1 Site Preparation Guide Scodix Ultra Press and Scodix Ultra-Pro Press and Scodix Ultra Foil Station

2 Important Notice Copyright Scodix Ltd. All rights reserved. All product names are trademarks of Scodix Ltd. Other names are the property of the respective owners. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system or translated into any language or computer language, in any form or by any means, electronic, mechanical or otherwise without prior written permission of Scodix Ltd. Disclaimer of Warranty Scodix Ltd. has made every effort to ensure the accuracy and relevancy of the material in this document. It is expected that all sections of this document will be read thoroughly and that all information and procedures should be fully understood. However, Scodix Ltd. assumes no responsibility for any errors that may have been included in this document, and reserves the right to make changes to the document without notice. Scodix Ltd. makes no warranty of any kind in regard to this document including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Scodix Ltd. disclaims any responsibility for incidental or consequential damages in connection with the furnishing, performance or use of this document. Parts of this document may be based on hardware or software developed by third-party vendors. Scodix Ltd. disclaims any responsibility for the accuracy of this document with respect to such hardware and software, and assumes no responsibility for incidental or consequential damages arising due to discrepancies between this document and such hardware or software. Safety Notice The Ultra Presses contain a UV lamp and high-voltage power supplies. The system also has moving parts. There is no danger to persons or equipment when the system is operated in accordance with the directions provided by Scodix Ltd. in this and other publications. All high-voltage power supplies are located behind protective covers with warning labels attached. Do not remove these protective covers. Environmental Policy Service personnel are advised that when changing any part of the Ultra Digital Press, care should be taken to dispose of those parts in the correct manner and, where applicable, they should be recycled. When the lifecycle of parts such as filters has been completed, the product should be disposed according to the laws and regulations of the local authority. For more detailed information regarding these recommended procedures, refer to your local or regional Scodix Ltd representative. Scodix Ltd. is committed to continuously seek and implement the best possible manufacturing procedures and servicing routines. Document p/n: DBK Revision: 9 Date: January 2016 Scodix Ultra Press Site Preparation Guide (DBK ) i

3 Miscellaneous Disclaimers The customer is responsible for preparing the site according to the requirements set out in this document. The customer is also responsible for any delays caused by the site not being ready for the installation, such as any extra expenses incurred by the Scodix Installation Team (or Scodix authorized personnel). Scodix does not accept any responsibility for any damage caused to its products by unauthorized personnel. Unless agreed otherwise, it is the customer's responsibility to arrange for the Scodix Press crates to be transported from the port of arrival to the installation site. Therefore, the customer should make sure that the company who delivers and unloads the Scodix Press crates, is given full details of the equipment required for unloading and moving the Scodix Press. Unless agreed otherwise, it is the customer's responsibility to arrange the following: The delivery of the crates containing the Scodix Press from the port of arrival to the site. The unloading of the crates off the truck at the site. (Note: The crates and the Scodix Press must be protected from the environmental (rain, snow, etc.) until they are unpacked into the production area.) The unpacking and the moving of the Scodix Press into the production area (supervised by Scodix personnel). It is the customer's responsibility to ensure that the following items (among others,) conform to the local authority s regulations: Safety requirements Electrical specifications and martials used Qualified local electrician licensed and authorized by the local electrical regulatory authority Fire prevention Health issues Installation provisions Production area requirements Depending on the shipping method used, the press may arrive with minor rust marks. These do not affect the performance or specification of the press whatsoever. How to use the Site Preparation Guide and the Site Preparation Checklist This document serves as a guide to the mandatory Site Preparation that must be performed prior to the delivery and installation of the Scodix Ultra Press. The customer is required to read this document carefully, understand all its details, and implement all the requirements. Scodix (or Scodix authorized) personnel will assist with the unpacking of the Scodix Press, help to move it to its site, and position it properly. Scodix (or Scodix authorized) personnel will also perform the final installation (details of which will be found in the Scodix Ultra Press Installation Guide). Certification This device complies with standards. Scodix Ultra Press Site Preparation Guide (DBK ) ii

