Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

Size: px
Start display at page:

Download "Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan"

Transcription

1 Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan

2 Substation Insulator Pollution Contamination Management

3 PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION Contents INTRODUCTION ENMAX INSULATOR FLASHOVER STATISTICS PRESENTED TO 2012 APIC POWER AND ENERGY INNOVATION FORUM MITIGATION MANAGEMENT PILOT PROJECT CONCLUSION

4 INTRODUCTION OF INSULATOR CONTAMINATION Insulator: isolation from the energized high voltage bus to ground Insulator pollution contamination 4

5 How does your car look in winter? Road salt on the car 5

6 INTRODUCTION OF INSULATOR CONTAMINATION Insulator flashover: surface discharge when moisture condenses on solid insulation subject to particulate pollution Factors of insulator flashover: Moisture condensation Pollution (By location) Industrial areas: fly-ash, variety of dust Agricultural areas: soil dust, fertilizers Highways: salt from roads during winter time By components: Soluble: Salt or Sodium Chloride Non-Soluble: Calcium Chloride, carbon, and cement dust ect. 6

7 INTRODUCTION OF INSULATOR CONTAMINATION Sequence of events leading to flashover Deposit of pollution on the insulator surface Surface layer is moistened by fog, misty rain Surface layer is heated Heating results in local drying and dry bands formed Partial arc occur across dry bands Increased partial discharge Partial discharges are connected to a complete flashover Video of the surface discharge 7

8 ENMAX EXPERIENCE OUTAGE STATISTICS CAUSED BY INSULATOR FLASHOVER 2008 with most interrupted customers and longest interruption duration Average Interruption time in minutes has significantly reduced since 2009 # of Customers Interrupted Year Average Interruption 30 Duration (min.)

9 MITIGATION MANAGEMENT Time based preventive maintenance program Review and enhance our substation washing program (Sub washing committee was formed in 2008) Meets twice a year to review frequencies Analyzes past year s sub washing for effectiveness Corrective maintenance program Visual inspection Anticipation of the contamination (weather condition change) 9

10 SUBSTATION WASHING PROGRAM IN DETAIL Factors of determining sub washing frequency Location of the sub (near high way, industry, river, land elevation) Area external to the sub (construction, type of roads) Past history of insulator flashover Type of insulators (polymer, porcelain) Type of bus (H bus-water drainage) Insulator hats are installed (prevent water drops freezing from skirt to skirt) Criticality of the sub (control center input) Management and Field input 10

11 H bus vs. Round bus

12 Types of Insulator in Enmax Porcelain Silicone covered porcelain Polymer

13 Substation Washing types High pressure washing Flood washing Corn blast washing Hand wash

14 Washing Experience hand wash Scratches on silicone coated porcelain insulator by hand wash

15 Washing Experience Polymer seam Seam of polymer insulators introduced in manufacturing process

16 Substation Washing types vs. Insulator type High pressure washing Flood washing Corn blast washing Hand wash Porcelain Insulators Silicon coated Insulators Polymer Insulator

17 # of Substations Substation Wash Schedule Washing schedule Distribution of Sub Washing Frequency 2/year 1/year 1/2 years 1/3 years 1/4 years Washing Frequency Ongoing review of the washing frequency

18 PILOT PROJECT DOBLE IPM Initialized in 2009 to utilize condition monitoring of pollution severity based on leakage current Installed Doble IPM in Fall 2010 on one substation next to highway and river

19 PILOT PROJECT DOBLE IPM Location

20 20 DOBLE IPM METHODOLOGY

21 21 LOCATION OF THE CURRENT SENSOR 138 kv

22 22 CURRENT SENSTOR MOUNTING LOCATION

23 23 DOBLE IPM METHODOLOGY

24 Evaluation of Pollution Level High cumulative charges + High peak currents (with high counts) High level of pollution Dry & polluted insulator -> lower peak current; Foggy, high humidity morning -> Flashover??? 24

