1 ALDERWOOD WATER & WASTEWATER DISTRICT SNOHOMISH COUNTY, WASHINGTON RESOLUTION NO A RESOLUTION of the Board of Commissioners of the Alderwood Water and Wastewater District, Snohomish County, Washington, establishing a written Cross-Connection Control Progra'm, and repealing Resolution No WHEREAS, it is the water purveyor's responsibility to provide water to the consumer that meets Washington State water quality standards; and WHEREAS, it is the water purveyor's responsibility to prevent the contamination of the public water supply system; and WHEREAS, cross-connections within the consumer's plumbing system pose a potential source of contamination of the public water supply system; and WHEREAS, pursuant to WAC and other state laws and regulations, the District, the consumer, the Washington State Department of Health, and the local authority having jurisdiction over enforcement of the Uniform Plumbing Code, as adopted in Washington, each have responsibilities relating to controlling crossconnections; and WHEREAS, pursuant to WAC , the District desires to provide a clear and uniform policy regarding these responsibilities and the District's enforcement of such policy; NOW, THEREFORE, BE IT RESOLVED that the Board of Commissioners of the Alderwood Water & Wastewater District, Snohomish County, Washington, establishes the following water service connection policy to protect the public water supply system from the risk of contamination from consumer water systems. For public health and safety, this policy shall apply equally to all new and existing consumers. AWWD Resolution No , - December 20,2010

2 DEFINITIONS: "Approved air gap" means a physical separation between the free-flowing end of a potable water supply pipeline and the overflow rim of an open or nonpressurized receiving vessel. "Approved backflow preventer" means an approved air gap, an approved backflow prevention assembly, or an approved AVB. The terms "approved backflow preventer," "approved air gap," or "approved backflow prevention assembly" refer only to those approved backflow preventers relied upon by the purveyor for the protection of the public water system. The requirements of WAC do not apply to backflow preventers installed for other purposes. "Approved backflow prevention assembly" means an RPBA, RPDA, DCVA, DCDA, PVBA, or SVBA of make, model, and size that is approved by the department. Assemblies that appear on the current approved backflow prevention assemblies list developed by the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research or other entity acceptable to the department are considered approved by the department. "Authority having jurisdiction" (formerly known as local administrative authority) means the local official, board, department, or agency authorized to administer and enforce the provisions of the Uniform Plumbing Code as adopted under chapter RCW. "Backflow" means the undesirable reversal of flow of water or other substances through a cross-connection into the public water system or consumer's potable water system. "Board of Commissioners" or "The Board" means those people elected to oversee the affairs of the Alderwood Water & Wastewater District. "Consumer" means any person receiving water from a public water system from either the meter, or the point where the service line connects with the distribution system if no meter is present. For purposes of cross-connection control, "consumer" means the owner or operator of a water system connected to a public water system through a service connection. "Consumer's water system," as used in WAC , means any potable or industrial water system that begins at the point of delivery from the public water system and is located on the consumer's premises. The consumer's water system includes all auxiliary sources of supply, storage, treatment, and distribution facilities, piping, plumbing, and fixtures under the control of the consumer. "Cross-connection" means any actual or potential physical connection between a public water system orthe consumer's water system and any source of nonpotable liquid, solid, or gas that could contaminate the potable water supply by backflow. AWWD Resolution No December 20,2010

3 "Cross-connection control program" means the administrative and technical procedures the purveyor implements to protect the public water system from contamination via cross-connections as required in WAC "Cross-connection control specialist" means a person holding a valid CCS certificate issued under chapter WAC. "Distribution system" hleans all piping components of a public water system that serve to convey water from transmission mains linked to source, storage and treatment facilities to the consumer excluding individual services. "Domestic water service connection" means a service hookup to a property that is contiguous to a water distribution main and where additional distribution mains or extensions are not needed to provide service. "Emergency" means an unforeseen event that causes damage or disrupts normal operations and requires immediate action to protect public health and safety. "High health cross-connection hazard" means a cross-connection involving any substance that could impair the quality of potable water and create an actual public health hazard through injury, poisoning, or spread of disease. "In-premises protection" means a method of protecting the health of consumers served by the consumer's potable water system, located within the property lines of the consumer's premises by the installation of an approved air gap or backflow prevention assembly at the point of hazard, which is generally a plumbing fixture. "Potable" means water suitable for drinking by the public. "Premises isolation" means a method of protecting a public water system by installation of approved air gaps or approved backflow prevention assemblies at or near the service connection or alternative location acceptable to the purveyor to isolate the consumer's water system from the purveyor's distribution system. "Public water supply system" shall mean any system providing water for human consumption through pipes or other constructed conveyances, excluding a system serving only one single-family residence and a system with four or fewer connections all of which serve residenc<?,s on the same farm. "Risk assessment investigation" means on-site inspection of a public water system by the department or designee to address a potential public health concern, regulatory violation, or consumer complaint. "Service connection" means a connection to a public water system designed to provide potable water to a single family residence, or other residential or nonresidential population. When the connection provides water to a residential population without AWWD Resolution No December 20,2010

4 clearly defined single family residences, the following formulas shall be used in determining the number of services to be included as residential connections on the WFI form. "Severe health cross-connection hazard" means a cross-connection which could impair the quality of potable water and create an immediate, severe public health hazard through poisoning or spread of disease by contaminants from radioactive material processing plants, nuclear reactors, or wastewater treatment plants. "Source water" means untreated water that is not subject to recontamination by surface runoff. "Uniform Plumbing Code (UPC)" means the code adopted under RCW (4) and implemented under chapter WAC. This code establishes statewide minimum plumbing standards applicable within the property lines of the consumer's premises. ABBREVIATIONS "AG" means Air Gap "AVB" means Atmospheric Vacuum Breaker "CCS" means Cross Connection Control Specialist "DCDA" means Double Check Detector Assembly "DCVA" means Double Check Valve Assembly "DOH" means Department of Health "PVBA" means Pressure Vacuum Breaker Assembly "PWS" means Public Water System "RPBA" means Reduced Pressure Backflow Assembly "RPDA" means Reduced Pressure Detector Assembly "SVBA" means Spill Resistant Vacuum Breaker Assembly "WAC" means Washington Administrative Code "WQD" Water Quality Department AWWD Resolution No December 20, 2010

5 PREVENTION OF CONTAMINATION: 1. Purpose. The purpose of the District's cross-connection control program is to protect the public water system from contamination via cross-connections and to comply with the requirements of WAC Consumer Responsibilities. The consumer is responsible for its water system, which consists of all plumbing located on the consumer's property, beginning at the downstream end of the service connection or water meter located on the public right-of-way or a District-held easement. 3. District Obligations. The District is not responsible for eliminating or controlling cross-connections within the consumer's water system. Pursuant to WAC the District's responsibility for cross-connection control begins at the water supply source and includes all the public water treatment, storage, and distribution facilities, and ends at the point of delivery to the consumer's water system. To prevent contamination of the public water system from crossconnections located on consumers' property, the District shall implement and promulgate a premises isolation cross-connection control program that includes the criteria listed in attached Exhibit A. This program shall ensure that crossconnections between the distribution system and a consumer's water system are eliminated or controlled by the installation of an approved backflow preventer commensurate with the degree of hazard. This may be accomplished by premises isolation or both premises isolation and in-premises protection, as defined in as defined in WAC Enforcement. The District shall take appropriate corrective action when a crossconnection exists that is not controlled commensurate to the degree of hazard assessed by the District or when a consumer fails to comply with the District's requirements regarding the installation, inspection, testing, maintenance, repair or replacement of approved backflow preventers required by this Resolution. a. The District may, among other things: AWWD Resolution No December 20,2010