4 Table of Contents Important Notice... i Introduction... 5 Ultra Press Configurations...5 Ultra Press with Foil Station... 5 Ultra Press without Foil Station... 5 About this Guide...5 Dimensions and Weight...6 Crated Dimensions and Weight... 6 Uncrated - Doorway minimum Dimensions and Weight... 7 Ultra Press Dimension Diagrams (without Foil Station)...7 Ultra Press Height with doors closed... 7 Ultra Press Width with doors closed - Stacker View (without Foil Station)... 8 Ultra Press Height with Engine doors open - Feeder View (without Foil Station)... 8 Ultra Press Maximum length (without Foil Station)... 8 Ultra Press Dimension Diagrams (with Foil Station)...9 Ultra Press Maximum length (with Foil Station)... 9 Ultra Foil Station Side View... 9 Ultra Foil Station Exit View Ultra Press Weight distribution per Leg...11 Ultra Press Distance between Legs - Top View (without Foil Station) Working Area Dimensions (without Foil Station)...14 Ultra Press Top view - 1 meter gap on sides (without Foil Station) Minimum gap between the Press and ceiling View of Press with Conveyor door open (without Foil Station) Requirements Electrical Power Requirements...16 Floor Requirements...17 Maximum Load Details Utilities and Service Requirements...17 Electrical Connection Requirements...20 Ultra Press Electrical Connections without Transformer: Ultra Press Electrical Connections with Transformer: Connecting the Press to the Main Power Supply Environmental Requirements...21 Press Storage Environment Requirements Working Environment Requirements...22 Illumination Requirements Waste Disposal Requirements Noise Level Requirements Ventilation Requirements Scodix Ultra Press Site Preparation Guide (DBK ) iii

5 Additional Items Provided Site Preparation Checklist How to use the Site Preparation Checklist...24 Site Preparation Checklist...24 Scodix / Distributor Engineer Remarks...25 Signatures...25 Support and Contact Information Document History...26 Scodix Ultra Press Site Preparation Guide (DBK ) iv

6 Introduction Ultra Press Configurations Ultra Press with Foil Station Stacker Foil Statio UV Conveyor Press Engine Feeder Feeder Side Stacker Side Operator Side Ultra Press without Foil Station. Non Operator Side Stacker Side Feeder Side Operator Side About this Guide The content in this guide is relevant to both configurations, unless specifically indicated. Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Configurations 5 of 26

7 Dimensions and Weight This section describes the Scodix Ultra weight, dimensions and working area requirements. It contain the following sections: o Crated Dimensions, page 6 o Uncrated - Doorway minimum Dimensions, page 7 o Working Area Dimensions, page 11 Crated Dimensions and Weight The following table shows the Ultra Press dimensions and weight: Length Height Width Weight Box # UNIT (mm) (mm) (mm) (kg) Box 1 Engine Unit 4,200 2,100 2,038 3,056 Box 2 Feeder + Stacker 2,440 1,940 1,720 1,094 Box 3 UV Conveyor Unit 3,200 1,406 1,350 1,248 Box 4 Foiler 2,000 1,500 1,700 1,100 Length Height Width Weight Box # UNIT (in.) (in.) (in.) (lb.) Box 1 Engine Unit ,737 Box 2 Feeder + Stacker ,412 Box 3 UV Conveyor Unit ,751 Box 4 Foiler ,425 The Scodix Ultra Press should be transported by a forklift that has a minimum lifting capability of at least 5 tons. Scodix Ultra Presses are shipped in wooden crates. The equipment should only be unpacked by a qualified service engineer. Due to its delicate nature, it is essential that the proper equipment is available for handling and moving the shipping crates. The crates are equipped with tilt- and shock watches. Before opening them, check that both the tilt- and shock indicators have not turned red. If either indicator is red, immediately inform Scodix personnel before continuing. Scodix Ultra Press Site Preparation Guide (DBK ) Dimensions and Weight 6 of 26