25 Imax Calculation Maximum peak leakage current is defined as Imax= (SCD/15.32)^2 SCD_138 = /145 = 17mm/kV SCD: Specific Creepage Distance in mm/kv KV is the maximum phase to phase voltage 138kV insulator: Creepage distance is 99 inch. Guideline for peak leakage current threshold value is set at 25% of Imax I_138_threhold = 308 ma (???) 25

26 DOBLE IPM LEAKAGE CURRENT MEASUREMENT Plot from Jan April

27 DOBLE IPM LEAKAGE CURRENT MEASUREMENT March 15, 2012 Substation wash 27

28 Doble IPM EXPERIENCE Limitation in Leakage current method in Calgary winter (dry and heavy polluted insulator -> small leakage current) Benchmark is not available (Doble threshold value too high) Lack of Doble support 28

29 Conclusions Washing committee enhanced sub washing program: less flashover outages and duration of outage decreases Equipment upgrade is ongoing: H bus replacement, porcelain insulator replacement Leakage current detection: correlation to relative humidity, ESDD (equivalent salt deposit density) tests 29

30 enmax.com Change this under "View" menu, Header/Footer options

31 PRESENTED BY SIMON CHAN T&D ASSET MANAGEMENT ENMAX POWER CORPERATION I Contents EFFECTS OF CONTAMINATION PRESENTED TO 2012 APIC POWER AND ENERGY INNOVATION FORUM MITIGATION METHODS

32 Questions?? Change this under "View" menu, Header/Footer options

33 Effects of Contamination Effects of contamination include: Flash Over on Equipment (Equipment failure) Electrical Tracking (Wood Pins, Cross Arms) Pole Fires Material Failures (Automatic Sleeves) Exterior Rusting, peeling of paint. Consequences Poor reliability Safety $$$ 33

34 Equipment/Material Flashover Padmount Switchgear Rusting, peeling of paint on exterior. Higher risk of flashovers 34

35 Electrical Tracking Wood Pins Androlite Arms Wood Cross Arms Insulators 35

36 36 Wood Pin

37 37 Androlite Arms

38 Pole Fires Pole fires caused by contamination can only occur under the following conditions: Leakage current from energized equipment. Heat

39 Road Salt vs Pole Fires

40 MITIGATION METHODS Androlite Conversion Insulator Washing Switch Cleaning Material Standard Change Pole Fire Mitigation Program Wood Pin Program Padmount Painting/Exterior Replacement 40

41 Androlite Conversion Flattening Androlite Configuration to Current Construction Standards

42 Insulator Washing Maintenance Program EPC initiated a multi-year insulator washing maintenance program. Priority is on City of Calgary Priority One sanding routes. Extra emphasis on areas where pole fires occurred previously. Twice a year cycle. Late March to early April. Late September to early October

43 Insulator Washing Maintenance Program

44 Pad Mount Switch Dry Ice Cleaning Contaminants have caused flashovers to Live Front Pad Mount Switch Gear. EPC has implemented a 5 year inspection and dry ice cleaning cycle for switches. EPC is exploring possibilities of dry ice cleaning for Distribution Automation Pad Mounted Switches.

45 Material Standard Changes Porcelain to Polymer Porcelain insulators Over insulated 34 kv polymer insulators. Change to Porcelain Fused Cut Outs and lightning arrestors to Polymer. Cross Arms (Wood to Fiber glass) Fiber glass replaces deteriorated wood crossarms.

46 Material Standard Changes

47 Material Standard Changes

48 Material Standard Changes Cut Outs 48

49 49 Splices

50 Splices Automatic to Compression Sleeves Initial samples Corrosion found. Corrosion was more evident near major roadways. In 2011, only compression splices are to be used for all new construction and repair work. Ongoing further investigation of automatic splices. 50

51 Pole Fire Mitigation Program In 2001, EPC initiated a multi-year over-insulation and insulator washing maintenance program. A total of $.57M were spent in the next seven years ( ). No structures that had been mitigated with upgraded insulation have been involved in pole fires.

52 Pole Fire Mitigation Program EPC has seen an increase in contamination of the distribution overhead structures. In 2008, there were 76 pole fire incidents causing nearly customer interruptions and significant customer interruption time.

53 53 Pole Fire Locations

54 Incidents Pole Fire Mitigation Program 80 Pole Fires (YTD) Year

55 Pole Fire Mitigation Program Alternatives Considered 1) Do nothing 2) Dry Ice Washing 3) Bonding 4) Over Insulation

56 Pole Fire Mitigation Program Over Insulation Wood crossarm Fiberglass crossarm Porcelain insulator 34 kv class polymer insulator Porcelain cutout Polymer cutout

57 Pole Fire Mitigation Program

58 Pole Fire Mitigation Program Current Progress Primarily focus is on mitigating overhead structures with equipment only. Mitigated nearly 70% of these structures. Expected completion 2014.

59 59 POLES MITIGATED

60 Wood Pin Program Prevalent standard of insulator support until early 1970s when steel pins become industry standard. Increased risk to the safety of the general public and EPC employees. Minimize hazards.

61 Wood Pin Program Material Change Wood pins to Steel Pins Contamination due to road salt increased rate of deterioration in wood pins due to electrical tracking.

62 Wood Pin Program Started in 2008 Nearly 4000 Structures containing wood pin to replace. Expected completion in 2014.

63 Equipment Painting/Exterior Replacement Existing Padmount Painting Program Typically pad mounted equipment a year. Severe deterioration Replacement of doors and tops 63

64 Questions?? Simon Chan, Lily Hoyer, Change this under "View" menu, Header/Footer options

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment Abstract This paper provides an overview of how CO 2 cleaning works on energized electrical equipment. It also presents

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-0 Exhibit F Schedule Page of 0 DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment

More information

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Cigré WG C Topics: The selection of insulators with respect to polluted conditions Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-0 Exhibit C Page of OVERALL EXTERNAL SERVICES COSTS 0 INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services comprise those services

More information

Composite Insulator Components

Composite Insulator Components Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the

More information

ILMOS Insulator Leakage Current Monitor

ILMOS Insulator Leakage Current Monitor ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-0 Exhibit C Page of OVERALL EXTERNAL SERVICES COSTS 0 INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services comprise those services

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-00 Tab Schedule Filed: 00 Aug Page of OVERALL EXTERNAL SERVICES COSTS INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services represent

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Capital Expenditure $3,931,290 ($3,530,841 in 2013) Background:

INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Capital Expenditure $3,931,290 ($3,530,841 in 2013) Background: EB-0-0 0 IRM Application Filed: September, 0 Page of INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Program Title: Switching Units and Transformers 0 0 0 Capital Expenditure $,,0 ($,0, in 0) Background:

More information

Polluted Outdoor Insulators Maintenance and Washing

Polluted Outdoor Insulators Maintenance and Washing Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان

More information

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development MARKET FORCES THAT INFLUENCE RAYCHEM SALES PUBLIC UTILITY COMMISSIONS (System Reliability) SALES US FISH & WILDLIFE (Avian Electrocutions)

More information

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Transmission Silicone Insulators Line Post 69 kv to 230 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

INSULATOR REQUERIMENTS:

INSULATOR REQUERIMENTS: 2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

EMERGENCY PREPAREDNESS & RESILIENCY IN THE ENERGY INDUSTRY

EMERGENCY PREPAREDNESS & RESILIENCY IN THE ENERGY INDUSTRY EMERGENCY PREPAREDNESS & RESILIENCY IN THE ENERGY INDUSTRY MATTHEW A. WALDRIP, PWS, CESSSWI SENIOR ENVIRONMENTAL SPECIALIST PRESENTATION OVERVIEW Overview of The Electric Grid Challenges Resulting from