6 (i) (ii) (iii) Require the consumer to install an approved backflow preventer for premises isolation commensurate with the degree of hazard; or Install, at the consumer's expense, an approved backflow preventer for premises isolation commensurate with the degree of hazard; or Deny or discontinue water service to a consumer's premises u'ntil the cross-connection hazard is eliminated or controlled to the satisfaction of the District. Except in the event of an emergency, the District shall notify the authority having jurisdiction prior to denying or discontinuing water service to a consumer's premises for one or more of the reasons listed above. b. Upon identification of a cross-connection exists that is not controlled commensurate to the degree of hazard, the District will notify the customer by mailing a letter substantially in the form of Exhibit B. c. Upon determination that a consumer fails to comply with the District's requirements regarding the installation, inspection, testing, maintenance or repair of approved backflow preventers, the District will notify the customer by mailing a letter substantially in the form of Exhibit C. d. If, after being notified pursuant to Paragraphs 4.b and 4.c above, the customer fails to correct the deficiency, then the District will give the consumer and the authority having jurisdiction notice by mail substantially in the form of Exhibit D. If the customer still fails to correct the deficiency within ten (10) days, then the District will exercise one or more of its remedies pursuant to Paragraph 4.a. AWWD Resolution No December 20,2010

7 EXHIBIT A Cross-Connection Control Program Standards The following methods of cross-connection control are considered minimum protection at the water service connection at the property line: 1. The public water supply to any premise listed under WAC (4)(b)(i)(ii)(iii) (Table 9) shall require an approved air gap(ag) separation or an approved reduced pressure backflow assembly(rpba) installed immediately downstream of the domestic water service connection, prior to any branch connections.... Pnlpedy 0 0 D 0 0 p- O D 0 D 0 I U! lxtureprolecljon I 0 D D 0 WATER MAIl WATER r.eter PWS JURISDICTION DOH Regulations Apply 1=, I, " I P1wnIIII Isolation TABLE 9 LOCAL ADMINISTRATIVE AUTHORITY JURISDICTION Building/Plumbing Codes Apply SEVERE* AND HIGH HEALTH CROSS-CONNECTION HAZARD PREMISES REQUIRING PREMISES ISOLATION BY AG OR RPBA Agricultural (farms and dairies) Beverage bottling plants Car washes Chemical plants Commercial laundries and dry cleaners Premises where both reclaimed water and potable water are provided Film processing facilities AWWD Resolution No December 20, 2010

8 Food processing plants Hospitals, medical centers, nursing homes, veterinary, medical and dental clinics, and blood plasma centers Premises with separate irrigation systems using the purveyor's water supply and with chemical addition+ Laboratories Metal plating industries Mortuaries Petroleum processing or storage plants Piers and docks. Radioactive material processing plants or nuclear reactors Survey access denied or restricted Wastewater lift stations and pumping. stations Wastewater treatment plants Premises with an unapproved auxiliary water supply interconnected with the potable water supply + For example, parks, playgrounds, golf courses, cemeteries, estates, etc. * RPBAs for connections serving these premises are acceptable only when used in combination with an in-plant approved air gap; otherwise, the purveyor shall require an approved air gap at the service connection. 2. The public water supply to any premise on which material dangerous to health or toxic substances are stored or handled, and which, in the assessment of the district CCS poses a potential high health cross-connection hazard to the public water system, shall require an approved AG separation or an approved RPBA installed immediately downstream of the domestic water service connection, prior to any branch connections. 3. The public water supply to any premise where entry is restricted so that inspection for cross-connections cannot be made with sufficient frequency or at sufficient short notice to assure that cross-connections do not exist shall require an approved AG separation or an approved RPBA installed immediately downstream of the domestic water service connection, prior to any branch connections. 4. The public water supply to any premise having a repeated history of cross connections being established or re-established, shall require an approved AG AWWD Resolution No December 20,2010

9 separation or an approved RPBA installed immediately downstream of the domestic water service connection, prior to any branch connections. 5. The public water supply to any premise which has an unapproved auxiliary water supply on or available to the consumer's premises that is either not approved for human consumption by the health agency having jurisdiction or is not otherwise acceptable to the purveyor, and with no known cross-connections, shall require an approved AG separation or an approved RPBA installed immediately downstream of the domestic water service connection, prior to any branch connections. 6. The public water supply to any premise which has internal crossconnections that are not correctable or which has complex plumbing arrangements that make it impractical to ascertain whether or not cross-connections exist, shall require an approved AG separation or an approved RPBA installed immediately downstream of the domestic water service connection, prior to any branch connections. 7. The public water supply to any premise which has a heat exchanger or a solar hot water system shall require a risk assessment inspection by the district WOO to determine the level of backflow protection that may be required to be installed immediately downstream of the domestic water service connection, prior to any branch connections. 8. The public water supply to a fire system which will contain any chemical additives, including food-grade additives, shall require an approved RPBA (or RPOA) installed immediately downstream of the public water service connection, prior to any branch connections. 9. The public water supply to a fire system with no chemical additives shall require an approved OCVA (or OCOA) installed immediately downstream of the public water service connection, prior to any branch connections. 10. The public water supply to any premise which poses a high probability of changes in the use of water by tenants, such as, but not limited to, shopping malls or strip malls, shall require an approved OCVA installed immediately downstream of the domestic water service connection, prior to any branch connections. 11. The public water supply to any premise where cross-connections are unavoidable or not correctable, such as, but not limited to, tall buildings (over 30 feet), or water booster pump systems, shall require an approved OCVA installed immediately downstream of the water service connection, prior to any branch connections. AWWD Resolution No December 20,2010

10 EXHIBIT 8 Sample Initial Notice Letter Re: Dear Cross-Connection Control; Premises Isolation _ It has come to our attention that o you do not have a backflow preventer o your backflow preventer has not been tested as required o your backflow preventer is not functioning properly. This presents a risk of contamination of the District's public water supply and is a health hazard. It is also a violation of the District's Premises Isolation Cross-Connection Control Program, which was adopted by District Resolution No., as well as WAC Enclosed is an explanation of what is required to correct this deficiency. Please take the necessary corrective action as soon as possible and notify me when it has been completed. If you have any questions, please contact me at (425) Very truly yours, AWWD Resolution No December 20,2010