8 1,769 mm (70 inch.) 1,130 mm (45 inch.) Uncrated - Doorway minimum Dimensions and Weight Length Height Width Weight UNIT (mm) (mm) (mm) (kg) Engine 3,956 1,769 1,889 2,455 Feeder 2,082 1,544 1, Stacker , UV Conveyor 2,952 1,095 1, Foiler 1,661 1,449 1, Scodix Ultra Full Unit (Without Foiler) 6,327 1,788 1,889 4,084 Scodix Ultra Full Unit (With Foiler) 7,877 1,788 1,980 4,984 Length Height Width Weight UNIT (in.) (in.) (in.) (lb.) Engine ,412 Feeder ,226 Stacker UV Conveyor ,874 Foiler ,984 Scodix Ultra Full Unit (Without Foiler) ,004 Scodix Ultra Full Unit (With Foiler) ,988 Ultra Press Dimension Diagrams (without Foil Station) Ultra Press Height (doors closed) (without Foil Station) Feeder Side Stacker Side Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Dimension Diagrams (without Foil Station) 7 of 26

9 2,244 mm (89 inch.) Ultra Press Width - Stacker View (without Foil Station) 1,889 mm (74 inch.) Stacker 1,345 mm (53 inch.) Ultra Press Height (Engine doors open) - Feeder View (without Foil Station) Feeder Ultra Press Maximum length (without Foil Station) 5,412 mm (214 inch.) 6,327 mm (250 inch.) Feeder Side Stacker Side Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Dimension Diagrams (without Foil Station) 8 of 26

10 Ultra Press Dimension Diagrams (with Foil Station) Ultra Press Maximum length (with Foil Station) Stacker Side Feeder Side Foil UV Conveyor Ultra Foil Station Unit Side View Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Dimension Diagrams (with Foil Station) 9 of 26

11 Ultra Foil Station Exit View Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Dimension Diagrams (with Foil Station) 10 of 26

12 Ultra Press Weight distribution per Leg The maximum load on a press leg = 800 kg. Ultra Press Distance between Legs - Top View (without Foil Station) Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Weight distribution per Leg 11 of 26

13 Scodix Ultra Press Site Preparation Guide (DBK ) Ultra Press Weight distribution per Leg 12 of 26

14 Ultra PRO + Foil Station Legs layout Scodix Ultra Press Site Preparation Guide (DBK ) Ultra PRO + Foil Station Legs layout 13 of 26

15 3,780 mm (149 inch.) Feeder Stacker 2,387 mm (94 inch.) Working Area Dimensions (without Foil Station) The Press working area should be large enough for efficient and comfortable operation and servicing. The minimum size of the working area required for the Ultra Press, can be the size of the press plus 1 meter (40 inch.) in all directions around the Press. Leave a gap of at least 1 meter all around the Scodix Press, for easy access and working space. Leave space for forklift access at the Feeder and Stacker, for loading and unloading paper. Ultra Press Top view - 1 meter gap on sides (without Foil Station) 8,327 mm (328 inch.) 1,000 mm (40 inch.) Operator Side 1,000 mm (40 inch.) 1,000 mm (40 inch.) 1,000 mm (40 inch.) Non-Operator Side Main Electrical Connection Air and LAN Hot air exhaust The minimum height of the ceiling can be 200 mm (8 inch.) above the maximum height of the Press (with the doors open): 2,365 mm (94 inch.) mm (8 inch.) = 2,565 mm (101 inch.). Minimum gap between the Press and ceiling View of Press with Conveyor door open (without Foil Station) Ceiling Scodix Ultra Press Site Preparation Guide (DBK ) Working Area Dimensions (without Foil Station) 14 of 26

