1 Development and performance analysis of an objectoriented model for phase change material thermal storage Michael Jokiel Project Work June 2016 July 2016 Department of Thermal Energy SINTEF Energy Research

2 Abstract On the basis of the energy system installed at the University College of Bergen (Høgskolen i Bergen) the general fundamentals of thermal energy storage (TES) are presented. In particular, the advantages of TES that consist of phase change materials (PCM) are discussed. Building climate control systems are facing dynamic boundary conditions like a changing ambient temperature or varying cooling loads inside the building. TES can be implemented in the systems to correct the gap between supply and demand and to improve the performance and reliability of the thermal system. Surplus energy could be saved and reused in case of heating or cooling shortages. PCMs are a promising type of an efficient TES. During a constant-temperature process a high amount of latent heat of fusion can be released or absorbed. Based on these conditions, a dynamic model for a PCM energy storage is developed. The utilized equations and derived relations are illustrated, followed by an explanation of the required input data. The TES model was written in object-oriented Modelica code. The model was implemented into an existing model library and validated with different sets of measurement data from both the plant in Bergen and the PCM manufacturer. The performance of the TES of the University College in Bergen was examined and assessed in comparison to provided manufacturer's performance data sheets and preliminary design calculations. The report ends with a conclusion and proposals for further work.

3 Content ABSTRACT... 2 LIST OF FIGURES... 2 LIST OF TABLES... 5 LIST OF SYMBOLS AND ABBREVIATIONS INTRODUCTION BASICS THERMAL ENERGY STORAGE PCM THERMAL ENERGY STORAGE AT UNIVERSITY COLLEGE BERGEN THE HEAT EXCHANGER MODEL FOR A PCM THERMAL STORAGE DERIVATION GENERAL LAYOUT INTERNAL STRUCTURE Liquid Cell Wall Cell PCM Cell VALIDATION FREEZING AND MELTING PROFILES MEASUREMENT AT UNIVERSITY COLLEGE OF BERGEN IN Measurement Measurement MEASUREMENT AT UNIVERSITY COLLEGE OF BERGEN IN Measurement (4 sections) Measurement (3 sections) Measurement CONCLUSION AND PROPOSAL FOR FURTHER WORK REFERENCES A APPENDIX ADDITIONAL RESULTS A.1 MEASUREMENT DATA A.2 MEASUREMENT DATA A.3 MEASUREMENT DATA A.4 MEASUREMENT DATA (4 SECTIONS) A.5 MEASUREMENT DATA (3 SECTIONS) A.6 MEASUREMENT DATA A.7 COMPARISON OF APPROACHES FOR HEAT TRANSFER COEFFICIENT ESTIMATION

4 List of Figures Figure 1 Types of energy storage (Sharma 2007, modified)... 9 Figure 2 Schematic cycle for melting and freezing of a PCM (Mehling 2008) Figure 3 PCM cold storage tanks of University College Bergen (Dar2014) Figure 4 Cooling demand over the daytime at University College Bergen (Sweco 2014, modified) Figure 5 Simplified scheme of the energy system at University College Bergen (Dar 2014) 12 Figure 6 Simplified scheme of the chilled water distribution loop (Dar 2014, modified) Figure 7 Detailed system scheme of the chilled water distribution loop at University College Bergen (Dar 2014) Figure 8 Derivation of the model: PCM containers in a PCM storage tank (a) (Dar 2014), typical heat exchanger used for most HX models (b) (TIL Library) Figure 9 Derivation of the model: Transforming stacked PCM containers to a rectangular flow channel structure (PCM Products Ltd. 2011, modified) Figure 10 Derivation of the model: New flow channel structure resembles initial heat exchanger Figure 11 Interface of the PCM heat exchanger model (Simulation environment: Dymola)17 Figure 12 Side view of the tank's internal scheme Figure 13 Input parameters as a function of tank and container geometry Figure 14 Engineering drawing for the PCM cold storage tank (Sweco2014) Figure 15 Single FlatICE container (PCM Products Ltd. 2011) Figure 16 Internal interface of the PCM heat exchanger model Figure 17 Numbers of published papers related to the topic of "phase change heat transfer" (ScienceDirect.com, July 2016) Figure 18 Calculation of the freezing time factor kfreeze time Figure 19 Measured and predicted freezing times for varying temperature differences in min Figure 20 Measured and predicted melting times for varying temperature differences in min Figure 21 Measurement , water mass flow rate in m3/h Figure 22 Measurement , water inlet and outlet temperature in Figure 23 Measurement , heat transfer rate of the PCM in kw Figure 24 Measurement , water mass flow rate in m3/h Figure 25 Measurement , water inlet and outlet temperature in Figure 26 Measurement , heat transfer rate of the PCM in kw Figure 27 Simulation end results for measurement Figure 28 Measurement (4 sections), water mass flow rate in m3/h Figure 29 Measurement (4 sections), water inlet and outlet temperature in Figure 30 Measurement (4 sections), heat transfer rate of the PCM in kw Figure 31 Simulation end results for measurement (4 sections) Figure 32 Measurement (4 sections), model's prediction of the liquid mass fraction with discretization of n = 3 (cell 1 at the front and cell 3 at the end of the tank)

5 Figure 33 Measurement (3 sections, initial x < 1), water mass flow rate in m3/h Figure 34 Measurement (3 sections, initial x < 1), water inlet + outlet temperature in Figure 35 Measurement (3 sections, initial x < 1), heat transfer rate of the PCM in kw Figure 36 Simulation end results for measurement (3 sections, initial x < 1) Figure 37 Measurement (3 sections, initial x = 1), water inlet + outlet temperature in Figure 38 Simulation end results for measurement (3 sections, initial x = 1) Figure 39 Measurement , water mass flow rate in m3/h Figure 40 Measurement , water inlet and outlet temperature in Figure 41 Measurement , heat transfer rate of the PCM in kw Figure 42 Simulation end results for measurement Figure 43 Future outlook: Potential of live visualization for non-measurable system parameters like the integrated heat transfer rate for each PCM container (side view on the tank's inlet, 2x5 stacked containers with exemplified values) Figure 44 Measurement , definition of the sections Figure 45 Measurement , integrated heat transfer rate section 1 in kwh. 55 Figure 46 Measurement , integrated heat transfer rate section 2 in kwh. 56 Figure 47 Measurement , integrated heat transfer rate section 3 in kwh. 56 Figure 48 Measurement , water mass flow rate in m3/h Figure 49 Measurement , water inlet and outlet temperature in Figure 50 Measurement , heat transfer rate of the PCM in kw Figure 51 Measurement , measured water mass flow rate in m3/h Figure 52 Measurement , measured inlet and outlet water temperature in C Figure 53 Measurement , measured and predicted outlet water temperature in Figure 54 Measurement , difference of measured and predicted outlet temperature in Figure 55 Measurement , measured and predicted heat transfer rate in kw Figure 56 Measurement (4 sections), definition of the sections Figure 57 Measurement (4 sections), integrated heat transfer rate section 1 in kwh Figure 58 Measurement (4 sections), integrated heat transfer rate section 2 in kwh Figure 59 Measurement (4 sections), integrated heat transfer rate section 3 in kwh Figure 60 Measurement (4 sections), integrated heat transfer rate section 4 in kwh Figure 61 Measurement (3 sections), definition of the sections Figure 62 Measurement (3 sections), integrated heat transfer rate section 1 in kwh

6 Figure 63 Measurement (3 sections), integrated heat transfer rate section 2 in kwh Figure 64 Measurement (3 sections), integrated heat transfer rate section 3 in kwh Figure 65 Measurement , definition of the sections Figure 66 Measurement , integrated heat transfer rate section 1 in kwh Figure 67 Measurement , integrated heat transfer rate section 2 in kwh Figure 68 Measurement , integrated heat transfer rate section 3 in kwh Figure 69 Comparison of approaches for alpha estimation, heat transfer coefficient alpha in W/m2K for case 1 "flow over plane" and case 2 "heated walls" Figure 70 Comparison of approaches for alpha estimation, water inlet and outlet temperature in for case 1 "flow over plane" and case 2 "heated walls" Figure 71 Simulation end results for measurement , heat transfer coefficient estimated applying the case "heated walls"

7 List of Tables Table 1 Parameter list for the PCM heat exchanger Table 2 Parameter list for initialization of the PCM heat exchanger Table 3 Measured and predicted freezing and melting time

8 List of Symbols and Abbreviations Greek Letters α Heat Transfer Coefficient W m 2 K 1 β Thermal Expansion Coefficient K 1 λ Thermal Conductivity W m 1 K 1 ρ Density kg m 3 η Dynamic Viscosity kg m 1 s 1 υ Kinematic Viscosity m 2 s 1 Roman Letters A Cross-Sectional Area m 2 b Flow Channel Width m b PCM Storage Tank Width m c p Specific Heat Capacity (p const.) kj kg 1 K 1 d PCM Container Wall Thickness m h Flow Channel Height m h PCM Storage Tank Height m h Specific Enthalpy kj kg 1 k Factor l Flow Channel Length m l PCM Storage Tank Length m m Mass kg m Mass Flow Rate kg s 1 n Number, Amount s 1 n Discretization Nu Nusselt-Number Q Integrated Heat Flow Rate, Energy Q Heat Flow Rate, Cooling Capacity W p Pressure bar Pr Prandtl-Number kg m s 1 R Thermal Resistance m K W 1 Ra Rayleigh-Number Re Reynolds-Number t Time s T Temperature K v Specific Volume m 3 kg 1 v Relative Fluid Velocity m s 1 V Volume Flow m 3 s 1 x Liquid Mass Fraction 6

9 Subscripts cells containers flow channel in init NS out port tank wall WE Discretization Related to PCM Containers Related to the Gap Between PCM Containers At Inlet Value for Initialization In the Direction of the Heat Flow At Outlet Related to the Heat Port of the Cell Related to PCM Storage Tank Related to PCM Container Wall In the Direction Perpendicular to the Heat Flow Abbreviations HDPE HX PCM SLE TES High-Density Polyethylene Heat Exchanger Phase Change Material Solid-Liquid Equilibrium Thermal Energy Storage 7

10 1 Introduction Buildings account for 37 % of the energy use in the EU (Perez-Lombard 2008). In order to reduce the energy demand and the climate gas emissions, the energy efficiency in buildings has to be improved. In non-residential buildings, such as offices and educational buildings, substantial amounts of waste heat are often available due to the high cooling demand. Thus, energy systems for such buildings should be designed to avoid heat disposal. This has been the design principle for the energy system at the University College in Bergen (Dar 2014). The system employs different types of thermal energy storages (TES) energy wells and phase change materials (PCM) to transfer and to store surplus heat to utilize it upon demand. This report focuses on modelling and analysis of the PCM storage system. Models of storage systems and simulations of their performance are required to be able to make assumptions and predictions on the design, dimensioning and layout of storage units. Real world test rigs can be cost intensive and especially time intensive, since the storage of thermal energy is connected to rather slow and inert processes. With the help of a model the dynamic behaviour of the system can be examined for several boundary conditions. Chapter 2 provides detailed information about the TES that is utilized at the University College in Bergen. The motivation of using PCM as a TES is discussed. After the basics about the implementation of TES are given, chapter 3 presents a derivation of a model for a PCM thermal energy storage. The required information about the utilized equations and the needed input parameters are explained. Chapter 4 includes the validation results of the modelled TES. For this sake real world measurement data is used, taken from the construction in Bergen and the PCM manufacturer. Additionally, the performance of the installed PCM storage system in Bergen is evaluated and comparisons to the assumptions that were applied at the design phase are made. In particular charging and discharging dynamics of the PCM storage are examined. The last chapter summarizes the conclusions that were drawn from the analysis. The presented results increase the understanding of the PCM storage and should provide a base for improved implementation of such a storage in future systems. Finally, deficits of the current model are presented and activities for further work are proposed. 8

11 2 Basics 2.1 Thermal Energy Storage An energy storage provides the ability to capture energy produced at a point of time for later utilization. Energy is available in different forms, such as thermal, chemical, electrical, potential and kinetic. The energy storage often involves converting energy from forms that are difficult to store to more conveniently storable forms. Figure 1 presents the different types for energy storages. Figure 1 Types of energy storage (Sharma 2007, modified) Thermal energy storage (TES) has been recognized as one of the most efficient ways to enhance the energy efficiency and sustainability of heating and cooling systems (Liu 2016). Storing high or low temperature energy for a later use can bridge the time gap between energy availability and energy use. That way the use of TES in building applications can improve the indoor thermal comfort, reduce machinery size, decrease running cost, improve the system reliability and therefore enhance the total energy efficiency. Thermal energy can be stored in PCMs. Due to their high latent heat during phase change processes large amounts of energy can be stored in relatively small volumes. The stored energy can be retrieved when the process is reversed. Figure 2 illustrates that heating and cooling the material occurs without a temperature change during the actual phase change. Therefore an energy flow to the PCM can be provided even if only small temperature differences between the PCM and the heat transfer fluid are available. 9

12 Figure 2 Schematic cycle for melting and freezing of a PCM (Mehling 2008) A subcooling effect results from nucleation processes during the beginning of the PCM freezing. It is dependent on the type of the PCM, just as the particular freezing and melting temperature. The choice of a proper PCM with a suitable freezing/melting temperature is dependent on the overall cooling system and can be customized for any application. The following section gives a small overview of the energy system at the University College in Bergen. Furthermore the procedure for implementing a PCM thermal energy storage system in the energy system will be discussed. 2.2 PCM Thermal Energy Storage at University College Bergen This section gives a brief explanation on how to implement a TES into an energy system. For this sake the energy system of the University College of Bergen will be displayed, which features four PCM cold storage tanks (see figure 3) in its chilled water distribution loop. 10 Figure 3 PCM cold storage tanks of University College Bergen (Dar2014)

