AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 8000 TYPE: Vertical Slider (Single Hung)

Size: px
Start display at page:

Download "AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 8000 TYPE: Vertical Slider (Single Hung)"

Transcription

1 Architectural Testing AAMA THERMAL PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 8000 TYPE: Vertical Slider (Single Hung) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance Factor - Frame (CRF f ) 53 Condensation Resistance Factor - Glass (CRF g ) 74 Unit Size 47-1/4'' x 59'' (1200 mm x 1499 mm) Layer 1 DS PPG Solarban 70 (e=0.018*, #2) Gap '' Gap, Steel Intercept Spacer (CU-S), 90% Argon-Filled* Layer 2 DS Clear Gap '' Gap, Steel Intercept Spacer (CU-S), 90% Argon-Filled* Layer 3 DS Clear Reference must be made to Report No. A , dated 05/19/10 for complete test specimen description and data E. Jensen Ave Fresno, CA phone: fax:

2 Architectural Testing AAMA THERMAL PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM 720 Cel-River Road Rock Hill, South Carolina Report Number: Test Date: Report Date: Test Record Retention Date: A /04/10 05/19/10 05/04/14 Test Sample Identification: Series/Model: 8000 Type: Vertical Slider (Single Hung) Test Sample Submitted by: United States Aluminum - South Gate, California Test Procedure: The condensation resistance factor (CRF) and thermal transmittance (U) were determined in accordance with AAMA , Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections 1. Average warm side ambient temperature 2. Average cold side ambient temperature mph dynamic wind applied to test specimen exterior " +0.04" static pressure drop across specimen. Test Results Summary: F F Condensation resistance factor - Frame (CRF f ) Condensation resistance factor - Glass (CRF g ) Thermal transmittance due to conduction (U) (U-factors expressed in Btu/hr ft 2 F) E. Jensen Ave Fresno, CA phone: fax:

3 Architectural Testing A Page 2 of 9 Test Sample Description: CONSTRUCTION Frame Interior Sash Size (in.) Non-Standard 47-1/4 x /4 x 30 Daylight Opening (in.) CORNERS Fasteners Sealant MATERIAL Color Exterior Finish Exterior Color Interior Finish Interior GLAZING METHOD 43 x 24-3/8 Coped Screws Yes AT (0.25") Skip/Debridge 2"/15" Gray Mill finish Gray Mill finish Exterior 40-1/8 x 24-3/8 Coped Screws Yes AT (0.25") Skip/Debridge 2"/15" Gray Mill finish Gray Mill finish Exterior Glazing Information: Layer 1 Gap 1 Layer 2 Gap 2 Layer 3 Gas Fill Method Desiccant DS PPG Solarban 70 (e=0.018*, #2) 0.44'' Gap, Steel Intercept Spacer (CU-S), 90% Argon-Filled* DS Clear 0.44'' Gap, Steel Intercept Spacer (CU-S), 90% Argon-Filled* DS Clear Single-Probe Method* Yes *Stated per Client/Manufacturer NA Non-Applicable See Description Table Abbreviations

4 Architectural Testing A Page 3 of 9 Test Sample Description: (Continued) COMPONENTS Type WEATHERSTRIP Polypile with center & side fins Polypile with center & side fins Quantity 2 rows 1 row Sill. Location Jambs. Interior meeting rail. Exterior meeting rail. HARDWARE Block & tackle balance system 1 Jambs. Latch lock 2 Bottom rail of the interior sash. DRAINAGE 2" x 3/16" weephole 2 Sill face.

