Adding glazing as an energy saving renovation measure in cold climates

Similar documents
Johan Stein Building Physics, dept. of Building and Environmental Technology, Lund Institute

Infiltration simulation in a detached house empirical model validation

Extended pilot study of an energy efficient glazed office building during pre-design and design. Åke Blomsterberg (WSP och LTH)

Summer season temperature control in Finnish apartment buildings

This is the published version of a paper presented at CLIMA 2013, Prague, June 16-19,

Simson, Raimo; Fadejev, Jevgeni; Kurnitski, Jarek; Kesti, Jyrki; Lautso, Petteri Assessment of Retrofit Measures for Industrial Halls

LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES

Effect of energy renovation on thermal sensation and comfort

Postprint.

Available online at ScienceDirect. Energy Procedia 96 (2016 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Adaption of the passive house concept in northern Sweden - a case study of performance

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Cost optimal energy efficiency in multifamily houses

Jukka Lahdensivu Tampere University of Technology, Department of Structural Engineering

Study of energy efficient measures a life cycle perspective

ENERGY PERFORMANCE OF DIFFERENT TYPES OF DOUBLE SKIN FACADES IN VARIOUS CLIMATES

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Review of DSF in Sweden

Danish national plans for Nearly Zero Energy Buildings

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

ACTIVE SOLAR SHADING. Dennis Johansson 1,2 1 Swegon, Tomelilla, Sweden 2 Building services, Lund University, Lund, Sweden

171: An urban office designed for the southern Brazilian climate

Is it possible to build near zero energy single family buildings in very cold arctic climate?

The Centre for Sustainable Building (ZUB) * A Case Study

PILOT STUDY: HELLENIC HOTEL

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone

Division of Fluid and Climate Technology, School of Civil and Architectural Engineering, KTH Royal Institute of Technology, Handen-Stockholm, Sweden

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Passive houses for the Northern climate

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

2000 Antwerp, terraced house

4/13 Ministry of the Environment degree

In office buildings, often large windows have been. Total economy of windows and facades in low energy office buildings. Articles

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS

OVERALL PERFORMANCE OF VENTILATED DOUBLE FAÇADES COMPARED TO A STATE OF THE ART SINGLE SKIN FAÇADE

THE IMPACT OF THE SHAPE FACTOR ON FINAL ENERGY DEMAND IN RESIDENTIAL BUILDINGS IN NORDIC CLIMATES

Best Practice Guidelines for Double Skin Facades

Demand controlled ventilation in residential buildings

Achieving energy reduction by applying passive cooling strategies in a hot arid region: a case study of the UAE

Improving Energy Efficiency in Buildings (IEEB) Energy Quarter, Ritaharju Monitoring

Analysis of a plus-energy house for improved building and HVAC system design

Understanding thermal mass

A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey

Performance of EN ISO utilisation factor heat demand calculation method in a cold climate

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y

SIMULATING ENERGY USE IN MULTI-FAMILY DWELLINGS WITH MEASURED, NON CONSTANT HEAT GAINS FROM HOUSEHOLD ELECTRICITY

Simulation and Energy Analysis of Thermal Environment of Unassisted Passive Solar House

Interventions for Ensuring Thermal Comfort Equality in Apartment Buildings

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Tage Møller Architect office building

Passive Houses Worlswide: International Developments

This paper was presented at 12th REHVA World Congress (Clima 2016).

Building Technology Research in Architectural Practice: Lessons Learned from Implementations of Energy-Efficient Advanced Building Technologies

CASE STUDIES - CENTRE FOR SUSTAINABLE BUILDING (ZUB) KASSEL, GERMANY

THERMAL MASS CHAPTER 6. Understanding thermal mass. Seasonal effects of thermal mass

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

Monitoring of Advanced Facades and Environmental Systems

A comparison between four dynamic energy modeling tools for simulation of space heating demand of buildings

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Effect of insulation ground on anti-condensation in rural residence

A STUDY OF WALL SURFACE TEMPERATURE VARIATIONS FOR HOUSING IN MODERATE CLIMATES

THE POTENTIAL OF PREDICTIVE CONTROL IN MINIMIZING THE ELECTRICITY COST IN A HEAT-PUMP HEATED RESIDENTIAL HOUSE

Optimal Design of an Office Building for Low-Primary Energy Requirement and High-Indoor Thermal Comfort Level

ANNUAL ENERGY SIMULATION OF A WHOLE BUILDING

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

UNDERFLOOR HEATING A solution or a problem?

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN

1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7

Concept 9: Exterior refurbishment of wooden frame walls with flex system board insulation

Potential of natural ventilation in shopping centres

Renovation of the Brogården area to Passive Houses

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Optimal design for a dual-airflow window for different climate regions in China

Aalborg Universitet Investigation of Different Configurations of a Ventilated Window to Optimize Both Energy Efficiency and Thermal Comfort

A Solar Wall System Utilized in Rural Houses of Northeast China

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

Work Package 2: Performance of naturally ventilated buildings

ROW - Albertslund, DK

Minimum Energy Consumption 84% energy heating savings*

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

Low energy buildings

Investigation and evaluation of high-rise buildings in IDA ICE

SURNA Grow Facility: Systems Comparison - IEA

TECHNIQUES TO REDUCE THE ENERGY CONSUMPTION IN BUILDING IN HOT ARID REJOIN

USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM. Åke Blomsterberg 1, Tomas Johansson 1.

Available online at ScienceDirect. Energy Procedia 57 (2014 )

Assessing the Effect of Window, its Shape and Shading Devices on the Heating and Cooling Energy Consumption (In the Region of Mashhad City)

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions.

SectIon Energy Effldency

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

Transcription:

Adding glazing as an energy saving renovation measure in cold climates Birgitta Nordquist 1 and Kimmo Hilliaho 2 and Petter Wallentén 3 1 Building Services, Building and Environmental Technology, Lund Institute of Technology, Lund University, Lund, Sweden 2 Service Life Engineering of Structures Group, Structural Engineering Unit, Dept. of Civil Engineering, Tampere University of Technology, Tampere, Finland 3 Building Physics, Building and Environmental Technology, Lund Institute of Technology, Lund University, Lund, Sweden birgitta.nordquist@hvac.lth.se Abstract Adding exterior insulation as an energy saving renovation measure is not always possible for cultural heritage reasons. This study explores the energy saving that can be made if glazing instead is added to a heavy structure as a brick building creating a double skin façade. Extensive measurements have been made in a full-scale building. The building has then been modelled in IDA-ICE and simulations, validated by the measurements, have been made for both an outdoor climate representing the southern part of Sweden, Malmö and for one climate representing the northern part of Finland; Sodankylä. The annual heating energy savings have been calculated for various design combinations; different U-values and for both mechanical exhaust respectively mechanical supply and exhaust ventilation systems. The results show that an energy saving is achieved in the order of 8-38% depending on the design of the building; the glazing and the ventilation system. As both a southern and northern climate of Scandinavia are studied the results indicates how this type of renovation measure would perform in general in this part of the world. Keywords: energy saving, double skin-façade, renovation, brick building, simulations 1 Introduction If the environmental challenges are to be met in terms of reducing the total energy use in the building sector, renovation measures of the existing building stock must be included, since the majority of houses in e.g. 30 years are already built. Knowledge about different technical measures that can be applied is therefore important to retrieve. One possible renovation measure is to add glazing to an existing building. Studies including temperate and hot climates are reported [1], [2], [3]. However as the energy demands for lower energy use are getting stronger it becomes increasingly more relevant to also learn even more about the energy performance of the construction in colder

2 climates. This includes attaining knowledge on how large energy saving that is possible to achieve. This knowledge can contribute to the decision making process when choosing between different energy saving measures to apply in existing buildings. When undertaking several renovation measures on a 1930-ties brick building, situated in a cold climate, adding exterior insulation to the brick façade was first intended. For cultural heritage reasons this was not allowed and the idea of adding glazing to the facades came up. A mechanically supply and exhaust ventilation system with a rotary heat exchanger was also installed. Situated in an area with sustainable renovation goals the building was extensively equipped with temperature, relative humidity and air flow sensors in several points of the building and ventilation system to allow study of the performance to be possible. Double skin facades are extensively studied for double glazing. However adding glazing on heavy structures as brick is not that widely studied especially lacking fieldmeasurements and simulations [4]. This paper will contribute with knowledge about the possible energy savings for full scale buildings to this identified gap by studying this for the 1930-ties brick building. The aim is to attain values of the possible energy saving that can be achieved with this type of renovation measure in cold climates. As a colder climate is in focus calculations should be made for both southern and northern parts of Scandinavia with the aim to cover the borders and thereby most outdoor climates of Scandinavia. This article focuses on the heating period and the possible energy savings for this period of the year. The conditions for the thermal indoor climate and performance during the summer period should also be addressed but is excluded here. It is also limited to the saving in terms of kwh and the cost and monetary consideration is not included. 2 Method 2.1 Description of the building and the installation systems The building envelope consisted of 1 ½ bricks. 8 mm single glazing with a U-value of 5,8 W/m 2 K and double glazing on the top with 2,6 W/m 2 K had been added 0,75 m outside the brick walls on the south, east and west facades. Adding glazing on the north façade was not possible for space reasons and is usually not done due to lack of insolation. The building and the added glazing on the south and east façade can be seen in Figure 1. Different installation systems were installed to address the heating and cooling needs during the year. During the heating season the building was heated with a hydronic radiator system supplied by district heating. The intention was also to pre-heat the outdoor air by letting it pass through the cavity between the old brick façade and the added glazing before passing through the ventilation unit. When the temperature was above 20 C in the cavity the air path was changed so that the outdoor air entered the ventilation unit directly without being pre-heated in the cavity. The outdoor air was then passed through an air intake on the north façade.

3 During the summer season the outdoor air was always passed directly to the ventilation unit. To reduce the possible over-heating in the cavity, several cooling options were installed including a separate ventilation system. A concrete duct had been placed in the ground. Outdoor air entered the duct via a vertical concrete duct situated among trees. A supply fan was located in the vertical duct. The air was intended to be cooled in the ground and then supplied to the bottom of the cavity. A corresponding exhaust fan removed the same amount of air from the cavity via high placed ventilation ducts. It is worth mentioning that the cooled air, with an increased relative humidity due to cooling, is not intended to be supplied to the building. The building was equipped with another ventilation unit previously mentioned. Ventilation windows, which were opened by motors when the cavity temperature exceeded 23 C were placed at the top of the cavity. The air supply rate to the building is 50 l/s fulfilling the Swedish building regulation of 0,35 l/s m 2 floor area for dwellings and the exhaust rate is 53 l/s. The summer air flow through the cooling system of the cavity is designed to be 150 l/s for both supply and exhaust sides. Fig. 1. The studied building located in Sege Park in Malmö, with the added glazing visible on the south and east façade. The inlet pipe to the added concrete duct for the cooling of the cavity can be seen on the left part of the picture. 2.2 Energy calculation An extensive set of sensors for temperature, relative humidity, air flows etc were installed in the building and measurements were performed over in total 2 years. The existing (as designed) building was modelled in IDA-ICE. The IDA-ICE model was validated for winter, spring/autumn respectively summer conditions by these measurements. A detailed description of the model and the measurements are made in [5]. Two locations in Scandinavia, shown in Figure 2, has been studied, Malmö in the southern part of Sweden and Sodankylä in the northern part of Finland. A climate file

4 for the year of 2014 was used for Malmö. The specific year of 2014 was used to make it possible to validate the model with the full-scale measurements which comprised of values attained during 2014. The Sodankylä weather file in the simulations was the test reference year for heating and cooling of buildings in Finland (version 2012). The Finnish test reference year, 2012, is based on the weather logs at Vantaa, Jyväskylä and Sodankylä weather stations from 1980 to 2009. They consist of weather data for twelve months, which have weather conditions close to the long-term climatological average [6]. Fig. 2. The two studied locations; Malmö in Sweden and Sodankylä in Finland. Full year simulations were made and a large amount of parameters were attained. In this paper the energy use for heating has been retrieved and summarized. 3 Results 3.1 Energy saving of renovated building The simulated energy need for heating during the heating season in Malmö are presented in Table 1 for a number of different designs; before renovation and after with various characteristics.

5 Table 1. Need of heating energy and energy saving in percentage of energy need before renovation in Malmö, southern part of Sweden for two types of ventilation systems; exhaust respectively mechanical supply and exhaust system. Case Before energy renovation measures (exhaust ventilation) Exhaust ventilation Annual Heating energy need (kwh) 20 558 - Only glazing, no pre-heating of outdoor air via cavity 18 709 9 % 20ºC 30ºC 50ºC 17 850 13% 17 262 16% 17 124 17% Supply and exhaust ventilation with heat exchanger 16 384 20% Only glazing, no pre-heating of outdoor air via cavity 14 672 29% 20ºC 14 686 29% 30ºC 14 355 30% 50ºC 14 332 30% Energy saving in whole percentage The same design values as in the existing building were applied in the simulations. The set point of changing the path of the outdoor air between pre-heating in the cavity respectively directly to the ventilation unit was in the existing building 20 C. The measurements showed that the air temperature in the cavity can increase above 20 C during the winter depending on among all the insolation [7]. This means that there may exist a heating need also when the outdoor air is not passed via the cavity. The effect of a set point of 30 C and 50 C were therefore also studied. The simulated energy need for heating during the heating season in Sodankylä are presented in Table 2.

6 Table 2. Need of heating energy and energy saving in percentage of energy need before renovation in Sodankylä, northern part of Finland for two types of ventilation systems; exhaust respectively mechanical supply and exhaust system. Case Before energy renovation measures (exhaust ventilation) Annual Heating energy need (kwh) 49 167 - Exhaust ventilation 45 054 8% Only glazing, no pre-heating of outdoor air via cavity 43 467 12% 20ºC 30ºC 50ºC 43 467 12% 43 147 12% 43 080 12% Supply and exhaust ventilation with heat exchanger 40 706 17% Only glazing, no pre-heating of outdoor air via cavity 37 859 23% 20ºC 37 460 24% 30ºC 37 422 24% 50ºC 37 409 24% Energy saving in whole percentage The energy saving in terms of percentages was larger for Malmö. The reductions in terms of kwh was however larger for Sodankylä. The design of the glazing were also changed for the Malmö location to study the effect of double respectively triple glazing as well. This is presented in Table 3.

7 Table 3. Need of heating energy and energy saving in percentage of energy need before renovation in Malmö, southern part of Sweden with improved glazing for two types of ventilation systems; exhaust respectively mechanical supply and exhaust system. Case Before energy renovation measures (exhaust ventilation) Exhaust ventilation Annual Heating energy need (kwh) 20 558 - Only Single glazing, U-value=5,7 W/m 2 K, g=0,82 18 709 9 % Single glazing + pre-heating of outdoor air 17 850 13% Only Double glazing, U-value=2,6 W/m 2 K, g=0,73 17 310 16% Double glazing + pre-heating of outdoor air 16 125 22% Only Triple glazing, U-value=1,7 W/m 2 K, g=0,63 16 642 19% Triple glazing + pre-heating of outdoor air via cavity 15 364 25% Supply and exhaust ventilation with heat exchanger 16 384 20% Only Single glazing 14 672 29% Single glazing + pre-heating of outdoor air 14 686 29% Only Double glazing U-value=2,6 W/m 2 K, g=0,73 13 367 35% Double glazing + pre-heating of outdoor air 13 376 35% Only Triple glazing, U-value=1,7 W/m 2 K, g=0,63 12 766 38% Triple glazing+ pre-heating of outdoor air via cavity 12 728 38% Only Triple glazing, U-value=0,7 W/m 2 K, g=0,24 13 313 35% Triple glazing+ pre-heating of outdoor air via cavity 13 429 35% Energy saving in whole percentage U-value is the heat transfer coefficient for the glazing, the g-value is the solar transmittance of the glazing. The energy saving of the heating energy need was between 8-38% depending on the design. Both the U-value and the g-value and the combination of them have influence on the energy need. 4 Discussion In the existing building the outdoor air is not passed through the cavity when the cavity temperature exceeds 20 C. The increased set point from 20 C to 30 C resulted in somewhat increased energy savings. However increasing further to 50 C was marginal. There will also emerge disadvantages with increasing the supply air temperature for air quality reasons which also must be considered. One specific year was used as a climate file for the Malmö location to allow validation with the full-scale measurements. The year was compared to a normal year for

8 the period of 1999-2010 in [4]. The weather data match each other pretty closely although the radiation level for the monitored year was higher than for the long-term average especially for the summer months. Higher radiation levels could imply overestimated energy saving during the winter period and increased over-heating during the summer time. This paper focuses on the heating period and during the months of October-April the deviation is small except for April. So except for April the used whether file should not imply a significant difference from normal conditions for the Malmö location. The assessment is therefore made that the studied data represent normal conditions. The cost and profitability has not been studied. This depends on a number of parameters such as: energy price, political decisions as subsidies for energy saving renovations, future energy demands and also the condition of the building and cultural heritage aspects. These parameters will vary depending on the conditions and prerequisites that are valid for each object. The level of deterioration of a brick façade and needed measures to repair and subsequent costs for this will affect the economic considerations when choosing between different renovation measures. If the brick façade has deteriorated and something needs to be done to repair it, the studied solution might be an alternative which will stop further deterioration and protect the façade in the future. The intention of this study was to contribute with levels of possible energy savings for this type of renovation. This can constitute a part of the input to the profitability calculation the designer makes. Conclusions The conclusion can be drawn that the calculated energy saving is in the span of 8-38% depending on the chosen type of glazing. For the existing glazing design the energy reduction is 9-30% compared to before the renovation in the southern part of Sweden (Malmö) and 8-24 % in the northern part of Finland (Sodankylä). The saving is about 3000-6000 kwh in southern Sweden and about 6000-12 000 kwh in northern Finland for the existing glazing design. As both a southern and northern outdoor climate of Scandinavia is studied the results indicates how this type of renovation measure would perform in general in this cold part of the world. The simulation results indicates that energy savings are possible to make which makes this construction worth considering when exploring different options. 5 Acknowledgements The Swedish Energy Agency and Tampere University are acknowledged for financing the study. The study is also a result of a co-operation between the Tampere University

9 in Finland and Lund University in Sweden. The city of Malmö is gratefully acknowledged for allowing the analysis to be made, for supplying the measurement data, and for undertaking and financing the renovation including the measurement equipment. References 1. Wong P. Natural ventilation in Double-Skin façade Design for Office Building on Hot and Humid Climate, University of New South Wales, Australia, (2008). 2. Ghaffarianhoseini A., Ghaffarianhoseini A., Berardi U., Tookey J., Hin Wa Li D., Kariminia S. Exploring the advantages and challenges of double-skin facades (DSFs), Renewable and Sustainable Energy Reviews 60 (2016) 1052-1065, Elsevier. (2016) 3. Wang Y., Chen Y., Zhou J. Dynamic modeling of ventilated double skin façade in hot summer and cold winter zone in China. Building and Environment 106 (2016) 365-377. Elsevier (2016). 4. Hilliaho K. Energy Saving Potential and Interior Temperatures of Glazed Spaces Evaluation through Measurements and Simulations. PhD thesis. Tampere University of Technology, Tampere (2017). 5. Hilliaho K., Nordquist B.; Wallentén P. Energy saving and indoor climate effects of an added glazed façade to a brick wall building: Case study. Journal of Building Engineering 7 (2016) 246-262 (2016). 6. K. Jylhä, T. Kalamees, H. Tietäväinen, K. Ruosteenoja, J. Jokisalo, R. Hyvönen, S. Ilomets, S. Saku, A. Hutila, Test reference year 2012 for building energy demand and impacts of climate change, Reports 2011:6, Finnish meteorological Institute, Helsinki, 2011, 112 p. (in Finnish). 7. Avgenakis G. Inglasning av tegelfasad, