Low SCR Wind Identification and Mitigation. Will Lovelace MIPSYCON 2015 November 11 th, 2015
|
|
- Poppy Griselda Atkins
- 5 years ago
- Views:
Transcription
1 Low SCR Wind Identification and Mitigation Will Lovelace MIPSYCON 2015 November 11 th, 2015
2 System Background - Diagram
3 System Background - Diagram
4 System Background - Description MW wind farm on remote 115 kv system 133 GE 1.5 MW Type 3 machines Four control groups 54 mile ACSR (weak) to the south 58 mile T2-477/477 ACSR (strong) to the east Originally two load serving lines networked in 2008 when the wind farm was built
5 System Background - Limits Wind-adjusted ratings Line L1 and L3 Steady State voltage stability limits 120 MW on Line L1 SPS Flow > 120 MVA on line L1 towards S1 Trip 80 MW wind generation at farm
6 System Background - Operating Processes Limit Wind Farm during local 115 kv line switching L1 No limit L2 60 MW L3 60 MW No limits for transient stability during prior outage
7 Composite Short Circuit Ratio (CSCR) CSCR = SCC system P wind SCC system is the 3ph fault MVA at the high-side wind generator transformer equivalent bus with all local and nearby high-side wind generator transformer equivalent buses shorted Local and nearby wind machines disconnected P wind is the total nameplate capacity of all local and nearby wind generation
8 Composite Short Circuit Ratio (CSCR) 0.6 kv 34.5 kv SCC system 115 kv System Intact SCC system = 307 MVA CSCR 1.5 Outage of L2 SCC system = 176 MVA CSCR 0.9
9 Composite Short Circuit Ratio (CSCR) Historically, a CSCR < ~3.0* meant instability Presently a CSCR > ~1.0* could be managed with control changes in some cases MPC s current CSCR interconnection criteria is: CSCR < 3.0* (or applicable manufacturer data) requires further analysis *The above CSCR limits are not prescriptive and CSCR needs to be considered on a case-by-case basis.
10 Event A - 6/7/2011 A. Initial B-phase SLG fault on L2 B. L2 opens after ~2 cyc and wind farm begins to go unstable C. SUB A Zone 1 Phase B-C element asserts after ~2.5 cyc D. L4 opens after ~2 cyc
11 Event A - 6/7/2011 A B C D
12 Event B - 11/28/2011 A. L1 manually opened by MPC Operators and voltage begins to decay B. SUB A & B Zone 1 Phase A-B & B-C elements looking both directions assert after ~4.4 sec C. L2 opens after ~1.5 cyc
13 Event B - 11/28/2011 A B/C B C
14 Wind Farm Instability vs. Distance Relaying The swing briefly (1/4 cyc) tricks the distance element of the SEL 311C into seeing a forward fault Too fast (25 Hz) to be handled with OOS tripping/blocking Option: Introduce a Zone 1 phase distance delay NOTE: Be careful with this so as not to propagate the swing outside the local system
15 Wind Farm Instability vs. Distance Relaying While not intended the operation of the Zone 1 distance element protects the rest of the system by tripping the farm BUT The wind turbine restart procedure is long and complicated due to loss of the grid tie, and the operation of the distance element in every situation is not guaranteed
16 GE Study #1 Identify and Qualify Issues A model of the local system was built in GE s EMTP-type proprietary software Three historical events ran 6/7/ /9/ /28/2011 Model output benchmarked against historical recordings Preliminary recommendations
17 GE Study #1 Modeling/Validation Simulated voltage (p.u.) at Sub B during manual opening of L3 Lighter shaded line is the historical recording. Motor modeling assumptions correct, but other load responses not modeled.