16 2,365 mm (94 inch.) 2,565 mm (101 inch.) Feeder Side Stacker Side Scodix Ultra Press Site Preparation Guide (DBK ) Working Area Dimensions (without Foil Station) 15 of 26

17 Requirements This section describes the requirements for installing a Scodix Ultra Press. It contain the following sections: o o o o Electrical Power Requirements Floor Utilities and Services Environment The Scodix Ultra Press and its feeder and stacker must only be lifted and/or transported by specially trained and qualified personnel using lifting bars, lifting straps and other specialized equipment that meets Scodix s specifications and all additional requirements imposed by government regulations. Improper lifting may cause serious personal injury and/or damage to the press and its peripherals or to other property. Electrical Power Requirements Requirement Specification Voltage Frequency Rated Current Circuit Breaker RCD (Residual- Current Device) Ground resistance Additional ground connection 3 X Phases 230 VAC (MAX) 3PH +N+GND (connection must be of Star type ) Note: 50 / 60 Hz 44 Amps 230 V (MAX) between each phase and Neutral (voltage can be lower by up to 5%) 400 V (MAX) between phase to phase (voltage can be lower by up to 5%) 44 Amps minimum 3-phase circuit breaker Tripping characteristic type G, AIS to comply with local electrical regulations Short circuit Rating value: 10kA Use a circuit breaker with the nearest Amp rating higher than stated value. Scodix recommends installing an adjustable RCD (Residual-Current Device) that supports up to 1000 ma. The local electrician must adjust the RCD on site. Recommend devices: ECL RCD circuit breaker 4 poles - Hager manufacturer p/n HMF480T ECL RCD add on blocks - Hager manufacturer p/n BTC480E Less than or equal to 1.0Ω According to the CE regulations, an additional PE wire needs to be connected, with the same gauge as the Mains Power Cable. Power Consumption Note: For UPS or Transformer Max 30 KVA Average 15 KVA (during printing) (for Ultra Press without Foil Station) Average 18 KVA (during printing) (for Ultra Press with Foil Station) When using a UPS or Transformer, the above criteria must be checked, and the Y Connectivity must be maintained. Scodix Ultra Press Site Preparation Guide (DBK ) Electrical Power Requirements 16 of 26

18 Floor Requirements The floor must meet the following requirements: Floor Level < 1% Vibration-free floor Floor Surface Floor Size While the Press is in operation, the floor vibration must be less than: Vrms < 0.2 G Vpk < 0.6 G The floor covering must be a hard and smooth surface, such as tiles, flat epoxy or flat concrete without holes or bumps. The floor covering must be a hard and smooth surface, such as tiles, flat epoxy or flat concrete without holes or bumps. If the press will be installed on an elevated (raised) floor, the raised floor must be bigger that the footprint of the Press to enable the installation and operation of the Press. (At least double the length and width). Maximum Load Details Ultra Press (without Foil Station): Maximum weight of the press, with the Feeder fully loaded: 4,525 kg (11,464 lbs.). Ultra Press (with Foil Station): The maximum weight of the press, with the Feeder fully loaded: 5,825 kg (14,330 lbs.). The maximum paper load permitted on the Feeder / Stacker is 175 kg (386 lbs.). Utilities and Service Requirements The following initial requirements must be in place before installation. Before starting the installation process, the customer must verify the compliance and existence of each item in the table below, sign next to each row and then send this page to support@scodix.com. Requirement Description Mains Connection The maximum cable thickness that can be inserted into the terminal connector (press side) is 6 AWG. Other Details Scodix Ultra Press Site Preparation Guide (DBK ) Floor Requirements 17 of 26

19 Requirement Description Other Details Power Cable and Connectors (Press side) Mains Power Cable must be prepared and connected from wall to press, by the customer s qualified and licensed local electrician, according to local safety standards, and only using materials authorized for that purpose by the local regulatory body. Mains Power Cable is to be supplied by the customer. Mains Plug The Scodix Ultra Press must be hard-wired to the main electrical power supply, or plugged in with a suitable electric plug device. Mains Power Cable is to be supplied by the customer. Example: Transformer If a Scodix Ultra Press is installed where 3 X Phases 230 VAC (MAX) is not available, then a 30 kva capacity transformer is required. Transformer output: 3 X Phases 230 VAC (MAX) + neutral + ground, 44 Amps. Note: (voltage can be lower by up to 5%) Compressed Air Air pressure: 7-10 bar continues and regulated Air Flow: minimum and constant flow of 34 CFM at the press connection! ( 952 Liter/minute) Customer to provide the air hose from wall to the press. Hose: High pressure 12 mm (0.47 inch.), outside diameter, This hose that connects the press to the wall air outlet- should not exceed 7 meters. Air flow and pressure test should be done by Service personnel using the Scodix Jig: ultra air flow jig P/N: KIT for 15 min in order to verify constant pressure and flow. press will not operate if the these requirements will not be met. Cleanliness: 20 micron element with an auto-drain Oil and water free, (Drier is required) Over-pressure strain relief Certification: The Air system used at the site must have a UL certified over-pressure strain relief. Scodix Ultra Press Site Preparation Guide (DBK ) Utilities and Service Requirements 18 of 26

20 Requirement Description Other Details Operations Environment Temperature: 15 C to 30 C (59 F to 86 F) Humidity: 40% to 80% relative humidity, non-condensed. Shutdown Conditions: 10 C to 35 C; 20% to 80% relative humidity. Network LAN TCP/IP Cat. 5E LAN Cable to be supplied by customer. Internet connection Fast (active) Ethernet connections, with open ports to access the Internet. Required for remote support, using TeamViewer. Acetone 2 liters Customer to provide (Local Purchase) Alcohol / IPA 2 liters Customer to provide (Local Purchase) Scodix Ultra Press Site Preparation Guide (DBK ) Utilities and Service Requirements 19 of 26

21 Electrical Connection Requirements Electrical installation must conform to local safety standards, and only using materials authorized for that purpose by the local regulatory body. It is the customer s responsibility to have a qualified and licensed electrician on site to connect the main electrical power cable to the press and its peripherals. During preparation of the site, contact your Scodix representative in order to coordinate the preparations for electrical connections and to coordinate the arrival of the electrician for the Scodix Ultra Press installation. Ultra Press Electrical Connections without Transformer: Stacker Engine Mains from the Wall: 3 X Phases 230 VAC (MAX) + neutral + ground, 44 Amps; Note: 230 V (MAX) between each phase and Neutral (voltage can be lower by up to 5%) 400 V (MAX) between phase to phase (voltage can be lower by up to 5%) Feeder Ultra Press Electrical Connections with Transformer: Stacker Engine Transformer Output: 3 X Phases 230 VAC (MAX) + neutral + ground, 44 Amps 30 KVa (voltage can be lower by up to 5%) CB Before transformer (According to the local voltage and current provided.) Feeder CB after Transformer 44 Amp or higher. Connecting the Press to the Main Power Supply The press requires electrical isolation and lockout during service and maintenance procedures. Mount an isolator box and key on the wall near the press. This key must be in possession of the Service Personnel at all times. Scodix Ultra Press Site Preparation Guide (DBK ) Electrical Connection Requirements 20 of 26

