BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T 11D. POWER SYSTEM OPERATION FORCED OUTAGES Supercedes 1T-11D issued 03 June 2009
|
|
- Jeffery Washington
- 6 years ago
- Views:
Transcription
1 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T 11D POWER SYSTEM OPERATION FORCED OUTAGES Supercedes 1T-11D issued 03 June 2009 Effective Date: 26 August 2011 Expiry Year: 2015 Original signed by: APPROVED BY: Devinder Ghangass General Manager, Real Time Operations Denotes Revision
2 Page 2 of GENERAL This order covers operations of the bulk Power System after forced outage to equipment affecting the bulk Power System. Outage notification requirements and restoration processes are described in this order. Operations after forced outages in the Distribution System are described in separate Distribution Operating Orders. Operations following a major telecommunications outage are described in System Operating Order 7T-20D. Grid Operators, Load Operators, Plant Operators and Designated Stations shall report to the Transmission Coordinator as soon as practicable, all forced or accidental outages in the bulk power system and their causes, occurring within their boundaries. Outages of 25 kv and lower voltage feeder circuits need not be reported unless: The feeder supplies station service to a microwave site, Control Centre, series capacitor station, generating station or a 230 kv or higher voltage station or a station with a tie to another utility. The fault caused an appreciable 'bump' to the transmission system. 100 MW or more load was lost. Generation was lost. Communication and restoration procedures for declared High Level Emergencies are described in OO 6T-00, "Emergency Response Procedures". 2.0 RESTORATION - AUTHORITY Forced outages on Level I and II equipment, which is under the control of Transmission or Generation Coordinator or which requires authorization of the Transmission or Generation Coordinator for operation must not, except as provided in Emergency Orders, be restored without reference to the Transmission or Generation Coordinator, as applicable. Two exceptions are as follows: The HVDC may be restored to previous loading without reference to the Transmission Coordinator when the VI System is tied to the Integrated System via 2L129 and/or 1L18 only. When 5L29 and/or 5L31 are in service, the Transmission Coordinator will authorize loading of the HVDC. The Transmission Coordinator may give permission to a Grid Operator or Designated Station for manual reclose (reference OO 1T-29A) without reference to Transmission Coordinator if auto reclosing is disabled for some reason. Also, if Live Line Permits are in effect and can be returned in time (reference OO 1T-29A) permission may be granted for one manual reclose on any circuit. Forced outages on equipment which normally requires 'prior notification' (i.e. Level III) of the Transmission or Generation Coordinator to operate, but which have resulted in power outages to customers, can be restored by Grid Operators and Designated Stations without prior reference to the Transmission or Generation Coordinator, provided the Grid Operator or Designated Station has assurance that the disturbance is localized. However, all load that was shed by underfrequency relay shall not be restored without permission from the Transmission Coordinator pending notification from the Western Electricity Coordinator Council Reliability Coordinator (WECC RC).
3 Page 3 of RESTORATION REPAIR PROCEDURE Whenever Transmission System equipment is forced out of service and has the following impact: customers are without power, transmission service is curtailed by more than 100 MW or if Marketer(s) can demonstrate real hardship due to the curtailment, BCH will be in violation with Applicable Laws, Applicable Reliability Standards, or Regulatory requirements. Real Time Operation staff (RTO) will call out BC Hydro Field Operations to investigate and make safe the Transmission System equipment as soon as possible. For repairs under $5K, BC Field Operations will charge their work to an appropriate Corrective work order in accordance with BCH Asset Management business rules to capture such cost. For repairs exceeding $5K, work on the above types of critical outage will continue but Field Services will consult and coordinate with Asset Management at the earliest opportunity to optimize a repair strategy. For transmission line outages, response will be in accordance to BCH Standard For permanent sustained outages to BCH Distribution Substations and Transmission Voltage Customers whose operations are continuous around-the-clock it is intended that repair work will be performed in a manner that will restore service as quickly as feasible. The BC Hydro Field Manager will provide an initial Estimated Restoration Time (ETR) to the Control Centre to be communicated to the Customer. The Control Centre will be advised by the Field Manager if the ETR changes or every 4 hours to confirm accuracy and the Control Centre will advise the Customer of any updates. A resource plan will be developed by the BC Hydro Field Manager in conjunction with BCH Asset Program Management to ensure the return to service is achieved as soon as safely possible. This resource plan will include strategies such as working around the clock if circumstances and safety permit. For non-critical outages, RTO will notify BC Hydro Field Operations to assess and stabilize the situation so that repair of equipment can be delayed until the next working day. BC Hydro Field Operations will charge this work to an appropriate Corrective work order in accordance with BCH Asset Management business rules costs under $5K. No single work can exceed $5K without approval from Asset Management. If Asset Management decides not to approve the work exceeding $5K, they will notify RTO and provide reasons for not proceeding. 4.0 SPECIAL REPAIR PROCEDURE Some major repair of damaged plant/equipment may require special planning, organization and communications, involving other participants and stakeholders. These major repairs are: Very expensive typically costing $1M or more Very complicated or extensive typically more than 4 weeks to complete The flow chart in Appendix 1 should be used for major repair processes. 5.0 TRANSMISSION LINE FAULT LOCATING Transmission Coordinators are responsible for reporting Level 1 and 2 transmission line forced outages and the Grid Operators and GMS OAD s are responsible for reporting Level 3 and 4 transmission and sub-transmission line forced outages in CROW.
4 Page 4 of 5 The Transmission Coordinator will ensure that Grid Operators have initiated appropriate action whenever Levels I and II major transmission lines do not reclose successfully. The Transmission Coordinator through the Grid Operator will provide any available FLAR fault location information to the Field staff and enter it in CROW. For any inter-area transmission lines that do not reclose successfully, the Control Centre will notify the appropriate BC Hydro Field Operations Manager(s). If more than one BC Hydro Field Operations Manager is notified, they will have joint responsibility to coordinate patrols and fault location. One FO Manager shall take the lead role and that person shall be named to the Control Centre promptly for coordinated communications regarding progress, plans and priorities. After the fault location has been confirmed, the FO Manager for that area shall be responsible for making repairs and for informing the Control Centre of the estimated outage duration. 6.0 REPAIR OF FAULTED GENERATION PLANT Repair to a generating plant is the responsibility of the Generator Owner. BC Hydro Plant Manager shall keep the Control Centre informed on the condition and status of repairs to a BC Hydro generating plant, either directly or through the Designated Stations. If a generating plant is critical to maintain the reliability of the Transmission System, repair of the generating plant shall be given a high priority. 7.0 REVISION HISTORY Revised by Revision Date Summary of Revision TCSF 15 September 2005 Major revision. DSG 4 Oct 2005 Clarified what RTO stands for and clarified responsibility for creating CROW entries. AW 15 January 2008 Section 3 updated for BCH Standard and procedure for returning customers that have 24 hour operations to service AW 4 February 2008 Section 3 updated AMS 03 June 2009 Updated for SCMP. DSG 26 August 2011 Updated after BCH/BCTC merger
5 Appendix 1 - Major Incidence Repair/Communications Flow Chart OO 1T-11D Page 5 of 5 Incident Control Centre dispatches Field Operations crews to obtain information. Crews will secure and make safe the site, restore customers to the extent possible, and perform damage assessment. If BC Hydro System Control Manager deems necessary, initiate Telephone Conference Call with 1) BC Hydro Asset Management 2) Field Operations 3) System Planning (optional) to conduct situation assessment. Project Sponsor assigned from BC Hydro Asset Management 1) Control Centre will inform DLoB of any significant impact or additional risk to their customers, including TVCs and their respective KAMs. 2) Control Centre will inform GLoB and IPPs of any significant impact or additional risk to their plants. Note: BC Hydro SOC must not be violated if transmission information is provided. Project Sponsor; 1) Arranges for Funding 2) Coordinates with Planning to rebuild or to modify 3) Prepares Repair Plan and Contracts 4) Prepares Communication Plan 5) Appoints Project Manager Project Manager manages the repairs and communications with stakeholders. Project Manager must be available during crucial stages of the project.
FRCC - PROC - RC - EOP-004. FRCC Disturbance Reporting Procedure
FRCC - PROC - RC - EOP-004 FRCC Disturbance Reporting Procedure Revisions Rev. No. Date Description Developed by: Approved by: 1 September 2, 2009 Conversion of RRO Legacy document FRCC Disturbance Reporting
More informationOutage Scheduling Manual
MANUAL 29 Outage Scheduling Manual July 2015 2.2 Transmission Facilities Outage Scheduling Procedures To provide the NYISO with enough time to perform the required studies and verify power system thermal,
More informationPlan. Security of Supply Participant Rolling Outage. Plan
Plan Security of Supply Participant Rolling Outage Security of Supply - Participant Rolling Outage Plan 31 March 2017 Table of Contents 1 PURPOSE OF THIS DOCUMENT... 1 2 DEFINITIONS... 1 2.1 Associated
More informationOperating Procedure PURPOSE... 1
No. 5310 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 1 2. SCOPE/APPLICABILITY... 2 2.1. Background... 2 2.2. Scope/ Applicability... 2 3. PROCEDURE DETAIL... 2 3.1. Reporting Requirements/...
More informationAMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER
AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November
More informationA. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements
A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements 2. Number: PRC 006 RFC 01 3. Purpose: To establish ReliabilityFirst requirements for automatic Load shedding (UFLS) to support
More informationAMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER
AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November
More informationGenerator Assessment & Roles During A Restoration
Generator Assessment & Roles During A Restoration PJM State & Member Training Dept. PJM 2015 Objectives Students will be able to: Identify the process and requirements for operating during system restoration
More informationPJM Manual M36 System Restoration. A.1 Critical Black Start Criteria
5/1/2018 OC Meeting PJM Manual M36 System Restoration A.1 Critical Black Start Criteria A.1.1 Goal PJM and its stakeholders have developed requirements for the amount and redundancy of Black Start generation
More informationRCR-35 Reliability Coordinator Reliability Plan for the SaskPower Subregion of the Midwest Reliability Organization
RCR-35 Reliability Coordinator Reliability Plan for the SaskPower Subregion of the Midwest Reliability Organization - 1 - Introduction The North American Electric Reliability Council (NERC) requires every
More informationNYSRC RELIABILITY RULES For Planning And Operating the New York State Power System
NYSRC RELIABILITY RULES For Planning And Operating the New York State Power System Version 18 January 5, 2007 NYSRC RELIABILITY RULES For Planning and Operating the New York State Power System Version
More informationWolverine Power Supply Cooperative, Inc. Senior Transmission System Operator
I. OBJECTIVE Wolverine Power Supply Cooperative, Inc. Senior Transmission System Operator A. The Senior Transmission System Operator is responsible for the reliable and safe operation of Wolverine s transmission
More informationDistribution System Operating Code
Distribution System Operating Code Draft Rev 5 Approved September 2007 Comments to this document can be forwarded to: RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission System
More informationConnection Study Requirements
Document Release Released: September 20, 2010 The Customer shall comply with all the applicable requirements in this document when performing connection studies to produce the engineering study report.