18 GE Study #2 Quantify Issues and Propose Solutions Refine modeling of Study #1 Comprehensive analysis Long-term voltage stability (plant level control) Short-term voltage stability (generator level control) Voltage regulator stability (dq/dv) Fast Dynamics Specific control change recommendations
19 GE Study #2 Voltage Stability P-V and Q-P analysis Long-term (LT) and short-term (ST) Combinations of local outages and contingencies
20 GE Study #2 Voltage Regulator Stability (dq/dv) Practical limit (+/-10% margin) For most conditions, more limiting than voltage stability Hard limit
21 GE Study #2 Limits Note capacitive load has a 10 MW negative effect
22 GE Study #2 Control Change Summary Generator-level control changes Plant-level control changes Operating process changes
23 GE Study #2 Generator level Control Changes Weak grid control changes on ALL turbines Decreased gains in control loop Lower rate of active current change Fast-stop feature enabled on 53 turbines Detects a large increase in system impedance between time-steps and trips turbine Turbines automatically restart after 2 minutes
24 GE Study #2 Plant Level Control Changes Reduce response time of voltage regulator Enable line-drop compensation Slow down power factor regulation Limit wind farm to 120 MW following a fast stop event
25 GE Study #2 Operating Process Changes Prior to control changes being implemented During local 115 kv switching: Maintain MW limits During local 115 kv outages: 80 MW limits During adjacent 230 kv and 115 kv system outages: MW limits
26 GE Study #2 Operating Process Changes After control changes implemented During local 115 kv switching: Maintain MW limits During local 115 kv outages: 120 MW limits During adjacent 230 kv and 115 kv system outages: no limits Indication of a fast stop event sent to the MPC control room Following a fast stop event, the MPC operator must assess the state of the grid and release the wind farm to full output if allowable
27 Control/Process Change Example A. Fault on L3 opens line B. Fast Stop trips up to 53 turbines prior to distance relaying seeing a fault C. After 2 minutes tripped turbines reconnect to grid with plant limiting output to 120 MW D. Operator closes L3 and releases farm to full output
28 Testing Test #1 Wind farm at 110 MW Opened L2 51 turbines operated on fast stop L2 was closed after approximately 2 minutes
29 Testing Test #1 Opening L2 w/ Fast Stop vs. Opening L3 w/o Fast Stop
30 Testing Test #2 Wind farm at 185 MW Opened L1 No turbines operated on fast stop Oscillations due to system response
31 Testing Test #3 Wind farm at 60 MW Opened L2 No turbines operated on fast stop
32 Performance Experience Overtripping occassionally occurs Remote 230 kv bus fault example
33 Will Lovelace Questions?
What makes a Wind Plant Grid Friendly?
Stable Renewable Plant Voltage and Reactive Power Control NERC ERSTF June 11-12, 2014 Sebastian Achilles Nicholas Miller Einar Larsen Jason MacDowell GE Energy Consulting 1 / Topics Features of modern
More informationTRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA
TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA For Compliance with NERC Reliability Standard: TPL-001-4 1/10/2017 Version: 4.2 Table of Contents 1 Revision and Approval History... 2 1.1 Revision
More informationFault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012
Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012 1 Presentation Overview Joint Working Group The Issue Structure of the Report Wind Plant Configuration Wind Turbine Generators
More informationGOLDEN VALLEY ELECTRIC ASSOCIATION
October 13, 2008 GOLDEN VALLEY ELECTRIC ASSOCIATION Eva Creek Wind Farm-Limited Study Doubly Fed Asynchronous Generators Power Flow, Reactive Compensation, Transient Stability Revision 0 PROJECT NUMBER:
More informationStandard MH-TPL Transmission System Planning Performance Requirements
A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: MH-TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon
More informationMapping Document for FAC-010-3
