UPS SYSTEM TEST GALAXY 5000 SITE ACCEPTANCE TEST PROCEDURE

Size: px
Start display at page:

Download "UPS SYSTEM TEST GALAXY 5000 SITE ACCEPTANCE TEST PROCEDURE"

Transcription

1 UPS SYSTEM TEST GALAXY 5000 SITE ACCEPTANCE TEST PROCEDURE Your reference: PO: XXXX Customer project name : Project Name Here Maint Software Version: xx.xx Issued by : M. Coates Our reference : /13391 All technical information contained in this document is the exclusive property of MGE UPS Systems and may neither be used nor disclosed without its prior written consent. is an equal opportunity employer which values workforce diversity. The Schneider Electric CPCS quality and environmental system is ISO 9001 and ISO certified. SARL au capital de Euros. RCS Nanterre B SIRET CODE APE 516 J.

2 UPS System Galaxy kVA Configured as N+1 UPS System Ref: METHOD STATEMENT OF SITE ACCEPTANCE TEST 1.0 BALANCE TEST AT 100% LOAD 2.0 SYSTEM TRANSFER / RE-TRANSFER TEST 3.0 LOSS AND RETURN OF NORMAL AC POWER TEST 4.0 SYSTEM (AUTO) RE-START

3 UPS System Galaxy kVA Configured as N+1 UPS System Ref: SYSTEM DESCRIPTION The MGE Galaxy 5000 is an on line (double conversion) solid state uninterruptible power supply (UPS) system, rated at 100 kva. This project consists of 1 x 100kVA Galaxy 5000 unit configured as an N system. Each UPS is supplied with a battery to supply a load of pf for 30mins. UPS No.1-1PDK32003 This series of tests results are for the UPS Module connected as an N system. IMPORTANT All the measurements and records will be achieved as stated in the procedure attached hereafter. All measurements and records will be consigned in a test report. The load will be of resistive type via a loadbank.

4 UPS Type 3 x Galaxy kVA Configured as N+1 SIGNATURE IDENTIFICATION LOG Procedure 1. All personnel attending this SAT must be identified including vendor personnel. 2. Print name, department / organisation 3. Record signature, initials and date. 4. SAT Lead responsible to ensure that as a minimum all personnel, who have recorded information during the SAT, have recorded their name on the Signature Identification Log.

5 1.0 BALANCE TEST AT 100% LOAD Objective: Demonstrate the operation of the UPS system voltage regulation on a balanced load Procedure: A test is carried out with all three phases loaded at 100% of system load i.e. 160kW The following are measured at a common output point within the installation: UPS Output Voltages phase to phase, and the three phase and neutral currents Acceptance Criteria: Results within unit specification Results: All OK Comments: Comments Checked By: Date: ( Yes / No )

6

7

8 3.0 SYSTEM TRANSFER / RE-TRANSFER TEST Objective: To demonstrate that the UPS system can be commanded to a transferred state by shutting down UPS units in turn and then reversing the procedure to bring the UPS units back on-line. Procedure: The operator will shut down UPS units in turn demonstrating the transfer process and the N+1 operation of the system. Acceptance Criteria: Information correctly represented on client s BMS System / UPS s displays Results: All OK Comments: Comments Checked By: Date: ( Yes / No )

9 The following results show the transfer of the 100% system load from Inverters to Mains 2(Static- Switches) and back to Inverters with voltage stabilization for the load. Load Voltage during Load Transfer Test Load Current during Load Transfer Test

10 3.0 LOSS AND RETURN OF NORMAL AC POWER TEST Objective: Demonstrate the correct operation of the UPS in case of loss and return Of AC mains i.e. UPS switches to battery in case of loss of mains and back to normal operation upon return of mains. Procedure: The UPS module runs normally with load. The input switches Q1 or the Mains 1 supplies to each UPS are switched OFF to represent a mains failure. The load voltage, load current on phases L1, L2 + L3 at the output of the UPS system are recorded. A loadbank will be connected to simulate full system load: 0.8pf. The system will then run on battery for 30 minutes and the end voltage recorded. The system will then be re-charged for 3 hours and the system will then be run on battery for 24 minutes and the end voltage recorded. Acceptance Criteria: UPS system performs correctly Results: All OK Comments: Comments Checked By: Date: ( Yes / No )

11 30 minute battery discharge at 160kW

12

13 System re-charged for 3 hours and run on battery for 24 minutes

14

15 4.0 SYSTEM (AUTO) RE-START Objective: To demonstrate that the UPS system can re-start on the return of AC mains power. Operation procedures should include all necessary safety steps which will require operator management of the process. Procedure: At the end of battery test 2, allow the system to shut down on low DC voltage. Then restore AC mains and allow the system to re-charge to minimum level and then return to on-line operation with appropriate operator intervention. Acceptance Criteria: System re-starts. Information correctly represented on client s BMS System. Results: All OK Comments: After two hours the BCB will trip to prevent deep discharge. This will need to be closed if necessary. Comments Checked By: Date: ( Yes / No )

EPS 7000 and EPS 8000

EPS 7000 and EPS 8000 EPS 7000 and EPS 8000 Single and Parallel Operation 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS

More information

APC by Schneider Electric MGE GALAXY 7000 Uninterruptible Power Supply Guide Specifications 160 kva to 500 kva Single UPS 3-phase system

APC by Schneider Electric MGE GALAXY 7000 Uninterruptible Power Supply Guide Specifications 160 kva to 500 kva Single UPS 3-phase system APC by Schneider Electric MGE GALAXY 7000 Uninterruptible Power Supply Guide Specifications 160 kva to 500 kva Single UPS 3-phase system THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION

More information

APC by Schneider Electric MGE GALAXY 9000 Uninterruptible Power Supply Guide Specifications 800/900 kva to 4800/5400 kva Parallel UPS, three-phase

APC by Schneider Electric MGE GALAXY 9000 Uninterruptible Power Supply Guide Specifications 800/900 kva to 4800/5400 kva Parallel UPS, three-phase APC by Schneider Electric MGE GALAXY 9000 Uninterruptible Power Supply Guide Specifications 800/900 kva to 4800/5400 kva Parallel UPS, three-phase THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH

More information

MGE TM Galaxy TM 6000: Specification guide

MGE TM Galaxy TM 6000: Specification guide MGE TM Galaxy TM 6000: Specification guide Parallel UPS, 250 to 3000 kva* * Power rating for an N+1 configuration. Contents 1 - UPS definition... D-3 1.1 - Purpose... D-3 1.2 - Brief description... D-3

More information

DEMONSTRATIVE PROJECT ON GRID-INTERCONNECTION INTERCONNECTION OF CLUSTERED PHOTOVOLTAIC POWER GENERATION SYSTEMS

DEMONSTRATIVE PROJECT ON GRID-INTERCONNECTION INTERCONNECTION OF CLUSTERED PHOTOVOLTAIC POWER GENERATION SYSTEMS DEMONSTRATIVE PROJECT ON GRID-INTERCONNECTION INTERCONNECTION OF CLUSTERED PHOTOVOLTAIC POWER GENERATION SYSTEMS New Energy and Industrial Technology Development Organization (NEDO) Demonstrative Test

More information

UPS Electrical Design and. Installation. critica POWER SUPPLIES

UPS Electrical Design and. Installation. critica POWER SUPPLIES UPS Electrical Design and critica POWER SUPPLIES Installation Important considerations for the electrical design and installation of UPS systems in mission critical applications Where Critical Power applications

More information

e-auction under MP e- Procurement Implementation

e-auction under MP e- Procurement Implementation e-auction under MP e- Procurement Implementation Presented By: N.K Brahme Madhya Pradesh State Electronics Dev. Corporation Ltd. Nodal Officer (e- Procurement), Bhopal. Project Overview e-procurement is

More information

Code of Conduct on. Energy Efficiency and Quality of. AC Uninterruptible Power Systems (UPS)

Code of Conduct on. Energy Efficiency and Quality of. AC Uninterruptible Power Systems (UPS) EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for the Environment and Sustainability Renewable Energies Unit Ispra, 22 December 2006 Code of Conduct on Energy Efficiency and

More information

APC by Schneider Electric APC SYMMETRA MW 400 kw to 1600 kw Multi-Module Uninterruptible Power Supply

APC by Schneider Electric APC SYMMETRA MW 400 kw to 1600 kw Multi-Module Uninterruptible Power Supply APC by Schneider Electric APC SYMMETRA MW 400 kw to 1600 kw Multi-Module Uninterruptible Power Supply THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI)

More information

Financials 102. Accounts Payable

Financials 102. Accounts Payable Financials 102 Accounts Payable Introduction to This Guide Copyright Copyright 2010 ACS Technologies Group, Inc. All rights reserved. Reproduction of any part of this publication by mechanical or electronic

More information

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP Service Manual Imperial Series Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP Contents of Service Manual 1. Safety Precautions ------------------------------------------------------------------

More information

PhD Dissertation Defense Presentation

PhD Dissertation Defense Presentation PhD Dissertation Defense Presentation Wednesday, September 11 th, 2013 11:00am 1:00pm C103 Engineering Research Complex ADVANCED INVERTER CONTROL FOR UNINTERRUPTIBLE POWER SUPPLIES AND GRID-CONNECTED RENEWABLE

More information

NEW FEATURE AVAILABLE Store-to-Store Transfers through the Business Center

NEW FEATURE AVAILABLE Store-to-Store Transfers through the Business Center NEW FEATURE AVAILABLE Store-to-Store Transfers through the Business Center At the request of the Big O Tires Franchisees, we have built, tested and are now ready to implement the new process for store-to-store

More information

SMALL GENERATOR INTERCONNECTION REQUEST (Application Form)

SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Attachment 2 Transmission Provider: Bluestem Electric Cooperative, Inc. Designated Contact Person: Kevin Heptig Address: P.O. Box 5, Wamego, Kansas

More information

IEC Functional Safety Assessment

IEC Functional Safety Assessment IEC 61508 Functional Safety Assessment Project: DeltaV SIS DeltaV SIS Relay Module, KJ2231X1- EA1 DeltaV SIS Voltage Monitor, KJ2231X1 EB1 Customer: Emerson Process Management Fisher Rosemount Systems

