TECHNICAL DATA. A REFERENCE FOR The Electrical Power Industry. www. ElectricalPartManuals. com ANDERSON POWER SYSTEMS, INC.

Size: px
Start display at page:

Download "TECHNICAL DATA. A REFERENCE FOR The Electrical Power Industry. www. ElectricalPartManuals. com ANDERSON POWER SYSTEMS, INC."

Transcription

1 POWER SYSTEMS, INC. TECHNICAL DATA A REFERENCE FOR The Electrical Power Industry ANDERSON www. ElectricalPartManuals. com

2

3 TABLE NUMBER INDEX PAGE NUMBER ANGLES 65 Aluminum Angle Conductors, Physical Properties Aluminum Angle Conductors, Electrical Properties Copper Bus Angles, High Conductivity, Physical and Electrical Properties. 23 ARMOR RODS ALUMINUM 44 Preformed Armor Rods for All-Aluminum Based Conductors, Physical Properties Preformed Alumoweld Armor Rods for Alumoweld Strand, Physical Properties Preformed Cadmium Copper Armor Rods for Copper and Copper Covered Steel-Copper Conductors Preformed Conductor Reference Preformed Copper-Covered Steel Armor Rods for Copper-Covered Steel Strand and Copper Covered Steel-Copper Conductors Preformed Galvanized Steel Armor Rods for ACSR Conductors, Physical Properties Preformed Line-Guards for All-Aluminum Based Conductors, Physical Properties Preformed Line-Guards for All-Aluminum Based Conductors, Physical Properties Straight Armor Rods for ACSR, Physical Properties Straight Armor Rods for Stranded Aluminum Conductors, Physical Properties Tapered Armor Rods for ACSR, Physical Properties Tapered Armor Rods for Stranded Aluminum Conductor, Physical Properties.. 44 BARS RECTANGULAR 58 Aluminum Rectangular Bus Bars, Current Ratings in Amperes Aluminum Rectangular Bus Bars, Physical and Electrical Properties Aluminum Rectangular Bus Bars, Current Ratings in Amperes Copper Rectangular Bus Bars, Current Carrying Capacity in Amperes at 60 Cycles Copper Rectangular Bus Bars, Physical and Electrical Properties 22 CABLES AND WIRES 32 ACSR, Physical and Electrical Characteristics ACSR/AW, Physical Characteristics ACSR, Compresto Conductors, Physical and Electrical Properties ACSR Conductors, Physical Characteristics ACSR Conductors, Extra-High Strength, Physical Characteristics All-Aluminum and ACSR Cable with Armor Rods, Characteristics All-Aluminum Cable, Bare, Physical Characteristics, Class A; AA; AAA All-Aluminum Cable, Bare, Physical Characteristics, Class B and C All-Aluminum, High Strength (AAAC) Conductors, Physical Properties All-Aluminum Compresto Conductors, Physical and Electrical Properties All-Aluminum, Alloy 5005, Conductors, Physical Properties Aluminum Solid Conductor Wire Alumoweld Wire and Strand, Physical and Electrical Characteristics Conversion Chart, Diameters to Conductors and Ultimate Strength Copper Cable, Concentric-Lay-Stranded Dimensions and Strandings Copper Cable, Rope Lay-Stranded Dimensions 8 5 Copper Cable and Wire, Bare, Physical Properties. 9 6 Copper Cable, Bare, Electrical Properties Copper Cable, Bare-Indoors, Current Ratings Copper Cable, Bare-Outdoors, Current Ratings Copper, ACSR, and Aluminum Conductors, Current Ratings, Outdoors, 60 Cycles 28 9 Copperweld Conductors, Physical Properties Copperweld Type M, Guy Strands Copperweld Copper Conductors, Physical Properties Copper Wire, Solid, Dimensions, Ultimates Galvanized Steel Guy Wire, Physical Properties 42 CHANNELS 63 Aluminum Channel Conductors, Physical Properties Aluminum Channel Conductors, Electrical Properties Aluminum Channel Conductors of Uniform Thickness, Physical and Electrical Properties Aluminum Integral Web Channel Conductors, Physical and Electrical Properties Copper Channels, Unventilated, Current Ratings and Physical Properties.. 23 CONDUIT DATA 91 Conduit Elbows, Large Radius Conduit Elbows, Standard Radius Conduit, Locknut Spacing and Clearance. 79 www. ElectricalPartManuals. com

