NITIN CORPORATION. 402, 4 th Floor, Bezzola Commercial Complex, V.N. Purav Marg, Sion Trombay Road, Chembur, Mumbai , India.

Size: px
Start display at page:

Download "NITIN CORPORATION. 402, 4 th Floor, Bezzola Commercial Complex, V.N. Purav Marg, Sion Trombay Road, Chembur, Mumbai , India."

Transcription

1 402, 4 th Floor, Bezzola Commercial Complex, V.N. Purav Marg, Sion Trombay Road, Chembur, Mumbai , India. WEB : E MAIL : enquiry@corponit.com nitincorporation@yahoo.com FAX : PH (O) : / MW NEW BAGASSE FIRED POWER PLANT AVAILABLE FOR IMMEDIATE SALE Technical Details: Turbine and Accessories Turbogenerator Hangzhou Steam Turbine Co. - China Nanyang Explosion Protection Group Co. Ltd. - China Capacity MW. Design Triple extraction cum condensing Steam inlet parameters Extraction Steam flow at Normal condition 9 ata 5 TPH 3 ata 30 TPH Power Generation at Extraction Mode MW 105 ata and 510 Deg. C. ( But the Turbine was designed for 540 Deg C) 9 ata, 20 ata extraction-uncontrolled extraction 3 ata - controlled extraction Power Generation in Condensing Mode Boiler Capacity Type MW Cethar Vessels (P) Ltd. - Thiruchirapalli 110 TPH CFBC - 1 -

2 Feed water inlet temperature Steam outlet parameters 210 Deg.C. 108 ata and Deg.C at the main steam stop valve outlet. Cooling Tower Paharpur Cooling Tower LTD - Cul Capacity per cell 3000 Cu.m/hr No. of cell operating / standby Two (2) Hot water temperature 42 Deg.C Cold water temperature 32 Deg.C Design ambient Wet bulb 27 Deg.C temperature Water Treatment Plant Capacity Solid contact clarifier flow rate Multigrade Filter flow rate Weak Acid cation exchanger flow rate UF permeate flow rate RO plant flow rate Permeate output Cation and Anion exchanger flow rate Mixed bed system flow rate Dense Phase Ash Handling System Designed for Pneumatic handling system for DOSHION LIMITED 39 M3/hr 220 cu.m/hr. 65 cu.m 65 cu.m. 65 cu.m/hr. 39 cu.m./hr. 780 cu.m./day in 20 hrs. 39 cu.m./hr with an OBR of 780 cu.m in 20-4 cycle of operation. 39 cu.m./hr. with an OBR of 5460 cu.m Macawber Beekay Pvt Ltd - New Delhi 1 x 110 TPH CFBC Bed ash cooler, Economiser, Air Pre-Heaters and ESP hoppers Fuel & Ash Handling System TECPRO SYSTEMS LIMITED BELT CONVEYOR B-1 COAL BELT CONVEYOR CBC-1 COAL BELT CONVEYOR CBC-2 COAL BELT CONVEYOR CBC-3 COAL BELT CONVEYOR CBC-4-2 -

3 COAL BELT CONVEYOR CBC-5 COAL BELT CONVEYOR CBC-6 SLAT CHAIN CONVEYOR SC-2 SLAT CHAIN ELEVATOR (TC-1) SLAT CHAIN ELEVATOR (TC-2) LT Package ABB Ltd LT Package Consist of PCC Section - 1 PCC Section - 2 Boiler MCC (MCC-1) Boiler Valve Distribution MCC - I (MCC-2) Boiler Valve Distribution MCC - II (MCC-3) Soot Blower (MCC-4) ESP MCC (MCC-5) TG MCC (MCC-6) RO Plant MCC - I (MCC-7 ) RO Plant MCC - II (MCC-8 ) Auxiliary MCC ( MCC-9 ) Water System MCC ( MCC-10 ) Bagasse & Ash Handling System MCC (MCC-11 ) Coal Handling System MCC (MCC-12 ) Air Conditioning System MCC ( MCC - 13) Main Lighting Distirbution Board BFP Change over Panel VFD Package ABB Ltd Boiler Feed Pump - ( 600 kw, Type-I (ACB 3 Nos VFD), Drive Model ACS Nos ID Fan - (275 kw, Type-II (VFD with Standby) Drive Model ACS MCW Pump ( 250 kw, Type-II (VFD with 3 Nos Standby) Drive Model ACS Nos PA Fan ] ( 250 kw, Type-II (VFD with Standby) Drive Model ACS Nos SA Fan ( 160 kw, Type-II (VFD with Standby - 3 -

4 2 Nos 2 Nos drive ) Drive Model ACS Cooling Tower Fan ( 55 kw, Type-II (VFD with Standby drive and Drive Model ACS Air Compressor ( 55 kw, Type-II (VFD with Standby) , Sheet 07 of 11, Rev.1 ) Drive Model ACS /11 KV Sub-Station System Voltage Highest system voltage Power frequency withstand capability Basic insulation level Creepage distance for insulators Distributed Digital Control System - DCS Provided for ABB Ltd 110 kv rms 123 kv rms 230 kv rms 550 kv peak 25 mm/kv YOKOGAWA INDIA LTD Boiler, Turbine, Generator and its auxiliaries, Balance of plant, RO plant, compressor, electrical breakers etc. Transformers Generator Transformer 1 no Maximum Continuos Rating (MVA) at ONAN/ONAF HV 25/31.5 LV 25/31.5 Rated Voltage HV Winding 110 LV Winding 11 Converter Transformer Maximum Continuos Rating (MVA) at ONAN/ONAF 1 no - 4 -

5 HV 4.00 LV 2.00/2.00 Rated Voltage HV Winding 11 LV Winding 0.433/0.433 Compressor for each compressor Suction Pressure Suction Temperature Discharge Pressure at Air Drier Outlet Kirloskar Pneumatic Company Limited 450 Ncum/hr Kg/Sq.cm Minimum : 25 Deg.C Maximum : 41 Deg.C Average : 30 Deg.C Design : 40 Deg.C 7 Kg/Sq.cm.(g) at 100% capacity The compressor reciprocating, non-lubricated, horizontal, double acting, two stage compressor assembly with belt drive and slide rails. The compressor is water cooled from external source. (Both Working) TEFC squirrel cage, energy efficient, electric motors suitable for VFD as well as DOL starter. Air receiver of capacity 2 cu.m with foundation bolts, timer operated auto drain valve with bypass arrangement, pressure gauge, temperature gauge, pressure switches, safety valve etc. Refrigerated type air dryer with evaporator, capillary tube, Hot gas bypass valve, filter / dryer, condenser, compressor, accumulator, water separator with drain and other accessories. Cooling Tower make up water Pump KSB Model CPK GC End Suction Raw Water Temperature 40 Deg.C - 5 -

6 120 Deg.C 122 Cu.M/hr 136 Cu.M/hr KSB 3 Nos. Model CPK C End Suction DM Water Temperature 40 Deg.C 120 Deg.C 27 Cu.M/hr 30 Cu.M/hr VERTICAL TURBINE PUMPS Service Model / Size Temperature Service Model / Size Temperature Service 2 W + 1 S 1 W + 1 S Condenser Main circulating water pump WPIL C30TC Vertical Turbine Water 34 Deg.C 90 Deg.C 2376 Cu.M/hr 2640 Cu.M/hr Auxiliary cooling water pump WPIL C18TC Vertical Turbine Water 34 Deg.C 90 Deg.C 648 Cu.M/hr 720 Cu.M/hr Raw water Transfer pump WPIL - 6 -

7 Model / Size Temperature 1W + 1 S GM12TC Vertical Turbine Water 34 Deg.C 90 Deg.C 216 Cu.M/hr 240 Cu.M/hr Piping System 1 lot UNITECH MACHINES LIMITED Piping system & appurtenances, tanks & vessels and thermal insulation - 7 -