Mapping Document for FAC-010-3 The Project 2015 09 standard drafting team (SDT) is proposing the retirement of the NERC FAC 010 3 Reliability Standard. The SDT further proposes a new paradigm regarding
More informationStandard TPL Transmission System Planning Performance Requirements
A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationStandard Development Timeline
Standard TPL-001-4 Transmission System Planning Performance Requirements Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationTransfer Capability Methodology. for the Near-Term. Transmission Planning Horizon
Transfer Capability Methodology for the Near-Term Transmission Planning FAC-013-2 Version 2.2 June 30, 2018 Table of Contents 1 PURPOSE... 3 2 DEFINITION... 3 3 APPLICABILITY... 3 4 TRANSFER CAPABILITY
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationSPP RTO Compliance Forum TPL Jason Terhune
SPP RTO Compliance Forum TPL-001-4 Jason Terhune 501-688-8261 jterhune@spp.org 1 TPL Standards have been Consolidated TPL-001-0.1 TPL-002-0b TPL-003-0b TPL-004-0a TPL-001-4 R1 R2 R3 R4 R5 R6 R7 R8 2 Overview
More informationA. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements
A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements 2. Number: PRC 006 RFC 01 3. Purpose: To establish ReliabilityFirst requirements for automatic Load shedding (UFLS) to support
More informationCoordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function
Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function Mariana B. Pereira 1, Sebastian A. Achilles 2, Nath Venkit 2 Energy Consulting General
More informationRochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017
Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA March 21, 2017 Contents 1 Background...3 2 National and Regional Criteria and Guides...4 2.1 2.1 NERC Transmission Planning Standards...4 2.2
More informationInvestigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection
7th Solar Integration Workshop, 24-25 October 2017, Berlin, Germany Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection Baheej
More informationWind Farms in Weak Grids Compensated with STATCOM
Nordic PhD course on Wind Power (June 5-11, 2005) Final Examination Report Ph.D. Candidate: Akarin Suwannarat Supervisors: Birgitte Bak-Jensen Institute of Energy Technology, Aalborg University Pontoppidantstraede
More informationConnection Study Requirements
Document Release Released: September 20, 2010 The Customer shall comply with all the applicable requirements in this document when performing connection studies to produce the engineering study report.
More informationA. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements
A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements 2. Number: PRC 006 RFC 01 3. Purpose: To establish ReliabilityFirst requirements for automatic underfrequency Load shedding
More informationGenerator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report
Generator Interconnection Affected System Impact Study Plains & Eastern Clean Line Final Report May 19, 2015 MISO 2985 Ames Crossing Eagan Minnesota - 55121 http://www.misoenergy.org Midcontinent Independent
More informationGrid Interconnection Issues for Wind Generation
Grid Interconnection Issues for Wind Generation NRECA APPA - DOE Teleconference December 8, 2005 By Thomas A. Wind, PE Wind Utility Consulting Jefferson, Iowa Topics I Will Cover What are the key technical
More informationStakeholder Communication. Inputs, Assumptions, and Preliminary Assessment. Base Model. Needs, Solutions, Sensitivity: Yr 5
Methodology and Assumptions 1.1 Overview These sections describe the process we used to perform a network assessment of the ATC transmission system. The description includes study assumptions, methods
More informationCriteria. C~/v~ ~ ~ ~ G! " A1A "~"" T"""g"'~10N COr'P""''~ P LG -C R-0001-V T~c~e: Transmission System Planning Criteria
A1A "~"" T"""g"'~10N COr'P""''~ Criteria Department: Document No: System Planning and Strategic Projects P LG -C R-0001-V 19.2 T~c~e: Transmission System Planning Criteria issue gate: Previous Date: February
More informationPID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation
PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation Prepared by: Entergy Services, Inc. T & D Planning 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date Description
More informationInformation Document Protection System Information ID# R
Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between the Information Document and the related authoritative document(s)
More informationHydro-Quebec s experience with HYPERSIM Real-time Power System Simulator
Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator Christian Larose, Power System Simulation, Hydro-Québec (CANADA) June 26, 2013 Presentation overview > Application of Hypersim at
More informationWIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY
WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS J O G Tande and K Uhlen SINTEF Energy Research, Norway SUMMARY Cost efficient utilisation of the wind energy resource requires wind farms to be located
More informationWind Farm Performance on the Grid: Perception and Reality
Wind Farm Performance on the Grid: Perception and Reality WindVAR and LVRT Data and Graphs provided by Nicholas W. Miller GE Energy, Energy Consulting 1 GE Energy Wind Energy Grid Performance: A Perception
More informationDaniel Feltes Phone: Fax:
Coordination of Controls of Renewable Power Plants to Meet Steady State and Dynamic Response Requirements for Voltage Control and Reactive Power Supply Dinemayer Silva Phone: 518-395-5169 Fax: 518-346-2777
More informationA PRACTICAL GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS
A PRACTICAL GUIDE TO PERFORMING WIDE-AREA COORDINATION ANALYSIS November 10, 2015 Author and Presenter: Bipasha Barman, P.E. POWER Engineers Other Authors: Jason Clack, P.E. POWER Engineers Vernon Padaca,
More informationEffects of Unbalanced Faults on Transient Stability of Cogeneration System
ffects of Unbalanced Faults on Transient Stability of Cogeneration System WI-NNG CHANG CHIA-HAN HSU Department of lectrical ngineering Chang Gung University 259 Wen-Hwa st Road, Kwei-Shan, Tao-Yuan, Taiwan,
More informationLesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System
Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System Primary Interest Groups Balancing Authorities (BAs) Transmission Operators (TOPs) Generator Operators
More informationASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved.
ASSOCIATED NERC STANDARD(S): TPL-001-4 (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. Phase in of individual TPL-001 requirements will be based on the effective dates
More informationTransmission Competitive Solicitation Questions Log Question / Answer Matrix Delaney to Colorado River 2014
No. Comment Submitted ISO Response Date Q&A Posted 1 Can the CAISO provide a line rating methodology (similar to a NERC FAC-008 standard) or include a requirement of using any The ISO does not provide
More informationA Transmission Planning Case Study for Wind Integration CREZ in ERCOT
A Transmission Planning Case Study for Wind Integration CREZ in ERCOT Warren Lasher Director, System Planning Electric Reliability Council of Texas, Inc. NAWEA 2013 Symposium The ERCOT Region The ERCOT
More informationTRI-COUNTY RURAL ELECTRIC COOPERATIVE, INC. Policy Bulletin No Appendix A SAFETY & INTERCONNECTION REQUIREMENTS FOR ALTERNATE ENERGY PRODUCTION
TRI-COUNTY RURAL ELECTRIC COOPERATIVE, INC. Policy Bulletin No. 3-17 Appendix A SAFETY & INTERCONNECTION REQUIREMENTS FOR ALTERNATE ENERGY PRODUCTION The Cooperative recognizes the various electric industry
More informationCalifornia Independent System Operator Renewable Integration Study
California Independent System Operator Renewable Integration Study Clyde Loutan Proposed Transmission Plan for Integration of Renewables Transmission System Analysis - Overview Joint Study between the
More informationTechnical considerations for integration of distributed renewables on the grid
Technical considerations for integration of distributed renewables on the grid A paper by Dr Charlotte Higgins, Dr Bunmi Adefajo & Kumbuyani Chisoro Kumbuyani Chisoro Manager Southern Africa TNEI Services
More informationPlanning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES
Planning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES Effective Date: September 11, 2017 Revision History Date Version Description June 6, 1998 0.0 Initial LGEE document
More informationStandard TPL (i) System Performance Under Normal Conditions
Standard TPL-001-0.1(i) System Performance Under rmal Conditions A. Introduction 1. Title: System Performance Under rmal ( Contingency) Conditions (Category A) 2. Number: TPL-001-0.1(i) 3. Purpose: System
More informationTransient Stability Analysis of an Industrial Cogeneration System
Transient Stability Analysis of an Industrial Cogeneration System Hung-Cheng Chen Shang-Yi Chen Shun-Chung Shih Department of Electrical Engineering, National Chin-Yi University of Technology hcchen@ncut.edu.tw
More informationANTICIPATING AND ADDRESSING SECURITY CHALLENGES IN AN EVOLVING POWER SYSTEM
ANTICIPATING AND ADDRESSING SECURITY CHALLENGES IN AN EVOLVING POWER SYSTEM January 2017 PRESENTED BY JENNY RIESZ SLIDE 1 AGENDA 1. Introduction to the NEM 2. Future Power System Security Program 3. Identifying
More informationPOTOMAC ELECTRIC POWER COMPANY
POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission
More informationFeasibility Study Report
Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Stanly County, NC Total Output Requested By Customer: 30 MW Commercial Operation Date Requested By Customer: 12/1/2019 Feasibility
More information11. TRANSMISSION AND INTERCONNECTION FACILITIES
11. TRANSMISSION AND INTERCONNECTION FACILITIES Three transmission line corridors have been investigated in this report, but no route (or routes) has been recommended. One of the five possible configurations
More informationPeak West-wide System Model Validation Activities
Peak West-wide System Model Validation Activities 10/24/2016 Brett Wangen Hongming Zhang Gareth Lim Purpose of This Discussion Provide West-wide System Model (WSM) overview Give insight into ongoing model
More informationTransmission Planning Procedures and Planning Criteria TDOG108
Transmission Division Operating Guidelines Transmission Planning Procedures and Planning Criteria TDOG108 Page 1 of 33 Approved by: William R. Kaul, Vice President Transmission Approved date: 10/13/16
More informationCOLUMBIAGRID 2018 SYSTEM ASSESSMENT DRAFT STUDY PLAN
COLUMBIAGRID 2018 SYSTEM ASSESSMENT DRAFT STUDY PLAN January 11, 2018 ColumbiaGrid 8338 NE Alderwood Road, Suite 140 Portland, OR 97220 www.columbiagrid.org (503) 943-4940 8338 NE Alderwood Road, Suite
More informationSYSTEM IMPACT STUDY FINAL REPORT
SYSTEM IMPACT STUDY FINAL REPORT Prepared for Tri-State Generation & Transmission Association, Inc. By Dennis Woodford, Garth Irwin, and Andrew Isaacs. Electranix Corporation 107 865 Waverley St., Winnipeg,
More informationTransmission Planning Standards for the Baltimore Gas & Electric Company Transmission System
Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents Page I. Introduction...
More informationSteady-state and transient voltage stability analysis of a weak distribution system with a remote doubly fed induction generator-based wind farm
RESEARCH ARTICLE Steady-state and transient voltage stability analysis of a weak distribution system with a remote doubly fed induction generator-based wind farm Amit Kunwar, Ramesh Bansal 2 & Olav Krause
More informationDynamic Compensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network
INTERNTIONL ONFERENE ON ONTROL, UTOMTION, OMMUNITION ND ENERGY ONSERVTION -2009, 4th-6 th June 2009 Dynamic ompensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network 1
More informationPlatte River Power Authority. Ten-Year Transmission Plan ( )
Platte River Power Authority Ten-Year Transmission Plan (2015-2024) Prepared by PRPA System Planning December 31, 2014 Table of Contents I. Executive Summary II. III. IV. Scope Assumptions Criteria V.
More informationSession 9: Photovoltaic System Case Studies And Electric Distribution Planning for DER October 21, 2015 Santiago, Chile
Session 9: Photovoltaic System Case Studies And Electric Distribution Planning for DER October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado, U.S.A.
More informationAESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS
APPENDIX G AESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS Transmission Planning Criteria - Basis and Assumptions Version 1.0 1. Introduction This document presents the reliability standards,
More informationXXXX. Bremner Trio Small Hydro Project. Interconnection System Impact Study
XXXX Bremner Trio Small Hydro Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY, LIMITATION
More informationTPL 001 AB 0 System Performance Under Normal Conditions
Alberta Reliability Standard System Performance Under rmal Conditions TPL-001-AB-0 TPL 001 AB 0 System Performance Under rmal Conditions 1. Purpose The purpose of this reliability standard is to ensure
More informationLimon 100 MW Wind Farm System Interconnection Study
Limon 100 MW Wind Farm System Interconnection Study October 27, 2004 Studies Conducted By: Garrett Durland Limon Wind Farm Impact Study I. Introduction In April 2004, Western Area Power Administration
More informationTransmission Expansion Advisory Committee. October 11, 2012
Transmission Expansion Advisory Committee October 11, 2012 Issues Tracking Issues Tracking Open Issues None New Issues 3 2012 RTEP - Renewable Portfolio Standards Scenarios Progress Update Scenario #1
More informationCapacity and Location Effects of Wind Turbine Energy Systems on Power Systems Stability
International Journal on Power Engineering and Energy (IJPEE) Vol. (4) No. () ISSN Print (234 738) and Online (234 73X) January 23 Capacity and Location Effects of Wind Turbine Energy Systems on Power
More informationDesign & Implementation of an Industrial Facility Islanding and Load Shed System
Design & Implementation of an Industrial Facility Islanding and Load Shed System Mark Adamiak GE Digital Energy Bernard Cable GE Energy 1. Abstract The availability of electricity supply in all areas of
More informationVoltage Stability Assessment of a Power System Incorporating Wind Turbine Using Power System Analysis Toolbox (Psat)
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 2 Ver. VI (Mar Apr. 2014), PP 19-25 Voltage Stability Assessment of a Power System
More informationHarnessing Renewables in Power System Restoration
Harnessing Renewables in Power System Restoration Dr. Wei Sun, and Amir Golshani Assistant Professor, EECS Dept. University of Central Florida (South Dakota State University) Panel: Cascading Failures:
More informationSOUTH AUSTRALIA SYSTEM STRENGTH ASSESSMENT
SOUTH AUSTRALIA SYSTEM STRENGTH ASSESSMENT Published: September 2017 IMPORTANT NOTICE Purpose AEMO has prepared this document to provide information about the levels of system strength required to securely
More informationAMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER
AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November
More informationPage 1 of 5 Version 1
GREATER BAY AREA BLACKSTART TECHNICAL VARIABLES and CRITERIA Geographic Area of Consideration Upon the loss of AC to the Greater Bay Area (GBA), the potential blackstart resource must support the restoration
More information500 MW Wind Farm Technical System Impact Study
FINAL REPORT Report to: El Paso Electric for 500 MW Wind Farm Technical System Impact Study Prepared by: Goran Drobnjak Sang Lee Emad Ahmed Reigh Walling Einar Larsen February 19, 2008 EPE_TechSIS_Final.doc
More informationNERC PLANNING STANDARDS
NERC PLANNING STANDARDS North American Electric Reliability Council April 2004 Version of All Planning Standards Terms and Their Definitions As Used in the Analysis (Study) an examination or simulation
More informationAMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER
AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November
More informationSystem Integrity Protection Schemes Increasing operational security and system capacity
21, rue d Artois, F-758 PARIS C2-21 CIGRE 212 http : //www.cigre.org System Integrity Protection Schemes Increasing operational security and system capacity E. HILLBERG 1, F. TRENGEREID 2, Ø. BREIDABLIK