13 These tanks are filled with small containers that contain PCM. The salt hydrate in these containers has a phase change temperature of 10 C (PCM Products Ltd. 2011). Water flows through the tanks and through the small flow passage between the stacked PCM containers. The educational building of the University College of Bergen has a total area of over 50,000 m² and was projected for an annual heating demand of 2600 MWh and a cooling demand of 1060 MWh. Its peak heating and cooling loads are 2830 kw and 3000 kw, respectively (Dar 2014). The installed cooling capacity is higher than the heating demand, due to the high amount of excess heat during summer months due to solar radiation and high internal loads from students, computers, servers, IT rooms, etc. To maintain the thermal comfort of the building on an appropriate level the room temperature needs to stay at minimum 18 C (Uno 2007), despite a fluctuating ambient temperature and varying internal loads. An implemented TES has a compensating effect that enables the system to react to transient peak ambient temperatures without increasing the power consumption of the heat pump system. Figure 4 illustrates the potential of decreasing the machinery size of the cooling system after an implementation of a thermal storage at the energy system of the University College in Bergen. Figure 4 Cooling demand over the daytime at University College Bergen (Sweco 2014, modified) The utilized liquid chillers are providing an averaged capacity of only 1400 kw over the whole daytime, although the peak load of the cooling demand is 3000 kw. Furthermore, the cooling demand during the night-time is drastically reduced. Thus, a thermal storage unit can utilize this discrepancy and save the cooling capacity at night to release it on demand during 11

14 the day. Thus, there is no necessity to design the liquid chillers to cover the peak load, which leads to smaller machinery size and thus lower operating costs. To optimize investment costs and to minimize operational costs, the heating and cooling production system combines an ammonia heat pump/chiller installation with thermal energy storages: a ground-source TES for seasonal energy storage and four PCM accumulation tanks to provide peak load cooling and backup cooling capacity (Dar 2014). Thus, the PCM tanks are used as daily energy storage. A simplified scheme of the integrated thermal energy system can be seen in figure 5. Figure 5 Simplified scheme of the energy system at University College Bergen (Dar 2014) The report focuses on the performance evaluation of the PCM cold storage and the chilled water distribution loop. Therefore only the cooling performance of the energy system will be evaluated, leaving aside the heating system, the adiabatic cooling system and the ground source TES. A simplified scheme of the evaluated subsystem is shown in figure Figure 6 Simplified scheme of the chilled water distribution loop (Dar 2014, modified)

15 The PCM cold storage tanks are positioned in the chilled water distribution loop. Four tanks with a total volume of 228 m 3 (single tank volume 57 m 3 ) and a total storage capacity of 11,240 kwh (single tank capacity 2810 kwh) are implemented in the energy system, rendering the PCM storage system the largest of its kind in Europe. The PCM storage enabled a ~50 % reduction in the installed chiller cooling capacity resulting in reduced operational costs for the energy system. Furthermore, an investment cost reduction was obtained, mainly due to the reduction in the installed chiller cooling capacity and the number of boreholes (Dar 2014). Figure 7 shows a detailed system scheme for the chilled water loop, implementing the PCM storage tanks into the energy system of the University College in Bergen. Figure 7 Detailed system scheme of the chilled water distribution loop at University College Bergen (Dar 2014) The model derived in chapter 3 will simply consist of the PCM tank and inlet and outlet boundaries for the water (orange rectangle in figure 7). The blue and yellow dashed lines in figure 7 mark the flow directions for water, corresponding to different operation modes for the PCM storage tanks. When the PCM tanks are not in use, the equivalent bypass valves are closed and no mass flow occurs at the energy meter OE03. The purpose of the chilled water loop is to provide water for space cooling at a supply temperature of 7 13 C at an 13

16 inlet/return temperature of approximately 17 C. In case the PCM tanks are used, two different operation modes can be distinguished: The mass flow direction marked with blue in figure 7 represents the operation mode of charging or freezing of the PCM. In this mode, the bypass valves allow a mass flow of chilled water into the PCM tanks. The mass flow is supplied from the supply/inlet side of the space cooling unit, resulting in a reduced cooling capacity that can be provided to the building. The charging operation mode will be usually initiated if the inlet water temperature (sensor RT02) reaches a very low level of < 7 C or if the cooling demand of the building is generally on a reduced level, for example at night-time operation. The mass flow direction marked with yellow in figure 7 displays the operation mode of discharging or melting the PCM. In this case the PCM storages are fed by heated water from the space cooling return/outlet side, for example in case of return water temperatures of > 17 C (sensor RT01). Without the cooling effect of a discharging PCM storage, the overheated water would result in an increased power demand in the heat pump/chiller unit. Hence, with a proper application of the charging and discharging ability of the PCM storage tanks, surplus cooling capacity can be used (in the form of freezing the PCM) to compensate peak cooling demands (in the form of melting the PCM), leading to an increased overall efficiency of the cooling system. Precise knowledge about the dynamic charging and discharging behaviour of the PCM storage is fundamental for designing and dimensioning a storage system. Models and simulations can provide new information and understanding about the storage performance. Consequently, the next chapter discusses an approach for modelling a PCM thermal storage. 14

17 3 The Heat Exchanger Model for a PCM Thermal Storage In this chapter the general approach for modelling a PCM thermal energy storage system will be discussed. The PCM storage model has been implemented using already existing Modelica libraries for thermal fluid systems. "TIL" is a model library for thermal components and systems, while "TIL Media" contains a model library including thermophysical properties for the utilized fluids (Frohböse 2015). These libraries were provided by TLK-Thermo GmbH, a German company for simulation technology and software development. The aim with the Modelica model is to be able to investigate the charging and discharging dynamics and hence to increase the understanding of the PCM storage. That way the model could provide a best practice data sheet and a base for a more optimal implementation of future systems. 3.1 Derivation The first challenge in modelling a TES consisting of PCM is to find suitable equations and relations to express the real world behaviour of the storage. Since a thermal storage is basically just exchanging heat with the chilled water distribution loop, a suitable approach for a model is to use a simple heat exchanger (HX) model and modify and extend it to represent a PCM cold storage. A derivation for this modification and extension will be given in this section. The utilized PCM storage tank from the University College of Bergen is filled with smaller PCM containers that are stacked inside the tank, as shown in figure 8 (a). The water flows in between these containers. Figure 8 (b) shows a typical heat transfer model, which served as a general starting point for the present PCM storage model. Figure 8 Derivation of the model: PCM containers in a PCM storage tank (a) (Dar 2014), typical heat exchanger used for most HX models (b) (TIL Library) 15

18 The actual PCM storage is cylindrical. However, for simplification, a rectangular model was applied. Figure 9 illustrates the steps of transforming the stacked PCM containers in a cylindrical tank to a setup that resembles an ordinary rectangular HX structure. Figure 9 Derivation of the model: Transforming stacked PCM containers to a rectangular flow channel structure (PCM Products Ltd. 2011, modified) After the PCM containers are stacked in a compact way inside the tank, a cross-sectional area as shown in figure 9b is formed. Figure 9c assumes that the walls between individual containers that are arranged side by side can be neglected. Hence, the formerly tubes of the ordinary HX model from figure 8b are now the gaps between the containers, resulting in very wide, flat and narrow water flow channels. Finally, figure 9d is derived by transforming the formerly round shape of the tank into a square one while the cross-sectional area of the tank is kept constant. A square cross-sectional flow area will be easier to manage in regard to mass flow and heat transfer calculations. Figure 10 Derivation of the model: New flow channel structure resembles initial heat exchanger Figure 10 summarizes the geometric derivation of the model. The newly derived HX model in figure 10b resembles an ordinary HX model. To apply an existing HX model for the PCM tank, the following assumptions need to be made: - Flat rectangular flow ducts are used within the HX instead of ordinary round pipes. - The walls of the flow channels are the walls of the PCM containers. 16

19 - A mass flow is only existent on the water side. The PCM side of the HX is a closed system with a constant mass of PCM. - The mass flow of water occurs in one direction. There is no occurrence of backflow or recirculation flow within the PCM tank. - No additional geometries like fins are used in the PCM heat exchanger. The heat transfer occurs only between the boundaries of "water to container wall" and "container wall to PCM". The following section provides further information about the composition and parametrization of the modified HX model. 3.2 General Layout This chapter gives a detailed overview of the model's general structure and its parametrization. The layout of the HX model will be illustrated and exemplary estimations for the input parameters are given. Figure 11 shows the setup of the model. Figure 11 Interface of the PCM heat exchanger model (Simulation environment: Dymola) 17

20 The setup consists basically of three main parts: In the upper right corner is the SIM-block. It provides the required material data and properties of the liquid (water), the PCM (salt hydrate, type "S10", manufacturer PCM Products Ltd.) and the container's wall (high-density polyethylene, HDPE). On the left hand side in figure 11 are the file reader blocks, which provides the measurement data for the simulation. More information about the utilized measurement data is given in chapter 4. The measurement data is used as an input for the actual PCM heat exchanger block in the middle of figure 11. The HX block is estimating the heat transfer rate between a layer of PCM containers and the half of its surrounding flow channel on each container side. The corresponding system boundaries for the model are shown in figure 12. Figure 12 Side view of the tank's internal scheme Since the water is assumed to be equally distributed over the cross-sectional area, the heat transfer rate will be the same for each particular container layer. After the heat transfer rate for one layer (Q PCM,container layer) has been calculated, it will be multiplied with the total amount of flow channels to compute the tank's overall heat transfer rate (Q PCM). The disadvantage of this method is that the tank material itself (i.e. the mass of the steel wall) is not considered in the calculation. This simplification is discussed in detail in the validation chapter 4. The remaining blocks on the right side in figure 11 are serving for performance analysis or debugging. The input parameters for the PCM storage model are listed in Table 1. 18

21 Table 1 Parameter list for the PCM heat exchanger Input Parameters PCM Storage Discretization in Direction of the Flow Channel Discretization in Direction of the PCM n cells,flow channel Tank Height h tank [m] Tank Length l tank [m] Container Wall Thickness d wall [m] n cells,pcm Tank Width b tank [m] Number of Flow Channels n flow channels Flow Channel Height h flow channel [m] Measured Inlet Water Temp. T water,in [ C] Measured Mass Flow Rate m water [ kg s ] Material Properties of the PCM Material Properties of the Wall (HDPE) In addition to the parameters presented in Table 1, the measured outlet water temperature T water,out and the measured cooling capacity Q PCM will be utilized in the validation (see chapter 4). The differentiation between the discretization in the direction of the flow channel and in the direction of the PCM is due to the internal structure of the PCM storage model, which will be discussed in chapter 3.3. Most of the required input parameters from table 1 are dependent on the dimension of both the PCM cold storage tank and the particular PCM containers, as illustrated in figure 13. Figure 13 Input parameters as a function of tank and container geometry In addition, initial values are required as well (table 2). Initial values influence the quality of the model's calculations especially in the beginning of the simulation (see chapter 4.3.2). Table 2 Parameter list for initialization of the PCM heat exchanger Initial Parameters PCM Storage Freezing Progress in Direction of the Channel Freezing Progress in Direction of the PCM x init,flow channel Water Temperature T init,water [ C] PCM Temperature T init,pcm [ C] x init,pcm Wall Temperature T init,wall [ C] 19

22 The PCM cold storage tanks that are used in the University College of Bergen has been designed by the Swedish engineering consultancy company Sweco. Figure 14 shows the engineering drawing for a 57 m 3 PCM tank. Figure 14 Engineering drawing for the PCM cold storage tank (Sweco2014) As mentioned in chapter 2.2, these tanks are filled with small containers that contain PCM. The containers are called FlatICE elements, provided by the British company PCM Products Ltd. The salt hydrate in these containers has a phase change temperature of 10 C (PCM Products Ltd. 2011). Water flows through the tanks and through the small flow passage between the stacked PCM containers. 20 Figure 15 Single FlatICE container (PCM Products Ltd. 2011)

23 Figure 15 shows the dimensions for a single PCM container. The nominal height is 45 mm. However, when several PCM containers are stacked on top of each other, squeezing occurs. This leads to a decreased height of the container. For that case, the manufacturer of the containers, PCM Products Ltd., suggests to assume a container height of 40 mm. With all the provided geometric data from figure 14 and figure 15, the values for the flow channel dimensions and the input parameters in table 1 can be calculated. The length of the water flow channel equals the length of the PCM tank. l tank = l flow channel = 9 m (1) The total cross-sectional area of the PCM tank is given in figure 14 with A = 6.35 m 2. Since the modelled PCM tank has a square shape (see derivation in chapter 3.1) and since the width of the flow channel equals the width of the overall tank (when the effect of the walls on the side is neglected), the width of the flow channel is b tank = b flow channel = 6.35 m 2 = 2.52 m (2) The height of the flow channel is the gap between two PCM containers. The gap is formed due to the small round auxiliary platforms of the containers, as shown in figure 15. h flow channel = 40 mm 32 mm = 8 mm (3) The total number of PCM containers that can be stacked within the PCM tank is the ratio between the tank height and the container height n containers = h tank 2.52 m = h container 0.04 m = 63 (4) Therefore the amount of flow channels is n flow channels = 63 as well. All these parameters will be used within the PCM heat exchanger model to estimate the performance of the storage. How the heat transfer is calculated will be discussed in detail in the following chapter. 21