4 TABLE NUMBER PAGE NUMBER 93 Conduit or Tubing, Internal Area Conduit, Rigid Metal Conduit Size for Cable Electrical Metallic Tubing, Weights and Dimensions Number of Conductors in Conduit or Tubing Number of Conductors in Conduit or Tubing Temperature Conversion Chart, Fahrenheit to Centigrade Temperature Conversion Chart, Centigrade to Fahrenheit Thread Dimensions, National Course Series Thread Dimensions, National Fine Series Thread Dimensions, National Special Pitches. 84 Thread Standard System of Marking 84 HOLLOW SQUARE 61 Aluminum Square Tubular Conductors, Physical Properties Aluminum Square Tubular Conductors, Electrical Properties Copper Square Tube, Unventilated, Current Ratings and Physical Properties Copper Square Tube, Ventilated, Current Ratings and Physical Properties 26 TUBING 52 Aluminum Tubular Conductors, ASA, Schedule 40, Physical Properties Aluminum Tubular Conductors, ASA, Schedule 40, Electrical Properties Aluminum Tubular Conductors, ASA, Schedule 80, Physical Properties Aluminum Tubular Conductors, ASA, Schedule 80, Electrical Properties Aluminum Tubular Conductors, Physical Properties Aluminum Tubular Conductors, Electrical Properties Copper Tubular Conductors, Bare, Current Ratings, Indoors, 60 Cycles Copper Tubular Conductors, Bare, Current Ratings, Outdoors, 60 Cycles Copper Tubular Conductors, Physical Properties of Extra-Heavy and Standard Pipe Sizes, High Conductivity, Hard-Drawn15 15 Copper Tube, Type B, Current Ratings and Physical Properties Copper Tube, Type K, Current Ratings and Physical Properties Copper Tube, Type L, Current Ratings and Physical Properties Copper Tube, Type M, Current Ratings and Physical Properties Copper Tubular Conductors, Vertical Deflection in Inches, and Deflection Factors. 20 ELECTRICAL DATA 71 Alternating Current Formulae Amperes in A-C Circuits, Formulae for Determining. 65 Chart Current Carrying Capacity, Approximate Ratio of Outdoor to Indoor Current Carrying Capacities, Relative, Copper, Copper Alloys, and Aluminum Electrolysis Current in Pipe Lines Galvanic Series of Metals Potentials of Metals Properties of Aluminum Alloys Properties of Aluminum and Copper Alloys Properties of Copper Alloys Properties, Physical Constants of Metals Proximity Effect, Correction Factor for Buses Reactance Volts Drop to Neutral 69 Graph Reactance Volts Drop to Neutral. 68 Graph Reactance Volts Drop per Foot of Bus Length, Square and Round Tubular Buses Reactance Spacing Factor, Overhead Line Conductors Resistance and Reactance, Formulae for Combining System Diagrams 65 MECHANICAL DATA Chart Beam Formulae for Horizontal Buses Coefficients of Linear Expansion for Structural and Bus Materials 75 Chart Expansion of Steel, Copper, and Aluminum with Temperature Changes Power Transmission by Shaft.. 75 Chart Shape Correction Factors for Rectangular Copper Bars Short Circuit Forces on Buses, Formulae.. 61 Chart Short Circuit Forces on Buses, Maximum Time to Change Speed of Rotating Mass.. 75 USEFUL DATA Useful Data for Electrical Construction and Maintenance www. ElectricalPartManuals. com