More information

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1. E. A. Solomonik 36-WG11/Nberg/158 19/06/03 L. L. Vladimirsky, E. A. Solomonik HVDC Power Transmission Research Institute (NIIPT) COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT

More information

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018 Evaluation Test Procedures for Distribution Crossarms Southeastern Electric Exchange November, 2018 What: Research, Testing and Applications Center in the School of Electrical & Computer Engineering at

More information

Cutouts and Fuse Links Equipment to protect against faults and over-current conditions on power distribution systems. Open-Type Cutouts Linkbreak Cutouts Loadbreak Cutouts Cutout-Arrester Combinations

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation Si-COAT 570 RTV Silicone HVIC Reliability & Beyond Seminar Presentation Overview Background & industry pressures Early validation of Si-COAT HVIC The science of Si-COAT Q&A Si-COAT HVIC : The Background

More information

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES The National Electrical Safety Code (NESC) is a set of rules to safeguard people during the installation, operation,

More information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.

More information

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate

More information

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS by Abdelrahman Khaled A Thesis Presented to the Faculty of the American University of Sharjah College of Engineering in Partial Fulfillment of the Requirements

More information

Comparison of effects of Various Contaminations on SiR insulators

Comparison of effects of Various Contaminations on SiR insulators Volume 120 No. 6 2018, 609-620 ISSN: 1314-3395 (on-line version) url: http://www.acadpubl.eu/hub/ http://www.acadpubl.eu/hub/ Comparison of effects of Various Contaminations on SiR insulators Satheesh

More information

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv K-LINE INSULATORS LIMITED Catalogue TD-IPS TORONTO, ONTARIO, CANADA TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission &

More information

SECTION G40 SITE ELECTRICAL UTILITIES 11/10

SECTION G40 SITE ELECTRICAL UTILITIES 11/10 G40 GENERAL SECTION G40 SITE ELECTRICAL UTILITIES 11/10 RFP Part 3 including the Engineering System Requirements (ESR) provide project specific requirements. The RFP Part 4, Performance Technical Sections

More information

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot

More information

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot

More information

DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE

DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE EB-0-0 Exhibit D Page of DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE 0 EXECUTIVE SUMMARY Background Over the past number of years, THESL has put considerable effort into its Asset Management

More information

Exhibit to Agenda Item #1

Exhibit to Agenda Item #1 Exhibit to Agenda Item #1 Board Directors Meeting Wednesday,, scheduled to begin at 5:30 p.m. Customer Service Center, Rubicon Room Powering forward. Together. Agenda 2016 SD-4 annual monitoring report

More information

Diagnostic Techniques of Composite Insulators

Diagnostic Techniques of Composite Insulators Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI

More information

Protective Coatings for Underground Utility Concrete Structures. By: John E. Davis Inside Sales & Marketing Specialist: Sauereisen, Inc.

Protective Coatings for Underground Utility Concrete Structures. By: John E. Davis Inside Sales & Marketing Specialist: Sauereisen, Inc. Protective Coatings for Underground Utility Concrete Structures By: John E. Davis Inside Sales & Marketing Specialist: Sauereisen, Inc. As our cities and municipalities grow older, the utility and wastewater

More information

Intelligent Load Management

Intelligent Load Management T H E O F F I C I A L P U B L I CAT I O N O F 12 Save Money With Substation Maintenance 22 Grid-Tied Wind Energy Systems 28 Distributed Energy Storage and Utilities, Commercial Buildings Intelligent Load

More information

Polymer Cutout Testing Recommendations

Polymer Cutout Testing Recommendations 1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)

More information

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT Cheap and reliable supply of electrical energy has been identified as an indicator of economic development and social welfare of any modern society.