24 3.3 Internal Structure The PCM heat exchanger model consists basically of three different types of cells. Liquid cells are connected with the PCM cell over wall cells as shown in figure 16. Figure 16 Internal interface of the PCM heat exchanger model Figure 16 shows the internal structure of the PCM heat exchanger model. This structure resembles the tank's internal scheme from figure 12. The discretization of the particular cells is possible along the water flow channel and in depth direction to the PCM. Therefore, n cells,flow channel and n cells,pcm are eligible parameter for the simulation. While n cells,flow channel affects the discretization of all three cell types, n cells,pcm is only discretizing the PCM cell into the direction of the heat transfer (which is perpendicular to the water flow direction). The heat transfer rate in each cell is dependent on the type of heat transfer and will be discussed in detail in the following sections Liquid Cell The energy balance equation for the liquid cell is m water c p dt water dt = m in h in + m out h out + Q (5) For the present case, three different options for the heat transfer type are possible: Conduction, natural convection or forced convection. Whether the dominating type of heat 22

25 transfer is conduction or convection, can be deduced from the Rayleigh number (Ra), a dimensionless number in fluid mechanics. It is calculated as Ra = c p ρ g β ΔT l 3 υ λ (6) With applying the gravitational acceleration g in m/s 2, the thermal expansion coefficient β in K 1, the characteristic length l in m, the kinematic viscosity υ in m 2 /s and the thermal conductivity λ in W/mK. Computing the Rayleigh number for several possible boundary conditions for the present case lead always to a Rayleigh number of > 1700, which indicates that forced convection is the dominant heat transfer type for the liquid cell. The heat transfer rate for forced convection is Q water = α water A (T port T water ) k temp dependence (7) The heat transfer area A describes the area between water and wall. For example, in case of a single PCM container with a discretization of 1 into every dimension, the heat transfer area would be 0.5 m 0.25 m = m 2 (see figure 15). The factor k temp dependence considers the change of the water's thermophysical properties as a result of a changing temperature between the water directly at the wall and in the middle of the flow channel (VDI Heat Atlas 2013): Pr k temp dependence = ( ) Pr atwall 0.25 (8) Finally, to calculate the heat transfer coefficient α water and to describe the forced convective heat transfer for the particular case of a PCM heat exchanger, several possible cases can be found in literature. The validation showed that the best simulation results are obtained when assuming the case "flow over a horizontal plane", followed by the case "flow in a flat gap between two heated walls". The equations and the simulation results for the case "flow in a flat gap between two heated walls" will be given in the appendix chapter A.7. For the case "flow over a horizontal plane", the heat transfer coefficient becomes (VDI Heat Atlas 2013): 23

26 α water = k freeze time λ Nu l flow channel (9) The freezing time factor k freeze time is considering the effect, that the time for freezing the PCM is greater than the time for melting the PCM. Further information and a calculation of this factor will be given in the section of PCM heat transfer in the end of this chapter. The Nusselt number can be calculated from Nu = Re Pr 1 3 (10) This equation is valid for laminar flows with Re < (1^5). Chapter 4 will show a maximum water volume flow of up to 100 m 3 /h, resulting in a Re of slightly higher than 1^5. However, tests with a Nusselt number for turbulent conditions resulted in only minor changes to the overall quality of the simulation results. The corresponding Reynolds number is Re = l flow channel v ρ η (11) With applying the dynamic viscosity η in kg/(ms) and flow velocity v of v = m ρ A flow channel (12) The calculation of the flow velocity might be inaccurate, since the small auxiliary platforms of the PCM containers are affecting the flow conditions within the rectangular flow channels. This effect was however neglected in the present study Applying equations 7 12, the convective heat transfer in the liquid cell can be estimated Wall Cell The energy balance equation for the wall cell is m wall c p dt wall dt = Q wall,portn + Q wall,ports + Q wall,portw + Q wall,porte (13) While the liquid cell only possesses one single heat port that connects the liquid cell with the adjacent wall cell, the wall cell itself possesses four heat ports. Two of them are connected to the liquid cell (port "S") and the PCM cell (port "N"). The remaining two ports on the side 24

27 of the wall cell are connected to the previous (port "W") and next wall cell (port "E"), in case of a discretization of n cells,flow channel > 1. For this case the heat transfer type is clearly just heat conduction. The respective heat transfer rates are calculated for each heat port separately: Q wall,portx = T portx T wall R X (14) With R X as the heat resistance in Km/W, which is dependent on the direction of the heat transfer. The heat resistance in the direction of the heat transfer is R NS = d wall/2 λ HDPE A NS (15) And in the direction perpendicular to the heat transfer the heat resistance is R WE = l WE /2 λ HDPE A WE (16) The "NS" and "WE" subscripts are identifying the particular cross-section areas for calculating the heat resistance in the direction of the tank's length ("WE") and in the direction of the tank's width ("NS"). Thus, R NS is the heat resistance for the heat transfer between water and PCM, and R WE is the heat resistance for the heat transfer between the particular wall cells PCM Cell The balance equation for the PCM cell is m PCM dh PCM dt = Q PCM,portN + Q PCM,portS + Q PCM,portW + Q PCM,portE (17) The main difference to the balance equations of the liquid and wall cell is the use of the derivation of the enthalpy instead of the derivation of the temperature, because the proper calculation of the thermal capacity c p in the area of the phase change is nontrivial. The determination of the heat transfer type for the PCM cell is quite challenging. In the case of a completely frozen PCM the heat transfer will be just heat conduction. But as soon as the PCM starts to melt, the heat transfer type will start to change. On the one hand the thermal conductivity λ will alter with the change of the phase and the liquid mass fraction x. On the other hand, as soon as molten PCM is formed, it will start to move within the PCM container, 25

28 leading to a heat transfer that resembles natural convection. The same applies for complete liquid PCM. The part of the PCM that is close to the wall will change its temperature and thus its properties. That way a changed buoyancy can lead to small mass flows within the container, affecting the heat transfer type. Finally, the most challenging case is the beginning of freezing. The emerging and increasing layer of frozen PCM directly at the wall might act as some sort of an isolator for the remaining liquid PCM, leading to a higher freezing time than melting time for PCM storages (see freezing/melting profiles in chapter 4.1). Libeer (2016) proposes the following explanation for the huge difference in the melting and freezing time: The convective heat transfer rate is highly dependent on the buoyancy force that is dominant during the melting of pure PCM. Fluctuating liquid water within the PCM cell is increasing the heat transfer rate. That way, the time to melt the PCM decreases drastically in comparison to the freezing process. Sun (2015) explains the time difference of the phase changes with the temperature difference within the PCM container as well. The temperature difference enhances the natural convection within the cell, since liquid PCM has a lower density and viscosity than the solid PCM. With progressing PCM melting, liquid PCM continues to move to the top of the container while the solid PCM descends to the bottom, thus enhancing the melting process and reducing the melting time. Therefore, the heat transfer rate for horizontally aligned PCM containers is higher on the lower side of the PCM containers than on the upper side. In recent years the effort in researching the phenomena of heat transfer that is related to PCM has greatly increased. Figure 17 shows the number of published papers related to the topic. The number of published papers is raising each year. This shows on the one hand the increased attention towards the topic of PCM thermal storage. On the other hand it shows the need for further research on the topic of phase change related heat transfer. General understanding of the PCM heat transfer is required as well as more detailed equations to describe the heat transfer for a PCM with appropriate quality. 26

29 Figure 17 Numbers of published papers related to the topic of "phase change heat transfer" (ScienceDirect.com, July 2016) At present, for the model utilized in this project report, it is assumed that the heat transfer type is mere heat conduction nevertheless. Thus, the applied equations for PCM cell are analogous to the equations applied to the wall cell (equations 14 16). Q PCM,portX = T portx T wall R NS (18) R NS = R WE = d wall 2 λ PCM A NS (19) l WE 2 λ PCM A WE (20) To consider at least the general difference between melting and freezing time, a factor k freeze time is introduced in the heat transfer equations for the liquid cell (see equation 9). This factor was implemented into the liquid cell instead of the PCM cell, since it is easier to affect the model's performance with changes of the heat transfer coefficient of the liquid side than with changes of the heat transfer resistance of the PCM cell. Therefore it was decided that the freezing progress of the PCM cell is directly affecting the heat transfer coefficient of the water α liq, utilizing the factor k freeze time : α liq = f(k freeze time ) (21) The factor k freeze time is a function of the liquid mass fraction of the PCM. To compute k freeze time, a polynomial regression function is used: 27

30 k freeze time = f(x PCM ) = ax 3 + bx 2 + cx + d (22) The parameters for the regression function are adjusted such that the heat transfer coefficient becomes smaller when the molten PCM starts to freeze. Figure 18 shows the model's setup for calculating k freeze time. Figure 18 Calculation of the freezing time factor k freeze time Most of the time, k freeze time equals one. It will decrease to a lower value (< 1) and thus start to slow down the heat transfer rate as soon as dx becomes negative, which implies the start of freezing. As discussed before, the freezing process of the PCM is increasingly covering the wall with frozen PCM, leading to a delayed heat transfer in comparison to the melting processes. However, to keep k freeze time from delaying the heat transfer every single time a partial or only transient freezing process occurs, a hysteresis is added to ensure the factor k freeze time is just taking action for cases when it is actually required. All the equations required for describing the heat transfer of the PCM heat exchanger have now been introduced. Therefore, the introduction of the model's internal structure is completed and the following chapter will discuss the validation results and performance evaluation. dt 28

31 4 Validation In this chapter the simulation results will be compared with measurement data to assess the accuracy and quality of the PCM storage model. For that purpose the British PCM manufacturer PCM Products Ltd. and the Swedish engineer company Sweco provided several sets of freezing/melting profiles and measurement data. Three different data sets were available. Each of these will be used for validation in the following chapters. The complexity of the validation will increase with each chapter. In chapter 4.1, the melting and freezing profiles will be used to verify the model's estimations for the freezing and melting time, with a constant mass flow and a constant inlet temperature. Chapter 4.2 utilizes measurement data from the PCM storage at the University College in Bergen, thus the inlet temperature changes over time and the model's dynamic response can be evaluated. However, only limited phase change processes occur during the recorded time period and the focus of the validation lies on the correct calculation of the sensible heat transfer. Finally, in chapter 4.3 measurement data with highly dynamic operation modes is utilized. The model needs to consider the changing inlet temperature and changing inlet mass flow. Furthermore, actual charging and discharging cycles with complete freezing or melting cycles need to be predicted by the model. The chapter concludes with an evaluation of the general measured PCM tank performance. 4.1 Freezing and Melting Profiles 2011 Freezing and melting profiles serve to describe the general behaviour of a PCM in regard to its performance during phase change processes. Every PCM features individual characteristic freezing and melting profiles. The profiles used in this chapter are provided by the PCM manufacturer PCM Products Ltd. Table 3 compares the measured values taken from the PCM Products Ltd. profiles with the predicted values from the model. Figures 19 and 20 compare the trajectory of the measured and predicted freezing and melting profiles, respectively, as a function of the temperature difference. 29

32 Table 3 Measured and predicted freezing and melting time Temperature Measurement Model Measurement Model Difference T t freezing t freezing t melting t melting Figure 19 Measured and predicted freezing times for varying temperature differences in min 30 Figure 20 Measured and predicted melting times for varying temperature differences in min

33 The temperature difference is the difference in temperature between the supplied water and the PCM, which is kept close to the freezing/melting temperature point. Thus, the freezing and melting time decreases with increasing temperature difference. As already discussed in chapter 3.3, the melting time is only half of the freezing time. Based on figures 19 and 20, the model is capable of estimating the correct trajectory for the freezing and melting time. Unfortunately, no information was available about the mass flow that was applied when the measured profiles were recorded. However, as shown in chapter 3.3, the heat transfer coefficient is a function of the Reynolds number and thus of the mass flow rate. The heat transfer rate is different for every mass flow. The mass flow rate for the model was set to 10 m 3 /h, a value taken from the measurement sets of the following chapters. Therefore the freezing and melting profiles can be just utilized for a very preliminary validation to reproduce the general trajectory for the freezing time and melting time. Furthermore, the freezing and melting profiles were used to adjust the parameters of the regression function (equation 22) to calculate the freezing factor k freeze time (section 3.3). Without the freezing factor the values for the freezing and melting time would be almost equal. 4.2 Measurement at University College of Bergen in 2015 The following measurement data set of the PCM cold storage performance was collected by Sweco from until at the University College in Bergen, during normal operation of the building and the energy system. The PCM cold storage was little used during the investigated period. Because of summer vacations, few people were present in the building, and the weather was rather cold, leading to a low cooling demand. Therefore the cooling capacity from the heat pump together with the adiabatic cooling system were sufficient to supply the building's cooling demand. Nevertheless, the data set can be used to validate the PCM storage model in the region of sensible heat transfer with T PCM < 10 C and a liquid mass fraction of x = 0. The particular measurement data set that was utilized for the validation of the model consists of: supply and return temperature T water,in and T water,out, the mass flow rate m water into the PCM tanks, and the cooling capacity Q PCM of the PCM storage. 31

34 The values for the inlet temperature and the mass flow rate are used as input parameters for the model. The measured outlet temperature and cooling capacity serve for the comparison to the predicted outlet temperature and the predicted cooling capacity by the model Measurement The first measurement excerpt used for the validation is a two days recording with just sensible heat transfer, no phase change and a constant mass flow rate. Figures illustrate the general operation mode of the PCM storage during the measured two days. The inlet temperature of the water was only changing by 2 K. For the first twelve hours the inlet and outlet temperature are the same, implying a system in a steady state. Thus, the heat transfer rate is zero as well (figure 23). In the subsequent hours the inlet temperature starts to fluctuate. The model is capable of estimating the correct outlet temperature from the PCM tank. However, each time a local peak occurs in the outlet temperature, the model is struggling with calculating the correct temperature. Figure 23 shows at :00 that the modelled PCM storage is not capable to provide an appropriate heat flow rate to keep the outlet temperature above the inlet temperature. A reason might be that the steel tank mass was not considered (see chapter 3.2). With an additional thermal mass that is capable of saving thermal energy during the steady state operation mode before, the predicted outlet temperate could have kept closer to the initial temperature of 8 C and thus closer to the measured outlet temperature. However, quite satisfying validation results are obtained with progressing measurement data. After :00 both the simulated and measured outlet temperature are very close. The same applies for the simulated and measured heat transfer rate in figure 23. In the next step, to increase the complexity of the inputs for the model, the following measurement data set will provide a changing mass flow rate. 32