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93 1990 NATIONAL ELECTRICAL CODE* TABLE WIRE & CONDUIT TABLES AMPACITIES OF INSULATED CONDUCTORS RATED VOLTS, BASED ON AMBIENT TEMPERATURE OF 30 C (86 F) RACEWAY OR CABLE OR EARTH TRADE SIZE OF METALLIC CONDUIT OR TUBING BASED ON NEC CHAPTER 9, TABLE 1 FOR 40% FILL AND TABLES 3A, 3B, 3C, 4 & 5B REFER TO NEC CHAPTER 9 FOR MAXIMUM NUMBER OF CONDUCTORS IN TRADE SIZES OF METALLIC CONDUIT OR TUBING. PROPERTIES OF CONDUCTORS MUST AGREE WITH NEC CHAPTER 9 TABLE 8. DIMENSIONS OF INSULATED CONDUCTORS PER NEC CHAPTER 9 (TABLE 5 FOR COPPER TABLE 5A FOR ALUMINUM THW, THHN, XHHW) (UNDERLINE INSULATION TYPE INDICATES DRY AND DAMP LOCATION ONLY RATINGS) THHN IS RATED 90 C IN DRY LOCATION Table Ampacity Insulated COPPER (100 ) 95 (100 ) 100 (110 ) (125 ) 130 (125 ) 130 (150 ) 150 (150 ) 150 (175 ) 170 (175 ) 175 (200 ) 195 (200 ) CU WIRE SIZE AWG kcmil #6 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M 750M 800M 900M 75 C (167 F) THHW, THW RHW, USE Conduit Conduit 3W 3Ø4W CU WIRE SIZE AWG kcmil #14 #12 #10 #8 #6 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M 750M 800M 900M 75 C (167 F) THWN, XHHW Conduit Conduit 3W 3Ø4W C (194 F) FEP(14-2), THHN CU WIRE FEPB(14-8), XHHW SIZE AWG Conduit Conduit kcmil 3W 3Ø4W #14 #12 #10 #8 #8 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M Table Ampacity Insulated ALUMINUM (100 ) 100 (100 ) 100 (110 ) 115 (110 ) 120 (125 ) 135 (125 ) 135 (150 ) 150 (150 ) 155 (175 ) 175 (175 ) 180 (200 ) (200 ) AL WIRE SIZE AWG kcmil 8 #6 #4 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M 750M 75 C (167 F) THHW, USE THW Conduit Conduit 3W 3Ø4W AL WIRE SIZE AWG kcmil #8 #6 #4 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M 750M Conduit Conduit 3W 3Ø4W AL WIRE SIZE AWG kcmil #8 #4 #2 #1 1/0 2/0 3/0 4/0 250M 300M 350M 400M 500M 600M 700M 750M Conduit Conduit 3W 3Ø4W www. ElectricalPartManuals. com 75 C (167 F) XHHW 90 C (194 F) THHN XHHW

94 POWER SYSTEMS, INC. ANDERSON 210 N. Allen St. Centralia, MO USA Phone: Fax: NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Copyright 2003 Hubbell / Anderson Printed in USA AEC-41 Rev A www. ElectricalPartManuals. com

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Engineering Data for Copper and Aluminum Conductor Electrical Cables 2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION

More information

NEC Ampacity Data Table (B)(2)(b) Ambient Temperature Correction Factors Based on 40 C (104 F)

NEC Ampacity Data Table (B)(2)(b) Ambient Temperature Correction Factors Based on 40 C (104 F) 05-01-2018 NEC Ampacity Data Table 310.15(B)(2)(b) Ambient Temperature Crection Facts Based on 40 C (104 F) F ambient temperatures other than 40 C (104 F), multiply the allowable ampacities specified in

More information

ANNEX B: APPLICATION INFORMATION FOR AMPACITY CALCULATION ITEMS B (B)(1) THROUGH B (B)(7)

ANNEX B: APPLICATION INFORMATION FOR AMPACITY CALCULATION ITEMS B (B)(1) THROUGH B (B)(7) ITEMS B.0.5(B)() THROUGH B.0.5(B)(7) B.0.5(B)() EQUATION APPLICATION INFORMATION This informative annex provides application information for ampacities calculated under engineering supervision. B.0.5(B)()

More information

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes.