More information

Smart Distribution Applications and Technologies - Program 124

Smart Distribution Applications and Technologies - Program 124 Smart Distribution Applications and Technologies - Program 124 Program Description Program Overview New technologies will be critical to future smart grid operation. These technologies will include advanced

More information

POWERED FOR LIFE

POWERED FOR LIFE www.gelecenergy.com POWERED FOR LIFE INNOVATION TO BRING EDISON'S DREAM TO LIFE We will make electricity so cheap that only the rich will burn candles. Thomas Alva Edison 02 ENERGY FOR ALL. Pushing the

More information

SMALL GENERATION SYSTEM APPLICATION (10 kw OR LESS)

SMALL GENERATION SYSTEM APPLICATION (10 kw OR LESS) SMALL GENERATION SYSTEM APPLICATION (10 kw OR LESS) This application, terms, and conditions, and Interconnection Agreement is for Xcel Energy customers requesting the installation of a small generation

More information

HansaWorld Enterprise

HansaWorld Enterprise HansaWorld Enterprise Integrated Accounting, CRM and ERP System for Macintosh, Windows, Linux, PocketPC 2002 and AIX Consolidation Program version: 4.2 2004-12-20 2004 HansaWorld Ireland Limited, Dublin,

More information

Systems Commissioning Table of Contents

Systems Commissioning Table of Contents Systems Commissioning Table of Contents C NC NA I. General II. Commissioning III. Mechanical Systems A. Testing, Adjusting, and Balancing B. Piping IV. Electrical Systems A. Load Balancing B. Electrical

More information

EXM UPS 80kW - 200kW Efficient and Flexible Power-Optimized For Medium-Size UPS Applications

EXM UPS 80kW - 200kW Efficient and Flexible Power-Optimized For Medium-Size UPS Applications EXM UPS 80kW - 200kW Efficient and Flexible Power-Optimized For Medium-Size UPS Applications T M Liebert EXM UPS Medium-Size UPS as dynamic as your Business Small- and medium- sized businesses need UPS

More information

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A.

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A. FAST POWER FACTOR REGULATOR Computer-14df - xx - 144a INSTRUCTION MANUAL ( M 981 611 / 00A ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14f --------- Page 2 POWER FACTOR REGULATOR COMPUTER-

More information

2017 NEC Changes for Renewable Energy Systems Session one by Christopher LaForge

2017 NEC Changes for Renewable Energy Systems Session one by Christopher LaForge 2017 NEC Changes for Renewable Energy Systems Session one 2017 by Christopher LaForge Christopher LaForge IREC Certified Master Trainer NABCEP Certified Photovoltaic Installation Professional 30 years

More information

Consistent System-Wide Control

Consistent System-Wide Control Consistent System-Wide Control SIMATIC HMI: all relevant data at a glance siemens.com/simatic-hmi Answers for industry. Operator control and monitoring of production, diagnostics and energy data: SIMATIC

More information

Electrical Research and Testing Laboratory Nuremberg

Electrical Research and Testing Laboratory Nuremberg siemens.com/energy/transformers Electrical Research and Testing Laboratory Nuremberg Testing and research at the cutting edge of technology Answers for energy. The latest methods, outstanding expertise

More information

Keatec Energy Catalogue 2018 Services

Keatec Energy Catalogue 2018 Services Keatec Energy Catalogue 2018 Services Keatec Energy designs, manufactures, installs and services DC and AC uninterruptible power solutions for Telecommunication, Commercial Information Technology (IT),

More information

TÜV SÜD BABT Production Quality Certification Scheme

TÜV SÜD BABT Production Quality Certification Scheme TÜV SÜD BABT Production Quality Certification Scheme The Production Quality Certification Scheme for Manufacturers A Certification Body of Copyright TÜV SÜD BABT 2014 Page 1 of 38 CONTENTS Page AMENDMENT

More information

LIEBERT Nfinity UPS. GUIDE SPECIFICATIONS for a 4 to 16 KVA (208/120V or 240/120V) Single - Phase Uninterruptible Power Supply System 1.

LIEBERT Nfinity UPS. GUIDE SPECIFICATIONS for a 4 to 16 KVA (208/120V or 240/120V) Single - Phase Uninterruptible Power Supply System 1. LIEBERT Nfinity UPS GUIDE SPECIFICATIONS for a 4 to 16 KVA (208/120V or 240/120V) Single - Phase Uninterruptible Power Supply System 1.1 SUMMARY 1.0 GENERAL This specification describes the Nfinity UPS,

More information

SECTION [ ] [16611] SOLID STATE UNINTERRUPTIBLE POWER SUPPLY

SECTION [ ] [16611] SOLID STATE UNINTERRUPTIBLE POWER SUPPLY APC by Schneider Electric MGE GALAXY 300 Data Center Grade Three Phase Uninterruptible Power Supply 3 400/400-230V Solutions - Guide Specifications 10kVA to 40kVA UPS THIS GUIDE SPECIFICATION IS WRITTEN

More information

Powerware 9120 UPS. Date: Issued By: Product Affected May 27, 2003 Gary Bankay PowerFlex 7000 MV Drive