35 Figure 21 Measurement , water mass flow rate in m 3 /h Figure 22 Measurement , water inlet and outlet temperature in Figure 23 Measurement , heat transfer rate of the PCM in kw 33

36 4.2.2 Measurement Figures present measured and simulated data from another period in The main difference in this data set in comparison to the measurement from June 7 th is the varying water mass flow rate and a short time period with partial melting. The first hours consist of a steady state operation mode, leading to a heat flow rate of approximately zero, as shown in figure 26. After 24 hours, at :00, the mass flow decreases to zero for roughly six hours (figure 24). When the water mass flow increases again, the inlet water temperature has increased from 9 to 17 C, causing a partial melting process of the formerly frozen PCM (figure 25). At :00 the inlet temperature is decreased to 9 C again, leading to a decreasing outlet water temperature that is slowly converging towards T in. The model predicts the outlet water temperature with a proper tendency, as it can be seen in figure 25. During the period when no mass flow occurs (starting at :00) the predicted outlet temperature remains the same, while the measured outlet temperature increases. This results from the increasing inlet temperature, since figure 26 shows that there is no heat transfer from the PCM during this time period. Despite this minor inaccuracy of the model during that special operation mode, the outlet temperature is predicted correctly again when the mass flow is applied at :00. After the mass flow increases again the inlet temperature increases to 17 C. The model calculates a slightly lower outlet peak temperature than the measured one. However, the simulated heat transfer rate is exactly the same as the measured one during that period. An explanation might be that the fluctuating mass flow has caused inaccuracies for the temperature sensor, since a manual calculation of the heat transfer rate for this particular point leads to the same outlet temperature the one given by the model. After the inlet temperature has decreased to 9 C again at and after the PCM starts to completely freeze again at :00, the model predicts an outlet temperature close to the melting temperature of 10 C, which is approximately 0.5 C higher than the measured outlet temperature. This difference might arise from the improper calculation of the heat transfer during the dynamic phase change. Partial melting and freezing processes impact the heat transfer rate, since the local boundary conditions directly at the PCM container wall are changed for every particular liquid mass fraction x. As discussed in chapter 3.3, adequate equations to predict this specific behaviour in a more detailed way are currently lacking. 34

37 Figure 24 Measurement , water mass flow rate in m 3 /h Figure 25 Measurement , water inlet and outlet temperature in Figure 26 Measurement , heat transfer rate of the PCM in kw 35

38 Nevertheless the results of the model's calculations are satisfactory. Figure 27 shows the results of the live simulation after the end of the measurement period at :00. The yellow blocks on the right hand side in figure 27 show the measured and modelled integrated heat transfer rates and thus the amount of energy the PCM has absorbed and released during the investigated time period. Figure 27 Simulation end results for measurement Section 1 ends at :00 and covers the time period when outlet and inlet temperature are roughly the same. The integrated heat transfer for that section (first row of yellow blocks in figure 27) correctly implies that almost no energy was transferred during that steady state operation mode. Section 2 starts when the mass flow increases again and ends when the inlet temperature decreases to 9 C at :00. It represents the melting section and the model successfully estimates the correct amount of transferred energy for that period (second row of yellow blocks in figure 27). The remaining part of the simulation is covered by section 3, displaying the freezing part. As mentioned in the discussion above, the modelled PCM is releasing too much energy during this section (20 % more than the measurement) leading to an increase in the predicted outlet temperature. The graphs for the particular integrated heat transfer rates as a function of the time are given in the appendix. These graphs will be presented in the appendix for each of the subsequent chapters as well. 36

39 In general the validation of the model after applying the measurement data sets from 2015 is quite satisfactory. With the measurement of June 7 th the estimated water outlet temperature was predicted too close to the measured water inlet temperature. On the contrary, with the measurement of June 21 st the estimated water outlet temperature was too close to the PCM storage temperature. Nevertheless the overall deviation of the simulated outlet temperature from the measured outlet temperature was quite low. Figure 54 in the appendix A.3 illustrates that the deviation between estimated and measured outlet temperature is generally less than 0.5 K for the whole measurement data of The chapter illustrated some inconsistencies between the simulation and the measurement. With these deviations in mind, the following measurement data set will focus on evaluating the PCM storage behaviour in connection to complete charging and discharging cycles. 4.3 Measurement at University College of Bergen in 2016 The measurements presented in this section were conducted by Sweco from until For several days in the recorded time period the PCM storage setup was run in a test mode. Instead of supplying all four PCM tanks with water, only one single tank was operated while the others were bypassed. Since the measurement data of 2015 illustrated that the PCM storage tanks were barely in use, an operation mode with only a quarter of the original amount of PCM mass is supposed to provide new information about the freezing and melting processes with preferably complete freezing/melting of the PCM tank. The overall system performance during the charging and discharging cycles and the actual status of the particular tanks could hence be better evaluated Measurement (4 sections) Measured and simulated data for the mass flow rate, inlet and outlet temperatures and heat flow rate from is shown in figures 28, 29 and 30, respectively. The test mode with only PCM tank #1 in operation started from May 30 th 11:30 and lasts until June 1 st 5:30. During that time the tank is operated in a highly dynamic operation mode and performs four charging/discharging processes. This is the reason for calling this chapter "4 sections". In the subsequent chapter the same measurement data will be investigated, but with only three charging/discharging sections to stress the importance of the initialization of the model. 37

40 Figure 28 Measurement (4 sections), water mass flow rate in m 3 /h Figure 29 Measurement (4 sections), water inlet and outlet temperature in Figure 30 Measurement (4 sections), heat transfer rate of the PCM in kw 38

41 Apart from a very short period in the middle of the measurement period, the mass flow was constantly higher than zero (figure 28). The inlet water temperature was varying between 16 C for the melting sections and 5 6 C for the freezing sections (figure 29). The model is capable of reproducing the general trajectory of the measured outlet temperature. The biggest deviations of the model's estimation, especially in regard to the predicted heat transfer rate, occurs in the melting sections (1 and 3 in figure 29). Both in section 1 and in section 3 the predicted outlet temperature is missing the correct value for the outlet temperature during the very beginning and during the very end of the respective section. A reason might be that in chapter 3.3 only a factor for modifying the freezing time (k freeze time ) has been implemented to consider the effect of the freezing process on the ordinary heat transfer coefficient. However, figures 29 and 30 illustrate that the melting progress appears to have a larger impact on the heat transfer as expected. The ordinary heat transfer coefficient seems to be influenced by the melting process, but in a slightly moderated way than by the freezing process. Thus, a factor for the melting behaviour k melting is currently lacking and needs to be included in the model in the future. As for the freezing in section 2 and section 4, the trajectory of the predicted outlet temperature resembles the one of the measured outlet temperature. Although the progress seems to be different for both trajectories, both are roughly converging towards the same temperature at the end of the section. The same observation is valid for the heat transfer rate, which has a different slope for the predicted and the measured value as well. The predicted heat transfer during the freezing process seems to increase too much during the very beginning of the section and remains on a slightly lower level than the measured heat transfer which seems to have a more consistent trajectory in general. This chapter shows furthermore, that a general understanding and a thorough interpretation of the measured values is essential for improving the quality of the model. The measurement illustrates a tank behaviour that cannot be completely specified by appropriate equations yet. Figures 28 shows a varying mass flow rate of approximately m 3 /h for both melting sections, with a decreasing mass flow rate in section 1 and an increasing mass flow rate in section 3. However, the corresponding heat transfer rates for these sections (figure 30) remain on slightly the same level ( kw for section 1 and 120 kw for section 2, with a transient peak of 200 kw). In comparison, the heat transfer 39

42 rates during the freezing sections 2 and 4 are altering more, between a value of roughly kw, despite of a constant mass flow rate in section 2 and section 4 (100 m 3 /h and 60 m 3 /h, respectively). The trajectory of the heat transfer rates are very similar for both freezing sections, although the mass flow rate is differing by a factor of almost 2. Also, the measured outlet temperature seems to converge faster towards the value of the inlet temperature during the freezing sections than in the melting sections (figure 29). It appears the heat transfer rate during the freezing process in the tank is less dependent on the mass flow rate as supposed in chapter The heat flow rate during melting processes seems to be steadier than the more fluctuating heat transfer rate in the freezing sections. Chapter discussed several explanations for this differing behaviour of the PCM tank for freezing and melting processes. Nevertheless, the validation of the model during the freezing sections is quite satisfying. Despite the slightly inaccurate trend of the trajectory of the heat transfer rate in section 2 and 4, the integrated values for the heat transfer rate in these sections are very similar, as shown by the model results at the end of the simulation in figure 31. Figure 31 Simulation end results for measurement (4 sections) In figure 31, the integrated values of the heat transfer for the freezing sections (section 2 and 4) are quite close, implying that the implementation of the factor for the freezing time k freeze time in chapter 3.3 was successful. However, figure 29 illustrated that the trajectory 40

43 of the predicted outlet temperature can be still improved. Thus, more research on defining the correct parameters of the regression function in equation 22 needs to be performed or an even more detailed estimation for the freezing behaviour needs to be implemented. Figure 31 illustrates that especially in section 3 the values for the integrated heat transfer rate are deviating for the model's prediction and the measurement. As explained above, further research on the detailed melting behaviour is required to model the heat transfer in a more precise way. Finally it shall be mentioned that the overall tank performance appears to be in a proper condition. The melting (discharging) sections are starting at :30 and at :30, respectively. They last for roughly 12 hours over the whole daytime until the night. The freezing (charging) sections start at :00 and at :00, respectively. They last for 12 hours during the night-time until the next morning. Therefore, the general operation of the PCM tank seems to fit the initial statements about the PCM storage performance that were discussed in chapter 2.2. Figure 31 tells that, as for the measured data, the amount of energy that was absorbed during section 1 (1103 kwh) equals roughly the amount of energy that is released again in section 2 (1113 kwh). The same applies for the subsequent sections, with absorbing about the same energy in section 3 (1536 kwh) that will be released again in section 4 (1618 kwh). However, the initial design guides and preliminary calculations assumed a maximum cooling capacity of 2800 kwh per single PCM tank (see chapter 2). Although figure 29 illustrated that the measured outlet temperature has already begun to converge towards the inlet temperature in the end of section 2 and 4, and although the heat transfer rate in these freezing sections is converging to zero despite of rather high amounts of mass flow rates, it appears that nevertheless only 50 % of the available capacity of the PCM tank has been used. This result can be confirmed by the model, as shown in figure 32, illustrating the model's prediction of the liquid mass fraction for a discretization in the direction towards the flow channel of n cells,flow channel = 3. 41

44 Figure 32 Measurement (4 sections), model's prediction of the liquid mass fraction with discretization of n = 3 (cell 1 at the front and cell 3 at the end of the tank) The model predicts that the PCM storage is only partially melting, until a liquid mass fraction of x = , just as it was reasoned by comparing the integrated heat transfer rates above. Therefore it appears that a fully frozen PCM tank cannot be obtained during just one night-time of charging the tank (i.e. 12 hours). It seems the preliminary assumed cooling capacity of 2800 kwh per tank cannot be completely utilized during an ordinary operation mode with charging the tank at night and discharging it at daytime. Further investigations in regard of retrieving the complete potential of a PCM storage tank will be discussed in chapter 4.3.3, where an operation mode with an extended melting section will be evaluated. Figure 32 shows the advantage of modelling the PCM storage. A model provides understanding about the system which is not accessible by measurements under normal circumstances. With varying the discretization of the modelled tank with n cells,flow channel along the tank and n cells,pcm into the perpendicular direction, it is possible to make assumptions on the three-dimensional freezing and melting progresses inside the tank. In figure 32, the rather imbalanced values for the liquid mass fraction in the beginning of the simulation are the result of improper initialization of the PCM tank. Since initialization has a huge effect on the simulation results, the following chapter will focus on this topic. 42

45 4.3.2 Measurement (3 sections) In this chapter mostly the same measurement data is used as above. However, the first part of the measurement data, i.e. the daytime of May 30 th, is cut out such that the data set starts at 22:00 on May 30 th. That way the simulation begins from a different starting point which requires a different initialization. The impact of the changed initialization on the subsequent sections of the PCM storage behaviour can be investigated. The measurement data and simulation results for this period are presented in figures Furthermore figure 36 presents the integrated values for the heat transfer rate at the end point of the measurement period. The sections 1 3 in figure 34 are equal to the sections 2 4 in figure 29. For the last freezing section the model predicts the same trajectory for the outlet temperature as previously. However, the model's estimations for the other two sections are dependent on the initial parametrization of the PCM Tank. The results for the figures have been taken from a simulation that was initialized with a partially frozen PCM tank. The discretization was set to n cells,flow channel = 3 and n cells,pcm = 2. As for the initial liquid mass fraction, x init,pcm was set to 0.95 and x init,flow channel was chosen in a way to decrease the initial liquid mass fraction by 0.2 for each discretized cell in the direction of the flow channel. As a result of the initially frozen PCM the predicted outlet temperature in figure 34 is slightly lower than the measured one. Though, the trajectory for the estimated outlet temperature in section 2 is more satisfying than in the previous chapter. The model still fails to reproduce the correct overall slope for the outlet temperature trajectory, but the yellow blocks in figure 36 illustrate that the difference in the integrated value of the heat transfer rate has highly decreased for this section (measured kwh, predicted kwh) in comparison to the previous chapter (measured kwh, predicted kwh). It is self-evident that the integrated value of the predicted heat transfer rate in section 1 is now diverging from the integrated value for the measured heat transfer rate in figure 36. This is because of the new initialization that assumed a partially frozen PCM for the start, leading to a predicted outlet temperature that is lower than the measured outlet temperature in section 1 (figure 34). The initialization of the model has a huge impact not only on the very beginning of the simulation, but also for the subsequent sections as it was shown in this chapter. 43