More informationA. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements
A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements 2. Number: PRC 006 RFC 01 3. Purpose: To establish ReliabilityFirst requirements for automatic underfrequency Load shedding
More informationDispatch Data Exchange Manual. June, 2012
Dispatch Data Exchange Manual June, 2012 Table of Content Page No. 1 Introduction...1 2 Overview of the NITS...2 3 Major Transmission lines...2 4 Existing Generating Plants...4 5 Responsibility of the
More informationNERC PLANNING STANDARDS
NERC PLANNING STANDARDS North American Electric Reliability Council April 2004 Version of All Planning Standards Terms and Their Definitions As Used in the Analysis (Study) an examination or simulation
More informationMapping Document. Project Phase 2 of System Protection Coordination. Revisions or Retirements to Already Approved Standards
Mapping Document Project 2007-06.2 Phase 2 of System Protection Coordination Revisions or Retirements to Already Approved Standards This mapping document explains how each of the existing Requirements
More informationNERC Reliability Functional Model
NERC Reliability Functional Model Function Definitions and Responsible Entities Version 3 Approved by Standing Committees: Operating Committee: December 6, 2006 Planning Committee: December 6, 2006 Standards
More informationInterconnection System Feasibility Study
Interconnection System Feasibility Study Zonnebeke Wind Project Report No: T&S Planning 2015-053 November 2015 FINAL British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority
More informationRochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017
Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA March 21, 2017 Contents 1 Background...3 2 National and Regional Criteria and Guides...4 2.1 2.1 NERC Transmission Planning Standards...4 2.2
More informationStandard TPL System Performance Following Extreme BES Events
A. Introduction 1. Title: System Performance Following Extreme Events Resulting in the Loss of Two or More Bulk Electric System Elements (Category D) 2. Number: TPL-004-1 3. Purpose: System simulations
More informationOMS/DMS Implementation at SDG&E
OMS/DMS Implementation at SDG&E Vic Romero Director Asset Management & Smart Grid Projects March 26, 2013 2012 San Diego Gas & Electric Company. All copyright and trademark rights reserved. Outage and
More informationImplementation Plan IRO Reliability Coordination Current Day Operations
Implementation Plan IRO-005-4 Reliability Coordination Current Day Operations Approvals Required IRO-005-4 Reliability Coordination Current Day Operations Prerequisite Approvals None Revisions to Glossary
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION NORTH AMERICAN ) Docket No. RR07-11- ELECTRIC RELIABILITY CORPORATION ) ) COMPLIANCE FILING OF THE NORTH AMERICAN ELECTRIC RELIABILITY
More informationPOTOMAC ELECTRIC POWER COMPANY
POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission
More informationINTERCONNECTION REQUIREMENTS FOR CLOSED-TRANSITION TRANSFER OF STANDBY GENERATORS
INTERCONNECTION REQUIREMENTS FOR CLOSED-TRANSITION TRANSFER OF STANDBY GENERATORS March 2008 Table of Contents 1.0 Introduction 3 1.1 Scope 3 1.2 Copyright and Reprint 3 1.3 Disclaimer 3 1.4 Project Responsibilities
More informationProcedure No. Operating Version No. Procedure Effective Date System Emergency Notice Templates Distribution Restriction: None 1.
No. 4420C 1. Detail 1.1. Purpose and Distribution The California ISO sends System Emergency notices when adverse grid or market conditions require activation of the California ISO Electrical Emergency
More informationFERC Directives in Order 693 Addressed in IROL Implementation Plan
The following Interconnection Reliability Operating Limit (IROL) standards were under development when the Version 0 project was initiated: IRO-008 Reliability Coordinator Operational Analyses and Real-time
More informationDesignated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects. System Protection Subgroup
Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects System Protection Subgroup For any substation facility included in the scope of a transmission
More informationOperating Procedure PURPOSE... 1
Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 2 2. SCOPE/APPLICABILITY... 2 2.1. Background... 2 2.2. Scope/ Applicability... 2 3. PROCEDURE DETAIL... 3 3.1. Order of Steps... 3 3.2. Restricted
More informationThis section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective.