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes. CHAPTER 35 SERVICES SECTION E3501 GENERAL SERVICES E3501.1 Scope. This chapter covers service conductors and equipment for the control and protection of services and their installation requirements. E3501.2

More information

Power Systems 2 ELE3015. Lecture 1: Transmission Lines

Power Systems 2 ELE3015. Lecture 1: Transmission Lines Power Systems 2 ELE3015 Lecture 1: Transmission Lines Transmission Lines: Introduction Use to carry electrical power from point of generation to the point of use. Usually over large distances. Made with

More information

TEMPORARY METER POLE INSTALLATION

TEMPORARY METER POLE INSTALLATION TEMPARY METER POLE INSTALLATION MEMBER PROVIDED Location to be made by REMC within 50' of our transformer or existing service Temporary pole to be properly braced 24" 3 wire weatherhead (located 24" from

More information

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables PART 1 - GENERAL 1.01 DESIGN REQUIREMENTS A. Scope: Power Conductors and Cables in this section are defined as system voltages above 120V and less than 600V. B. System Voltages Three Phase and Single Phase:

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

Electrical Conductors Line

Electrical Conductors Line Electrical Conductors Line IUSA is present in Mexico, Europe, Asia, the US, Central and South America. Established in 1939. Workforce of over 12,000 employees. Manufacturing facilities established in Mexico

More information

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW THHN/THWN-2/THW/THWN/TW Listed E-492385 / E-472248 APPLICATIONS THHN/THWN-2 building wire is primarily used for general purpose applications in conduit and cable

More information

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

NORMAS DE REFERENCIA AEIC CS 1: ASTM B AEIC CS 1: Especificación para Solid-Type Impregnated-Paper-Insulated Metallic Sheathed AEIC CS2: Especificación para Impregnated-Paper and Laminated Paper- Polypropylene Insulated, High- Pressure Pipe-Type

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

REA LISTED. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products.

REA LISTED. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products. Grounding BURNDY Products E-44 TYPE GRC HIGH STRENGTH GROUND ROD CLAMP For Copper Cable to Rod High copper alloy ground connector for joining a range of cable to copper clad, galvanized steel, and stainless

More information

CHAPTER 13 GROUNDING AND BONDING

CHAPTER 13 GROUNDING AND BONDING GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent

More information

ELECTRICAL DEFINITIONS

ELECTRICAL DEFINITIONS CHAPTER 35 ELECTRICAL DEFINITIONS SECTION E3501 GENERAL E3501.1 Scope. This chapter contains definitions that shall apply only to the electrical requirements of Chapters 34 through 43. Unless otherwise

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Greenbook Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 08-15-17 Rev. #06:

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION The following rules and information are issued to make it possible for anyone engaged in electrical wiring or installation of electrical

More information

ORDINANCE NO NOW, THEREFORE, BE IT ENACTED BY THE CITY COUNCIL OF THE CITY OF FAIRBANKS, ALASKA, as follows:

ORDINANCE NO NOW, THEREFORE, BE IT ENACTED BY THE CITY COUNCIL OF THE CITY OF FAIRBANKS, ALASKA, as follows: Introduced by: Mayor Eberhart Date: May 23, 2016 ORDINANCE NO. 6013 AN ORDINANCE TO AMEND FGC CHAPTER 10, ARTICLE IX NATIONAL ELECTRICAL CODE, BY ADOPTING THE 2014 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

BASIC CONCEPTS IN ELECTRICAL DESIGN. Prepared by Engr. John Paul Timola

BASIC CONCEPTS IN ELECTRICAL DESIGN. Prepared by Engr. John Paul Timola BASIC CONCEPTS IN ELECTRICAL DESIGN Prepared by Engr. John Paul Timola ELECTRICAL CONDUCTORS AND INSULATORS Electrical Conductors substances that offer a very low resistance to current flow. Insulators

More information

Cables ELE E L CT E C R T R IC I C A A L L

Cables ELE E L CT E C R T R IC I C A A L L E LECTRICAL ELECTRICAL Cables July 28, 2009 CONDUMEX INCORPORATED WIRE & CABLE PRODUCT INDEX BUILDING WIRE MTW/THHN/THWN 600 VOLTS COPPER 14 AWG SOLID 750 MCM STRANDED UL 83 XHHW-2 600 VOLTS COPPER 14

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES CONTENTS Page # 100-200 OR 400 AMP

More information

E APPENDIX. The following problems are intended for solution using finite element. Problems for Computer Solution E.1 CHAPTER 3

E APPENDIX. The following problems are intended for solution using finite element. Problems for Computer Solution E.1 CHAPTER 3 E APPENDIX Problems for Computer Solution The following problems are intended for solution using finite element analysis software. In general, the problems associated with Chapters 3, 4, and 9 can be solved

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

Kaf-Tech Product Specification

Kaf-Tech Product Specification Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE

More information

A is for Apple Arbutus B is for Ball Bittern

A is for Apple Arbutus B is for Ball Bittern A is for Apple Arbutus B is for Ball Bittern Manufacturing Standards for North American Bare Overhead Conductors by Gordon Baker General Cable IEEE TP+C Winter Meeting Jan 23, 2006 Albuquerque, NM i:\ieee

More information

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant SSE XHHW-2/RW90 600V WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant and is available in all COLORS in sizes 14 AWG-1000 KCMIL for copper

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

1.05 Power System Fault and Coordination Study with Arc Flash Calculations PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call 811 Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES 4901 East Park 30 Drive P.O.

More information

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

St. Clair County Electrical Code Regulations

St. Clair County Electrical Code Regulations St. Clair County Electrical Code Regulations St. Clair County has adopted the 2011 National Electrical Code as amended with the following listed articles as the St. Clair County version of the National

More information

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways. SECTION 16120 WIRE, CABLE AND BUSWAYS PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies providing wire, cable and busways. B. Definitions: 1. Cable: Cable having low smoke generating characteristics.

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

SHORT CIRCUIT PERFORMANCE TEST ON 1020 kcmil ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

SHORT CIRCUIT PERFORMANCE TEST ON 1020 kcmil ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION To: Mr. Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA SHORT CIRCUIT PERFORMANCE TEST ON 1020 kcmil ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics

More information

ELECTRICAL SECTION 2

ELECTRICAL SECTION 2 ELECTRICAL SECTION 2 COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. This Section includes raceways, conductors and cables, grounding materials, boxes, electrical identification

More information

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

SECTION ELECTRICAL UTILITY SERVICES

SECTION ELECTRICAL UTILITY SERVICES SECTION 33 71 73 ELECTRICAL UTILITY SERVICES PART 1 GENERAL 1.1 REFERENCES A. American Association of State Highway Officials (AASHO): 1. Standard Specifications B. California Administrative Code (CAC):

More information

Article 300: Wiring Methods And Materials

Article 300: Wiring Methods And Materials Part E: Code Book Questions Article 300: Wiring Methods And Materials 1.! Conductors of A.C. or D.C. circuits rated 600 volt or less, shall be permitted to occupy the same! conduit if.! (a)!conductors

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 48-05 Van Dam Street Long Island City, NY 11101 ELECTRIC METER SHOP DEPARTMENT METER ENGINEERING SPECIFICATION MES-350 REVISION 3 June 2016 EFFECTIVE DATE

More information

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES 7.01 GENERAL UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES Also refer to Chapter 3 (Service Entrances), and Chapter 4 (Metering Installation). OPPD will install,

More information

Technical Bulletin #27 Wiring for Architectural Applications

Technical Bulletin #27 Wiring for Architectural Applications 400, du Parc, Saint-Eustache, Québec Canada, J7R 0A1 Tel: +1.450.491.5671 +1.800.665.1166 Fax: +1.450.491.3788 www.heicolighting.com Technical Bulletin #27 Wiring for Architectural Applications WIRE SIZE

More information

15 kv EPR Insulated, Jacketed, URD Cable

15 kv EPR Insulated, Jacketed, URD Cable 15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

Sentron Low Amp Busway

Sentron Low Amp Busway Sentron Low Amp Busway Sentron Low Amp Busway is a member of the Siemens Sentron Busway family. Sentron Low Amp Busway specifically addresses the needs of low amp power distribution applications, with

More information

WIRING METHODS CHAPTER 38

WIRING METHODS CHAPTER 38 CHAPTER 38 WIRING METHODS SECTION E3801 GENERAL REQUIREMENTS E3801.1 Scope. This chapter covers the wiring methods for services, feeders and branch circuits for electrical power and distribution. E3801.2

More information

A. Coordinate arrangement, mounting, and support of electrical equipment:

A. Coordinate arrangement, mounting, and support of electrical equipment: SECTION 260500 -BASIC ELECTRICAL MATERIALS AND METHODS PART 1- GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Electrical equipment coordination and installation. 2. Sleeves for raceways

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 25 05 26 GROUNDING AND BONDING A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS GENERAL NOTES 1. Residential and commercial meter loops are typically used when constructing facilities for permanent service. It is important that all guidelines outlined in this document be followed