5 Architectural Testing A Page 4 of 9 Test Duration: 1. The environmental systems were started at 16:55 hours, 05/03/ The thermal performance test results were derived from 03:56 hours, 05/04/10 to 07:56 hours, 05/04/10. Condensation Resistance Factor (CRF): The following information, condensed from the test data, was used to determine the condensation resistance factor: T h T c FT p FT r W FT GT CRF g CRF f = Warm side ambient air temperature F = Cold side ambient air temperature F = Average of pre-specified frame temperatures (14) F = Average of roving thermocouples (4) F = = [(FT p - FT r ) / (FT p - (T c + 10))] x 0.40 FT p (1-W) + W (FT r ) = Frame Temperature F = Glass Temperature F = Condensation resistance factor Glass CRF g = (GT - T c ) / (T h - T c ) x = Condensation resistance factor Frame 53 CRF f = (FT - T c ) / (T h - T c ) x 100 The CRF number was determined to be 53 (on the size as reported). When reviewing this test data, it should be noted that the frame temperature (FT) was colder than the glass temperature (GT) therefore controlling the CRF number. Refer to the 'CRF Report' page and the 'Thermocouple Location Diagram' page of this report.

6 Architectural Testing A Page 5 of 9 Thermal Transmittance (U c ): T h = Average warm side ambient temperature F T c = Average cold side ambient temperature F P = Static pressure difference across test specimen 0.00 psf 15 mph dynamic perpendicular wind at exterior Nominal sample area ft 2 Total measured input to calorimeter Btu/hr Calorimeter correction Btu/hr Net specimen heat loss Btu/hr U = Thermal Transmittance 0.48 Btu/hr ft 2 F Glazing Deflection (in.): Edge Gap Width Estimated center gap width upon receipt of specimen in laboratory (after stabilization) Center gap width at laboratory ambient conditions on day of testing Center gap width at test conditions Frame Gap 1/Gap / / / / 0.44 Interior Sash Gap 1/Gap / / / / 0.44 The sample was inspected for the formation of frost or condensation, which may influence the surface temperature measurements. The sample showed no evidence of condensation/frost at the conclusion of the test. A calibration of the Architectural Testing Inc. 'thermal test chamber' (ICN ) in Fresno, California was conducted in April 2010 in accordance with Architectural Testing Inc. calibration procedure. Prior to testing the specimen was sealed with silicone on the interior side and checked for air infiltration per Section

7 Architectural Testing A Page 6 of 9 CRF Report Time: 05:56 06:26 06:56 07:26 07:56 AVERAGE Pre-specified Thermocouples - Frame FT P Pre-specified Thermocouples - Glass GT Cold Point (Roving) Thermocouples FT R W FT Warm Side - Room Ambient Air Temperature Cold Side - Room Ambient Air Temperature CRF f CRF g

8 Architectural Testing A Page 7 of 9 Thermocouple Location Diagram SELECT DRAWING, DRAG HERE, AND IDENTIFY COLD POINTS Cold Point Locations

9 Architectural Testing A Page 8 of 9 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period such materials shall be discarded without notice and the service life of this report by Architectural Testing will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Simon Smeds Technician Kenny C. White Laboratory Manager Individual-In-Responsible-Charge WSS:he A Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Description Table Abbreviations (1) Appendix-B: Drawings (23)

10 Architectural Testing A Page 9 of 9 Revision Log Rev. # Date Page(s) Revision(s) 0 05/19/10 All Original Report Issue. Work requested by Mr. John Frey of United States Aluminum This report produced from controlled document template ATI 00025(c), revised 04/28/10.

11 Appendix A: Description Table Abbreviations A CODE Frame / Sash Types DOOR DETAILS AI Aluminum w/ Vinyl Inserts (Caps) N Not Applicable AL Aluminum AP Aluminum w/ Thermal Breaks - Partial CODE Door Type AS Aluminum w/ Steel Reinforcement EM Embossed AT Aluminum w/ Thermal Breaks - All Members ( > 0.21") FL Flush AU Aluminum Thermally Improved - All Members (0.062" ") LF Full Lite AV Aluminum / Vinyl Composite LH 1/2 - Lite AW Aluminum-clad Wood LQ 1/4 - Lite FG Fiberglass LT 3/4 - Lite PA ABS Plastic w/ All Members Reinforced RP Raised Panel PC ABS Plastic-clad Aluminum PF ABS Plastic w/ Foam-filled Insulation CODE Skin PH ABS Plastic w/ Horizontal Members Reinforced AL Aluminum PI ABS Plastic w/ Reinforcement - Interlock FG Fiberglass PL ABS Plastic GS Galvanized Steel PP ABS Plastic w/ Reinforcement - Partial ST Steel PV ABS Plastic w/ Vertical Members Reinforced WD Wood PW ABS Plastic-clad Wood VY Vinyl ST Steel VA Vinyl w/ All Members Reinforced CODE Panel VC Vinyl-clad Aluminum FG Fiberglass VF Vinyl w/ Foam-filled Insulation PL Plastic VH Vinyl w/ Horizontal Members Reinforced WP Wood - Plywood VI Vinyl w/ Reinforcement - Interlock WS Wood - Solid VP Vinyl w/ Reinforcement - Partial VV Vinyl w/ Vertical Members Reinforced CODE Sub-Structure VW Vinyl-clad Wood GS Galvanized Steel VY Vinyl ST Steel WA Aluminum / Wood composite WD Wood WD Wood VY Vinyl WV Vinyl / Wood composite WF Fiberglass/Wood Combination CODE Core Fill WC Composite/Wood Composite (Shaped vinyl/wood composite members) CH Cellular - Honeycomb CW Copper Clad Wood EP Expanded Polystyrene CO Vinyl/Wood Composite Material PI PU Polyisocyanurate Polyurethane CODE Tint Codes WP Wood - Plywood AZ Azurlite WS Wood - Solid CODE Spacer Types (See sealant) BL Blue XP Extruded Polystyrene A1 Aluminum BZ Bronze A2 Aluminum (Thermally-broken) CL Clear CODE Spacer Sealant A3 Aluminum-reinforced Polymer EV Evergreen D Dual Seal Spacer System A4 Aluminum / Wood GD Gold S Single Seal Spacer System A5 Aluminum-reinforced Butyl (Swiggle) GR Green A6 Aluminum / Foam / Aluminum GY Gray CODE Grid Description A7 Aluminum U-shaped LE Low 'e' Coating N No Muntins A8 Aluminum-Butyl (Corrugated) (Duraseal) OT Other (use comment field) G Grids between glass ER EPDM Reinforced Butyl RC Solar or Reflective Coating S Simulated Divided Lites FG Fiberglass RG Roller Shades between glazing T True Muntins GL Glass RS Silver (reflective coating) OF Organic Foam SF Suspended Polyester Film P1 Duralite SR Silver CODE Grid Size Codes PU Polyurethane Foam BG Blinds between the Glazing Blank for no grids SU Stainless Steel, U-shaped DV Dynamic Glazing-Variable 0.75 Grids < 1" CU Coated Steel, U-shaped (Intercept) DY Dynamic Glazing-NonVariable 1.5 Grids >= 1" S2 Steel (Thermally-broken) S3 Steel / Foam / Steel CODE Gap Fill Codes S5 Steel-reinforced Butyl AIR Air CODE Thermal Breaks S6 Steel U-channel w/ Thermal Cap AR2 Argon/Krypton Mixture F Foam SS Stainless Steel AR3 Argon / Krypton / Air U Urethane CS Coated Steel ARG Argon/Air V Vinyl TP Thermo-plastic CO2 Carbon Dioxide FB Fiberglass WD Wood KRY Krypton/Air O Other ZE Elastomeric Silicone Foam SF6 Sulfur Hexaflouride AB ABS ZF Silicone Foam XE2 Xenon/Krypton/Air NE Neoprene ZS Silicone / Steel XE3 Xenon/Argon/Air AI Air N Not Applicable XEN Xenon/Air N Not Applicable TS Thermo-plastic w/ stainless steel substrate N Not Applicable P Polyamide

12 Appendix B: Drawings A