More information

C Pollution measurement based on DDG method for different type s of insulator profile

C Pollution measurement based on DDG method for different type s of insulator profile 21, rue d'artois, F-75008 Paris http://www.cigre.org C4-401 Session 2004 CIGRÉ Pollution measurement based on DDG method for different type s of insulator profile M.R.Shariati *, A.R.Moradian, M.R.Ghaemi,

More information

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results

More information

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN 21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and

More information

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators The 5 th PSU-UNS International Conference on Engineering and 467 Technology (ICET-2011), Phuket, May 2-3, 2011 Prince of Songkla University, Faculty of Engineering Hat Yai, Songkhla, Thailand 90112 Study

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-00 Exhibit F Tab Schedule Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE 0 PREDICTIVE MAINTENANCE Predictive maintenance expenditures fund work that is required to test and audit distribution

More information

Duke Energy Carolinas Distribution Construction Standards Reference Guide

Duke Energy Carolinas Distribution Construction Standards Reference Guide Duke Energy Carolinas Distribution Construction Standards Reference Guide The Duke Energy Carolinas (DEC) Distribution Construction Standards are available on the My Duke Energy Contractor Portal. Access

More information

NEW! PUPI Fiberglass Transmission & H-frame Products

NEW! PUPI Fiberglass Transmission & H-frame Products NEW! PUPI Fiberglass Transmission & H-frame Products REV06-2013 PUPI Transmission and H-frame Products Everything that makes PUPI the leader in fiberglass distribution crossarms makes us the best choice

More information

TEMPERED GLASS INSULATORS

TEMPERED GLASS INSULATORS TEMPERED GLASS INSULATORS SUSPENSION-TYPE» Non-conducing support composed of an insulating glass piece and iron fittings allowing other units to be connected in series. A fastening iron fitting is included

More information

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area

More information

GROUP A. Polymeric Insulators.

GROUP A. Polymeric Insulators. GROUP A Polymeric Insulators PYUNGIL Bldg., 1475-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-6650~3 FAX : 82-31-424-7300 www.pyungil.com Silicone Railway

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

A Discussion of Porcelain-Insulator Cutouts

A Discussion of Porcelain-Insulator Cutouts A Discussion of Porcelain-Insulator Cutouts All porcelain-insulator distribution fuse cutouts are not equal. Although S&C uses some of the same insulator suppliers as other U.S. competitors, S&C s porcelain

More information

A-PDF PPT TO PDF DEMO: Purchase from to remove the watermark

A-PDF PPT TO PDF DEMO: Purchase from   to remove the watermark EMERGING TECHNOLOGIES SILIDRIL - Polymeric Coating & SHRIJI - CONDUCTIVE SILICON GEL By: Surat Prestech Pvt. Limited Prepared By Mr. Nitin Oza, M.E. & Dr. Rafael Mier, PhD. A-PDF PPT TO PDF DEMO: Purchase

More information

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 18 23.00 40 (August 2016) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 18 23.00 40 (August 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

33-SDMS-02 SPECIFICATIONS FOR

33-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.

More information

Section X - Miscellaneous

Section X - Miscellaneous Section X - Miscellaneous A. Introduction This section provides design criteria, specific requests/recommendations and preferences related to specifying and constructing systems and materials used in HRSD

More information

Section 32 - Miscellaneous

Section 32 - Miscellaneous Section 32 - Miscellaneous A. Introduction This section provides design criteria, specific requests/recommendations and preferences related to specifying and constructing systems and materials used in

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Porcelain Insulator Performance under Different Condition of Installation around Aligarh

Porcelain Insulator Performance under Different Condition of Installation around Aligarh Porcelain Insulator Performance under Different Condition of Installation around Aligarh Asfar Ali Khan and Ekram Husain Abstract Modern Society is strongly dependent on a reliable power supply. The availability

More information

PPL Electric Utilities Summer Readiness Overview June 2018

PPL Electric Utilities Summer Readiness Overview June 2018 SUMMARY PPL Electric Utilities Summer Readiness Overview June 2018 For PPL Electric Utilities (PPL Electric), summer readiness means the company must respond effectively to summer storms as well as provide

