking water, it is recommended that the concentration be adjusted to mg/l, the optimum level for control of tooth decay. Where supplies contain naturally occurring fluoride at levels higher than.5 mg/l but less than 2.4 mg/l the Ministry of Health and Long Term Care recommends an approach through local boards of health to raise public and professional awareness to control excessive exposure to fluoride from other sources. c This standard applies to water at the point of consumption. Since lead is a component in some plumbing systems, first flush water may contain higher concentrations of lead than water that has been flushed for five minutes. d Where both nitrate and nitrite are present, the total of the two should not exceed 0 mg/l (as nitrogen). e The standard is expressed as a running annual average of quarterly samples measured at a point reflecting the maximum residence time in the distribution system. f An aesthetic objective of 5 NTU for Turbidity has been set for all waters at the point of consumption. 2-JUL-207 Page 3 Module: d03_wb_swip.rdf

24 APPENDIX TABLE 4 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF CHEMICAL / PHYSICAL PARAMETERS - HEALTH RELATED Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units MC SAMPLE #,-DICHLOROETHENE 4,2-DICHLOROBENZENE 200,2-DICHLOROETHANE 5,4-DICHLOROBENZENE 5 2,3,4,6-TETRACHLOROPHENOL ,4,6-TRICHLOROPHENOL ,4-D ,4-DICHLOROPHENOL A-CHLORDANE ALACHLOR ALDRIN 700 ANTIMONY 6.8 +/-0.8 ARSENIC 25 +/-0.30 ATRAZINE 5000 ATRAZINE+DE-ALKYLATEDATRAZINE BARIUM /-3.00 BENZENE 5 BENZO(A)PYRENE 0 BORON /-3.00 BROMOXYNIL 5000 CADMIUM 5 0 +/-0.3 CARBARYL CARBOFURAN CARBON TETRACHLORIDE 5.2 CHLOROBENZENE 80 CHLOROETHENE 2 CHROMIUM 50. +/-0.34 DE-ETHYLATED ATRAZINE DICAMBA DICHLOROMETHANE 50.2 DICLOFOP-METHYL 9000 DIELDRIN DIQUAT 70.5 DIURON FLUORIDE MG/L.5 b.42 G-CHLORDANE GLYPHOSATE HEPTACHLOR 3000 HEPTACHLOR EPOXIDE LEAD 0 c 0 +/-0.6 MERCURY 00 5 METOLACHLOR JUL-207 Page 4 Module: d03_wb_swip.rdf

25 APPENDIX TABLE 4 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF CHEMICAL / PHYSICAL PARAMETERS - HEALTH RELATED Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units MC SAMPLE # METRIBUZIN NITROGEN; NITRATE+NITRITE MG/L 0 d.036 <T NITROGEN; NITRITE MG/L d.00 OP-DDT OXYCHLORDANE PARAQUAT 0.5 PCB; TOTAL PENTACHLOROPHENOL PICLORAM PP-DDD PP-DDE PP-DDT PROMETRYNE 000 SELENIUM 0.2 +/-0.50 SIMAZINE TETRACHLOROETHENE 30 TRIALLATE TRICHLOROETHENE 5 TRIFLURALIN TRIHALOMETHANES; TOTAL 00 e 6 URANIUM /-0.8 VINYL CHLORIDE 2 Shortforms: <T - A measurable trace amount; interpret with caution <W - No measurable response (zero) : < Reported value - No measurable response (zero) : < Reported value < - Actual result is less than reported value ND - Not detected!np - No appropriate procedure available NA - Result not available NS - Not sampled - Nanograms per litre - Micrograms per litre MG/L - Milligrams per litre 2-JUL-207 Page 5 Module: d03_wb_swip.rdf