11 EXHIBIT C Sample Second Notice Letter Re: Cross-Connection Control; Premises Isolation Dear --~~-- Please refer to our, 20_, letter regarding your noncompliance with the District's Cross-Connection Control Program. As we stated, o you do not have a backflow preventer o your backflow preventer has not been tested as required o your backflow preventer is not functioning properly. This is not only a violation of the District's Program, but also violates WAC and is a potential public health hazard. This is your second notice. The District has the legal authority to enforce the requirement of its Cross Connection Control Program and may, among other things: a. Require the consumer to install an approved backflow preventer for premises isolation commensurate with the degree of hazard; or b. Install, at the consumer's expense, an approved backflow preventer for premises isolation commensurate with the degree of hazard; or c. Deny or discontinue water service to a consumer's premises until the cross-connection hazard is eliminated or controlled to the satisfaction of the District. To avoid an enforcement action, please take the necessary corrective measures per the enclosed standards within thirty (30) from the date of this notice and notify me when it has been completed. If you have any questions, please contact me at (425) Very truly yours, AWWD Resolution No December 20, 2010

12 EXHIBIT D Sample Final Notice Letter Re: Cross-Connection Control; Premises Isolation Dear -~--~- Please refer to our, 20_, and,20_.,letters regarding your noncompliance with the District's Cross-Connection Control Program. As we stated, o you do not have a backflow preventer o your backflow preventer has not been tested as required o your backflow preventer ~s not functioning properly. This is not only a violation of the District's Program, but also violates WAC 246"'" and is a potential public health hazard. You still have not rectified the deficiency. The District has the legal authority to enforce the requirement of its Cross Connection Control Program and may, among other things: d. Require the consumer to install an approved backflow preventer for premises isolation commensurate with the degree of hazard; or e. Install, at the consurner's expense, an approved backflow preventer for premises isolation commensurate with the degree of hazard; or f. Deny or discontinue water service to a consumer's premises until the cross-connection hazard is eliminated or controlled to the satisfaction of the District. If you have not completed the necessary corrective measures per the enclosed standards and notify me when it has been completed within ten (10) from the date of this notice, the District will begin an enforcement action. If you have any questions, please contact me at (425) Very truly yours, cc: [authority having jurisdiction]. AWWD Resolution No December 20,2010

13 ADOPTED BY THE BOARD OF COMMISSIONERS OF ALDERWOOD WATER & WASTEWATER DISTRICT, SNOHOMISH COUNTY, WASHINGTON, at a regular meeting thereof held this 20th day of December ATTEST: Secretary AWWD Resolution No December 20,2010

Premises Isolation Cross-Connection Control Program

Premises Isolation Cross-Connection Control Program Cedar River Water & Sewer District Premises Isolation Cross-Connection Control Program PURPOSE: To protect the public water system from contamination via cross-connections and potential crossconnections.

More information

Cross Connection Control & Backflow Assembly Testing

Cross Connection Control & Backflow Assembly Testing Cross Connection Control & Backflow Assembly Testing Protecting the quality of our drinking water includes protecting the water as it passes through the pipes to all the buildings in the Roosevelt Water

More information

Cross Connection Control. WAC It s the Law Hydraulics Terms & Applications Backflow Assembly Assistance Program Questions

Cross Connection Control. WAC It s the Law Hydraulics Terms & Applications Backflow Assembly Assistance Program Questions Cross Connection Control WAC 246-290-490 - It s the Law Hydraulics Terms & Applications Backflow Assembly Assistance Program Questions WAC 246-290-490 (1) (a) All community water system shall comply with

More information

The following words and terms, when used in this article, shall have the following definitions, unless the context clearly indicates otherwise:

The following words and terms, when used in this article, shall have the following definitions, unless the context clearly indicates otherwise: AVONDALE BACKFLOW ORDINANCE 24-1 Definitions. The following words and terms, when used in this article, shall have the following definitions, unless the context clearly indicates otherwise: "Approved"

More information

CHAPTER 6 SECTION 6.19 AN ORDINANCE OF THE TOWN OF MAYODAN TO PROTECT THE QUALITY OF THE PUBLIC POTABLE WATER SUPPLY

CHAPTER 6 SECTION 6.19 AN ORDINANCE OF THE TOWN OF MAYODAN TO PROTECT THE QUALITY OF THE PUBLIC POTABLE WATER SUPPLY CHAPTER 6 SECTION 6.19 AN ORDINANCE OF THE TOWN OF MAYODAN TO PROTECT THE QUALITY OF THE PUBLIC POTABLE WATER SUPPLY SECTION 1 GENERAL PROVISIONS 1.1 Policy. The policy of the Town of Mayodan and the intention

More information

LAKEHA YEN UTILITY DIS1RICT King County, Washington. Resolution

LAKEHA YEN UTILITY DIS1RICT King County, Washington. Resolution LAKEHA YEN UTILITY DIS1RICT King County, Washington Resolution A Resolution of the Board of Commissioners of the Lakehaven Utility District, King County, Washington, establishing a crossconnection control

More information

Premises having a repeated history of cross-connections being established or reestablished.

Premises having a repeated history of cross-connections being established or reestablished. Golden Heart Utilities/College Utilities Cross-Connection Control Program Program Summary Golden Heart Utilities (GHU)/College Utilities (CUC) administers a program of surveying, inspection, record keeping,

More information

ORDINANCE NO. 519 AN ORDINANCE ADOPTING THE RULES AND REGULATIONS RELATING TO WATER SUPPLY CROSS-CONNECTIONS AND REPEALING ORDINANCE NO. 459.

ORDINANCE NO. 519 AN ORDINANCE ADOPTING THE RULES AND REGULATIONS RELATING TO WATER SUPPLY CROSS-CONNECTIONS AND REPEALING ORDINANCE NO. 459. 3-4 3-4.2 ORDINANCE NO. 519 AN ORDINANCE ADOPTING THE RULES AND REGULATIONS RELATING TO WATER SUPPLY CROSS-CONNECTIONS AND REPEALING ORDINANCE NO. 459. The City of Columbia City ordains as follows: The

More information

CITY OF HAMILTON Codified Ordinance CHAPTER 941

CITY OF HAMILTON Codified Ordinance CHAPTER 941 CITY OF HAMILTON Codified Ordinance CHAPTER 941 Backflow and Backsiphonage Prevention 941.01 Definitions.1 941.02 Water system.3 941.03 Cross-connection prohibited.4 941.04 Survey and investigations.4

More information

MODEL ORDINANCE FOR CROSS CONNECTION CONTROL BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF, STATE OF WYOMING:

MODEL ORDINANCE FOR CROSS CONNECTION CONTROL BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF, STATE OF WYOMING: MODEL ORDINANCE FOR CROSS CONNECTION CONTROL BILL NO. ORDINANCE NO. BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF, STATE OF WYOMING: Section I. Cross Connection Control - General Policy A. Purpose.

More information

Missouri American Water Cross Connection Control Program

Missouri American Water Cross Connection Control Program Missouri American Water Cross Connection Control Program January 2015 INDEX Page SECTION I SECTION II SECTION III PURPOSE....1 DEFINITIONS....2 BACKFLOW PROTECTION REQUIREMENTS....5 SECTION IV BACKFLOW

More information

The rules and regulations, as part of this document, shall apply to all premises serviced by the public water system of the Northeast Water System.