Powerware 9120 UPS. Date: Issued By: Product Affected May 27, 2003 Gary Bankay PowerFlex 7000 MV Drive Medium Voltage Support Technical Services Update Title: Powerware 90 UPS Product Update Number: PF000_GEN- Date: Issued By: Product Affected May, 0 Gary Bankay PowerFlex 000 MV Drive Only personnel who

More information

Erneuerbare Energie braucht Speicher: Dezentrale Kurzspeicherloesungen im Alltag

Erneuerbare Energie braucht Speicher: Dezentrale Kurzspeicherloesungen im Alltag GENERATE STORE UTILIZE Erneuerbare Energie braucht Speicher: Dezentrale Kurzspeicherloesungen im Alltag Dipl. Phys Alexander Voigt, Verwaltungsbeirat GILDEMEISTER energy solutions www.gildemeister.com

More information

City of Hemphill, Texas APPLICATION FOR EMPLOYMENT

City of Hemphill, Texas APPLICATION FOR EMPLOYMENT City of Hemphill, Texas APPLICATION FOR EMPLOYMENT City Hall PO Box 788 211 Starr Street Hemphill, TX 75948 (409) 787-2251 (409) 787-2259 (fax) PLEASE COMPLETE ALL REQUESTED INFORMATION, INCLUDING ORIGINAL

More information

EMPLOYEE TRAINING MANAGER GETTING STARTED. January 2018

EMPLOYEE TRAINING MANAGER GETTING STARTED. January 2018 EMPLOYEE TRAINING MANAGER GETTING STARTED January 2018 Description This document describes how to get started using Employee Training Manager, a desktop software application that allows you to record and

More information

This Specification Data Sheet brought to you by: Trinity Blvd. Fort Worth, Texas /

This Specification Data Sheet brought to you by: Trinity Blvd. Fort Worth, Texas / This Specification Data Sheet brought to you by: 15825 Trinity Blvd. Fort Worth, Texas 76155 817/465-9494 equipment@technicaldiagnostic.com www.technicaldiagnostic.com www.test-equipment-rental.com The

More information

EPS /625/750/800/1,000/1,100 kva Performance power protection for critical applications. schneider-electric.com

EPS /625/750/800/1,000/1,100 kva Performance power protection for critical applications. schneider-electric.com EPS 8000 555/625/750/800/1,000/1,100 kva Performance power protection for critical applications schneider-electric.com 2 schneider-electric.com 555 1,100 kva robust three-phase power protection with adaptability

More information

FITTING AND CONNECTION OF CENTRAL UNIT EEN-CIC12

FITTING AND CONNECTION OF CENTRAL UNIT EEN-CIC12 FITTING AND CONNECTION OF CENTRAL UNIT EEN-CIC12 GENERAL This central unit (ref. EEN-CIC12) enables you to control Intratone products such as Audio and Visio intercom panels, proximity readers, RF receivers

More information

Solar Electric Systems Safety for Firefighters

Solar Electric Systems Safety for Firefighters Solar Electric Systems Safety for Firefighters AUTHOR: Ted Spooner Chair of the Australian standards committee responsible for PV systems Co-convener of the International Electrical Commission (IEC) working

More information

Product brochure. Eaton 9390 UPS kva. est 1989 ACUTE DATA INFRAS TRATEGIES

Product brochure. Eaton 9390 UPS kva. est 1989 ACUTE DATA INFRAS TRATEGIES Product brochure Eaton 9390 UPS 20-160 kva est 1989 ACUTE DATA INFRAS TRATEGIES Innovative design delivers industry-leading power performance The Eaton 9390 is a double-conversion uninterruptible power

More information

DS-520 Digital Indicator Operation Manual 73366

DS-520 Digital Indicator Operation Manual 73366 DS-520 Di gi tal Indi cator Operation Manual 73366 SECTION DS-520 SERIES OPERATING MANUAL INDEX PAGE NUMBER 1.0 GENERAL 2-3 1.1. Features 2 1.2. Keyboard & Display Layout 2 1.3. Key Switch Information

More information

Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF

Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF Daker DK 4.5-10 kva Parallel installation quick start Part. LE08927AA-09/15-01 GF Daker DK 4.5-10 kva UK ENGLISH 3 2 Daker DK 4.5-10 kva Index Introduction 2 1 Important Safety Instructions 2 2 Parallel

More information

Job Aid Administration of Consultants and Individual Contractors

Job Aid Administration of Consultants and Individual Contractors Administration of Consultants and Individual Contractors Table of Contents Page Overview..3 Objectives...3 Enterprise Roles..3 Search for Business Partner (BP) Record Requisitioner.....4 Search and Request

More information

MONTHLY TECHNICAL PROGRESS REPORT. Product Design Improvement

MONTHLY TECHNICAL PROGRESS REPORT. Product Design Improvement 9 ~.:, -, /23$ MONTHLY TECHNICAL PROGRESS REPORT DOE CONTRACT: DE-FC21-95MC31184 TITLE: MCFC Product Design Improvement DATE: January 1999 INTRODUCTION This contract is supported by DOE and DOD/DARPA

More information

City of Santa Monica Building and Safety Division Submittal Requirements Expedited Solar Photovoltaic (10 kw or Less)