More informationDRAFT STUDY PLAN FOR 2018
DRAFT STUDY PLAN FOR 2018 Introduction The Ten-year transmission planning process is intended to facilitate a timely, coordinated and transparent process that fosters the development of electric infrastructure
More informationJuly 15 July 31. August First ballot September 1 10, Drafting Team considers comments and makes any revisions indicated
Standard FAC-008-1 Facility Ratings Methodology Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard
More informationReliabilityFirst Regional Criteria 1. Verification and Data Reporting of Generator Gross and Net Reactive Power Capability
ReliabilityFirst Regional Criteria 1 Verification and Data Reporting of Generator Gross and Net Reactive Power Capability 1 A ReliabilityFirst Board of Directors approved good utility practice document
More informationMaui Electrical System Model Development: Data and Assumptions
Maui Electrical System Model Development: Data and Assumptions Prepared for the U.S. Department of Energy Office of Electricity Delivery and Energy Reliability Under Award No. DE-FC-06NT42847 Task 8 Deliverable
More informationENGINEERING RECOMMENDATION P2/6 SECURITY OF SUPPLY JULY Energy Networks Association Engineering Directorate
ENGINEERING RECOMMENDATION P2/6 SECURITY OF SUPPLY JULY 2006 Energy Networks Association Engineering Directorate NORTHERN IRELAND ELECTRICITY Ltd AMENDMENT SHEET ISSUE 1 - MAY 2015 SECURITY OF SUPPLY DOCUMENT
More informationCommunity Clean Energy Resiliency Initiative PON-ENE BESS Request for Proposals Question and Answer Log
Community Clean Energy Resiliency Initiative PON-ENE-2014-036 BESS Request for Proposals Question and Answer Log 03/09/16 Lead Time 1. The schedule included in the BESS RFP for the energy storage project
More informationIntegration issues and simulation challenges of high penetration PV
Integration issues and simulation challenges of high penetration PV March 6, 2014 EnerNex Capabilities Power Systems Modeling Transient Analysis Our preferred tools: EMTP RV, PSCAD Steady State & Quasi
More informationInterconnection System Feasibility Study
Interconnection System Feasibility Study Zonnebeke Wind Project Report No: T&S Planning 2015-053 November 2015 FINAL British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority
More informationSSR STUDY REPORT FINAL
System Support Resource Study Escanaba 1 & 2: 25 MW Coal 36 Month Suspension 6/15/2012 6/15/2015 SSR STUDY REPORT FINAL June 21, 2012 Redacted version for January 3, 2013 filing EXECUTIVE SUMMARY An Attachment
More informationPID275 Feasibility Study Report 9.33 MW Distribution Inter-Connection Valentine Substation
PID275 Feasibility Study Report 9.33 MW Distribution Inter-Connection Valentine Substation Prepared by: Entergy Services, Inc. T & D Planning 639 Loyola Avenue L-ENT-17A New Orleans, LA 70113 Rev Issue
More informationAESO System Operating Limits Methodology for the Planning Horizon (R1 FAC-010-AB-2.1)
(R1 FAC-010-AB-2.1) 1 Purpose This document sets out the System Operating Limits Methodology the Alberta Electric System Operator ( AESO ) uses for any studies conducted on the interconnected electric
More informationGUYANA POWER AND LIGHT INC
GUYANA POWER AND LIGHT INC The Terms of Reference REQUEST FOR PROPOSALS: CONSULTANCY SERVICES COORDINATING GENERATOR PROTECTION WITH TRANSMISSION PROTECTION AND GENERATOR CONTROLS (GPL-PI-094-2016) November
More informationSYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm
SYNOPSIS OF THE THESIS Enhanced Power Quality Management of Grid Connected Wind Farm INTRODUCTION OF THE THESIS Faster depletion of fossil fuels and environmental damage has resulted into increased use
More informationControl of a Microgrid in Islanded Mode
Faculty of Science & Engineering School of Engineering and Energy Control of a Microgrid in Islanded Mode A thesis submitted in partial fulfillment of the requirements for the degree of Bachelor of Engineering