26 Footnotes: Maximum Concentration as per O.Reg 69/03. 2 Aesthetic Objective. 3 Operational Guideline. 4 Includes alpha-chlordane, gamma-chlordane and Oxychlordane. 5 Includes p,p'-dde, o,p'-ddt, p,p'-ddd and p,p'ddt. a Total toxic equivalents when compared with 2,3,7,8,-TCDD (tetrachlorodibenzo-p-dioxin). b Where fluoride is added to drinking water, it is recommended that the concentration be adjusted to mg/l, the optimum level for control of tooth decay. Where supplies contain naturally occurring fluoride at levels higher than.5 mg/l but less than 2.4 mg/l the Ministry of Health and Long Term Care recommends an approach through local boards of health to raise public and professional awareness to control excessive exposure to fluoride from other sources. c This standard applies to water at the point of consumption. Since lead is a component in some plumbing systems, first flush water may contain higher concentrations of lead than water that has been flushed for five minutes. d Where both nitrate and nitrite are present, the total of the two should not exceed 0 mg/l (as nitrogen). e The standard is expressed as a running annual average of quarterly samples measured at a point reflecting the maximum residence time in the distribution system. f An aesthetic objective of 5 NTU for Turbidity has been set for all waters at the point of consumption. 2-JUL-207 Page 6 Module: d03_wb_swip.rdf

27 ADVERSE RESULTS OF A DRINKING-WATER TEST UNDER O.REG. 70/03 According to section 6-3 of O.Reg. 70/03,the following are prescribed as adverse results of a drinking-water test for the purpose of section 8 of the Safe Drinking Water Act 2002:. A result that exceeds any of the standards prescribed by Schedule, 2 or 3 to the Ontario Drinking-Water Quality Standards, other than the standard for fluoride, if the result is from a sample of drinking water. 2. A result indicating the presence of Aeromonas spp., Pseudomonas aeruginosa, Staphylococcus aureus, Clostridium spp. or fecal streptococci (Group D streptococci) in a sample of drinking water. 3. A result indicating the presence of a pesticide not listed in Schedule 2 to the Ontario Drinking-Water Quality Standards in a sample of drinking water, at any concentration. 4. If the drinking-water system is required to provide secondary disinfection in accordance with section -5 of Schedule or section 2-5 of Schedule 2, the system provides chlorination, the system does not provide chloramination and a report under subsection 8() of the Act has not been made in respect of free chlorine residual in the preceding 24 hours, a result indicating that the concentration of free chlorine residual in the preceding 24 hours, a result indicating that the concentration of free chlorine residual is less than 0 milligrams per litre in, i. a distribution sample that is a grab sample, or ii. two distribution samples that are tested by continuous monitoring equipment, if the two samples were taken 5 minutes or more apart and the later of the two samples was the first sample that was taken 5 minutes or more after the earlier sample. 5. If the drinking -water system is required to provide secondary disinfection in accordance with section -5 of Schedule or section 2-5 of Schedule 2, the system provides chloramination and a report under subsection 8() of the Act has not been made in respect of combined chlorine residual in the preceding 24 hours, a result indicating that the concentration of combined chlorine residual is less than 0.25 milligrams per litre and the concentration of free chlorine residual is less than 0 milligrams per litre in, i. a distribution sample that is a grab sample, or ii. two distribution samples that are tested by continuous monitoring equipment, if the two samples were taken 5 minutes or more apart and the later of the two samples was the first sample that was taken 5 minutes or more after the earlier sample. 6. If the drinking-water system is required to provide filtration and a report under subsection 8 () of the Act has not been made in respect of turbidity in the preceding 24 hours, a result indicating that turbidity exceeds.0 Nephelometric Turbidity Units (NTU) in, i. a grab sample of water taken from a filter effluent line, or ii. two samples of water from a filter effluent line that are tested by continuous monitoring equipment, if, A. two samples were taken 5 minutes or more apart and the later of the two samples was the first sample that was taken 5 minutes or more after the earlier sample, and B. the filter effluent line is directing water to the next stage of the treatment process. 7. If an approval or order, including an OWRA order, identifies a parameter as a health-related parameter and establishes a maximum concentration for the parameter, a result indicating that the parameter exceeds the maximum concentration in a sample of drinking water. 8. A result indicating that the concentration of sodium exceeds 20 milligrams per litre in a sample of drinking water, if a report under subsection 8 () of the Act has not been made in respect of sodium in the preceding 60 months. 9. A result indicating that the concentration of fluoride exceeds.5 milligrams per litre in a sample of drinking water, if, i. the drinking-water system provides fluoridation and a report under subsection 8 () of the Act has not been made in respect of fluoride in the preceding 24 hours, or ii. the drinking-water system does not provide fluoridation and a report under subsection 8 () of the Act has not been made in respect of fluoride in the preceding 60 months. 2-JUL-207 Page 7 Module: d03_wb_swip.rdf