City of Santa Monica Building and Safety Division Submittal Requirements Expedited Solar Photovoltaic (10 kw or Less) City of Santa Monica Building and Safety Division Submittal Requirements Expedited Solar Photovoltaic (10 kw or Less) Permits for One- and Two-Family Dwellings This following information is to guide applicants

More information

Power Management Solutions Exploring Hidden Cost Opportunities

Power Management Solutions Exploring Hidden Cost Opportunities Power Management Solutions Exploring Hidden Cost Opportunities Stephen Barker Head Of Energy Efficiency & Environmental Care Siemens plc, Industry Sector UK Siemens AG, 2010 All Rights Reserved Agenda

More information

NEC Acostix. Sound Attenuation Calculations and Design Software. General Information

NEC Acostix. Sound Attenuation Calculations and Design Software. General Information NEC Acostix Sound Attenuation Calculations and Design Software General Information NEC Acostix TM is an Excel-Based programmable sheets to help engineers and manufacturers design acoustic enclosures, rectangular

More information

kva single and parallel UPS Systems User s and Installation Manual

kva single and parallel UPS Systems User s and Installation Manual 160-500 kva single and parallel UPS Systems User s and Installation Manual 160kVA - 500kVA UPS User s and Installation Manual 1. Safety Instruction... 5 2. Introduction... 7 2.1. System description...

More information

ROOFTOP PV GUIDELINES FOR SAFE AND LEGAL INSTALLATIONS IN CAPE TOWN

ROOFTOP PV GUIDELINES FOR SAFE AND LEGAL INSTALLATIONS IN CAPE TOWN Photo credit: Bruce Sutherland, City of Cape Town. Grid-tied PV system at the City of Cape Town s Royal Ascot building. ROOFTOP PV GUIDELINES FOR SAFE AND LEGAL INSTALLATIONS IN CAPE TOWN If you are considering

More information

Avoiding the Pitfalls of Generators and Large Motors

Avoiding the Pitfalls of Generators and Large Motors Avoiding the Pitfalls of Generators and Large Motors Overview One of my clients recently asked me to investigate an ongoing issue with their standby generator operation. The problem concerned the starting

More information

Design Installation and Testing of 1.6 kwp GPV System

Design Installation and Testing of 1.6 kwp GPV System Design Installation and Testing of 1.6 kwp GPV System Napat Watjanatepin Rajamangala University of Technology Suvarnabhumi Nonthaburi Campus THAILAND Phone:+66-2969-1521, Fax:+66-2525-2682 Email:watjanatepin@yahoo.com

More information

COSVR728 - SQA Unit Code F3H7 04 Evaluate and select work methods

COSVR728 - SQA Unit Code F3H7 04 Evaluate and select work methods Overview This standard is about 1 assessing and evaluating information 2 identifying safe and healthy work methods 3 identifying how materials and resources will be used 4 preparing, producing and agreeing

More information

Technical Specification Industrial Series - IS2 to IS48 Systems. CapDI Benefits. Feed Water Quality. Design and Scope of Supply.

Technical Specification Industrial Series - IS2 to IS48 Systems. CapDI Benefits. Feed Water Quality. Design and Scope of Supply. Technical Specification Industrial Series - IS2 to IS48 Systems Voltea s Industrial Series IS systems employ a simple, cost effective modular design providing flexibility to align with both current and

More information

AS/NZS 3010:2005 AS/NZS

AS/NZS 3010:2005 AS/NZS AS/NZS 3010:2017 Australian/New Zealand Standard Electrical installations Generating sets Superseding AS/NZS 3010:2005 AS/NZS 3010:2017 AS/NZS 3010:2017 This joint Australian/New Zealand standard was prepared

More information

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode)

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode) ANNEXURE-I-A QUOTATION ENQUIRY Ref: IIT (BHU)/IPCell/2017-18/UPS/1 KVA/574 Due Date: 26.09.2017 Date:16.09.2017 Upto 1:00 pm (Last date of quotation receiving) (Date of tender enquiry) To. Dear Sir, Please

More information

Journal of Asian Scientific Research

Journal of Asian Scientific Research Journal of Asian Scientific Research journal homepage: http://aessweb.com/journal-detail.php?id=5003 DESIGN OF A PV/DIESEL STAND ALONE HYBRID SYSTEM FOR A REMOTE COMMUNITY IN PALESTINE M.S. Ismail 1 M.

More information

YANMAR s 35 kw Combined Heat and Power System.

YANMAR s 35 kw Combined Heat and Power System. YANMAR s 35 kw Combined Heat and Power System www.yanmar-es.com YANMAR s 35 kw Combined Heat and Power System A DIFFERENT MINDSET = GAME CHANGER When thinking about heat and power for commercial buildings,

More information

Module: Channels & Marketing Messages

Module: Channels & Marketing Messages Module: Channels & Marketing Messages Channels Click on the Search button to view all channels added to your hotel, or filter by Channel. Tabs: Channel: Add, edit or view which channels are added to your

More information

SOX compliance through Role Design & SAP GRC Access Control The Omega Pharma case

SOX compliance through Role Design & SAP GRC Access Control The Omega Pharma case SOX compliance through Role Design & SAP GRC Access Control The Omega Pharma case Tim Goossens GRC Manager Produced by Wellesley Information Services, LLC, publisher of SAPinsider. 2016 Wellesley Information

More information

Applicant s Name: Visit https://ecpic.commissionaires.ca/login/ to get a check done electronically.

Applicant s Name: Visit https://ecpic.commissionaires.ca/login/ to get a check done electronically. Welcome to the T.E.A.M.S. driver application process. Please fill out the application form completely do not leave any blank spaces where information is requested. If information requested does not apply,

More information

CHAPTER 5 INFORMATION TECHNOLOGY SERVICES CONTROLS

CHAPTER 5 INFORMATION TECHNOLOGY SERVICES CONTROLS 5-1 CHAPTER 5 INFORMATION TECHNOLOGY SERVICES CONTROLS INTRODUCTION In accordance with Statements on Auditing Standards Numbers 78 and 94, issued by the American Institute of Certified Public Accountants

More information

How Configuration Management Systems Deliver Change and Compliance

How Configuration Management Systems Deliver Change and Compliance How Configuration Management Systems Deliver Change and Compliance KEITH SINCLAIR, CTO OPMANTEK 25 JANUARY 2018 VERSION 4 TABLE OF CONTENTS Executive Overview... 1 The Top Causes Of Downtime Explored...

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 33 53.00 20 (April 2008) ---------------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 33 53.00 20 (January 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Controlling the Agilent 1260 Infinity/1290 Infinity II Multisampler (G7167A/B) in Waters Empower 3 Environment

Controlling the Agilent 1260 Infinity/1290 Infinity II Multisampler (G7167A/B) in Waters Empower 3 Environment Controlling the Agilent 1260 Infinity/1290 Infinity II Multisampler (G7167A/B) in Waters Empower 3 Environment Technical Note Controlling the Multisampler using ICF - Technical Note Technical Guide for

More information

How to Test A SOA System. Carsten Feilberg, Strand & Donslund A/S, Denmark

How to Test A SOA System. Carsten Feilberg, Strand & Donslund A/S, Denmark How to Test A SOA System W6 Carsten Feilberg, Strand & Donslund A/S, Denmark How to test a SOA system Carsten Feilberg Strand & Donslund A/S Hannedal 9 DK-2860 Søborg www.s-d.dk What this talk will address

More information

Best Practices for Using Enphase Current Transformers (CTs) in Australia and New Zealand

Best Practices for Using Enphase Current Transformers (CTs) in Australia and New Zealand TECHNICAL BRIEF Best Practices for Using Enphase Current Transformers (CTs) in Australia and New Zealand Introduction A Current Transformer (CT) is a current measurement device used in conjunction with

More information

Operation Plan of a Photovoltaic and Diesel Engine Combined System with the Power Prediction Method. Abeer Galal El-Sayed

Operation Plan of a Photovoltaic and Diesel Engine Combined System with the Power Prediction Method. Abeer Galal El-Sayed Journal of American Science 20;9(5) Operation Plan of a Photovoltaic and Diesel Engine Combined System with the Power Prediction Method Abeer Galal El-Sayed Department of Electric Engineering, Faculty

More information

Pallet Safe: Installation Supplement Rev

Pallet Safe: Installation Supplement Rev Pallet Safe: Installation Supplement Rev. 4-1-13 Smartscan Incorporated, 33083 Eight Mile Road, Livonia MI 48152 Tel: (248)477-2900 Fax: (248) 477-7453 Web: www.smartscaninc.com SMARTSCAN INCORPORATED

More information

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation. A B C Details of the installation Owner*/Occupier*/Customer*/ (*Delete as necessary) Only for the reporting on the condition of an existing installation Purpose for which this report is required Installation

More information

Proposal No. P18/9978L Information Technology Service Management Solution

Proposal No. P18/9978L Information Technology Service Management Solution Proposal No. P18/9978L Information Technology Service Management Solution Answers to Vendor Questions Questions are in black, Answers are in red 1. Question: Whether companies from Outside USA can apply

More information

Operating Manual. Wärtsilä JOVYTEC L 6kVA 10kVA. BAX 3297_en

Operating Manual. Wärtsilä JOVYTEC L 6kVA 10kVA. BAX 3297_en Operating Manual Wärtsilä JOVYTEC L 6kVA 10kVA BAX 3297_en Index Date Name Revision 0 08.04.2009 Technik Original 1 2014-06-20 Chr. Fechteler 14/375 2 2015-07-22 Chr. Fechteler 15/381 3 2016-03-24 Chr.