46 Figure 33 Measurement (3 sections, initial x < 1), water mass flow rate in m 3 /h Figure 34 Measurement (3 sections, initial x < 1), water inlet + outlet temperature in 44 Figure 35 Measurement (3 sections, initial x < 1), heat transfer rate of the PCM in kw

47 Figure 36 Simulation end results for measurement (3 sections, initial x < 1) For the sake of completeness figures 37 and 38 show the results of the simulation with an initial liquid mass fraction of x init = 1 (fully molten) for every PCM cell. The results are extremely close to the results from the 4-sectional measurement data in the previous chapter (figures 29 and 31). Figure 37 Measurement (3 sections, initial x = 1), water inlet + outlet temperature in 45

48 Figure 38 Simulation end results for measurement (3 sections, initial x = 1) This measurement data set from was conducted with only PCM tank #1 in use. In the following chapter, the same procedure will be conducted for a different PCM tank Measurement Analogous to the previous chapter, this measurement data set focuses on the performance of a single PCM tank. During the recorded time period, only PCM tank #3 was supplied with water while the remaining tanks were shut down. In the investigated period the measured mass flow rate was always higher than zero and varied between m 3 /h. The freezing and thus charging sections start at :00 and at :00, respectively. They last during the whole night-time until the next morning. The melting and thus discharging section is starting at :00. It lasts over two days and one night until the beginning of the second night. The measured and simulated data for the mass flow rate, inlet and outlet temperatures and heat flow rate are shown in figures 39, 40 and 41, respectively. 46

49 Figure 39 Measurement , water mass flow rate in m 3 /h Figure 40 Measurement , water inlet and outlet temperature in Figure 41 Measurement , heat transfer rate of the PCM in kw 47

50 In general the same conclusions for the predicted outlet temperature can be drawn like in the chapters before: The quality of the prediction of the outlet temperature is better for the freezing sections. In the first half of the melting section the estimated outlet temperature is clearly lower than the measured outlet temperature (figure 40). In the second half of the melting section it is the opposite, and almost equal to the inlet temperature. However, figure 42 (as well as figure 67 in the appendix) show that the model is actually predicting the correct value for the integrated heat transfer for the melting section (measured kwh, predicted kwh). This means, that the model is capable of estimating the correct amount of energy the PCM tank is absorbing during this section. Though, the calculations for the corresponding heat transfer and thus for the temperature trajectory lack refinement and need to be improved for the melting progress in particular, as it was already mentioned in the previous chapters before. In general, the measurement during the extended melting section demonstrate some effects that require more detailed evaluation. The melting section can be roughly divided into 3 subsections, which are differing in their respective mass flow rates: The first sub-section starts at :00 and lasts 12 hours over the daytime. The mass flow rate during this subsection is m 3 /h (figure 39) and the heat flow rate is kwh (figure 41), which resembles the values for the 12-hour-melting sections from the measurement of in chapter The second sub-section starts at :00 and lasts 12 hours over the night-time. The mass flow rate is reduced to 10 m 3 /h during this time. As a result, the heat transfer rate decreases to 30 kw. In the last sub-section, which starts at :00, the mass low rate is increasing again to m 3 /h. However, the correspondent heat transfer rate remains on the low level of approximately kw (with a transient peak of 90 kw). A reason for this might be the decreased difference between the inlet water temperature and the PCM temperature after 24 hours of melting. Figure 40 shows that the temperature difference between inlet and outlet water temperature has decreased to < 2 K by then. Thus, the increase of the mass flow rate by the factor of 5 at the end of the melting section at :00 is needed to compensate the decreasing temperature difference, resulting in a nevertheless constant heat transfer rate in comparison to the previous sub-section. 48

51 As a result for the extended melting section that lasted 36 hours, figure 42 illustrates that a total amount of absorbed energy by the PCM of 2525 kwh was achieved. This value resembles the initial design parameter for the PCM tank of 2800 kwh (see chapter 2.2) and implies that the PCM tank appears to be able to utilize its total storage potential in this case, because of the highly extended melting period in combination with an increased mass flow rate at the very end of the melting section. Therefore, as discussed in chapter 4.3.1, the system is not capable of utilizing the complete tank potential during ordinary operation modes that require a charging during the night-time and a discharging during a daytime (i.e. 12 hours for each), as discussed in chapter 2.2. Furthermore, the actual cooling system of the University College of Bergen has implemented four PCM tanks instead of just one. Thus, it appears to be very unlikely that the full PCM storage potential of kwh could be utilized during ordinary operation modes. The results in these chapters have shown that both tanks are in principle fully operable. However, the complete potential of the PCM storage tanks cannot be retrieved during a single night-time charging and daytime discharging cycle. Nevertheless, the model managed to reproduce the tank's behaviour with adequate accuracy. Figure 42 Simulation end results for measurement

52 5 Conclusion and Proposal for Further Work A Modelica based model for simulating the performance of a PCM thermal energy storage has been derived based on a PCM storage unit at the University College of Bergen. The validation of the model was conducted using measurement data from the plant at Bergen. The aim with the model was to provide understanding about the PCM storage behaviour and charging dynamics, and to improve the dimensioning of such storage systems and the design of the operation modes. It was shown that the measured performance of the PCM tanks is generally matching the preliminary design parameters. Especially during a measurement period in 2016, the PCM storage has been successfully operated with charging and discharging cycles. It was shown that the maximum amount of cooling capacity of 2800 kwh promised by the manufacturer could be reached with the PCM tank, when the melting time is sufficiently long. However, the PCM tank's complete storage potential of kwh cannot be retrieved during ordinary night-time/daytime charging/discharging cycles. The preliminary design of the storage system appears to be oversized for the University College of Bergen for the present mode of operation. Further research needs to be performed whether the heat transfer rate during ordinary 12 hour charging sections could be enhanced to increase the amount of retrieved storage potential. The model was capable of predicting the measured values correctly with adequate quality. Especially the values for the amount of absorbed or released energy by the PCM storage were on a satisfying level. However, the correct trend of the trajectory for the outlet temperature still lacks refinement. The current deviations in the simulation results with respect to the measurement data can be related to the assumptions that were made while deriving the present model. More research needs to be conducted in expressing the influence of the phase change on the heat transfer process. The process of how the heat transfer coefficient is changing with progressing melting or freezing activities within the PCM containers needs to be reproduced in a more accurate way by implementing proper equations and correlations. In particular, the effect of the buoyancy within the PCM containers needs to be considered. As discussed in chapter 3.3.3, the changing buoyancy during a phase change has a huge 50

53 impact on the natural convection within the PCM container. For horizontally aligned PCM containers the heat transfer rate on the bottom of a PCM container is hence higher than for the upper side of the PCM container in case of melting. As mentioned in section 2.1, subcooling occurs during the freezing of PCM. The particular effect of subcooling on the freezing time, on the trajectory of the predicted temperature and on the overall heat transfer rate requires more investigation and a proper implementation in the model. Irreversibilities, entropy production and second law efficiency during a phase change need to be highlighted. Their effect on retrieving the maximum amount of storage capacity and their impact on the long-term performance of the PCM require more research. Furthermore, the mass flow rate within the flow channel should be calculated with a more detailed approach which considers the obstacles within the flow channel. The small auxiliary platforms on the surface of the PCM containers are causing local turbulences that affect the local heat transfer coefficient. Local differentiation between laminar and turbulent flow should to be considered as well. The PCM tanks at the University College of Bergen were equipped with flow distributors to ensure an evenly distributed mass flow rate of water. The present model assumes a perfectly distributed mass flow within the tank. The PCM container walls between the particular PCM containers were neglected. Their effect on the heat transfer needs to be investigated, since the HDPE walls increase the heat resistance for the heat flow within the layer of PCM containers. The tank's steel wall was neglected when estimating the heat capacity of the system. An increased thermal mass is affecting the heat transfer rate especially for the PCM containers close to the tank's wall. Moreover, more detailed material properties for the PCM are lacking for both the liquid and the solid state. Especially for the liquid state the material properties were only approximated with using comparable values from literature. More precise freezing and melting profiles are needed to validate the model for several boundary conditions, such as varying mass flow rates. Generally, more precise measurement data with a higher quality would greatly help to improve the model. As for future prospects, assuming that the model accuracy could be successfully increased as discussed above, the model could be used to provide best practise data sheets for future 51

54 dimensioning of new plants or for improving the operation of existing ones. Furthermore, the model could be utilized for visualizing and predicting the behaviour of system parameters that cannot be studied by measurements. A system layout as shown in figure 42 or a user interface as shown in figure 43 present possible ways to visualize non-measurable system parameters. That way, accurate information and updated values could be provided for e.g. the distribution of the temperature over the tank or the local liquid mass fraction x for a particular layer of the PCM storage. Such a visualization tool could enable live performance assessment, system debugging, maintenance operation for deficient PCM containers or general prevention of improper operation modes. Figure 43 Future outlook: Potential of live visualization for non-measurable system parameters like the integrated heat transfer rate for each PCM container (side view on the tank's inlet, 2x5 stacked containers with exemplified values) 52

55 6 References Dar, U., Høgskolen i Bergen Energisentral, SWECO. Frohböse, I., TIL Suite Simulates Thermal Systems Software Containing Models for Thermophysical Properties, Thermal Components and Systems, TLK-Thermo GmbH, Braunschweig Fox, R., et al., Introduction to Fluid Mechanics, Sixth Edition, Purdue University Libeer, W., et al., Two-Phase Heat and Mass Transfer of Phase Change Materials in Thermal Management Systems, Department of Mechanical Engineering, Stanford University Liu, L., et al., Thermal Conductivity Enhancement of Phase Change Materials for Thermal Energy Storage: A Review, School of Physics, Nanjing University Kalnæs, S., Jelle, B., Phase Change Materials and Products for Building Applications: A Stateof-the-Art Review and Future Research Opportunities, Department of Civil and Transport Engineering, Norwegian University of Science and Technology (NTNU) Mehling, H., Cabeza, L.F., Heat and Cold Storage with PCM: An up-to-date Introduction into Basics and Applications, Springer, ISBN PCM Products Ltd., PlusICE Phase Change Materials, retrieved PCM Products Ltd., Thermal Energy Storage Design Guide retrieved Perez-Lombard, L., Ortiz, J., Pout, C., A Review on Buildings Energy Consumption Information, Energy and Buildings 40 (3) (2008) Sharma, A., et al., Review on Thermal Energy Storage with Phase Change Materials and Applications, Department of Mechanical Engineering, Kun Shan University Stene, J.,2014. Heating/Cooling of Academy Buildings. The University of Bergen New Buildings/Renovation Sun, X., et al., Experimental Observations on the Heat Transfer Enhancement Caused by Natural Convection during Melting of Solid Liquid Phase Change Materials, School of Energy and Power Engineering, Changsha University of Science and Technology 53

56 Sweco, Høgskole i Bergen Funksjonsbeskrivelse, SWECO Uno, Housing, Energy and Thermal Comfort: A review. data/assets/pdf_file/0008/97091/e89887.pdf, retrieved Ure, Z., Thermal Storage, retrieved VDI Heat Atlas, th Edition, Verein Deutscher Ingenieure, VDI-Gesellschaft Verfahrenstechnik und Chemieingenieurwesen (GVC) 54

57 A Appendix Additional Results A.1 Measurement Data Given below are the integrated heat transfer rates Q for each section as a function of time for the measurement period of , discussed in section 4.2.2, figure 27. Figure 44 Measurement , definition of the sections Figure 45 Measurement , integrated heat transfer rate section 1 in kwh 55

58 Figure 46 Measurement , integrated heat transfer rate section 2 in kwh Figure 47 Measurement , integrated heat transfer rate section 3 in kwh A.2 Measurement Data The figures are illustrating the measurement data and the simulation results for the week from June 29 th until July 6 th 2015 during normal operation of the building, where typical low cooling demand conditions occur. Among other things, the measured values for the heat transfer seem to be improper, since a non-zero heat transfer is measured despite equal inlet and outlet temperatures. Therefore it was decided to not further utilize any data from this week for the sake of validation in the report. 56

59 Figure 48 Measurement , water mass flow rate in m 3 /h Figure 49 Measurement , water inlet and outlet temperature in Figure 50 Measurement , heat transfer rate of the PCM in kw 57

60 A.3 Measurement Data For a roundup of the measurement data set from 2015 the results of the simulation of the overall two month time period is given in figures The most important tendencies of the model's behaviour towards the 2015-measurement have been elaborated in chapter 4.2 of the report. Some improper peaks or major deviations of the measured values in the following figures might result from measurement inaccuracies or general system errors and are hence not discussed further. Figure 51 Measurement , measured water mass flow rate in m 3 /h Figure 52 Measurement , measured inlet and outlet water temperature in C 58