The rules and regulations, as part of this document, shall apply to all premises serviced by the public water system of the Northeast Water System. RULES AND REGULATIONS TO PROVIDE AN EFFECTIVE MEANS FOR PROTECTING THE PUBLIC WATER SYSTEM FROM CONTAMINATION DUE TO BACKFLOW OF CONTAMINATES THROUGH THE WATER SERVICE CONNECTION INTO THE PUBLIC WATER

More information

TITLE 64 LEGISLATIVE RULE BUREAU FOR PUBLIC HEALTH SERIES 15 CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION. use.

TITLE 64 LEGISLATIVE RULE BUREAU FOR PUBLIC HEALTH SERIES 15 CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION. use. TITLE 64 LEGISLATIVE RULE BUREAU FOR PUBLIC HEALTH SERIES 15 CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION 64-15-1. General. 1.1. Scope. -- This legislative rule governs cross-connection control and

More information

HIGHLANDS WATER COMPANY Lakeshore Drive Clearlake, California {707}

HIGHLANDS WATER COMPANY Lakeshore Drive Clearlake, California {707} HIGHLANDS WATER COMPANY 14580 Lakeshore Drive Clearlake, California 95422 {707} 994-2393 INFORMATION REGARDING RECENT BACKFLOW DEVICE INSTALLATION NOTICE If you have recently received a letter requiring

More information

CROSS-CONNECTION CONTROL PROGRAM

CROSS-CONNECTION CONTROL PROGRAM CROSS-CONNECTION CONTROL PROGRAM WATER AND SEWERAGE SYSTEM POLICY RESOLUTIONS City of Winston-Salem / Forsyth County North Carolina February 2016 This publication shall supersede all previous publications

More information

8.04 Protection Requirements

8.04 Protection Requirements repair, or maintenance of, or interfering with, any approved backflow prevention assembly, required by this policy, by any water user or any other person. E. The water user shall bear all costs for the

More information

TITLE 17. (b) Auxiliary Water Supply is any water supply other than that received from a public water system.

TITLE 17. (b) Auxiliary Water Supply is any water supply other than that received from a public water system. TITLE 17 DIVISION 1. STATE DEPARTMENT OF HEALTH SERVICES CHAPTER 5. SANITATION (ENVIRONMENTAL) GROUP 4. DRINKING WATER SUPPLIES ARTICLE 1. GENERAL 7583. Definitions. In addition to the definitions in Section

More information

CROSS-CONNECTION CONTROL PROGRAM HARVEST-MONROVIA WATER, SEWER AND FIRE PROTECTION AUTHORITY

CROSS-CONNECTION CONTROL PROGRAM HARVEST-MONROVIA WATER, SEWER AND FIRE PROTECTION AUTHORITY CROSS-CONNECTION CONTROL PROGRAM HARVEST-MONROVIA WATER, SEWER AND FIRE PROTECTION AUTHORITY Adopted February 8, 1988 Revised September 19, 1995 Revised February 8, 2005 Approved Witness TABLE OF CONTENTS

More information

Backflow Prevention Program Revised:

Backflow Prevention Program Revised: Backflow Prevention Program Revised: Approved by Director OBJECTIVE: The purpose of this policy is to define the minimum requirements for all connections to the University potable water system. Compliance

More information

DIVISION 3. CROSS CONNECTION CONTROL* Sec Definitions.

DIVISION 3. CROSS CONNECTION CONTROL* Sec Definitions. DIVISION 3. CROSS CONNECTION CONTROL* Sec. 30-91. Definitions. The following words, terms and phrases, when used in this division, shall have the meanings ascribed to them in this section. Approved means

More information

ARTICLE X. CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION ORDINANCE*

ARTICLE X. CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION ORDINANCE* ARTICLE X. CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION ORDINANCE* *Editor's note: Section 20 of Ord. No. 03-6, adopted May 14, 2003, repealed Ord. No. 02-7, from which 38-471--38-487 derived. Sections

More information

SECTION 3 CROSS CONNECTION CONTROL

SECTION 3 CROSS CONNECTION CONTROL SECTION 3 CROSS CONNECTION CONTROL Purpose The purpose of the Agency's cross connection control program is to: Protect the public water supply against contamination through cross connections by isolating

More information

CROSS-CONNECTION CONTROL PROGRAM OLD TOWN WATER DISTRICT OLD TOWN, MAINE

CROSS-CONNECTION CONTROL PROGRAM OLD TOWN WATER DISTRICT OLD TOWN, MAINE CROSS-CONNECTION CONTROL PROGRAM FOR THE OLD TOWN WATER DISTRICT OLD TOWN, MAINE As approved by the State of Maine Public Utilities Commission AS ADOPTED BY THE BOARD OF TRUSTEES 2011 TABLE OF CONTENTS

More information

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS Policy Number: 6030 Policy Title: Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS 1.1. The Fair Oaks Water District (FOWD) shall maintain a cross-connection and

More information

STANDARDS FOR BACKFLOW PREVENTION ASSEMBLIES

STANDARDS FOR BACKFLOW PREVENTION ASSEMBLIES STANDARDS FOR BACKFLOW PREVENTION ASSEMBLIES October 2009 200 South Ivy Street - Room 177 Medford, Oregon 97501 Phone: (541) 774-2430 Fax: (541) 774-2555 Standards For Backflow Prevention Assemblies Board

More information

DIVISION 5. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL

DIVISION 5. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL CITY OF GLENDALE CODE CHAPTER 33 ARTICLE II DIV 5 DIVISION 5. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL Sec. 33-86. Purpose. The purpose of this division is: (1) To protect the public potable water

More information

SECTION XIV: BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL Backflow Prevention & Cross-Connection Control Program Purpose

SECTION XIV: BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL Backflow Prevention & Cross-Connection Control Program Purpose SECTION XIV: BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL 14.1 Backflow Prevention & Cross-Connection Control Program Purpose The County is obligated to take all measures necessary to protect its water

More information

For further. information. contact your. local water. purveyor or the PNWS/AWWA. Cross-Connection. Control Committee. through the.

For further. information. contact your. local water. purveyor or the PNWS/AWWA. Cross-Connection. Control Committee. through the. What is a Cross Connection? A cross connection is a point in a plumbing system where the potable water supply is connected to a non-potable source. Briefly, a cross connection exists whenever the drinking

More information

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS Policy Number: 6030 Policy Title: Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS 1.1. The Fair Oaks Water District (FOWD) shall maintain a cross-connection and

More information

City of Weiser Cross Connection ordinance 1217

City of Weiser Cross Connection ordinance 1217 City of Weiser Cross Connection ordinance 1217 CROSS-CONNECTIONS SECTION: 7-4-1: Purpose 7-4-2: Definitions 7-4-3: Customer System Open for Inspection 7-4-4: Backflow Prevention Requirements 7-4-5: Type

More information

SECTION CROSS CONNECTION CONTROL TABLE OF CONTENTS

SECTION CROSS CONNECTION CONTROL TABLE OF CONTENTS SECTION 06200 CROSS CONNECTION CONTROL TABLE OF CONTENTS 06200 A Approved Backflow Prevention Assemblies 06200 B Installation of Assemblies 06200 C Facilities Requiring Protection 06200 D Testing and Test