More informationSYSTEM IMPACT STUDY FINAL REPORT
TI_04-1214 WIND PROJCT SYSTM IMPACT STUDY FINAL RPORT Prepared for Tri-State Generation & Transmission Association, Inc. By Dennis Woodford, Garth Irwin, and Andrew Isaacs. lectranix Corporation 107 865
More informationMEASUREMENTS AND SIMULATION FOR POWER QUALITY OF A WIND FARM
Research Article MEASUREMENTS AND SIMULATION FOR POWER QUALITY OF A WIND FARM 1 S.P. Shukla, 2 Sushil Kumar Address for correspondence 1 Department of Electrical Engineering, Bhilai Institute of Technology,
More informationMitigating Extraordinary Events using Wide Area Monitoring Applications
2, rue d Artois, F-75008 PARIS 53 RECIFE 20 http : //www.cigre.org Mitigating Extraordinary Events using Wide Area Monitoring Applications E. JOHANSSON, K. UHLEN, G. KJØLLE Norwegian University of Science
More informationResearch Co-design Activity
Research Co-design Activity A. Purpose of Co-design: The ultimate goals of this co-design activity are to: Directly involve all members of a group to make decisions together that would affect their daily
More informationJ. Electrical Systems 10-2 (2014): Regular paper
Khaled Saleh Banawair 1,*, Jagadeesh Pasupuleti 2, J. Electrical Systems 10-2 (2014): 133-148 Regular paper The Impact of Integration of Optimized Low Speed Wind Turbine Into Large Distribution Network
More informationTransmission Losses Report 2015
SP Energy Networks October 2015 Transmission Losses Report 2015 1. INTRODUCTION Special condition 2K of SPT s transmission licence requires SPT to publish an annual transmission losses report detailing
More informationNERC Lessons Learned and Industry Recommendation
NERC Lessons Learned and Industry Recommendation Donnie Bielak Reliability Engineering Agenda Lessons Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System
More informationNERC Reliability Initiatives and Smart Grid
NERC Reliability Initiatives and Smart Grid IEEE PES Late Breaking News July 28, 2009 Robert W. Cummings Director of Event Analysis & Information Exchange System Protection and Control Performance Improvement
More informationPlanned Islanding and Energy Storage at BC Hydro
Planned Islanding and Energy Storage at BC Hydro Workshop: International Smartgrid projects review December 10, 2010 Jaime Peralta M.Sc., P.Eng. Distribution Planning T&D Asset Investment Management BC
More informationFeasibility Study for the Q MW Solar Project
Feasibility Study for the Q195 74.9 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC
More informationTable of Contents. To provide a methodology for determining the System Operating Limits (SOL) for the Planning Horizon at the California ISO.
Table of Contents Purpose... 1 Applicable Reliability Standard(s)... 1 Applicability to California ISO... 1 SOLs and IROLs... 1 Study Methodology... 2 Supporting Information... 6 Responsibilities... 6
More informationTransmission System Security and Planning Standards
ver. 1.4 page 1 from 13 Transmission System Security and Planning Standards April 2014 ver. 1.4 page 2 from 13 TABLE OF CONTENTS 1 Introduction... 4 2 Definitions... 4 2.1 Transmission System... 4 2.2
More informationReview of AEMO s PSCAD Modelling of the Power System in South Australia
Review of AEMO s PSCAD Modelling of the Power System in South Australia Prepared by For Reference Ranil de Silva Director of Engineering Power Systems Consultants Australian Energy Market Operator Operational
More informationSYSTEM IMPACT STUDY FINAL REPORT
SYSTM IMPACT STUDY FINAL RPORT Prepared for Tri-State Generation & Transmission Association, Inc. By Dennis Woodford, Garth Irwin, and Andrew Isaacs. lectranix Corporation 107 865 Waverley St., Winnipeg,
More informationAnalysis of Wind Power Integration for Power System Transient Stability
Analysis of Wind Power Integration for Power System Transient Stability J. K. Muriuki, C. M. Muriithi and L. M. Ngoo Abstract Many developing nations are currently undertaking huge electric power generation
More information