More information

Revisions for the 2014 National Electrical Code Part 2

Revisions for the 2014 National Electrical Code Part 2 PDH Course E429 Revisions for the 2014 National Electrical Code Part 2 Patrick S. Ouillette, P.E. 2014 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

CATALOG. WIRE and CABLE. borderstates.com

CATALOG. WIRE and CABLE. borderstates.com 2015 CATALOG WIRE and borderstates.com Table of CONTENTS Building wire... 3 THHN... 5 THW-2...8 TFFN... 9 THHN CoilPAK... 11 THHN PullPro...13 XHHW... 15 NM...18 USE-2/RHW/RHW-2...22 SER...23 SEU...24

More information

Design Standard Conduit for Electrical Systems

Design Standard Conduit for Electrical Systems Design Standard Purpose: This design standard has the purpose of creating a consistent application for the installation of conduits throughout the East Side Union High School District, therefore achieving

More information

ABOUT US. 830 South West Street / Sikeston, MO / F: alanwire.com

ABOUT US. 830 South West Street / Sikeston, MO / F: alanwire.com ABOUT US Alan Wire Company began in 1974 as a small bare copper manufacturer serving the utility and electrical wholesale markets with copper grounding products. Over the last 40 years, the company has

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. We were turned down for an underground installation of

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

SECTION PART 1 GENERAL

SECTION PART 1 GENERAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.

More information

POWER AND LIGHTING DISTRIBUTION Reserved

POWER AND LIGHTING DISTRIBUTION Reserved CHAPTER POWER AND LIGHTING DISTRIBUTION Reserved INTERNATIONAL RESIDENTIAL CODE R This page left intentionally blank. R INTERNATIONAL RESIDENTIAL CODE SECTION E GROUND-FAULT AND ARC-FAULT CIRCUIT-INTERRUPTER

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

E101 ELEC. SPEC. Scale NONE

E101 ELEC. SPEC. Scale NONE General: Execution: It Is the Intent of these documents that a complete and working electrical Installation be provided for all the electrical products described, or shown as being part of this contract.

More information

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SECTION PARK NON-SEGREGATED BUS SPECIFICATION Page 1 of 5 SECTION ------- PARK NON-SEGREGATED BUS SPECIFICATION 1.0 SCOPE 1.1. This specification describes assemblies of 600V, 5Kv and 15Kv non-segregated bus duct, which will be installed indoors and

More information

Increasing the capacity of existing transmission lines by re-conductoring using ACSS HTLS conductors

Increasing the capacity of existing transmission lines by re-conductoring using ACSS HTLS conductors Increasing the capacity of existing transmission lines by re-conductoring using ACSS HTLS conductors Thomas Wilki Director, International Sales & Development Southwire Company ACSS CONDUCTORS - TOPICS

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

Article 324: Flat Conductor Cable (FCC) 1.! Type FCC (flat conductor cable) cable wiring system is designed for installations under.

Article 324: Flat Conductor Cable (FCC) 1.! Type FCC (flat conductor cable) cable wiring system is designed for installations under. Part F: Code Book Questions Article 324: Flat Conductor Cable (FCC) 1.! Type FCC (flat conductor cable) cable wiring system is designed for installations under.! (a) tile! (c) carpet squares! (b) carpet!

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Today s Topics Brief Overview of Southwire In-depth Discussion on Aluminum Characteristics Discussion of

More information

12/21/2018 WHAT S NEW SINCE What's New Since SPEC BOOK 2018 SPEC BOOK 2018 SPEC BOOK WHAT S NEW SINCE 2014

12/21/2018 WHAT S NEW SINCE What's New Since SPEC BOOK 2018 SPEC BOOK 2018 SPEC BOOK WHAT S NEW SINCE 2014 CHAPTER 2 STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS 2545.1B & 2565.1B QUALIFICATION OF WORKERS The provisions of 1802 are hereby supplemented with the following: Signal and Lighting Certification:

More information

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

B. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83. SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Grounding conductors. 2. Grounding connectors. 3. Grounding busbars. 4. Grounding

More information

AGENDA. NEC Code-Making Panel 6. Report on Comment Meeting. December 6 December 8, Redondo Beach, CA

AGENDA. NEC Code-Making Panel 6. Report on Comment Meeting. December 6 December 8, Redondo Beach, CA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 6 Report on Comment Meeting December 6 December

More information

RESIDENTIAL QUICK REFERENCE

RESIDENTIAL QUICK REFERENCE RESIDENTIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

SECTION RACEWAYS AND BOXES FOR ELECTRONIC SAFETY AND SECURITY

SECTION RACEWAYS AND BOXES FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 33 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies the furnishing, installation, and connection of conduit, fittings, and boxes to form complete, coordinated, raceway systems.