More information

Ordinances of the Plainview Water District Town of Oyster Bay, Nassau County, New York ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS

Ordinances of the Plainview Water District Town of Oyster Bay, Nassau County, New York ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS Section 7.1 STATEMENT OF POLICY It is the policy of the Water District to protect the public water system by containing potential contamination within

More information

CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM THE ISLAND WATER ASSOCIATION, INC. SANIBEL, FLORIDA

CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM THE ISLAND WATER ASSOCIATION, INC. SANIBEL, FLORIDA CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM THE ISLAND WATER ASSOCIATION, INC. SANIBEL, FLORIDA Revised 2013 TABLE OF CONTENTS Page Introduction Section 1 - Cross Connection Control: General

More information

ARTICLE IV CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

ARTICLE IV CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION ARTICLE IV CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION SECTION 111-103. Definitions. The following words, terms and phrases, when used in this article, shall have the meanings ascribed to them in

More information

ORDINANCE NO AN ORDINANCE OF THE COASTSIDE COUNTY WATER DISTRICT

ORDINANCE NO AN ORDINANCE OF THE COASTSIDE COUNTY WATER DISTRICT ORDINANCE NO. 2013-01 AN ORDINANCE OF THE COASTSIDE COUNTY WATER DISTRICT MODIFYING SECTION W OF THE DISTRICT S GENERAL REGULATIONS REGARDING WATER SERVICE PERTAINING TO THE CONTROL OF BACKFLOW AND CROSS-CONNECTIONS

More information

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM Last Approved Revision: March 28, 2019 TABLE OF CONTENTS SECTION I - GENERAL...

More information

KING COUNTY WATER DISTRICT NO. 125 KING COUNTY, WASHINGTON. RESOLUTION NO. ~ S D * \k: - dj (j

KING COUNTY WATER DISTRICT NO. 125 KING COUNTY, WASHINGTON. RESOLUTION NO. ~ S D * \k: - dj (j KING COUNTY WATER DISTRICT NO. 125 KING COUNTY, WASHINGTON RESOLUTION NO. ~ S D * \k: - dj (j A RESOLUTION OF KING COUNTY WATER DISTRICT NO. 125, KING COUNTY, WASHINGTON PROHIBITING CROSS-CO'N'NECTIONS

More information

DEQ CROSS CONNECTION CONTROL UPDATE MAY 9, 2018

DEQ CROSS CONNECTION CONTROL UPDATE MAY 9, 2018 DEQ CROSS CONNECTION CONTROL UPDATE MAY 9, 2018 Recent Changes Recent amendments to Act 399 included: Specific references to residential accounts. Reduction of device testing to 5 years (irrigation w/

More information

CITY OF GLENVILLE 20 North Court Street Glenville WV

CITY OF GLENVILLE 20 North Court Street Glenville WV CITY OF GLENVILLE 20 North Court Street Glenville WV 26351 304-462-8040 An ordinance to regulate Cross-Connection and Backflow Prevention Program/Policy within the City or in any area under the jurisdiction

More information

Cross-Connection Control Program and Plan of Operation

Cross-Connection Control Program and Plan of Operation WG.2: CROSS-CONNECTION/BACKFLOW PROTECTION PROGRAM Missoula Water s Cross Connection/Backflow Program has been approved by the Montana Department of Environmental Quality (DEQ) and is summarized in this

More information

CROSS - CONNECTION CONTROL PROGRAM BELFAST WATER DISTRICT

CROSS - CONNECTION CONTROL PROGRAM BELFAST WATER DISTRICT CROSS - CONNECTION CONTROL PROGRAM BELFAST WATER DISTRICT BELFAST, MAINE 04915 Approved by Trustees Revised and Approved by Trustees May 13, 1981 June 21, 2002 Approved by Approved by Department of Human

More information

DALTON UTILITIES CROSS CONNECTION CONTROL RULES AND REGULATIONS. Enacted By THE WATER, LIGHT & SINKING FUND COMMISSION OF DALTON, GEORGIA

DALTON UTILITIES CROSS CONNECTION CONTROL RULES AND REGULATIONS. Enacted By THE WATER, LIGHT & SINKING FUND COMMISSION OF DALTON, GEORGIA DALTON UTILITIES CROSS CONNECTION CONTROL RULES AND REGULATIONS Enacted By THE WATER, LIGHT & SINKING FUND COMMISSION OF DALTON, GEORGIA Revised May 2015 TABLE OF CONTENTS Section I. Definitions...3 II.

More information

CHAPTER 53: BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL

CHAPTER 53: BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL Section CHAPTER 53: BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL General Provisions 53.01 Introduction 53.02 Objectives of ordinance 53.03 Responsibilities 53.04 Definitions 53.05 Right of entry 53.06

More information

EL DORADO IRRIGATION DISTRICT

EL DORADO IRRIGATION DISTRICT EL DORADO IRRIGATION DISTRICT Per Administrative Regulation 5021 Cross-Connection Control and Prevention of Backflow Program Prepared by Environmental Division of the Engineering Department Revised November

More information

PROVIDENCE WATER SUPPLY BOARD CROSS-CONNECTION CONTROL PROGRAM RULES AND REGULATIONS

PROVIDENCE WATER SUPPLY BOARD CROSS-CONNECTION CONTROL PROGRAM RULES AND REGULATIONS PROVIDENCE WATER SUPPLY BOARD CROSS-CONNECTION CONTROL PROGRAM RULES AND REGULATIONS November 28, 2017 125 Dupont Drive Main: (401) 521-6300 Providence, RI 02907-3105 Fax: (401) 464-8721 PROVIDENCE WATER

More information

ORD-3182 BE IT ORDAINED BY THE COUNCIL OF THE CITY OF VIRGINIA BEACH, VIRGINIA:

ORD-3182 BE IT ORDAINED BY THE COUNCIL OF THE CITY OF VIRGINIA BEACH, VIRGINIA: ORD-3182 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 AN ORDINANCE TO AMEND SECTION 2-268 AND ARTICLES I AND III OF CHAPTER 37 OF THE CITY CODE, PERTAINING TO

More information

December Illinois American Water Cross Connection Control Program

December Illinois American Water Cross Connection Control Program December 2007 Illinois American Water Cross Connection Control Program INDEX Page SECTION I PURPOSE..... 1 SECTION II DEFINITIONS..... 3 SECTION III BACKFLOW PROTECTION REQUIREMENTS.....6 SECTION IV BACKFLOW

More information

ORDINANCE NO. 124 SECTION 1 - GENERAL POLICY. 1.0 PURPOSE- The purpose of this ordinance is:

ORDINANCE NO. 124 SECTION 1 - GENERAL POLICY. 1.0 PURPOSE- The purpose of this ordinance is: ORDINANCE NO. 124 AN ORDINANCE OF THE BOROUGH OF INDIAN LAKE, SOMERSET COUNTY, PENNSYLVANIA, ESTABLISHING A CROSS-CONNECTION CONTROL PLAN TO PROTECT THE PUBLIC WATER SUPPLY SYSTEM OF THE BOROUGH, PROVIDING