61 Figure 53 Measurement , measured and predicted outlet water temperature in Figure 54 Measurement , difference of measured and predicted outlet temperature in Figure 55 Measurement , measured and predicted heat transfer rate in kw 59

62 A.4 Measurement Data (4 sections) Given below are the integrated heat transfer rates Q for each section as a function of time for the measurement period of , discussed in section 4.3.1, figure 31. Figure 56 Measurement (4 sections), definition of the sections Figure 57 Measurement (4 sections), integrated heat transfer rate section 1 in kwh 60

63 Figure 58 Measurement (4 sections), integrated heat transfer rate section 2 in kwh Figure 59 Measurement (4 sections), integrated heat transfer rate section 3 in kwh Figure 60 Measurement (4 sections), integrated heat transfer rate section 4 in kwh 61

64 A.5 Measurement Data (3 sections) Given below are the integrated heat transfer rates Q for each section as a function of time for the measurement period of , discussed in section 4.3.2, figure 36. Figure 61 Measurement (3 sections), definition of the sections Figure 62 Measurement (3 sections), integrated heat transfer rate section 1 in kwh 62

65 Figure 63 Measurement (3 sections), integrated heat transfer rate section 2 in kwh Figure 64 Measurement (3 sections), integrated heat transfer rate section 3 in kwh A.6 Measurement Data Given below are the integrated heat transfer rates Q for each section as a function of time for the measurement period of , discussed in section 4.3.3, figure

66 Figure 65 Measurement , definition of the sections Figure 66 Measurement , integrated heat transfer rate section 1 in kwh Figure 67 Measurement , integrated heat transfer rate section 2 in kwh 64

67 Figure 68 Measurement , integrated heat transfer rate section 3 in kwh A.7 Comparison of Approaches for Heat Transfer Coefficient Estimation Chapter 3.3 discussed the different approaches for calculating the heat transfer coefficient on the liquid side of the PCM heat exchanger model. Literature provides several possible cases that can be utilized when modelling a PCM storage (VDI Heat Atlas 2013). The validation proved that the best simulation results were obtained when assuming the case "flow over a horizontal plane". The results for this particular approach of estimating the heat transfer coefficient were discussed in detail in chapter 4. The second possible case for calculating the heat transfer coefficient for the PCM heat exchanger model is "flow in a flat gap between two heated walls". The heat transfer coefficient becomes (VDI Heat Atlas 2013): With a Nusselt number of α water = k freeze time λ Nu 2 h flow channel (23) Nu = ( ( Re Pr 2 h 1.14 flow channel ) l flow channel ( Re Pr 2 h flow channel l flow channel ) 0.64 Pr 0.17 ) (24) This equation is valid for laminar flows. There is no need for considering a turbulent Nusselt number calculation in this particular case, since the Reynolds number is now: 65

68 Re = 2 h flow channel v ρ η (25) This case utilizes a different approach to estimate the flow characteristics for the heat transfer. Thus, the Reynolds number is a function of the channel height and not a function of the channel length as in the case before (equation 11). Hence, the Reynolds number remains < (1^5) for all measured volume flows in chapter 4 and no turbulent flow occurs. The equation for the flow velocity remains the same (see equation 12). For the sake of comparison, figures show the simulation results for the case "flow in a flat gap between two heated walls" for the same measurement data set from that was already used in chapter Figure 69 Comparison of approaches for alpha estimation, heat transfer coefficient alpha in W/m 2 K for case 1 "flow over plane" and case 2 "heated walls" Figure 70 Comparison of approaches for alpha estimation, water inlet and outlet temperature in for case 1 "flow over plane" and case 2 "heated walls" 66

69 Figure 71 Simulation end results for measurement , heat transfer coefficient estimated applying the case "heated walls" As shown on figure 69, the calculated heat transfer coefficient is higher by the factor of 10 for the case 2 "flow in a flat gap between two heated walls". The average heat transfer coefficient is 15 W for case 1 and 140 W m 2 K m 2 K for case 2. As a result, the trajectory of the predicted outlet temperature is fluctuating more (figure 70) than the trajectory that was estimated with applying case 1 "flow over a horizontal plane" in figure 29. Furthermore the deviations of the integrated values for the heat transfer rate between the measured and predicted values in figure 71 are higher than the values in chapter as well. Thus, for this case even more modifying factors like the freezing time factor k freeze time from chapter 3.3 are required to tune the equations and to shape the progress of the heat transfer towards the measured values. For the present time, the simulation results from chapter 4 that were estimated with applying the case 1, proved quite satisfying quality with comparatively little effort in modifying these factors. Thus, it was decided to continue working with applying the case of "flow over a horizontal plane". However, a future outlook might be to further investigate the performance of the system when case 2 is applied or even to derivate a completely new case that fits the PCM heat exchanger model the best, since it was shown that the calculation of the heat transfer coefficient has a high impact on the overall performance of the PCM storage model. 67

PHASE CHANGE MATERIAL THERMAL ENERGY STORAGE FOR A LARGE AMMONIA CHILLER/HEAT PUMP SYSTEM

PHASE CHANGE MATERIAL THERMAL ENERGY STORAGE FOR A LARGE AMMONIA CHILLER/HEAT PUMP SYSTEM PAPER ID XXXXX PHASE CHANGE MATERIAL THERMAL ENERGY STORAGE FOR A LARGE AMMONIA CHILLER/HEAT PUMP SYSTEM M. JOKIEL (a), H. KAUKO (b), *, C. SCHLEMMINGER (c), A. HAFNER (d), I. C. CLAUSSEN (b) (a) Technische

More information

Solar Flat Plate Thermal Collector

Solar Flat Plate Thermal Collector Solar Flat Plate Thermal Collector 1 OBJECTIVE: Performance Study of Solar Flat Plate Thermal Collector Operation with Variation in Mass Flow Rate and Level of Radiation INTRODUCTION: Solar water heater

More information

Transient behaviour of post-combustion CO 2 capture with MEA in coal fired power plants Master of Science Thesis [Sustainable Energy Systems]

Transient behaviour of post-combustion CO 2 capture with MEA in coal fired power plants Master of Science Thesis [Sustainable Energy Systems] Transient behaviour of post-combustion CO 2 capture with MEA in coal fired power plants Master of Science Thesis [Sustainable Energy Systems] SÓLEY EMILSDÓTTIR STEFANÍA ÓSK GARÐARSDÓTTIR Department of

More information

Thermal Behaviour of High Temperature PCMs under a Periodic Heat Transfer Fluid Flow Reversal

Thermal Behaviour of High Temperature PCMs under a Periodic Heat Transfer Fluid Flow Reversal Soheila Riahi Thermal Behaviour of High Temperature PCMs under a Periodic Heat Transfer Fluid Flow Reversal Soheila Riahi 1, Wasim Saman 1, Frank Bruno 1, Martin Belusko 1 1 Barbara Hardy Institute, University

More information

Modelling of Residential Heating Systems using a Phase Change Material Storage System

Modelling of Residential Heating Systems using a Phase Change Material Storage System Modelling of Residential Heating Systems using a Phase Change Material Storage System Corinna Leonhardt Dirk Müller Institute for Energy Efficient Buildings and Indoor Climate, E.ON Energy Research Center,

More information

Available online at ScienceDirect. Procedia Engineering 89 (2014 )

Available online at   ScienceDirect. Procedia Engineering 89 (2014 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 89 (2014 ) 143 150 16th Conference on Water Distribution System Analysis, WDSA 2014 Drinking Water Temperature Modelling in

More information

Heat exchangers and thermal energy storage concepts for the off-gas heat of steelmaking devices

Heat exchangers and thermal energy storage concepts for the off-gas heat of steelmaking devices Journal of Physics: Conference Series Heat exchangers and thermal energy storage concepts for the off-gas heat of steelmaking devices To cite this article: T Steinparzer et al 2012 J. Phys.: Conf. Ser.

More information

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System Journal of Energy and Power Engineering 7 (2013) 66-73 D DAVID PUBLISHING Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

More information

Available online at ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013

Available online at  ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 49 (2014 ) 993 1002 SolarPACES 2013 Thermal storage concept for solar thermal power plants with direct steam generation M. Seitz

More information

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ Forschungszentrum Jülich GmbH, FZJ ZAT-Report FZJ-ZAT-379 January 2003 Benchmark Activity on Natural Convection Heat Transfer Enhancement in Mercury with Gas Injection authors Dr. J. Wolters abstract A

More information

Thermal performance evaluation of an integrated photovoltaic thermal-phase change material system using Taguchi method

Thermal performance evaluation of an integrated photovoltaic thermal-phase change material system using Taguchi method University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part B Faculty of Engineering and Information Sciences 2017 Thermal performance evaluation of an integrated

More information

Heat Transfer Analysis for Phase Change Materials (PCMs)

Heat Transfer Analysis for Phase Change Materials (PCMs) Abstract Heat Transfer Analysis for Phase Change Materials (PCMs) Y. Tian, C.Y. Zhao* School of Engineering, University of Warwick, CV4 7AL, Coventry, UK *Corresponding author (Tel: +44 4 765339, Email:

More information

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK International Journal of Scientific & Engineering Research Volume 4, Issue 1, January-2013 1 CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK Mr. Mainak Bhaumik M.E. (Thermal

More information

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2016 Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

More information

CFD modeling of heat charging process in. a direct-contact container. for mobilized thermal. energy storage

CFD modeling of heat charging process in. a direct-contact container. for mobilized thermal. energy storage CFD modeling of heat charging process in a direct-contact container for mobilized thermal energy storage Arefeh Hesaraki Spring 2011 Thesis supervisors: Professor Jinyue Yan Hailong Li Abstract: Thermal

More information

Zafer URE.

Zafer URE. Zafer URE Unit 32, Mere View Ind. Estate, Yaxley, Cambridgeshire, PE7 3HS, UK Tel.: +44(0)1733-243400, Fax: +44(0)1733-243344, e-mail: z.ure@pcmproducts.net www.pcmproducts.net THERMAL ENERGY STORAGE Storing

More information

8. Optimization of a latent heat storage system

8. Optimization of a latent heat storage system 8. Optimization of a latent heat storage system In the current section, the goal of achieving an optimal temperature profile inside the packed bed will be pursued. With this purpose, the influence of the

More information

Delivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure

Delivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure Delivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure Determination of the delivery efficiency for a quality declaration for the ISSO database Delivery efficiency of the Jaga Low

More information

RIQUALIFICAZIONE DI EDIFICI ESISTENTI CON ELEVATI STANDARD ENERGETICI: METODI E TECNOLOGIE

RIQUALIFICAZIONE DI EDIFICI ESISTENTI CON ELEVATI STANDARD ENERGETICI: METODI E TECNOLOGIE RIQUALIFICAZIONE DI EDIFICI ESISTENTI CON ELEVATI STANDARD ENERGETICI: METODI E TECNOLOGIE CASE STUDY: Innovative Solar heating and cooling system with PCM tank at service of F-92 Building of ENEA CASACCIA

More information

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS) European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela

More information

TO CONDUCT THE PERFORMANCE TEST ON CHILLER UNIT BY USING NANOFLUID COOLED CONDENSER

TO CONDUCT THE PERFORMANCE TEST ON CHILLER UNIT BY USING NANOFLUID COOLED CONDENSER Int. J. Mech. Eng. & Rob. Res. 2015 Anandakumar J, 2015 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 4, No. 1, January 2015 2015 IJMERR. All Rights Reserved TO CONDUCT THE PERFORMANCE TEST ON CHILLER

More information

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

More information

Available online at ScienceDirect. Energy Procedia 73 (2015 )

Available online at   ScienceDirect. Energy Procedia 73 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 73 (2015 ) 281 288 9th International Renewable Energy Storage Conference, IRES 2015 High temperature latent heat thermal energy storage

More information

Chilled Water Plant Redesign

Chilled Water Plant Redesign 17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by

More information

BASIC EUROPEAN GLAZED COLLECTORS & SOLAR DOMESTIC

BASIC EUROPEAN GLAZED COLLECTORS & SOLAR DOMESTIC ISO 98061 ISO 98O62 ISO 9459-2 BASIC EUROPEAN AND INTERNATIONAL STANDARDS ON SOLAR THERMAL GLAZED COLLECTORS & SOLAR DOMESTIC HOT WATER SYSTEMS A brief review addressed to: Manufacturers, Retailers, Promoters,

More information

Paraffin Deposition Progress Report April June 2003

Paraffin Deposition Progress Report April June 2003 Paraffin Deposition Progress Report April June 2003 Single-Phase Studies The single phase paraffin project is now in the final phase using the Cote Blanche Island (CBI), CBI is the third fluid used in

More information

*Corresponding authors. Tel.: x415, address: (N. Zhu)

*Corresponding authors. Tel.: x415,  address: (N. Zhu) Optimal design of ground source heat pump system integrated with phase change cooling storage tank in an office building Na Zhu *, Yu Lei, Pingfang Hu, Linghong Xu, Zhangning Jiang Department of Building

More information

Fabrication and Experimental Investigation of PCM Capsules Integrated in Solar Air Heater

Fabrication and Experimental Investigation of PCM Capsules Integrated in Solar Air Heater American Journal of Environmental Sciences 7 (6): 542-546, 2011 ISSN 1553-345X 2011 Science Publications Fabrication and Experimental Investigation of PCM Capsules Integrated in Solar Air Heater 1,2 Mahmud

More information

Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers

Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers B Sreedhara Rao 1, Surywanshi Gajanan D 2, Varun S 2, MVS Murali Krishna 3, R C Sastry 2,* 1 Department