28 APPENDIX TABLE 5 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF MICRO, CHEMICAL / PHYSICAL PARAMETERS - NOT HEALTH RELATED Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units OBJECTIVE TYPE OF OBJECTIVE SAMPLE #,2-DICHLOROBENZENE 3 AO,4-DICHLOROBENZENE AO 2,3,4,6-TETRACHLOROPHENOL 000 AO 2,4,6-TRICHLOROPHENOL 2000 AO 2,4-DICHLOROPHENOL 300 AO. ALUMINUM 00 OG 2.2 +/-0.50 CHLOROBENZENE 30 AO COPPER 000 AO.4 +/-0.20 ETHYLBENZENE 2.4 AO IRON 300 AO 390 +/-0.00 MANGANESE 50 AO 4 +/-0.40 PENTACHLOROPHENOL AO TOLUENE 24 AO ZINC 5000 AO +/-0.49 Shortforms: <T - A measureable trace amount; interpret with caution <W - No measurable response (zero). <Reported value - No measurable response (zero). <Reported value < - Actual result is less than reported value ND - Not detected NA - Result not available NS - Not sampled DEG - Degree celsius AO - Aesthetic Objective OG - Operational Guideline FTU = NTU - Nephelometric Turbidity Unit TCU - True Colour Units - Nanograms per litre - Micrograms per litre MG/L - Milligrams per litre 2-JUL-207 Page 8 Module: d03_wb_swip.rdf

29 Footnotes: a Organic Nitrogen = (Total Kjeldahl Nitrogen - (Ammonia + Ammonium)) b The aesthetic objective for sodium in drinking water is 200 mg/l. The local Medical Officer of Health should be notified when the sodium concentration exceeds 20 mg/l so that this information may be communicated to local physicians for their use with patients on sodium restricted diets. c When sulphate levels exceed 500 mg/l, water may have a laxative effect on some people. d Applicable for all water at the point of consumption. 2-JUL-207 Page 9 Module: d03_wb_swip.rdf

30 APPENDIX TABLE 6 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF PARAMETERS WITH NO ODWQS Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units SAMPLE #,,-TRICHLOROETHANE,,2,2-TETRACHLOROETHANE.2,,2-TRICHLOROETHANE.,-DICHLOROETHANE,2,3,4-TETRACHLOROBENZENE,2,3,5-TETRACHLOROBENZENE 2,2,3-TRICHLOROBENZENE 5,2,4,5-TETRACHLOROBENZENE,2,4-TRICHLOROBENZENE 5,2-DIBROMOETHANE.,2-DICHLOROPROPANE,3,5-TRICHLOROBENZENE 5,3-DICHLOROBENZENE -METHYLNAPHTHALENE 0 2,3,4,5-TETRACHLOROPHENOL 2,3,4-TRICHLOROPHENOL 2,3,6-TRICHLOROTOLUENE 5 2,4,5-TRICHLOROPHENOL 2,4,5-TRICHLOROTOLUENE 5 2,4-D-PROPIONIC ACID 2,4-DB 2,6-DICHLOROBENZYL CHLORIDE 0 2-METHYLNAPHTHALENE 0 A-BHC (HEXACHLOROCYCLOHEXANE) ACENAPHTHENE 0 ACENAPHTHYLENE 0 AMETRYNE AMINOMETHYLPHOSPHONIC ACID 5 ANTHRACENE 0 ATRATONE B-BHC (HEXACHLOROCYCLOHEXANE) 2 BARBAN 5 BENZ(A)ANTHRACENE 20 BENZO(A)ANTHRACENE 20 BENZO(B)FLUORANTHENE 0 BENZO(E)PYRENE 0 BENZO(G,H,I)PERYLENE 20 BENZO(K)FLUORANTHENE 0 BERYLLIUM 0 +/-0.25 BROMODICHLOROMETHANE.4 <T 2-JUL-207 Page 0 Module: d03_wb_swip.rdf