More information

ARTICLE VI. The Town of Trappe Cross Connection and Backflow Prevention Program is contained in

ARTICLE VI. The Town of Trappe Cross Connection and Backflow Prevention Program is contained in The Town of Trappe Cross Connection and Backflow Prevention Program is contained in Section 14 Article VI of the Trappe Town Code as amended by Ordinance 02-2011, Feb. 2011 ARTICLE VI Town of Trappe Cross

More information

(Contaminant) Backsiphonage or Backpressure Backsiphonage or Backpressure

(Contaminant) Backsiphonage or Backpressure Backsiphonage or Backpressure Premises where the water supplier is denied access or restricted access for survey Premises where the water is being treated by the addition of chemical or other additives * Refer to OAR 333-061-0070(8)

More information

Ordinance No. 1 Quick Sheet

Ordinance No. 1 Quick Sheet Ordinance No. 1 Quick Sheet First Reminder Letter Bill Reminders Final Noncompliant Door Hanger Reminder Survey Mailer March April & May July July Testing period is from April 1st to June 30th If noncomplient

More information

130 CROSS CONNECTION CONTROL

130 CROSS CONNECTION CONTROL 130 CROSS CONNECTION CONTROL 130.01 APPROVED BACKFLOW PREVENTION ASSEMBLIES 130.01.01 Cross-Connection shall mean any unprotected actual or potential connection or structural arrangement between a public

More information

HOLLEY NAVARRE WATER SYSTEM, INC. BACKFLOW PREVENTION & CROSS CONNECTION CONTROL POLICIES & REGULATIONS

HOLLEY NAVARRE WATER SYSTEM, INC. BACKFLOW PREVENTION & CROSS CONNECTION CONTROL POLICIES & REGULATIONS HOLLEY NAVARRE WATER SYSTEM, INC. EFFECTIVE: AUGUST 15, 2017 REVISED: SEPTEMBER 6, 2017 8574 Turkey Bluff Road, Navarre, FL 32566 Phone: (850) 939 2427 Fax: (850) 939 9541 Table of Contents AUTHORITY...

More information

CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION

CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION 4.19.2018 CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION In accordance with the Pennsylvania Department of Environmental Protection s Safe Drinking Water Act, Highridge Water Authority (HWA), hereby implements

More information

Santa Rosa January Your instructors today: Neil Worthen John Hamner

Santa Rosa January Your instructors today: Neil Worthen John Hamner Cross-Connection Controls Santa Rosa January 2016 This document was prepared using funds under Agreement 15-017-550 with the California State Water Resources Control Board; the total Agreement is for $3,971,379

More information

JACKSON COUNTY WATER AND SEWERAGE AUTHORITY. Cross-Connection Control Program

JACKSON COUNTY WATER AND SEWERAGE AUTHORITY. Cross-Connection Control Program JACKSON COUNTY WATER AND SEWERAGE AUTHORITY Cross-Connection Control Program 2013-03-14_Policy Document, Cross-Connection Control Program, Rev 1, 2016-5-12.DocxPage 1 of 12 Pages Rev. 1, 5/12/2016 Cross-Connection

More information

Town of Chocowinity Backflow and Cross Connection Ordinance

Town of Chocowinity Backflow and Cross Connection Ordinance Town of Chocowinity Backflow and Cross Connection Ordinance SECTION 1: CROSS CONNECTION CONTROL...2 SECTION 2: DEFINITIONS...2 SECTION 3: RIGHT OF ENTRY...5 SECTION 4: ELIMINATION OF CROSS-CONNECTIONS...7

More information

PREMISE ISOLATION CROSS-CONNECTION CONTROL PROGRAM

PREMISE ISOLATION CROSS-CONNECTION CONTROL PROGRAM PREMISE ISOLATION CROSS-CONNECTION CONTROL PROGRAM CROSS-CONNECTION CONTROL PROGRAM COVINGTON WATER DISTRICT PREMISE ISOLATION CROSS-CONNECTION CONTROL PROGRAM TABLE OF CONTENTS PAGE 1. Authority 1 2.

More information

Rockwood Water People s Utility District Cross Connection Implementation and Regulations

Rockwood Water People s Utility District Cross Connection Implementation and Regulations Rockwood Water People s Utility District Cross Connection Implementation and Regulations To ensure clean, safe, potable water, Rockwood Water People s Utility District (PUD) maintains a cross connection

More information

Orange County Utilities Cross Connection Control Manual November 2017 Revision 3

Orange County Utilities Cross Connection Control Manual November 2017 Revision 3 Orange County Utilities Cross Connection Control Manual November 2017 Revision 3 Introduction Orange County Utilities (OCU) has had an active Cross Connection Control program for many years. The purpose

More information

CROSS CONNECTION CONTROL PROGRAM

CROSS CONNECTION CONTROL PROGRAM CROSS CONNECTION CONTROL PROGRAM I. PURPOSE Cross- connections between public water supplies and non-potable sources of contamination represent one of the most significant threats to health in the water

More information

RURAL WATER DISTRICT

RURAL WATER DISTRICT RURAL WATER DISTRICT C R O S S - C O N N E C T I O N C O N T R O L Ordinance No. «Merge Record #» TO PROVIDE AN EFFECTIVE MEANS FOR PROTECTING THE RURAL WATER DISTRICT FROM CONTAMINATION DUE TO BACKFLOW

More information

Backflow Prevention. Ohio EPA Rules Update. RCAP/Ohio AWWA Small Systems Operator Training May 24, 2016

Backflow Prevention. Ohio EPA Rules Update. RCAP/Ohio AWWA Small Systems Operator Training May 24, 2016 Backflow Prevention Ohio EPA Rules Update RCAP/Ohio AWWA Small Systems Operator Training May 24, 2016 Maria Lucente, P.E. Ohio Environmental Protection Agency Division of Drinking and Ground Waters Backflow

More information

Cross-Connection Control Program

Cross-Connection Control Program APPENDIX P 420 COLLEGE STREET SE LACE Y, W A 98503-1238 (360) 413-4341 Fax (360) 456-7799 Cross-Connection Control Program Department of Public Works 2 Adapted: February, 1992 Revised: May, 2016 Table

More information

DIVISION 2: BACKFLOW PREVENTION PROGRAM

DIVISION 2: BACKFLOW PREVENTION PROGRAM DIVISION 2: BACKFLOW PREVENTION PROGRAM 17-44 GENERALLY. The Backflow Prevention Program is designed to protect the potable water supply of the town. This will be accomplished by requiring the use of appropriate

More information

POLICY GOVERNING CROSS CONNECTIONS, AUXILARY INTAKES, BYPASSES, AND INTERCONNECTIONS

POLICY GOVERNING CROSS CONNECTIONS, AUXILARY INTAKES, BYPASSES, AND INTERCONNECTIONS POLICY GOVERNING CROSS CONNECTIONS, AUXILARY INTAKES, BYPASSES, AND INTERCONNECTIONS It is agreed by Winchester Utilities that the following provisions for controlling cross-connections shall apply to

More information

PORTLAND WATER DISTRICT CROSS-CONNECTION CONTROL PROGRAM 1989 REVISED MAY, 2006 REVISED SEPTEMBER, 2009 REVISED JUNE, 2017