More information

MRI General Ledger for Web Operational Training Guide Version 4.2

MRI General Ledger for Web Operational Training Guide Version 4.2 MRI General Ledger for Web Operational Training Guide Version 4.2 2012 MRI Software LLC. Any unauthorized use or reproduction of this document is strictly prohibited. All Rights Reserved. 2012 MRI Software

More information

Prepare and Clear Areas for Counter/Takeaway Service

Prepare and Clear Areas for Counter/Takeaway Service Unit Summary This Unit is about preparing work areas and service equipment, and displaying promotional materials and food properly. It also covers clearing these areas, including switching off service

More information

IECEE OPERATIONAL DOCUMENT

IECEE OPERATIONAL DOCUMENT IECEE OD-G-4001 Edition 1.3 2013-06-20 IECEE OPERATIONAL DOCUMENT IEC System of Conformity Assessment Schemes for Electrotechnical Equipment and Components (IECEE System) Guidance for Factory Inspectors

More information

Process Safety Management and Functional Safety Management. Spot the difference

Process Safety Management and Functional Safety Management. Spot the difference Process Safety Management and Functional Safety Management. Spot the difference A few key points for those Directors and Managers responsible for overseeing safety trips by The 61508 Association SAFETY

More information

Pressure Booster System. Hya-Eco VP. Type Series Booklet

Pressure Booster System. Hya-Eco VP. Type Series Booklet Pressure Booster System Hya-Eco VP Type Series Booklet Legal information/copyright Type Series Booklet Hya-Eco VP KSB Aktiengesellschaft Frankenthal All rights reserved. Contents provided herein must neither

More information

Retek Invoice Matching Operations Guide Addendum

Retek Invoice Matching Operations Guide Addendum Retek Invoice Matching 11.0.4 Operations Guide Addendum Corporate Headquarters: Retek Inc. Retek on the Mall 950 Nicollet Mall Minneapolis, MN 55403 USA 888.61.RETEK (toll free US) Switchboard: +1 612

More information

CENTRAL SUSQUEHANNA INTERMEDIATE UNIT Application: Fund Accounting

CENTRAL SUSQUEHANNA INTERMEDIATE UNIT Application: Fund Accounting CENTRAL SUSQUEHANNA INTERMEDIATE UNIT Application: Fund Accounting PO & Requisition Entry Learning Guide Copyright 2011 Central Susquehanna Intermediate Unit, USA Table of Contents Introduction...1 PO

More information

Setting Up CounterPoint

Setting Up CounterPoint 1 Installation and Configuration: Getting Started Setting Up CounterPoint Overview This document provides an overview of the steps to follow to set up your CounterPoint software. The steps outlined in

More information

IDENTIFY SECURE INTEGRATE

IDENTIFY SECURE INTEGRATE IDENTIFY SECURE INTEGRATE IRIZ ID Technologies encourages the pursuit of fresh knowledge and equipped to build new solutions. WE IDENTIFY SECURE AND INTEGRATE Category Department Company Facility Employee

More information

Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content

Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content Purpose The purpose of this Detailed Requirements Document (DRD) is to provide

More information

Custom Application 2018 Retrofit Program

Custom Application 2018 Retrofit Program The Retrofit Program is designed for Commercial and Industrial (C&I) customers to help replace aging and inefficient equipment and systems with more energy efficient technologies. Tailored to a customer's

More information

TMT Fleet Maintenance Windows. TruckMate Installation Guide

TMT Fleet Maintenance Windows. TruckMate Installation Guide TMW Asset Maintenance TMT Fleet Maintenance Windows TruckMate Installation Guide 1 Table of Contents TruckMate Interface... 3 TruckMate TMT Fleet Maintenance Interface... 4 TruckMate Installation from

More information

FRENIC4800VM5, a Water-Cooled High Capacity, High Voltage Inverter

FRENIC4800VM5, a Water-Cooled High Capacity, High Voltage Inverter FRENIC4800VM5, a Water-Cooled Capacity, Voltage Inverter MOKUTANI Masafumi HANAZAWA Masahiko ADACHI Akio ABSTRACT -voltage inverters used to drive main rolling mills for steel and non-ferrous metal materials,

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org C5-1036 AORC Technical meeting 2014 Solar PV Rooftop System Connection to MEA s Distribution Network: Technic and Economic Aspects Tosak Thasananutariya Metropolitan Electricity

More information

3456 en / c. 1 to 20 MW Land and offshore applications

3456 en / c. 1 to 20 MW Land and offshore applications 3456 en - 12.2005 / c 1 to 20 MW Land and offshore applications POWER ALTERNATORS Generating Progress Gas or steam turbine application There is currently an enormous increase in energy requirements throughout

More information

VFDs driving the boiler feed water pump of #11-13 Combined Cycled Generation Unit in Yangpu Thermal Power Plant by Bin Li

VFDs driving the boiler feed water pump of #11-13 Combined Cycled Generation Unit in Yangpu Thermal Power Plant by Bin Li VFDs driving the boiler feed water pump of #11-13 Combined Cycled Generation Unit in Yangpu Thermal Power Plant by Bin Li Brief introduction to Author: Li Bin, born in 1969, graduated from Beihang University

More information

Whitepaper Enterprise Mobile Manager

Whitepaper Enterprise Mobile Manager Whitepaper Enterprise Mobile Manager OVERVIEW OnPremise or Cloud Based Mobile Management Solution The AppTec cloud based mobile management solution with its very intuitively operable management console

More information

PREFERENCE MANAGER FOR MICROSOFT DYNAMICS. Implementation & Connectivity Overview

PREFERENCE MANAGER FOR MICROSOFT DYNAMICS. Implementation & Connectivity Overview PREFERENCE MANAGER FOR MICROSOFT DYNAMICS Implementation & Connectivity Overview TABLE OF CONTENTS 1. Introduction... 3 2. Supported Versions... 3 3. Prerequistes... 3 4. Integration Overview... 3 5. Data

More information

Defect Repair Report as of 9/12/2014

Defect Repair Report as of 9/12/2014 27.04 Page 1 of 16 Release Notes By Module Framework The system no longer bans you from the EFI Pace refresh screen. 27.04-512 Framework The system now recognizes the Log In Automatically setting on the

More information

Micro-generation using LMS Imagine.Lab AMESim

Micro-generation using LMS Imagine.Lab AMESim Micro-generation using LMS Imagine.Lab AMESim 2009/04/20 Event title (to be altered on title master) Presenter name presenter job title (to be altered on title master) Agenda Home electric network components

More information

Islamic Republic of Iran Ministry of Petroleum Vendor Evaluation Questionnaire

Islamic Republic of Iran Ministry of Petroleum Vendor Evaluation Questionnaire ١- Company Information ١ ١- Company's name: Ex -Name: ١ ٢ -Parent Company (If any) ١ ٣ -Subsidiaries and associated concern Co: Date of establishment: Date and place of registration : Full address: Tel

More information

GEOS / ENST Problem set #Grid Due: Tues. May 18

GEOS / ENST Problem set #Grid Due: Tues. May 18 GEOS 24705 / ENST 24705 Problem set #Grid Due: Tues. May 18 Problem 1: Three-phase power transmission The standard means by which electricity is transmitted in the U.S. is as 3-phase AC power. Each of

More information

Using UPSMON-PRO Monitoring Software. Opening UPSMON-PRO Monitoring Software

Using UPSMON-PRO Monitoring Software. Opening UPSMON-PRO Monitoring Software Using UPSMON-PRO Monitoring Software With this UPS monitoring software, you can : Get UPS connection from serial port, usb port, or snmp agent Monitor UPS status, battery capacity, output voltage, load

More information

3 TECHNICAL SPECIFICATIONS OF THE PHOTOVOLTAIC POWER GENERATING PLANT

3 TECHNICAL SPECIFICATIONS OF THE PHOTOVOLTAIC POWER GENERATING PLANT 3 TECHNICAL SPECIFICATIONS OF THE PHOTOVOLTAIC POWER GENERATING PLANT This section provides the technical details of the proposed photovoltaic power generating plant. The drawings relevant to this section

More information

FeliCa Reader/Writer. Digital Protocol Requirements Specification

FeliCa Reader/Writer. Digital Protocol Requirements Specification FeliCa Reader/Writer Digital Protocol Requirements Specification Version 1.0 October 05, 2017 Japan Electronic-money Promotion Association 1/18 Revision History Version No. 1.0 Date issued October 05,

More information

LSA Rating Table Low Voltage Alternators - 4 pole

LSA Rating Table Low Voltage Alternators - 4 pole LSA Rating Table Low Voltage Alternators - 10 to 3300 kva - 50 Hz / 12.5 to 3900 kva - 60 Hz General features and ratings Summary 1 - RATING DEFINITION... 3 2 - INSULATION CLASS AND TEMPERATURE RISE...

More information

Measurement Protocol for the calibration of a Fluke 744 Process Calibrator ILC 132

Measurement Protocol for the calibration of a Fluke 744 Process Calibrator ILC 132 National Laboratory Association of South Africa - NPC P.O. Box 298 Persequor Park Pretoria, South Africa, 0020 Reg. No: 1994/002856/08 Tel: (+27) 012 349 1500 Fax: (+27) 012 349 1501 http://www.nla.org.za

More information

WELMEC European cooperation in legal metrology Guide for the Testing of Automatic Catchweighing Instruments

WELMEC European cooperation in legal metrology Guide for the Testing of Automatic Catchweighing Instruments WELMEC 2.6 Issue 3 WELMEC European cooperation in legal metrology Guide for the Testing of Automatic Catchweighing Instruments May 2008 1 WELMEC European cooperation in legal metrology WELMEC is a co-operation

More information

Pre Bid Meeting clarification & Requirements

Pre Bid Meeting clarification & Requirements Pre Bid Meeting clarification & Requirements PLEASE PUT SEAL & SIGN ON LL THE PAGES OF THE TENDER & FOLLOWING CLARIFICATIONS: Date of Meeting: 13-12-2008 Note: This of 7 pages shall be treated as part

More information

CEN/TC 264/WG 17 N 147

CEN/TC 264/WG 17 N 147 1, avenue Albert Einstein BP 120 - F-78193 Trappes cedex Tél.: +33 (0)1 30 66 27 27 Fax : +33 (0)1 30 66 28 76 Fax labo. : +33 (0)1 30 66 27 28 www.crt-trappes.fr 48.03.154 / CD Trappes, le 10 mars 2009

More information

November 4, 2010, Rev 1

November 4, 2010, Rev 1 Advanced Power Systems November 4, 2010, Rev 1 Syracuse University Turbine Powered Data Center David R. Blair, P.E. David R. Blair, P.E. November 4, 2010 Serious Growth in Data Center Energy Requirements

More information