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard TPL Transmission System Planning Performance Requirements
A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon
More informationScheduled Outages and Service Interruptions in Connecticut. Quat Nguyen Connecticut Public Utilities Regulatory Authority August 31, 2015
Scheduled Outages and Service Interruptions in Connecticut Quat Nguyen Connecticut Public Utilities Regulatory Authority August 31, 2015 1 Topics Profiles of Connecticut EDCs SAIDI and SAIFI Interruptions
More informationManual 01 Revision 36
Manual 01 Revision 36 Bilge Derin Engineer, Real-Time Data Mgmt Markets & Reliability Committee December 21, 2017 M01 R36 Changes Summary Section Change to/updated Impact 2.3.1 NERC references updated
More informationNorthwest Power Pool Processes
Northwest Power Pool Processes Background The Northwest Power Pool membership (NWPP) was founded in 1941 to promote efficient production of electrical energy. The NWPP is the geographic area encompassed
More information804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION
Operating Policies and Procedures Emergency System Operations OPP 804 Issued:2008-11-13 Supersedes Interim OPP Effective:2008-05-01 804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION 1. Purpose To
More informationReliability Coordinator Plan
APPLICABILITY: Reliability Coordinator I. Purpose Peak Reliability s Reliability Coordinator (RC) Plan describes the processes implemented as the Reliability Coordinator responsible for coordinating and
More informationMapping of Revised TOP and IRO Reliability Standards to Address 2011 Southwest Outage Report Recommendations
Mapping of Revised TOP and IRO Reliability Standards to Address 2011 Southwest Outage Report Recommendations The following table provides a mapping of the recommendations applicable to the Reliability
More informationEast Kentucky Power Cooperative (EKPC) Transmission System Planning Criteria
East Kentucky Power Cooperative (EKPC) Transmission System Planning Criteria March 2016 Section 1 Overview and General Discussion The primary purpose of East Kentucky Power Cooperative s (EKPC s) transmission
More informationTransmission Reliability. BCUC Workshop 15 January 2004
Transmission Reliability BCUC Workshop 15 January 2004 Overview British Columbia Transmission Corporation (BCTC) is responsible for planning, operating and managing BC Hydro s transmission system pursuant
More informationOPERATIONS OM&A. Filed: August 15, 2007 EB Exhibit C1 Tab 2 Schedule 4 Page 1 of INTRODUCTION
Filed: August, 00 EB-00-0 Tab Schedule Page of OPERATIONS OM&A.0 INTRODUCTION Operations OM&A investments are required to manage the day to day flow of electricity within Hydro One Distribution s system.
More informationPRC-006, PRC-007, and PRC-009 Mapping to Proposed Continent-Wide Standard
PRC-006, PRC-007, and PRC-009 Mapping to PRC-006: Development and Documentation of Regional UFLS Programs Requirement in the Existing PRC Standards Standard R1: Each Regional Organization shall develop,
More informationLoad Shed Philosophy
APPLICABILITY: Reliability Coordinator I. Background While time limits exist for mitigation of the exceedance of certain types of system operating limits, events can occur quickly necessitating a responsive
More informationEAPP interconnection readiness workshop
1 EAPP interconnection readiness workshop Self-Assessment for EAPP/IC -Compliance Rwandan-Grid Gap Analysis & Proposed mitigations GENERATION, TRANSMISSION & DISTRIBUTION 01 st October, 2018 INTRODUCTION
More informationMATL Requirements Facility Interconnection Requirements
Table of Contents 1. Purpose... 2 2. References... 2 3. Responsibility... 2 4. Interconnection Criteria... 3 4.1 R3.1. & R3.2. Procedures for Coordinated Studies and Notification of New or Materially Modified
More information2005 Integrated Electricity Plan. Resource Options Workshop #2 Planning Criteria March 09, 2005
2005 Integrated Electricity Plan Resource Options Workshop #2 Planning Criteria March 09, 2005 Agenda for Presentation Introduction Review industry reliability standards and regulatory Generation Reliability
More informationStandard MH-TPL Transmission System Planning Performance Requirements
A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: MH-TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon
More informationGeneration Desk Logging
1. Provides guidelines for the different logging scenarios used by the Generation Dispatcher. Caution: Since Settlements reconciles and/or is supported by data from these entries, accurate and detailed
More informationInterconnection Feasibility Study
XXXXX Campbell River Power Enterprises Project April 5, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2011. All rights reserved. DISCLAIMER OF WARRANTY, LIMITATION
More informationMapping Document for FAC-010-3
Mapping Document for FAC-010-3 The Project 2015 09 standard drafting team (SDT) is proposing the retirement of the NERC FAC 010 3 Reliability Standard. The SDT further proposes a new paradigm regarding
More informationENMAX Power Corporation
Decision 22562-D01-2017 ENMAX No. 31 Substation Alteration May 25, 2017 Alberta Utilities Commission Decision 22562-D01-2017 ENMAX No. 31 Substation Alteration Proceeding 22562 Application 22562-A001 May
More informationPJM TO/TOP Matrix of Shared or Assigned Tasks
PJM TO/TOP Matrix of hared or ssigned Tasks Revision 07 pproved by the TO/TOP Matrix ubcommittee: October 18, 2013 pproved by the Transmission Owners greement-dministrative Committee: November 27, 2013
More information5.4 Post Contingency Local Load Relief Warning
5.4 Post Contingency Local Load Relief Warning Post Contingency Local Load Relief Warning Non-Market Post Contingency Local Load Relief Warning The purpose of the Post Contingency Local Load Relief Warning
More informationProposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources
Draft White Paper Proposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources Project 2014-01 Standards Applicability for Dispersed
More informationOperating Procedure PURPOSE... 1
No. 4120 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 2 2. SCOPE/APPLICABILITY... 3 2.1 Background... 3 2.2 Scope/ Applicability... 4 3. PROCEDURE DETAIL... 4 3.1 General Information... 4 3.2
More informationToward Ensuring Reliability: Reliability Performance Metrics. A NERC Staff White Paper
Toward Ensuring Reliability: Reliability Performance Metrics A NERC Staff White Paper Table of Contents Table of Contents Table of Contents... 2 Executive Summary... 3 Metrics Objective... 5 Metrics Background...
More informationUpdated October 2, 2014 TITLE: System Operator Transmission - Senior DEPARTMENT: System Operations
Updated October 2, 2014 System Operator Transmission - Senior interconnected system. Maintains the Western Electricity Coordinating Council (WECC) Coordinated Outage System (COS), documents standardized
More informationRequirements for the Provision of Load Shedding Service for Import Version 4.0
LOAD SHED SERVICE for IMPORT (LSSi) Requirements Requirements for the Provision of Load Shedding Service for Import Version 4.0 This document outlines the eligibility criteria and requirements that an
More informationPlatte River Power Authority. Ten-Year Transmission Plan ( )
Platte River Power Authority Ten-Year Transmission Plan (2015-2024) Prepared by PRPA System Planning December 31, 2014 Table of Contents I. Executive Summary II. III. IV. Scope Assumptions Criteria V.
More informationBR04 SERVICE PERFORMANCE MEASURES
SERVICE PERFORMANCE MEASURES 1 October 2013 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I M I T E D. A L L R I G H T S R E S E R V E D This document is protected by copyright vested
More informationParticipant Outage Plan
EA NETWORKS (ELECTRICITY ASHBURTON LTD) 20150324_Proposed_Participant_Outage_Plan Participant Outage Plan SYSTEM OPERATOR IMPOSED LOAD REDUCTION Reviewed March 2015 Contents Documentation Control... 2
More informationAESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS
APPENDIX G AESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS Transmission Planning Criteria - Basis and Assumptions Version 1.0 1. Introduction This document presents the reliability standards,
More informationReliability Coordinator Area System Operating Limit Methodology
Reliability Coordinator Area System Operating Limit Methodology Revision 1.0 MAINTAINED BY SPP Operations Staff PUBLISHED: 10/19/2018 LATEST REVISION: Effective 10/19/2018 Copyright 2018 by Southwest Power
More informationEOP-004-AB2-1 Disturbance Reporting
Alberta Reliability Standard Disturbance Reporting EOP-004-AB2-1 1. Purpose EOP-004-AB2-1 Disturbance Reporting The purpose of this reliability standard is to ensure that events that jeopardize the operation
More informationPID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation
PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation Prepared by: Entergy Services, Inc. T & D Planning 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date Description
More informationEducating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours
Background The class will be delivered over a 3-day period. The class is comprised of three training modules covering the areas of: Communications, Critical Thinking, and Restoration. The course consists
More informationPJM TO/TOP Matrix of Shared or Assigned Tasks
PJM TO/TOP Matrix of hared or ssigned Tasks Draft Version 11 s of eptember 8, 2017 Finalized pproved by the TO/TOP Matrix ubcommittee: June 16, 2017 pproved by the Transmission Owners greement-dministrative
More informationInterconnection Feasibility Study
XXXXX Campbell River Power Enterprises Project April 5, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2011. All rights reserved. DISCLAIMER OF WARRANTY, LIMITATION
More informationSummary of M-13 Rev. 66 Changes
Summary of M-13 Rev. 66 Changes Dean Manno SOS-Joint meeting September 6 th, 2018 M-13, Rev. 66 Changes Overview of Changes: Cover to Cover Periodic Review Section 3.2 added Production System Freeze Change
More informationSTCP 11-1 Issue Outage Planning
STCP 11-1 Issue 004 005 Outage Planning STC Procedure Document Authorisation Party Name of Party Representative Signature Date National Grid Electricity Transmission plc SP Transmission Ltd Scottish Hydro-Electric
More informationStandard PRC Automatic Underfrequency Load Shedding
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationInterconnection Feasibility Study
XXXXX Ditni Yoh Green Energy April 5, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2011. All rights reserved. DISCLAIMER OF WARRANTY, LIMITATION OF LIABILITY
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationTTC/ATC 1.0 DEFINITIONS
TTC/ATC In this section: Definitions Total Transfer Capability (TTC) Methodology Available Transmission Transfer Capability (ATC) Calculation Counterflow ATC Release of Unused Transmission in Pre- schedule
More informationRELIABILITY PLAN for the SERC Southeastern Subregion Reliability Coordinator July 14, 2016
Agenda Item 3.b.i ORS Meeting September 7-8, 2016 RELIABILITY PLAN for the SERC Southeastern Subregion Reliability Coordinator July 14, 2016 Introduction The Southern Company Services is the Southeastern
More informationSTCP 06-3 Issue 004 System Incident Management
STCP 06-3 Issue 004 System Incident Management STC Procedure Document Authorisation Party National Grid Electricity Transmission plc Name of Party Representative Signature Date SP Transmission Ltd Scottish
More informationUNOFFICIAL TRANSLATION SUPPLY OF REACTIVE POWER AND MAINTENANCE OF REACTIVE POWER RESERVES
UNOFFICIAL TRANSLATION SUPPLY OF REACTIVE POWER AND MAINTENANCE OF REACTIVE POWER RESERVES Guideline 1 (11) Contents 1 INTRODUCTION... 2 2 PRINCIPLES OF THE SUPPLY OF REACTIVE POWER... 2 2.1 Supply point
More informationPlanning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES
Planning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES Effective Date: September 11, 2017 Revision History Date Version Description June 6, 1998 0.0 Initial LGEE document
More informationPRC and EOP Effective 10/1/13
PRC-006-1 and EOP-003-2 Effective 10/1/13 Thomas Teafatiller, Senior Compliance Engineer (RE) tteafatiller.re@spp.org, 501.688.2514 Jason Speer, Senior Engineer (RTO) jspeer@spp.org, 501.614.3301 Greg
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationSecurity Guideline for the Electricity Sector: Identifying Critical Assets
Note: The guideline was developed for CIP-002-1 but is also applicable to CIP- 002-2 and CIP-002-3. Security Guideline for the Electricity Sector: Identifying Critical Assets Disclaimer: This supporting
More informationCALIFORNIA INDEPENDENT SYSTEM OPERATOR ANCILLARY SERVICES REQUIREMENTS PROTOCOL
VOLUME NO. III Page No. 655 CALIFORNIA INDEPENDENT SYSTEM OPERATOR ANCILLARY SERVICES REQUIREMENTS PROTOCOL VOLUME NO. III Page No. 656 ANCILLARY SERVICES REQUIREMENTS PROTOCOL Table of Contents ASRP 1
More informationReliability Coordinator Data Request and Specifications for Data Provision
Reliability Coordinator and Specifications for Provision Version 11.0 APPLICABILITY: Balancing Authorities, Generation s, s, and Owners I. Purpose Provide a documented specification to applicable functional
More informationProposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources
Draft White Paper Proposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources Project 2014-01 Standards Applicability for Dispersed
More informationnts Major Event Issue: Date Issued: Summary One s customers. 1. Prior to the occur? Hydro One did not Events. Notification Business (LOB).
Major Even nts RESPONSE REPORT Issue: July 8 to 9, 2016 2.1.4.2 Major Eventt Response Report Date Issued: July 4, 2017 Prepared for: Publication and Electronicc Filing with the Ontario Energy Board (OEB)
More information2015 Operational Practices Survey Questions
2015 Operational Practices Survey Questions This document of survey questions has been provided as a courtesy. It is not the actual survey, which will be completed electronically and only by a designated
More informationAssessment of Load Shed Service for Import (LSSi) Product
Assessment of Load Shed Service for Import (LSSi) Product Date: March 27, 2014 Prepared by: Prepared for: Mike Law Jenny Chen Senior Market Design Specialist Vice President, Market Services Table of Contents
More informationStandards de planification du NERC
Demande R-3498-2002 Standards de planification du NERC PREUVE EN CHEF DE TRANSÉNERGIE Original : 2002-11-27 HQT-4, Document 2 (en liasse) NERC PLANNING STANDARDS North American Electric Reliability Council
More informationINCIDENT CLASSIFICATION SCALE
INCIDENT CLASSIFICATION SCALE - Final version for SOC approval - Incident Classification Scale Subgroup 27 March 2018 Table of Contents 1. General... 3 2. Incident Classification Scale... 4 2.1 General
More informationAlberta Electric System Operator Needs Identification Document Application
Decision 22618-D01-2017 Alberta Electric System Operator Needs Identification Document Application Facility Applications June 22, 2017 Alberta Utilities Commission Decision 22618-D01-2017: Alberta Electric
More informationProject Revisions to TOP and IRO Reliability Standards Mapping Document Updated December 2014
Project 2014-03 Revisions to TOP and IRO Reliability Standards Mapping Document Updated December 2014 This mapping document showing the translation of Requirements in the following currently-enforceable
More informationReliability Coordinator Outage Coordination Methodology
Reliability Coordinator Outage Coordination Methodology Revision 1.0 MAINTAINED BY SPP Operations Engineering PUBLISHED: 4/30/2018 LATEST REVISION: Effective 4/30/2018 Copyright 2018 by Southwest Power
More informationExhibit A. Reliability Standards Proposed for Approval
Exhibit A Reliability Standards Proposed for Approval Proposed New Standard IRO-006-5 Standard IRO-006-5 Reliability Coordination Transmission Loading Relief A. Introduction 1. Title: Reliability Coordination
More information1304 SYSTEM EVENT MONITORING AND DISTURBANCE REPORTING
Operating Policies and Procedures Reporting OPP 1304 Issued: 2016-08-30 Supersedes: 2007-12-03 1. Purpose 1304 SYSTEM EVENT MONITORING AND DISTURBANCE REPORTING To establish processes for reporting AIES
More information1304 SYSTEM EVENT MONITORING AND DISTURBANCE REPORTING
Operating Policies and Procedures Reporting OPP 1304 Issued: 2016-08-30 Supersedes: 2007-12-03 1. Purpose 1304 SYSTEM EVENT MONITORING AND DISTURBANCE REPORTING To establish processes for reporting AIES
More information2005 Integrated Electricity Plan. Provincial IEP Committee Meeting #2 Planning Criteria February 22/23, 2005
2005 Integrated Electricity Plan Provincial IEP Committee Meeting #2 Planning Criteria February 22/23, 2005 2005 IEP Objectives Means Objectives Ends (Fundamental) Objectives Agenda Items No net imports
More informationBC HYDRO REAL TIME OPERATIONS OPERATING ORDER 6T OPERATION PLAN FOR CAPACITY AND ENERGY EMERGENCIES Supersedes 6T-25 issued 30 July 2013
BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 6T - 25 OPERATION PLAN FOR CAPACITY AND ENERGY EMERGENCIES Supersedes 6T-25 issued 30 July 2013 Review Year: 2015 APPROVED BY: Original signed by: Paul Choudhury
More informationPPL Electric Utilities Summer Readiness Overview June 2018
SUMMARY PPL Electric Utilities Summer Readiness Overview June 2018 For PPL Electric Utilities (PPL Electric), summer readiness means the company must respond effectively to summer storms as well as provide
More informationNYSRC RELIABILITY RULE/NERC STANDARD CROSS-REFERENCE
7/1/05 NYSRC RELIABILITY RULE/NERC STANDARD CROSS-REFERENCE NYSRC Reliability A. RESOURCE ADEQUACY A-R1. Statewide Installed Reserve Margin Requirements A-R2. Load Serving Entity ICAP Requirements None
More information