More information

Performance Testing of A Parabolic Trough Collector Array

Performance Testing of A Parabolic Trough Collector Array Performance Testing of A Parabolic Trough Collector Array İbrahim Halil Yılmaz *, Hakan Hayta, Recep Yumrutaş, Mehmet Sait Söylemez Department of Mechanical Engineering University of Gaziantep, 27310 Gaziantep,

More information

CFD Modelling and Analysis of Different Plate Heat Exchangers

CFD Modelling and Analysis of Different Plate Heat Exchangers CFD Modelling and Analysis of Different Plate Heat Exchangers Ahmed Y Taha Al-Zubaydi a *, Guang Hong b and W. John Dartnall c Faculty of Engineering and Information Technology, UTS, Sydney, Australia

More information

RESEARCH OF SOLAR WATER HEATERS MODEL

RESEARCH OF SOLAR WATER HEATERS MODEL RESEARCH OF SOLAR WATER HEATERS MODEL Donatas Dervinis Šiauliai University, Šiauliai State College, Lithuania Dainius Balbonas Šiauliai University, Šiauliai State College, Lithuania Annotation This paper

More information

EFFECT OF ROUGHNESS GEOMETRY ON HEAT TRANSFER AND FRICTION CHARACTERISTICS OF PCM STORAGE UNIT FOR NIGHT COOLNESS STORAGE IN SUMMER SEASON

EFFECT OF ROUGHNESS GEOMETRY ON HEAT TRANSFER AND FRICTION CHARACTERISTICS OF PCM STORAGE UNIT FOR NIGHT COOLNESS STORAGE IN SUMMER SEASON EFFECT OF ROUGHNESS GEOMETRY ON HEAT TRANSFER AND FRICTION CHARACTERISTICS OF PCM STORAGE UNIT FOR NIGHT COOLNESS STORAGE IN SUMMER SEASON by Shailndra Kumar SHUKLA, * and Satish K.SINGH Mechanical Engg.Deptt.,I.T.,B.H.U.,

More information

Partial Load Characteristics of the Supercritical CO2 Gas Turbine System for the Solar Thermal Power System with the Na-Al- CO2 Heat Exchanger

Partial Load Characteristics of the Supercritical CO2 Gas Turbine System for the Solar Thermal Power System with the Na-Al- CO2 Heat Exchanger The 6th International Symposium - Supercritical CO2 Power Cycles March 27 29, 2018, Pittsburgh, Pennsylvania Partial Load Characteristics of the Supercritical CO2 Gas Turbine System for the Solar Thermal

More information

WATER COOLING OF PHOTOVOLTAIC PANELS FROM PASSIVE HOUSE LOCATED INSIDE THE UNIVERSITY POLITEHNICA OF BUCHAREST

WATER COOLING OF PHOTOVOLTAIC PANELS FROM PASSIVE HOUSE LOCATED INSIDE THE UNIVERSITY POLITEHNICA OF BUCHAREST U.P.B. Sci. Bull., Series C, Vol. 75, Iss. 3, 2013 ISSN 2286-3540 WATER COOLING OF PHOTOVOLTAIC PANELS FROM PASSIVE HOUSE LOCATED INSIDE THE UNIVERSITY POLITEHNICA OF BUCHAREST Ana-Maria CROITORU 1, Adrian

More information

Analysis the impact of energy storage techniques in a cold distribution system

Analysis the impact of energy storage techniques in a cold distribution system Analysis the impact of energy storage techniques in a cold distribution system Tiago G. Dias a, Francisco S. Lemos a, João A. Fareleira a a Instituto Superior Tecnico, Universidade de Lisboa December,

More information

Thermally operated mobile air-conditioning system

Thermally operated mobile air-conditioning system Thermally operated mobile air-conditioning system Development and test of a laboratory prototype R. de Boer S.F. Smeding Paper to be presented on the International Sorption Heat Pump Conference 2008, Seoul,

More information

Simulation of Melting Process of a Phase Change Material (PCM) using ANSYS (Fluent)

Simulation of Melting Process of a Phase Change Material (PCM) using ANSYS (Fluent) Simulation of Melting Process of a Phase Change Material (PCM) using ANSYS (Fluent) Vikas 1, Ankit Yadav 2, S.K. Soni 3 1M.Tech. Scholar, PEC University of Technology, Chandigarh, India 2Assistant Professor,

More information

A SIMULATION OF AN UNDERGROUND HEAT STORAGE SYSTEM USING MIDNIGHT ELECTRIC POWER AT PARK DOME KUMAMOTO

A SIMULATION OF AN UNDERGROUND HEAT STORAGE SYSTEM USING MIDNIGHT ELECTRIC POWER AT PARK DOME KUMAMOTO A SIMULATION OF AN UNDERGROUND HEAT STORAGE SYSTEM USING MIDNIGHT ELECTRIC POWER AT PARK DOME KUMAMOTO Kouji Sakai*, Osamu Ishihara*, Kengo Sasaguchi*, Hiroyuki Baba** and Takamitsu Sato*** * Kumamoto

More information

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE Johan Heier 1, Chris Bales 1, Artem Sotnikov 2 and Ganna Ponomarova 2 1 Solar Energy Research Center (SERC), Dalarna University,

More information

Laboratory Testing of Safety Relief Valves

Laboratory Testing of Safety Relief Valves Laboratory Testing of Safety Relief Valves Thomas Kegel (tkegel@ceesi.com) and William Johansen (bjohansen@ceesi.com) Colorado Engineering Experiment Station, Inc. (CEESI) 5443 WCR 37, Nunn, Colorado 8648

More information

Abstract. Nomenclature. A Porosity function for momentum equations L Latent heat of melting (J/Kg) c Specific heat (J/kg-K) s Liquid fraction

Abstract. Nomenclature. A Porosity function for momentum equations L Latent heat of melting (J/Kg) c Specific heat (J/kg-K) s Liquid fraction Enthalpy Porosity Method for CFD Simulation of Natural Convection Phenomenon for Phase Change Problems in the Molten Pool and its Importance during Melting of Solids Abstract Priyanshu Goyal, Anu Dutta,

More information

MODELLING & SIMULATION OF LASER MATERIAL PROCESSING: PREDICTING MELT POOL GEOMETRY AND TEMPERATURE DISTRIBUTION

MODELLING & SIMULATION OF LASER MATERIAL PROCESSING: PREDICTING MELT POOL GEOMETRY AND TEMPERATURE DISTRIBUTION Proceeding of International Conference MS 07, India, December 3-5, 2007 1 MODELLING & SIMULATION OF LASER MATERIAL PROCESSING: PREDICTING MELT POOL GEOMETRY AND TEMPERATURE DISTRIBUTION M. A Sheikh Laser

More information

2

2 2 3 4 5 13 Experimental Investigation of Thermal Storage Properties of Different Materials Using Solar Air Collector 1*, samettin BULUT 2, 3 1 Harran University, Graduate School of Natural & Applied Sci

More information

Draft proposals for Test methods for close-coupled solar water heating systems - Reliability and safety

Draft proposals for Test methods for close-coupled solar water heating systems - Reliability and safety IEA/SHC Task 57, Subtask B Draft proposals for new test procedures B4: Final Draft Draft proposals for Test methods for close-coupled solar water heating systems - Reliability and safety HE Zinian Beijing

More information

Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches

Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches P. Oberdorfer * F. Maier and E. Holzbecher University of Göttingen Geoscience Centre Applied Geology *Corresponding

More information

Numerical modelling of shielding gas flow and heat transfer in laser welding process

Numerical modelling of shielding gas flow and heat transfer in laser welding process Numerical modelling of shielding gas flow and heat transfer in laser welding process Alireza Javidi Shirvan 1, Isabelle Choquet 1, Håkan Nilsson 2 1 University West, Department of Engineering Science,

More information

Shading effects on the winter thermal performance of the Trombe wall air gap: An experimental study in Dalian

Shading effects on the winter thermal performance of the Trombe wall air gap: An experimental study in Dalian Renewable Energy 31 (26) 1961 1971 www.elsevier.com/locate/renene Shading effects on the winter thermal performance of the Trombe wall air gap: An experimental study in Dalian B. Chen, X. Chen, Y.H. Ding,

More information

The formation of oscillation marks in continuous casting of steel

The formation of oscillation marks in continuous casting of steel The formation of oscillation marks in continuous casting of steel 1 Introduction Continuous casting is a method of producing an infinite solid strand from liquid metal by continuously solidifying it as

More information

Nuclear Power Plants Authority, 4 El-Nasr Avenue, Nasr City, P.O. Box 8191, Nasr City 11371, Cairo, Egypt

Nuclear Power Plants Authority, 4 El-Nasr Avenue, Nasr City, P.O. Box 8191, Nasr City 11371, Cairo, Egypt International Nuclear Energy, Article ID 569658, 6 pages http://dx.doi.org/10.1155/2014/569658 Research Article A Parametric Study of the Impact of the Cooling Water Site Specific Conditions on the Efficiency

More information

Thermal Energy Storage Tanks Using Phase Change Material (PCM) in HVAC Systems

Thermal Energy Storage Tanks Using Phase Change Material (PCM) in HVAC Systems 24 Thermal Energy Storage Tanks Using Phase Change Material (PCM) in HVAC Systems Motoi Yamaha 1 and Nobuo Nakahara 2 1 Chubu University, 2 Nakahara Laboratory, Environmental Syst.-Tech. Japan 1. Introduction

More information

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Chapter Six{ TC Chapter Six \l 1 } System Simulation Chapter Six{ TC "Chapter Six" \l 1 } System Simulation In the previous chapters models of the components of the cooling cycle and of the power plant were introduced. The TRNSYS model of the power plant

More information

CFD tools and lower order modeling for regenerative chambers with gas recirculation system

CFD tools and lower order modeling for regenerative chambers with gas recirculation system CFD tools and lower order modeling for regenerative chambers with gas recirculation system Ing. Alessandro Spoladore Prof. Carlo Cravero Università di Genova Facoltà di Ingegneria DIME 1 Computational

More information

Secondary Loop System for Automotiv HVAC Units Under Different Climatic Conditions

Secondary Loop System for Automotiv HVAC Units Under Different Climatic Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Secondary Loop System for Automotiv HVAC Units Under Different Climatic

More information

Advanced simulation methods for heat pump systems

Advanced simulation methods for heat pump systems Advanced simulation methods for heat pump systems Kristian Huchtemann Dirk Müller Institute for Energy Efficient Buildings and Indoor Climate E.ON Energy Research Center, RWTH Aachen University Jägerstraße

More information

DESIGN OF WATER SUPPLY PIPE NETWORKS

DESIGN OF WATER SUPPLY PIPE NETWORKS DESIGN OF WATER SUPPLY PIPE NETWORKS DESIGN OF WATER SUPPLY PIPE NETWORKS Prabhata K. Swamee Ashok K. Sharma Copyright # 2008 by John Wiley & Sons, Inc. All rights reserved Published by John Wiley & Sons,

More information

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS F. Asdrubali, G. Baldinelli, A. Presciutti, M. Caporali University of Perugia - Industrial Engineering Department, Via G. Duranti

More information

ANALYSIS FOR NATURAL CIRCULATION LOOP

ANALYSIS FOR NATURAL CIRCULATION LOOP ANALYSIS FOR NATURAL CIRCULATION LOOP Muddada Venkatesh 1, K.Mohanalakshmi 2, A.Lakshmu Naidu 3 1 Department of Mechanical Engineering,AITAM,Tekkali,Andhra Pradesh. 2 Department of Mechanical Engineering,AITAM,Tekkali,Andhra

More information

PlusICE DAY NIGHT. Phase Change Material Passive Cooling Products PHASE CHANGE MATERIAL PRODUCTS LIMITED

PlusICE DAY NIGHT. Phase Change Material Passive Cooling Products PHASE CHANGE MATERIAL PRODUCTS LIMITED TM PlusICE Phase Change Material Passive Cooling Products DAY NIGHT PHASE CHANGE MATERIAL PRODUCTS LIMITED NATURAL ALTERNATIVE TO REDUCE ENERGY THERMAL ENERGY STORAGE; Thermal Energy Storage (TES) is the

More information

Figure 1: Uncovered and covered PVT collectors

Figure 1: Uncovered and covered PVT collectors Low energy cooling of buildings with radiative cooling using hybrid PVT collectors Ursula Eicker, Antoine Dalibard, Simon Büttgenbach, Sebastian Fiedler, Jan Cremers University of Applied Sciences HFT

More information

Design Features of Combined Cycle Systems

Design Features of Combined Cycle Systems Design Features of Combined Cycle Systems 1.0 Introduction As we have discussed in class, one of the largest irreversibilities associated with simple gas turbine cycles is the high temperature exhaust.