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

GE EQUIPMENT CENTERS APPLICATION CONSIDERATIONS

GE EQUIPMENT CENTERS APPLICATION CONSIDERATIONS g GE Electrical Distribution and Control General Electric Company 41 Woodford Avenue, Plainville, CT 06062 860 747-7111 GE EQUIPMENT CENTERS APPLICATION CONSIDERATIONS Introduction For many years the petro/chemical

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

nts Issue: April 18 th, 2018 Date Issued: Summary about 11%) of customers. 1. Prior to the occur? Province. 3) If the public Major Event warning of

nts Issue: April 18 th, 2018 Date Issued: Summary about 11%) of customers. 1. Prior to the occur? Province. 3) If the public Major Event warning of Major Even nts RESPONSE REPORT Issue: April 7 th to 9 th, 2017 2.1. 4.2 Major Events Response Report Date Issued: April 18 th, 2018 Prepared for: Publication and Electronicc Filing with the Ontario Energy

More information

Panagiotis Charalampidis

Panagiotis Charalampidis Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,

More information

GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev )

GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev ) Milk and Dairy Food Safety Branch 1220 N Street, Sacramento, CA 95814 GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev. 10-20-2011) The outline below lists sanitary requirements

More information

ATTACHMENT 1. Building A Better Electric Utility: An Asset Management Plan for Saskatoon Light & Power

ATTACHMENT 1. Building A Better Electric Utility: An Asset Management Plan for Saskatoon Light & Power ATTACHMENT 1 Building A Better Electric Utility: An Asset Management Plan for Saskatoon Light & Power MARCH 2018 INTRODUCTION In 2011, it was identified that a strategic change would need to be made to

More information

Mitigation of Pole Top Fires Best Practice. Version 1

Mitigation of Pole Top Fires Best Practice. Version 1 Mitigation of Pole Top Fires Best Practice Version 1 March 2017 1 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Legal Notice... 3 3. Introduction... 4 3.1 Executive Summary... 4 3.2 Background... 4

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

Power IT Compact Secondary Substations, CSS. Technical catalogue for sheet steel substations

Power IT Compact Secondary Substations, CSS. Technical catalogue for sheet steel substations Power IT Compact Secondary Substations, CSS Technical catalogue for sheet steel substations The New Standard for Individual Solutions The new CSS substations represent a unique concept, which is introducing

More information

A. Prepare formwork shop drawings using qualified professional engineer. Include detail of fabrication, assembly, and support of formwork.

A. Prepare formwork shop drawings using qualified professional engineer. Include detail of fabrication, assembly, and support of formwork. DIVISION 03 CONCRETE 03 0100 MAINTENANCE OF CONCRETE 03 0505 UNDER SLAB VAPOR BARRIER A. Sheet vapor retarder shall be polyethylene sheet, ASTM D 4397, 10 mils thick minimum. Consult with Facilities Management

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 13 01 (August 2013) --------------------------- Preparing Activity: NAVFAC NEW UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement with UMRL dated

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 2004 Specifications CSJ 0720-03-095 SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 1. Description. Furnish and install Environmentally Controlled Communications Building

More information

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE Dionisios PYLARINOS Consultant, Hellenic Electricity Distribution Network Operator S.A., Greece dpylarinos@yahoo.com Kiriakos SIDERAKIS Assistant Professor,

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

Northeast Gas Operation School Thursday June 5 th

Northeast Gas Operation School Thursday June 5 th Northeast Gas Operation School Thursday June 5 th Recognition and Assessment of Atmospheric Corrosion Presented by Donald A. Doubleday Jr. National Grid New England Corrosion Engineer & Team Lead Contents

More information

ROOFING APPLICATION STANDARD (RAS) No. 109

ROOFING APPLICATION STANDARD (RAS) No. 109 ROOFING APPLICATION STANDARD (RAS) No. 109 1. 2. Scope 1.1 This Roofing Application Standard sets the requirements to determine whether a substrate and surrounding environmental conditions are appropriate

More information

DISTRIBUTION STORM HARDENING AND RESILIENCY. Matt Shellenberger, P.E. American Electric Power

DISTRIBUTION STORM HARDENING AND RESILIENCY. Matt Shellenberger, P.E. American Electric Power DISTRIBUTION STORM HARDENING AND RESILIENCY Matt Shellenberger, P.E. American Electric Power AMERICAN ELECTRIC POWER DEFINITIONS» Hardening: improves the durability and stability of infrastructure to withstand

More information

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it

More information

Transmission Owner Asset Management

Transmission Owner Asset Management Transmission Owner Asset Management Pieces of Asset Management New customers, load growth, repairs, maintenance, operational issues, etc. All the pieces make up the asset management plan for repair or

More information

DISTRIBUTION SYSTEM SYSTEM CHALLENGES

DISTRIBUTION SYSTEM SYSTEM CHALLENGES EB-0-0 Exhibit D Page of 0 0 0 DISTRIBUTION SYSTEM SYSTEM CHALLENGES INTRODUCTION The electrical distribution system owned and operated by Toronto Hydro-Electric System Limited ( THESL ) is comprised of

More information

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10

More information

Southern California Edison. Communication Overview

Southern California Edison. Communication Overview Southern California Edison Communication Overview City of El Segundo November 15, 2016 1 Topics of Discussion Outage Overview Repair Outage Overview A Word About Maintenance Outages Outage Indexes (SAIDI,

More information

Height Pole Care and Maintenance

Height Pole Care and Maintenance Height Pole Care and Maintenance Updated 9/1/2016 Page 1 9 TABLE OF CONTENTS INTRODUCTION...3 NEW HEIGHT POLE TESTING...3 FIELD CARE OF HEIGHT POLE...3 FIELD CLEANING...3 COMPLETE CLEANING OF HEIGHT POLE...

More information

fire Charcoat Charcoat IC Passive Protection

fire Charcoat Charcoat IC Passive Protection Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a

More information

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Performance investigation of composite and RTV SIR coated insulators at a coastal test station Performance investigation of composite and RTV SIR coated insulators at a coastal test station K. Siderakis High Voltage Laboratory, Technological and Educational Institute of Crete D. Pylarinos High Voltage

More information

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216

More information

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines K. R. Suri a, A. Gupta b, Y. Anand b, S. Anand b General Manager (Retd.), Power Grid Corporation of India Limited School of Energy

More information

20 YEARS WARRANTY Against Corrosion

20 YEARS WARRANTY Against Corrosion 20 YEARS WARRANTY Against Corrosion Relating to the quality of Magnelis ZM310-type coated flat carbon steel. Subject to the conditions of this document, this warranty covers the non-perforation nonrupture

More information

Overhead Transmission - Program 35

Overhead Transmission - Program 35 Program Description Program Overview Transmission companies face issues such as improving safety and reliability, as well as reducing operations and maintenance (O&M) costs. They are also seeking ways

More information

DURABILITY of CONCRETE STRUCTURES PART 4. Prof. Dr. Halit YAZICI

DURABILITY of CONCRETE STRUCTURES PART 4. Prof. Dr. Halit YAZICI DURABILITY of CONCRETE STRUCTURES PART 4 Prof. Dr. Halit YAZICI MARINE ENVIRONMENT PHYSICAL & MECHANICAL (freeze-thaw, waves, erosion, salt crystallization) CHEMICAL Sulfate (Mg 2 SO4) BIOLOGICAL (positive&negative

More information

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance. SERVICE ENTRANCES 3.01 POINT OF ENTRANCE General Service The customer, or the customer s electrician, should provide OPPD with a site plan, load schedule, and voltage requirements when requesting service.

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

CONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS

CONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS Underground Electric Distribution Standards I. SCOPE This section includes the standards for concrete, reinforcing steel, formwork, concrete placement, curing, and construction joints. Concrete work for

More information