22 Environmental Requirements Press Storage Environment Requirements The following data assumes that the Scodix Ultra Press is stored in its original crate: Storage Environment Temperature Relative Humidity Description 5 C to 35 C (41 F to 95 F) 50% to 80% relative humidity, non-condensing The Scodix Ultra Press should not be stored for longer than one month in an environment with a relative humidity greater than 60%. Make sure you have storage space for the following items: PolySENSE: The PolySENSE container should be stored under the following conditions: Store the PolySENSE in an environment below 35 C (95 F). Avoid direct sunlight, UV radiation and strong oxidizers. Keep containers tightly closed in a dry, cool and well-ventilated place. Store in a place that is only accessible by authorized personnel. Keep out of reach of children. Only store PolySENSE in the original HDPE container. Never mix liquids from one container with that from another. Do not store near inert gas, such as nitrogen. Keep the container away from oxidizing materials, acids and bases. Spare Parts: Ensure that a proper place in a controlled environment is available for spare parts, such as electronics boards, print heads and hardware. Paper (Printed Jobs): Protect paper from direct sunlight. In order to avoid moisture absorption, store the paper on shelves, pallets or in cabinets and not directly on the floor. Temperature and humidity are critical factors. A minimum temperature of 15 C (50 F) with 30% relative humidity should be maintained. A maximum temperature of 27.2 C (81 F) with 85% relative humidity should be maintained. Most environments with air conditioning systems provide the proper mix of temperature and humidity. For optimal results, coated paper should be stored a minimum of 48 hours in standard conditions before production. Important: It is highly recommended to use a humidifier in the Paper storage room, in very low humidity environments. Scodix Ultra Press Site Preparation Guide (DBK ) Environmental Requirements 21 of 26

23 Working Environment Requirements The Scodix Ultra Press functions normally in a typical controlled print shop environment. The area in which the Scodix Ultra Press is installed should be reasonably free of dust and other airborne particles. Dust and particles can damage the Print Heads and affect the printing quality. The Press should not be installed near equipment that produces strong radio frequency interference. The Press should not be installed near equipment that produces strong mechanical impact. Excessive vibrations generated by heavy machinery, such as shears or punchers, may affect print quality and should not be in the operating environment of the Scodix Ultra Press. Working Environment Operation conditions temperature and humidity Power-off conditions temperature and humidity External exhaust, air evacuation Description 15 C to 30 C (59 F to 86 F) 40% to 80% relative humidity, non-condensing 10 C to 35 C (50 F to 95 F) 20% to 80% relative humidity See the Ventilation section on page 23. Illumination Requirements Do not install the Scodix Ultra Press in an area exposed to direct sun light. Waste Disposal Requirements Dispose of the consumables and cleaning materials that you use in accordance with applicable regulations. Consult with your local authorities to determine the correct manner in which to dispose wastes, including the following wastes: Liquid from the printing heads cleaning station. Polymer should be disposed of as chemical waste according to local regulations. For more details, refer to the MSDS document for varnish material. Noise Level Requirements When all service doors and covers on the Scodix Ultra Press are closed, the operator is exposed to an effective maximum of 83 db of noise. The operator is required to wear Ear Protection. Scodix Ultra Press Site Preparation Guide (DBK ) Working Environment Requirements 22 of 26

24 Ventilation Requirements For proper ventilation of the Scodix Ultra Press site, 6 air-room cycles per hour are required. Heat emission reaches a maximum of 10 kilowatts power during production. If the site requires, (or Scodix recommends), hot air evacuation from the press, the customer can install an additional exhaust pipe above the press. There are two options: 1. Option # 1 - Without additional suction fan: This is relevant when the press is installed near to the external wall. The customer can install (for themselves), a flexible exhaust pipe with a diameter of 6'', with a length of up to 5 meters, and can include only one 90 degrees elbow. If a ridged Exhaust pipe is used then the length can be up to 6.5 meters. 2. Option # 2 With additional suction fan: This is relevant when the press is installed far from the external wall. The customer can install (for themselves), a longer exhaust pipe connected to an additional suction fan, or connected to the plant extraction system, according to the following specification: 1. The exhaust pipe should have a diameter of 6'' (to match the 6'' diameter of the press exhaust flange). 2. The working flow rate should be 700 CFM. 3. The suction pressure should be ~ 2000 Pa at the press exhaust flange. Figure 1: Non operator side view - Exhaust pipe with 6 flange Exhaust flange (6'' diameter) Stacker Exhaust pipe Additional Items Provided The following items are provided with the Scodix Ultra Press: # Description Quantity Unit 1 Clean room wipers 1 Package 2 Scodix PolySENSE 20 Kg 3 Cleaning fluid bottle 1 Bottle 4 Nitrile gloves 1 Package 5 Waste bottle and cork 3 6 Protective glasses 1 1 Scodix Ultra Press Site Preparation Guide (DBK ) Working Environment Requirements 23 of 26

25 Site Preparation Checklist How to use the Site Preparation Checklist During the Site Survey, the Site Preparation Checklist is used to ensure that the customer is aware of, and understands all the Site Preparation requirements. 1. The customer should check/mark each item, and sign below. By signing, the customer commits to implement all the site requirements (which are explained in details in this document), before the installation team arrives to install the Scodix Press. 2. The customer should give a copy of the signed Site Preparation Checklist to the Scodix representative. Site Preparation Checklist Environment and Safety Status Warning signs to ensure safety Fire and first aid equipment Eyewash station Required lighting conditions Required ambient temperature Required ambient relative humidity Required fresh air flow Safety glasses and rubber gloves Waste disposal Floor Status Floor is completely level or less than one degree from level Floor meets vibration-free requirements Floor cover material and flatness Floor withstands maximum loads and press weight Location and Accessories Status Waste receptacles for Scodix PolySENSE Storage area and its ambient Work table for examining printed outputs recommended Ethanol and Acetone to be available on site Press Transport and Positioning Status Lifting and transport equipment Hallway and door opening dimensions sufficient for transporting press components Elevator dimensions and weight limits sufficient for transporting press components Work-space dimensions Work-space height Scodix Ultra Press Site Preparation Guide (DBK ) How to use the Site Preparation Checklist 24 of 26

26 Connections Status Clear access to main electrical switch and circuit breaker Internet connection: Fast (active) Ethernet connections, with open ports to access the Internet. Main electrical connection location near the press Transformer location (if needed) For the items below: The customer is required to write the exact specification (value / amount) that they undertake to implement. Customer Signature Continuous air pressure flow: Electricity supply complies with Press requirements: Air pressure: Air flow: Phases: Voltage: Amps: Scodix / Distributor Engineer Remarks Remark Customer commitments Severity Fixed Signatures The Customer signs at the end of the Site Preparation Checklist to confirm that all site preparation requirements are understood and will be implemented before the installation date. Due date for Site Readiness: Planned Installation date: Customer Scodix / Distributor Date Scodix Ultra Press Site Preparation Guide (DBK ) Scodix / Distributor Engineer Remarks 25 of 26

27 Support and Contact Information Head Office Scodix Ltd. 13 Amal Street Afek Industrial Park Rosh Ha ayin, Israel Tel: +972 (0) Fax: +972 (0) Website: Document History Part Number Written by Approved by Date Remarks March 2013 Ronen S Yossi B April 2013 Initial document DBK Ronen S Yossi B December 2013 DBK Ronen S Yossi B May 2014 General updates Updated Fast (active) Ethernet connections. Updated maximum noise level to of 83 db. DBK Ronen S Yossi B July 2014 Updated power requirements DBK Ronen S / Yossi B Yossi B November 2014 Updated the power requirements. Updated the ventilation requirements. Updated the air pressure requirements. Updated the Site Preparation Checklist. Added Inch values to tables and drawings. Engine dimension was fixed. Added hot air exhaust location (top view). Added Power and Air connection location (top view). Updated lockout warning. Added Short Circuit Rating value. DBK Ronen S Yossi B January 2015 Added: Ultra Press Distance between Legs -Top view. Updated 220 V to 230 V. Updated 380 V to 400 V. DBK Ronen S Yossi B May 2015 Updated voltage variance to -5%. Added recommended RCD devices. Added additional ground connection. DBK Yossi B Yossi B January 2016 Added the Scodix Ultra Foil Station. Scodix Ultra Press Site Preparation Guide (DBK ) Document History 26 of 26