More information

BENJAMIN BELLO CHARLINE LEGER

BENJAMIN BELLO CHARLINE LEGER Sensible heat storage in a water tank Influence of the heat source location and the height of the tank on the temperature distribution Degree Project in the Engineering Programme Building and Civil Engineering

More information

Performance of a Solar Heating System with Photovoltaic Thermal Hybrid Collectors and Heat Pump

Performance of a Solar Heating System with Photovoltaic Thermal Hybrid Collectors and Heat Pump Performance of a Solar Heating System with Photovoltaic Thermal Hybrid Collectors and Heat Pump Mark Dannemand, Technical University of Denmark, Department of Civil Engineering, Denmark Simon Furbo, Technical

More information

Numerical Analysis of the Phase Change Behavior of High Power Latent Heat Storages with 3D Wire Structures

Numerical Analysis of the Phase Change Behavior of High Power Latent Heat Storages with 3D Wire Structures Numerical Analysis of the Phase Change Behavior of High Power Latent Heat Storages with 3D Wire Structures André Schlott *1, Judith Hörstmann 2, Olaf Andersen 1, Jens Meinert 1 1 Fraunhofer Institute for

More information

Modelling of an adsorption chiller with Modelica

Modelling of an adsorption chiller with Modelica Modelling of an adsorption chiller with Modelica Matthias Schicktanz Fraunhofer Institute Solar Energy Systems Heidenhofstr. 2, 79110 Freiburg matthias.schicktanz@ise.fraunhofer.de Abstract his paper describes

More information

Laboratory Test of a Cylindrical Heat Storage Module with Water and Sodium Acetate Trihydrate

Laboratory Test of a Cylindrical Heat Storage Module with Water and Sodium Acetate Trihydrate Downloaded from orbit.dtu.dk on: Nov 01, 2018 Laboratory Test of a Cylindrical Heat Storage Module with Water and Sodium Acetate Trihydrate Dannemand, Mark; Kong, Weiqiang; Berg, Jakob Brinkø; Furbo, Simon

More information

Available online at ScienceDirect. Energy Procedia 69 (2015 )

Available online at  ScienceDirect. Energy Procedia 69 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 69 (2015 ) 737 747 International Conference on Concentrating Solar Power and Chemical Energy Systems, SolarPACES 2014 Economic evaluation

More information

Laboratory Testing of Solar Combi System with Compact Long Term PCM Heat Storage

Laboratory Testing of Solar Combi System with Compact Long Term PCM Heat Storage Downloaded from orbit.dtu.dk on: Nov 16, 2018 Laboratory Testing of Solar Combi System with Compact Long Term PCM Heat Storage Berg, Jakob Brinkø; Englmair, Gerald; Dannemand, Mark; Kong, Weiqiang; Fan,

More information

Energy Conversion and Management

Energy Conversion and Management Energy Conversion and Management 50 (2009) 439 443 Contents lists available at ScienceDirect Energy Conversion and Management journal homepage: www.elsevier.com/locate/enconman PCM air heat exchangers

More information

Phase Change Materials (PCMs) for energy storage in Thermal Solar Cooling Systems. Andrea Frazzica Valeria Palomba Vincenza Brancato

Phase Change Materials (PCMs) for energy storage in Thermal Solar Cooling Systems. Andrea Frazzica Valeria Palomba Vincenza Brancato Phase Change Materials (PCMs) for energy storage in Thermal Solar Cooling Systems Andrea Frazzica Valeria Palomba Vincenza Brancato AGENDA Introduction Latent Thermal Energy Storage Example of latent TES

More information

Thermal Energy Storage Using Phase Change Material

Thermal Energy Storage Using Phase Change Material Thermal Energy Storage Using Phase Change Material Rajkumar.P 1, Karthick Raman. R 2, Navaneeth.V 2, Vishnu Prabhu. T 2 1 Assistant Professor, Department of Mechanical Engineering, Arjun College of Technology

More information

EML 5930 Graduate Design Project 1. Final Report. April 27, 2011

EML 5930 Graduate Design Project 1. Final Report. April 27, 2011 EML 5930 Graduate Design Project 1 Final Report April 7, 011 Shannon Ingersoll Table of Contents Abstract... Introduction... Methods... 6 Phase 1:... 6 Phase :... 10 Results... 17 Phase 1:... 17 Phase

More information

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach 8th Edition in SI Units Yunus A. Ç engel, Michael A. Boles McGraw-Hill, 2015 CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Objectives Develop the conservation

More information

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao

More information

DEVELOPMENT OF A FRAMEWORK BASED ON PYFMI FOR OPTIMIZATION AND FAULT DETECTION

DEVELOPMENT OF A FRAMEWORK BASED ON PYFMI FOR OPTIMIZATION AND FAULT DETECTION DEVELOPMENT OF A FRAMEWORK BASED ON PYFMI FOR OPTIMIZATION AND FAULT DETECTION G. A. Böhme 1 und N. Réhault 1 1 Fraunhofer-Institut für Solare Energiesysteme ISE, Freiburg, Germany ABSTRACT In this article

More information

Exergy analysis of a flat plate solar collector

Exergy analysis of a flat plate solar collector Exergy analysis of a flat plate solar collector Sunil Chamoli GRDIMT Dehradun, Uttarakhand, India Abstract In this study, exergetic performance analysis of flat plate solar collector has been carried out

More information

Research Article The Effect of PCM Capsule Material on the Thermal Energy Storage System Performance

Research Article The Effect of PCM Capsule Material on the Thermal Energy Storage System Performance ISRN Renewable Energy, Article ID 52928, 6 pages http://dx.doi.org/1.11/214/52928 Research Article The Effect of PCM Capsule Material on the Thermal Energy Storage System Performance R. Meenakshi Reddy,

More information

CFD SIMULATION AND EXPERIMENTAL VALIDATION OF FLUID FLOW IN LIQUID DISTRIBUTORS

CFD SIMULATION AND EXPERIMENTAL VALIDATION OF FLUID FLOW IN LIQUID DISTRIBUTORS CFD SIMULATION AND EXPERIMENTAL VALIDATION OF FLUID FLOW IN LIQUID DISTRIBUTORS Marc Heggemann 1, Sebastian Hirschberg 1, Lothar Spiegel 2, Christian Bachmann 2 1 Sulzer Innotec, Sulzer Markets & Technology

More information

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES SUMMARY 1 CONSERVATION OF MASS Conservation

More information

Convective heat transfer and flow characteristics of Cu-water nanofluid

Convective heat transfer and flow characteristics of Cu-water nanofluid Vol. 45 No. 4 SCIENCE IN CHINA (Series E) August 2002 Convective heat transfer and flow characteristics of Cu-water nanofluid LI Qiang XUAN Yimin School of Power Engineering, Nanjing University of Science

More information

1/48 STE-L4. Solar storage. water storage PCM stores volume design stratification heat losses

1/48 STE-L4. Solar storage. water storage PCM stores volume design stratification heat losses 1/48 STE-L4 Solar storage water storage PCM stores volume design stratification heat losses Heat storage for solar thermal systems 2/48 irregular heat supply irregular heat load during a day during a year

More information

HORIZONTAL SHELL SIDE FLUIDIZED BED HEAT EXCHANGER, DESIGN CONSIDERATIONS AND EXPERIENCES FROM A PILOT UNIT

HORIZONTAL SHELL SIDE FLUIDIZED BED HEAT EXCHANGER, DESIGN CONSIDERATIONS AND EXPERIENCES FROM A PILOT UNIT HORIZONTAL SHELL SIDE FLUIDIZED BED HEAT EXCHANGER, DESIGN CONSIDERATIONS AND EXPERIENCES FROM A PILOT UNIT M.C. van Beek 1, M. Cancela Vallespin 1, 1 Klaren International, Hanzeweg 35N, 3771 NG, Barneveld,

More information

Numerical Simulation of a Building Envelope with High Performance Materials

Numerical Simulation of a Building Envelope with High Performance Materials Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Numerical Simulation of a Building Envelope with High Performance Materials Mohammad H. Baghban *1, Per J. Hovde 1 and Arild Gustavsen 2

More information

An experimental investigation of cold storage in an encapsulated thermal storage tank

An experimental investigation of cold storage in an encapsulated thermal storage tank Experimental Thermal and Fluid Science 23 (2000) 133±144 www.elsevier.nl/locate/etfs An experimental investigation of cold storage in an encapsulated thermal storage tank Sih-Li Chen a, *, Chin-Lung Chen

More information

POTENTIAL USE OF PHASE CHANGE MATERIALS IN GREENHOUSES HEATING: COMPARISON WITH A TRADITIONAL SYSTEM

POTENTIAL USE OF PHASE CHANGE MATERIALS IN GREENHOUSES HEATING: COMPARISON WITH A TRADITIONAL SYSTEM 004_Caprara(546)_25 18-11-2009 11:53 Pagina 25 J. of Ag. Eng. - Riv. di Ing. Agr. (2009), 3, 25-32 POTENTIAL USE OF PHASE CHANGE MATERIALS IN GREENHOUSES HEATING: COMPARISON WITH A TRADITIONAL SYSTEM Claudio

More information

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor W.K. Lee 1, S.J. Kim 1, D.Y. Lee 1, W.K. Hwang 1, K.Y. Lee 1 1) Department of Mechanical and Control Engineering,

More information

Development of a hot water tank simulation program with improved prediction of thermal stratification in the tank

Development of a hot water tank simulation program with improved prediction of thermal stratification in the tank Downloaded from orbit.dtu.dk on: Aug 25, 2018 Development of a hot water tank simulation program with improved prediction of thermal stratification in the tank Fan, Jianhua; Furbo, Simon; Yue, Hongqiang

More information

Numerical Investigation on Latent Heat Storage Unit of Different Configurations Manish K Rathod and Jyotirmay Banerjee

Numerical Investigation on Latent Heat Storage Unit of Different Configurations Manish K Rathod and Jyotirmay Banerjee Vol:5, No:3, Numerical Investigation on Latent Heat Storage Unit of Different Configurations Manish K Rathod and Jyotirmay Banerjee Digital Open Science Index, Mechanical and Mechatronics Engineering Vol:5,

More information

Study of water falling film over horizontal drop shaped and inverted drop shaped tubes

Study of water falling film over horizontal drop shaped and inverted drop shaped tubes Study of water falling film over horizontal drop shaped and inverted drop shaped tubes Vipul Kumar Sharma, Nirmal Kant Singh 2 Dept. of Mechanical Engineering, GLBITM, Greater Noida, U.P, 236, India 2

More information

CFD-BASED INVESTIGATION OF HEAT TRANSFER CHARACTERISTICS OF FLUE GAS-WATER HEAT EXCHANGER PANELS PRODUCED WITH A NOVEL MANUFACTURING PROCESS

CFD-BASED INVESTIGATION OF HEAT TRANSFER CHARACTERISTICS OF FLUE GAS-WATER HEAT EXCHANGER PANELS PRODUCED WITH A NOVEL MANUFACTURING PROCESS CFD-BASED INVESTIGATION OF HEAT TRANSFER CHARACTERISTICS OF FLUE GAS-WATER HEAT EXCHANGER PANELS PRODUCED WITH A NOVEL MANUFACTURING PROCESS T. FUKUE 1, C. SPITAS 2, M. DWAIKAT 3 and M. ISHIZUKA 4 1 Department

More information

PAPER-I (Conventional)

PAPER-I (Conventional) 1. a. PAPER-I (Conventional) 10 kg of pure ice at 10 ºC is separated from 6 kg of pure water at +10 O C in an adiabatic chamber using a thin adiabatic membrane. Upon rupture of the membrane, ice and water

More information

COP-OPTIMISED PRESSURE CONTROL FOR A CENTRALISED CO 2 COOLING SYSTEM IN AIRCRAFT APPLICATIONS

COP-OPTIMISED PRESSURE CONTROL FOR A CENTRALISED CO 2 COOLING SYSTEM IN AIRCRAFT APPLICATIONS COP-OPTIMISED PRESSURE CONTROL FOR A CENTRALISED CO 2 COOLING SYSTEM IN AIRCRAFT APPLICATIONS S. ADEYEFA, O. SCHADE, U. CARL Hamburg University of Technology, Department of Aircraft Systems Engineering

More information

Experimental and Numerical Study of Heat Transfer Process of Chilled Water Storage Tank

Experimental and Numerical Study of Heat Transfer Process of Chilled Water Storage Tank Universal Journal of Mechanical Engineering 6(4): 63-75, 2018 DOI: 10.13189/ujme.2018.060402 http://www.hrpub.org Experimental and Numerical Study of Heat Transfer Process of Chilled Water Storage Tank

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BY AENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2016 Special 10(6): pages 72-78 Open Access Journal Cfd Analysis Of

More information

Cooling Systems using combined Water plus Phase Change Material in graphite reservoirs for cooling burst thermal loads

Cooling Systems using combined Water plus Phase Change Material in graphite reservoirs for cooling burst thermal loads Proceedings of the 3rd IASME/WSEAS Int. Conf. on HEA RANSFER, HERMAL ENGINEERING AND ENVIRONMEN, Corfu, Greece, August 2-22, 25 (pp43-49) Cooling Systems using combined plus Phase Change Material in graphite

More information

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max. SET - 1 1. a) Discuss about PMM I and PMM II b) Explain about Quasi static process. c) Show that the COP of a heat pump is greater than the COP of a refrigerator by unity. d) What is steam quality? What

More information

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool From the SelectedWorks of Innovative Research Publications IRP India Spring March 1, 2015 Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University

More information

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model Analysis of Uniformity and Energy Consumption in Supermarket installed DurkeeSox Air Dispersion System with PE Air Dispersion Model Summary: Taking partial area of a large supermarket for example, to simulate

More information

Comparison of Heat Transfer Coefficients in Free and Forced Convection using Circular Annular Finned Tubes

Comparison of Heat Transfer Coefficients in Free and Forced Convection using Circular Annular Finned Tubes Comparison of Heat Transfer Coefficients in Free and Forced Convection using Circular Annular Finned Tubes 1 Dr. Abdul Jabbar N. Khalif, 2 Israa Riyadh Aziz Al mousawi 1 Assistant professor College of

More information

AUTOMOTIVE COMPACT SURPERCHARGE-AIR INTERCOOLER NUMERICAL ANALYSIS. Abstract. 1. Introduction

AUTOMOTIVE COMPACT SURPERCHARGE-AIR INTERCOOLER NUMERICAL ANALYSIS. Abstract. 1. Introduction AUTOMOTIVE COMPACT SURPERCHARGE-AIR INTERCOOLER NUMERICAL ANALYSIS G. Starace, E. Carluccio, D. Laforgia Università degli studi di Lecce, Dipartimento di Ingegneria dell Innovazione via per Arnesano, 73100,

More information