31 APPENDIX TABLE 6 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF PARAMETERS WITH NO ODWQS Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter Units SAMPLE # BROMOFORM.5 BUTACHLOR. BUTYLATE CHLORMEQUAT CHLOROBROMURON.5 CHLOROFORM 5.6 CHLOROTOLURON.5 CHLORPROPHAM CHRYSENE 0 CIS-,2-DICHLOROETHENE CIS-,3-DICHLOROPROPENE COBALT 0 +/-0.8 CYPERQUAT. DIALLATE DIBENZ(A,H)ANTHRACENE 20 DIBENZO(A,H)ANTHRACENE 20 DIBROMOCHLOROMETHANE.2 DICHLOROACETONITRILE.5 DIFENOXURON.5 DIFENZOQUAT DIISOPROPYLETHER ENDOSULPHAN I 2 ENDOSULPHAN II 5 ENDOSULPHAN SULPHATE 5 ENDRIN 5 EPTAM FLUOMETURON.5 FLUORANTHENE 0 FLUORENE 0 GLUFOSINATE 2 HEXACHLOROBENZENE HEXACHLOROBUTADIENE HEXACHLOROETHANE INDENO(,2,3-C,D)PYRENE 20 LINURON MCPA,4CL2MEPHENOXY-ACETICACID MCPB,4CL2MEPHENOXY-BUTYRICACID. MCPP,2-4CL2MEPHENOXY-PROPACID MEPIQUAT METOBROMURON.5 2-JUL-207 Page Module: d03_wb_swip.rdf

32 APPENDIX TABLE 6 AUDIT SAMPLE RESULTS - 06-JUN-207 SUMMARY OF PARAMETERS WITH NO ODWQS Sample Legend: Sample # - TREATED ST. PAULS WS POE Parameter METOXURON MIREX MOLYBDENUM MONOLINURON MONURON NAPHTHALENE NEBURON NICKEL NITROGEN; AMMONIA+AMMONIUM OCTACHLOROSTYRENE PENTACHLOROBENZENE PERYLENE PHENANTHRENE PHOSPHORUS; PHOSPHATE PROMETONE PROPAZINE PROPHAM PROPOXUR PYRENE SIDURON SILVER SILVEX STRONTIUM STYRENE TERBUTRYNE TERT-BUTYL METHYL ETHER THALLIUM TITANIUM TRANS-,2-DICHLOROETHENE TRANS-,3-DICHLOROPROPENE VANADIUM Units MG/L MG/L SAMPLE # / / / /-0.7 <T +/-0. +/ / JUL-207 Page 2 Module: d03_wb_swip.rdf

33 Shortforms: <T - A measurable trace amount; interpret with caution <W - No measurable response (zero) : < Reported value - No measurable response (zero) : < Reported value < - Actual result is less than reported value ND - Not detected!np - No appropriate procedure available NA - Result not available NS - Not sampled - Nanograms per litre - Micrograms per litre MG/L - Milligrams per litre 2-JUL-207 Page 3 Module: d03_wb_swip.rdf

34 NO DATUM FOUND FOR THE FOLLOWING TABLE(S): -TABLE 2 - SUMMARY OF PARAMETERS EXCEEDING HALF OF THEIR HEALTH-RELATED ODWQS -TABLE 3 - SUMMARY OF MICROBIOLOGICAL PARAMETERS - HEALTH RELATED 2-JUL-207 Page 4 Module: d03_wb_swip.rdf

35 Stakeholder References Ministry of the Environment Drinking Water System Inspection Report Appendix B

36 Key Reference and Guidance Material for Municipal Residential Drinking Water Systems Many useful materials are available to help you operate your drinking water system. Below is a list of key materials owners and operators of municipal residential drinking water systems frequently use. To access these materials online click on their titles in the table below or use your web browser to search for their titles. Contact the Public Information Centre if you need assistance or have questions at / or pic .moe@ontario.ca. For more information on Ontario s drinking water visit and drinking.water@ontario.ca to subscribe to drinking water news. PUBLICATION TITLE Taking Care of Your Drinking Water: A Guide for Members of Municipal Councils FORMS: Drinking Water System Profile Information, Laboratory Services Notification, Adverse Test Result Notification Form Procedure for Disinfection of Drinking Water in Ontario Strategies for Minimizing the Disinfection Products Trihalomethanes and Haloacetic Acids Total Trihalomethane (TTHM) Reporting Requirements Technical Bulletin (February 20) PUBLICATION NUMBER 7889e0 749e, 5387e, 4444e 4448e0 752e 825e Filtration Processes Technical Bulletin 7467 Ultraviolet Disinfection Technical Bulletin 7685 Guide for Applying for Drinking Water Works Permit Amendments, Licence Amendments, Licence Renewals and New System Applications Certification Guide for Operators and Water Quality Analysts Guide to Drinking Water Operator Training Requirements Taking Samples for the Community Lead Testing Program Community Sampling and Testing for Lead: Standard and Reduced Sampling and Eligibility for Exemption 704e0 9802e 6560e0 7423e Guide: Requesting Regulatory Relief from Lead Sampling Requirements 660 Drinking Water System Contact List Technical Support Document for Ontario Drinking Water Quality Standards 728e 4449e0 March 205 ontario.ca/drinkingwater PIBS 8990b0

