A CONTRIBUTION TO OUTER SURFACE CRACK HEIGHT SIZING BY PAUT

Size: px
Start display at page:

Download "A CONTRIBUTION TO OUTER SURFACE CRACK HEIGHT SIZING BY PAUT"

Transcription

1 A CONTRIBUTION TO OUTER SURFACE CRACK HEIGHT SIZING BY PAUT Peter Ciorau,Tetra Tech Energy, Canada Jerome Poguet, Imasonic, France Lou Pullia, Ontario Power Generation, Canada Jessica Lam, Ontario Power Generation, Canada Chris Eaton, Ontario Power Generation, Canada Jason Coulas, Ontario Power Generation, Canada ABSTRACT The paper presents four problem-solving cases for sizing the outer surface cracks for the following components of CANDU nuclear generation station: steam generator lug welds, outlet weld of steam chest valve, bleed condenser inlet nozzle weld and primary circuits piping welds mock-ups for inspection qualification. The design, manufacture and performance assessment of miniature and sub-miniature 1-D linear phased array probes of high frequency (5-12 MHz) are commented and illustrated. A novel calibration technique on EDM notches and validated on fatigue cracks with known height is commented and illustrated. PAUT data were used for return-to-service decision for ECA engineering. It was found the PAUT is undersizing by mm the real fatigue cracks and oversizing by 1 to 3 mm the implanted cracks. PROBLEM STATEMENT Large-scale applications of PAUT on turbine components identified the needs to design, manufacture and use smaller 1-D linear array probes [ref.1] to detect and namely to size possible flaws in rotor steeple grooves and blade roots.. These probes were used for another firefighting problem-solving during the in-service inspections. During the outage QC NDT team found outer surface cracks on different components. Trying to grind was the first action, thinking the crack has a superficial height (shallow). The damage was done and after another NDT checking by liquid penetrants or fluorescent magnetic particles, the crack was still there. PAUT team was called to size the height and provide reliable number to ECA (Engineering Critical Assessment) team for a correct decision. One or two millimetre in height measurement could mean a return-to-service or an extended outage due to repair, post-heat treatment and re-checking by NDT methods. Over a 10-year period, OPG diversified the variety of miniature and sub miniature probes. The problems identified during the inspection were communicated to Imasonic helping them to improve the quality of these small probes to withstand harsh field conditions and a longer usage. A large variety of small probes (about 20 types, including cable orientation) were manufactured, tested by Imasonic and field-commissioned by OPG based on in-house high standard procedure with tight tolerances. The paper presents practical applications of these probes on four CANDU components: steam generator lug weld (lab measurements), commissioning aspect for ACFM method, outlet weld of main valve, sizing height of a SCC on inlet nozzle of bleed condenser and sizing OD implanted cracks on IQ mock-ups of ferritic steel piping welds (primary circuits). DESIGN, MANUFACTURE AND PERFORMANCE ASSESSMENT OF MINIATURE AND SUB- MINIATURE PROBES The need to develop miniature probes was identified early in 1998 for side technique of L-1 steeple in the first 15 mm from steeple/blade face. Imasonic-Besancon-France accepted the OPG challenge and developed over a 12-year period a large variety of miniature and sub-miniature probes (see some examples in Table 1 and Figure 1). 441

2 Figure 1: Examples of miniature and sub-miniature probes. The probes were checked according to in-house Imasonic procedures, a common designed OPG- Imasonic procedure and OPG in-house characterization procedures. Some issues were detailed in ref.1 to ref. 5. Special measures were taken to have a good detection in surface-wave domain (75-89 deg) and a 442

3 corrected calibrated depth reading in shear waves domain. Figure 2 and 3 present the NS-2 block with small SDH of 0.5 mm and calibration on TED-1 to TED-3 blocks and TOFD-1 to TOFD-3 blocks for EDM notches. After the ideal calibration, the probes were tested on blocks with fatigue cracks of known height (see example in Figure 4). Figure 2: Location of 0.5 mm-sdh on NS-2 block for angle, index, and depth calibration. Figure 3: Examples of depth reading of 1-mm (right) and 2-mm (left) EDM notches. Figure 4: Examples of crack height evaluation with probe P72-60T ; Undersizing by 0.2 mm. Crack tilt angle is also displayed (specular-left; diffracted-right). 443

4 FIELD EXAMPLES Outlet pipe of main valve Crack in Excavation Figure 5 illustrates the crack sizing and plotting into 3-D. Detection was performed by probe 52-60T (special round and contour wedge). The crack was removed. (Courtesy OlympusNDT-Waltham-USA) Figure 5: See the text above. STRESS CORROSION CRACK on INLET NOZZLE WELD-BLEED CONDENSER. The crack was found on the inlet nozzle weld (see Figure 6). During the inspection, it was found the crack height < 3 mm using a correction curve (see Figure 7). The crack was not repair, being acceptable by disposition ASME XI Table IWA , saving station 3 days outage time. 444

5 Figure 6: Location of SCC and principle of height sizing by a sub-miniature probe. SG LUG WELDS-CRACK SIZING ON MOCK-UPS (LAB) Toe cracks were found on fillet welds of SG Lugs. Two reference blocks were made with 7 implanted cracks on each block of known height and length (see Table 2 and Figure 8). The crack shape was a rectangular one. ACFM method was used for capability demonstration. It was required by ECA to size cracks with height > 1 mm. 445

6 It was found the ACFM was reading a larger length and height versus the design and QC documented value of implanted crack. PAUT was asked to check and confirm the crack height and length. PAUT inspection using high-frequency probes (6-10 MHz) size the implant gauging, which changed the microstructure and local magnetic permeability (see Figure 9-as an example). This fact might explain the length oversizing by ACFM by a factor of 2-3. The height of implanted cracks was found larger than design requirements (see Figure 10). Figure 9: Example of crack height sizing in S-scan (left) and excavation areas B-scan display for two implanted cracks nr,5 and 6 ref. block T 4078 (right). 446

7 Figure 10: Correlation between PAUT and implanted crack height (left); example of crack height sizing (design = 1.8 mm; PAUT=2.3 mm). IQ PIPING MOCK-UPS OUTER SURFACE CRACKS (LAB) Outer surface cracks (see Figure 11 left for some examples) were implanted either in HAZ or at t/2 distance from the weld. Some of the cracks were tilt 12.5or 37.5and skewed by PAUT measured the crack height in direct hit, either with crack under the probe wedge (short cracks) or with the crack in front of the probe (see Figure 11 right). Figure 11: Examples of OD cracks in the IQ mock-ups (left); crack height sizing by PAUT (right): h PAUT = 6.3 mm; h design = 5 mm / 12.5in HAZ; probe on the piping side. PAUT found the implanted cracks have a height larger than required and QC documented. The height is increasing with crack height/length and with the challenge of skewing the crack. The tolerances are within acceptable limits. Some examples are presented in Figure 12. Figure 12: Examples of S-scan sizing for OD cracks: left) 7-mm crack sized as 8.2 mm; right) 1.5-mm crack sized as 1.9 by PAUT. 447

8 CONCLUDED REMARKS The examples presented in this paper concluded: PAUT could reliable size cracks under the probe if the crack height is greater than 1.5 mm PAUT is undersizing fatigue cracks by mm. A safety value of + 1 mm added to PAUT crack height will provide a more conservative approach to ECA (ref.6-7). Implanted cracks are oversized; we don t know the reality, unless a mock-up will be destroyed and machined in fine steps or cut in slices by wire EDM. Miniature and sub-miniature probes could size the crack height in excavation, closer to fillet weld and on the nozzle weld with good repeatability. Imasonic probes provided high performance and over a 3-year interval [ ] reproducible results on IQ OD cracks. PAUT results were used for ECA in real life (bleed condenser, outlet pipe weld) as well as to explain some anomalies in length sizing by ACFM, in feasibility study for SG Lug crack sizing. The operation of implanting cracks on outer surface is not quite under control. Additional microporosity and slag are detected by PAUT. Magnetic properties are changed, which may influence the ACFM performance. Crack opening on OD is quite large ( mm) and visible on the pipe surface (see Figure 11 left). REFERENCES 1. OlympusNDT: Advances in Phased Array Ultrasonic Applications, chapter Miniature and Sub miniature Probes, Waltham, USA, Aug Poguet,J., Ciorau, P.: Reproducibility and Reliability of NDT phased array probes 16-th WCNDT, Montreal, Aug 30-Sept.03, 2004., NDT.net Ciorau,P., Pullia,L., Poguet, J.: A Contribution to Repeatability of 1-D Linear Array Probes Used on Large-Scale Inspection of Low-Pressure Turbine Components NDT.net, vol.11, no.10 (Oct.2006) 4. Ciorau,P., Pullia,L., Poguet, J.: Linear Phased Array Probes and Inspection Results on Siemens- Parson Turbine Blades - 4-th PA seminar-epri-miami Dec 2005, NDT.net Fleury,G., Poguet,J., Ciorau, P.: A Practical Proposal for Designing, Testing and Certification Phased Array Probes Used in Nuclear Applications. 4-th Int. NDE Conf. Nuclear, London, Dec, 2004, NDT.net, Ciorau, P.: A Contribution to Crack Sizing by Phased Array Ultrasonic Techniques. b. Part 2: Comparison with Optical, Magnetic Particles, Fracture Mechanics and Metallography for Last Significant Crack Tip. ndt.net vol.12, no.2 (Feb 2007) /6 th NDE Nucl-Budapest-Oct.2007 c. 7. Ciorau, P., Gray, D., Daks, W.: Phased Array Ultrasonic Technology Contribution to Engineering Critical Assessment (ECA) of Economizer Piping Welds -ndt.net vol. 11, no.5 (May 2006) /6 th NDE Nucl-Budapest-Oct.2007 ACKNOWLEDGEMENTS: 1. The authors wish to thank OPG-IMS Management for granting the publication and presentation of this paper. 2. One of the co-authors (P. Ciorau) wish to thank the following people: Wence Daks and Howard Smith- CADWIRE for 3-D drawings, Steve Hiroz, Jim Newsome, Steve Walling and Derek Roy-OPG IMS PAUT technicians for their contribution (PAUT, MP, photos) to this project. 448