PORTLAND WATER DISTRICT CROSS-CONNECTION CONTROL PROGRAM 1989 REVISED MAY, 2006 REVISED SEPTEMBER, 2009 REVISED JUNE, 2017 PORTLAND WATER DISTRICT CROSS-CONNECTION CONTROL PROGRAM 1989 REVISED MAY, 2006 REVISED SEPTEMBER, 2009 REVISED JUNE, 2017 225 DOUGLASS STREET - P.O. BOX 3553 PORTLAND, MAINE 04104 TABLE OF CONTENTS TABLE

More information

qwertyuiopasdfghjklzxcvbnmqwertyui opasdfghjklzxcvbnmqwertyuiopasdfgh jklzxcvbnmqwertyuiopasdfghjklzxcvb nmqwertyuiopasdfghjklzxcvbnmqwer

qwertyuiopasdfghjklzxcvbnmqwertyui opasdfghjklzxcvbnmqwertyuiopasdfgh jklzxcvbnmqwertyuiopasdfghjklzxcvb nmqwertyuiopasdfghjklzxcvbnmqwer qwertyuiopasdfghjklzxcvbnmqwertyui opasdfghjklzxcvbnmqwertyuiopasdfgh jklzxcvbnmqwertyuiopasdfghjklzxcvb nmqwertyuiopasdfghjklzxcvbnmqwer The City of Newark Backflow Prevention Program tyuiopasdfghjklzxcvbnmqwertyuiopas

More information

The Corporation Of The City of Grand Forks BYLAW NO. 1817

The Corporation Of The City of Grand Forks BYLAW NO. 1817 The Corporation Of The City of Grand Forks BYLAW NO. 1817 A Bylaw to Establish a Cross Connection Control Program and Process For the City of Grand Forks WHEREAS, Provincial legislation requires water

More information

ARTICLE VI. CROSS-CONNECTION/BACKFLOW PROTECTION

ARTICLE VI. CROSS-CONNECTION/BACKFLOW PROTECTION ARTICLE VI. CROSS-CONNECTION/BACKFLOW PROTECTION Sec. 18-161. General. (a) The intention of this chapter is to define the authority of the town as the water purveyor in the elimination of all hazards,

More information

City of Grass Valley City Council Agenda

City of Grass Valley City Council Agenda City of Grass Valley City Council Agenda Council Meeting Date: February 11, 2014 Date Prepared: February 4, 2014 Prepared by: Timothy M. Kiser, PE, Public Works Director/City E ngineer l)vt(( Title: Second

More information

DUPLIN COUNTY BACKFLOW PREVENTION ORDINANCE This ordinance shall be known as the Duplin County Backflow Prevention Ordinance.

DUPLIN COUNTY BACKFLOW PREVENTION ORDINANCE This ordinance shall be known as the Duplin County Backflow Prevention Ordinance. DUPLIN COUNTY BACKFLOW PREVENTION ORDINANCE 01- -2009 ARTICLE 1: INTRODUCTORY PROVISIONS & OBJECTIVES SECTION 101: TITLE This ordinance shall be known as the Duplin County Backflow Prevention Ordinance.

More information

Newport Water District CROSS CONNECTION CONTROL PROGRAM

Newport Water District CROSS CONNECTION CONTROL PROGRAM Newport Water District CROSS CONNECTION CONTROL PROGRAM P O BOX 142 124 MOOSEHEAD TRAIL NEWPORT MAINE 04953 0142 Approved: May 2008 Revised: June 2012 Revised: June 2014 NEWPORT WATER DISTRICT Cross Connection

More information

The Expected Range of Knowledge is a Foundation upon which the Specialist will build a strong professional capability.

The Expected Range of Knowledge is a Foundation upon which the Specialist will build a strong professional capability. Cross-Connection Control Program Specialist Expected Range of Knowledge Approved by the Cross-Connection Control Program Specialist Certification Committee 8/12/2003 The Expected Range of Knowledge is

More information

QUONSET DEVELOPMENT CORPORATION QUONSET & LADD WATER SYSTEMS CROSS CONNECTION CONTROL & BACKFLOW PREVENTION POLICY

QUONSET DEVELOPMENT CORPORATION QUONSET & LADD WATER SYSTEMS CROSS CONNECTION CONTROL & BACKFLOW PREVENTION POLICY QUONSET DEVELOPMENT CORPORATION QUONSET & LADD WATER SYSTEMS CROSS CONNECTION CONTROL & BACKFLOW PREVENTION POLICY I II Purpose Cross-connections between water supplies and non-potable sources of contamination

More information

City of Hollywood, Florida Department of Public Utilities Cross-Connection Control Plan

City of Hollywood, Florida Department of Public Utilities Cross-Connection Control Plan , Florida Department of Public Utilities Policies and Procedures Manual March 2015 Table of Contents Page Number Abbreviations --------------------------------------------------------------------------------

More information

WATER DEPARTMENT STANDARD SPECIFCATIONS SECTION 301 CROSS CONNECTION POLICY

WATER DEPARTMENT STANDARD SPECIFCATIONS SECTION 301 CROSS CONNECTION POLICY STANDARD SPECIFCATIONS SECTION 301 CROSS CONNECTION POLICY JANUARY 1, 2019 TABLE OF CONTENTS SECTION PAGE 1.0 Introduction... 1 2.0 Authority... 1 3.0 Reviews... 1 4.0 Responsibilities... 2 5.0 Contamination...

More information

Charlotte County Utilities Manual of Rules and Regulations Governing Cross- Connection Control FEBRUARY 2008

Charlotte County Utilities Manual of Rules and Regulations Governing Cross- Connection Control FEBRUARY 2008 Charlotte County Utilities Manual of Rules and Regulations Governing Cross- Connection Control FEBRUARY 2008 TABLE OF CONTENTS SECTION 1 - INTRODUCTION 1.1 General SECTION 2 - OVERVIEW 2.1 Purpose 2.2

More information

FRWA SAMPLE ORDINANCE

FRWA SAMPLE ORDINANCE FRWA SAMPLE ORDINANCE ORDINANCE NO. 427 AN ORDINANCE TO BE ENTITLED "AN ORDINANCE TO AMEND ORDINANCE NO. 425; PROVIDING FOR THE AMENDMENT OF ARTICLE V., BY ADDING THERETO ARTICLE V. -A-: CROSS-CONNECTION

More information

Cross-Connection Control and Backflow Prevention Program

Cross-Connection Control and Backflow Prevention Program Cross-Connection Control and Backflow Prevention Program Plumbing cross-connections, which are defined as actual or potential connections between a potable and non-potable water supply, constitute a serious

More information

Cross Connection Control Rules

Cross Connection Control Rules Source & Drinking Water Program Cross-Connection Control for Public Water Systems 2015 Focus on Change Seminars Introduction FL Department of Environmental Protection (FDEP) has had cross-connection control

More information

GASPARILLA ISLAND WATER ASSOCIATION, INC. (GIWA) BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL PROGRAM

GASPARILLA ISLAND WATER ASSOCIATION, INC. (GIWA) BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL PROGRAM GASPARILLA ISLAND WATER ASSOCIATION, INC. (GIWA) BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL PROGRAM I. INTRODUCTION A cross-connection is any temporary or permanent connection between a public water

More information

CROSS CONNECTION CONTROL ORDINANCE

CROSS CONNECTION CONTROL ORDINANCE CROSS CONNECTION CONTROL ORDINANCE Town of Franklin INTRODUCTION The purpose of this Cross-connection Control Ordinance is to define the authority of the Town of Franklin as the water purveyor (hereinafter

More information

C R O S S - C O N N E C T I O N C O N T R O L

C R O S S - C O N N E C T I O N C O N T R O L (MUNICIPALITY) ORDINANCE C R O S S - C O N N E C T I O N C O N T R O L Ordinance No. TO PROVIDE AN EFFECTIVE MEANS FOR PROTECTING THE PUBLIC WATER SUPPLY SYSTEM FROM CONTAMINATION DUE TO BACKFLOW OF CONTAMINANTS

More information

Hillsborough County Public Utilities Department Cross-Connection Control Plan

Hillsborough County Public Utilities Department Cross-Connection Control Plan Page: 1 of 19 Hillsborough County Public Utilities Department Cross-Connection Control Plan COMPONENT I A. Hillsborough County Code of Ordinances, Chapter 121 serves as the legal authority for the Hillsborough

More information

A BRIEF LOOK AT BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL LES O BRIEN

A BRIEF LOOK AT BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL LES O BRIEN A BRIEF LOOK AT BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL 1 LES O BRIEN 1 MILITARY VETERANS THANK YOU FOR YOUR SERVICE. 2 TOPICS TO DISCUSS: Federal Regulations Florida Statutes / Regulations DEP

More information

Cross-Connection Control and Backflow Prevention for Public Water Systems

Cross-Connection Control and Backflow Prevention for Public Water Systems Drinking Water and Aquifer Protection Program Cross-Connection Control and Backflow Prevention for Public Water Systems Focus On Change 2018 History Need To Know Rules and Regulations CCC Program Backflow

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 3-2005 AN ORDINANCE PROVIDING FOR A CITY WATER SYSTEM CROSS CONNECTION CONTROL PLAN; PROVIDING FOR PURPOSE AND INTENT; PROVIDING DEFINITIONS; PROVIDING FOR CUSTOMER'S WATER SYSTEM TO BE OPEN

More information

CITY OF LAKE CHARLES WATER DIVISION BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL POLICY

CITY OF LAKE CHARLES WATER DIVISION BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL POLICY CITY OF LAKE CHARLES WATER DIVISION BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL POLICY The City of Lake Charles has an obligation to provide safe, clean drinking water to our city and take every precaution

More information

Water Service 39 BACKFLOW PROTECTION

Water Service 39 BACKFLOW PROTECTION Water Service 39 BACKFLOW PROTECTION 52.20 DEFINITIONS. For the purpose of this chapter, the following definitions shall apply unless the context clearly indicates or requires a different meaning: AGENCY.

More information

Appendix A Water Facilities Inventory

Appendix A Water Facilities Inventory Appendix A Water Facilities Inventory Appendix B Intertie with Chehalis Appendix C Water Utility Policies Chapter 15.04 RULES AND REGULATIONS http://www.codepublishing.com/wa/centralia/centralia15/centralia1504.html

More information

ORDINANCE NO Chapter 203B of the Glencoe Municipal Code is established to read in its entirety as follows:

ORDINANCE NO Chapter 203B of the Glencoe Municipal Code is established to read in its entirety as follows: ORDINANCE NO. 602 The City Council of the City of Glencoe ordains: Section 1: 203B Chapter 203B of the Glencoe Municipal Code is established to read in its entirety as follows: The City of Glencoe hereby

More information

CROSS CONNECTION CONTROL PROGRAM of UTAH

CROSS CONNECTION CONTROL PROGRAM of UTAH CROSS CONNECTION CONTROL PROGRAM of UTAH April 2016 Cross Connection Control Commission Michael S. Moss, Secretary Division of Drinking Water 195 North 1950 West, 3 rd Floor P.O. Box 144830 Salt Lake City,

More information

1.2. RESPONSIBILITY OF THE DRINKING WATER PURVEYOR (LDWA).

1.2. RESPONSIBILITY OF THE DRINKING WATER PURVEYOR (LDWA). LDWA RES 2015-04 (fka 2015-12) LOCAL AUTHORITY: REQUIRED BY THE DDW/DEQ CROSS CONNECTION CONTROL PROGRAM IAW STATE OF UTAH RULE 309 & IPC OFFICIALLY ADOPTED BY THE LDWA BOARD OF DIRECTORS, 2016.01.07 SECTION

More information

14 On Tap Fall by Caigan McKenzie NESC Staff Writer

14 On Tap Fall by Caigan McKenzie NESC Staff Writer 14 On Tap Fall 2007 by Caigan McKenzie NESC Staff Writer n May 2000, a city employee in Pineville, Louisiana, mistakenly connected a business sewerage pipe to a six-inch water pipe. When company employees

More information

LAKE CRYSTAL MUNICIPAL UTILITIES CROSS CONNECTION AND BACKFLOW PREVENTION POLICY

LAKE CRYSTAL MUNICIPAL UTILITIES CROSS CONNECTION AND BACKFLOW PREVENTION POLICY LAKE CRYSTAL MUNICIPAL UTILITIES CROSS CONNECTION AND BACKFLOW PREVENTION POLICY 100 East Robinson Street Lake Crystal, Minnesota 56055 phone 507-726-2538 fax 507-726-2265 www.ci.lake-crystal.mn.us LAKE

More information

A bylaw to establish a cross connection control program and process for the District of Squamish.

A bylaw to establish a cross connection control program and process for the District of Squamish. The District of Squamish Bylaw No. 2259, 2013 A bylaw to establish a cross connection control program and process for the District of Squamish. WHEREAS, provincial legislation requires water suppliers

More information

Cross-Connection Control Policy

Cross-Connection Control Policy Cross-Connection Control Policy Policy on Cross-Connections OUC agrees with the American Water Works Association s (AWWA) statement issued on cross connection as follows: A statement adopted by the Board

More information

ROCHESTER PUBLIC UTILITIES PUBLIC WATER SYSTEM CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM FOR ROCHESTER, MINNESOTA

ROCHESTER PUBLIC UTILITIES PUBLIC WATER SYSTEM CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM FOR ROCHESTER, MINNESOTA ROCHESTER PUBLIC UTILITIES PUBLIC WATER SYSTEM CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM FOR ROCHESTER, MINNESOTA Rochester Public Utilities 4000 East River Road NE Rochester, Minnesota

More information

Backflow Prevention by Containment & Cross-Connection Control Program Easton Suburban Water Authority

Backflow Prevention by Containment & Cross-Connection Control Program Easton Suburban Water Authority Backflow Prevention by Containment & Cross-Connection Control Program Easton Suburban Water Authority Revised: March 2013 By: Paul Corriere Table of Contents FOREWORD... 1 INTRODUCTION... 2 DEFINITIONS...

More information