37 Principaux guides et documents de référence sur les réseaux résidentiels municipaux d eau potable De nombreux documents utiles peuvent vous aider à exploiter votre réseau d eau potable. Vous trouverez ci-après une liste de documents que les propriétaires et exploitants de réseaux résidentiels municipaux d eau potable utilisent fréquemment. Mars 205 Pour accéder à ces documents en ligne, cliquez sur leur titre dans le tableau ci-dessous ou faites une recherche à l aide de votre navigateur Web. Communiquez avec le Centre d information au public au ou au , ou encore à pic .moe@ontario.ca si vous avez des questions ou besoin d aide. TITRE DE LA PUBLICATION Pour plus de renseignements sur l eau potable en Ontario, consultez le site eaupotable ou envoyez un courriel à drinking.water@ontario.ca pour suivre l information sur l eau potable. NUMÉRO DE PUBLICATION Prendre soin de votre eau potable Un guide destiné aux membres des conseils municipaux Renseignements sur le profil du réseau d eau potable, Avis de demande de services de laboratoire, Formulaire de communication de résultats d analyse insatisfaisants et du règlement des problèmes Marche à suivre pour désinfecter l eau potable en Ontario Strategies for Minimizing the Disinfection Products Thrihalomethanes and Haloacetic Acids (en anglais seulement) Total Trihalomethane (TTHM) Reporting Requirements: Technical Bulletin (février 20) (en anglais seulement) Filtration Processes Technical Bulletin (en anglais seulement) 7467 Ultraviolet Disinfection Technical Bulletin (en anglais seulement) 7685 Guide de présentation d une demande de modification du permis d aménagement de station de production d eau potable, de modification du permis de réseau municipal d eau potable, de renouvellement du permis de réseau municipal d eau potable et de permis pour un nouveau réseau Guide sur l accréditation des exploitants de réseaux d eau potable et des analystes de la qualité de l eau de réseaux d eau potable Guide sur les exigences relatives à la formation des exploitants de réseaux d eau potable Prélèvement d échantillons dans le cadre du programme d analyse de la teneur en plomb de l eau dans les collectivités Échantillonnage et analyse du plomb dans les collectivités : échantillonnage normalisé ou réduit et admissibilité à l exemption Guide: Requesting Regulatory Relief from Lead Sampling Requirements (en anglais seulement) 660 Liste des personnes-ressources du réseau d eau potable Document d aide technique pour les normes, directives et objectifs associés à la qualité de l eau potable en Ontario 7889f0 749f, 5387f, 4444f 4448f0 752e 825e 704f0 9802f 6560f0 7423f 728f 4449f0 ontario.ca/eaupotable PIBS 8990b0

38 Ministry of the Environment Drinking Water System Inspection Report Appendix C Inspection Rating Record and Inspection Risk Methodology

39 April 202 APPLICATION OF THE RISK METHODOLOGY USED FOR MEASURING MUNICIPAL RESIDENTIAL DRINKING WATER SYSTEM INSPECTION RESULTS The Ministry of the Environment (MOE) has a rigorous and comprehensive inspection program for municipal residential drinking water systems (MRDWS). Its objective is to determine the compliance of MRDWS with requirements under the Safe Drinking Water Act and associated regulations. It is the responsibility of the municipal residential drinking water system owner to ensure their drinking water systems are in compliance with all applicable legal requirements. This document describes the risk rating methodology, which has been applied to the findings of the Ministry s MRDWS inspection results since fiscal ontario.ca/drinkingwater PIBS 6797e year The primary goals of this assessment are to encourage ongoing improvement of these systems and to establish a way to measure this progress. MOE reviews the risk rating methodology every three years. The Ministry s Municipal Residential Drinking Water Inspection Protocol contains up to 4 inspection modules and consists of approximately 20 regulatory questions. Those protocol questions are also linked to definitive guidance that ministry inspectors use when conducting MRDWS inspections.