More information

SECTION OVERHEAD CONDUCTOR RAIL

SECTION OVERHEAD CONDUCTOR RAIL SECTION 34 23 06 OVERHEAD CONDUCTOR RAIL PART 1 - GENERAL 1.1 DESCRIPTION This Section describes and specifies the performance requirements to design, furnish, install, test, and place into satisfactory

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 05 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Introduction to Substation Design TADP 542

Introduction to Substation Design TADP 542 Introduction to Substation Design TADP 542 Substation Structures- Introduction Instructor: Dr. Yenumula Prasad Transmission & Distribution Program Substation Structures Reference Substation Structure Design

More information

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance. SERVICE ENTRANCES 3.01 POINT OF ENTRANCE General Service The customer, or the customer s electrician, should provide OPPD with a site plan, load schedule, and voltage requirements when requesting service.

More information

TEMPORARY FACILITIES

TEMPORARY FACILITIES MUNICIPAL LIGHT & POWER & CHUGACH ELECTRIC ASSOCIATION ELECTRIC SERVICE REQUIREMENTS EXCERPT TEMPORARY FACILITIES 2015 EDITION Effective August 3, 2015 This is an EXCERPT; the complete book is available

More information

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC). SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.

More information

80M 4-Square. An antenna project to obtain a bigger signal on the 80 Meter (3.5 to 3.8 MHz) amateur radio band. Bruce Whitney W8RA

80M 4-Square. An antenna project to obtain a bigger signal on the 80 Meter (3.5 to 3.8 MHz) amateur radio band. Bruce Whitney W8RA An antenna project to obtain a bigger signal on the 80 Meter (3.5 to 3.8 MHz) amateur radio band Bruce Whitney W8RA The Goal: Convert a vacant back field into 4.2 db of power (directional) gain Switchable

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2008 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE The Contractors Choice the Contractors Choice Founded in 1958, with locations in Tulsa and Broken Arrow, Oklahoma. is part of the Quality Brands of Continental Industries. TABLE OF CONTENTS THE PROCESS...4

More information

POWER AND LIGHTING DISTRIBUTION

POWER AND LIGHTING DISTRIBUTION CHAPTER POWER AND LIGHTING DISTRIBUTION SECTION E RECEPTACLE OUTLETS E. General [.,.]. Outlets for receptacles rated at volts, - and -amperes shall be provided in accordance with Sections E. through E..

More information

Una e mpre sa Vi akab l e GLOSSARY.

Una e mpre sa Vi akab l e GLOSSARY. GLOSSARY www.centelsa.com.co CONDUCTORS Cu Copper conductors. CuSn Tinned copper conductor. ACDSR Rectangular soft bare copper wire. ACDSRP Paper insulated rectangular soft bare copper wire. ACDD Bare

More information

Substation Bus Design: Current Methods Compared with Field Results

Substation Bus Design: Current Methods Compared with Field Results Electrical Transmission and Substation Structures Conference 2009 ASCE 143 Substation Bus Design: Current Methods Compared with Field Results Keith Malmedal Ph.D. P.E. P.Eng. 1 and John Wendelburg P.E.

More information

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE). 6.01 GENERAL OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE See Chapter 3, Section 3.01 for more information about point of entrance (POE). In all cases, the customer installs, owns, and maintains the

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide labor, materials, equipment, and incidentals as shown, specified, and

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

PV Solar Wiring Solutions

PV Solar Wiring Solutions Priority Solar Projects Across the US 14 DISTRIBUTION CENTERS PV Solar Wiring Solutions ON TIME ACCURATE FLEXIBLE SERVICE CUSTOM SOLUTIONS Priority Capabilities: Premier Supplier of Wire & Cable Cut to

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information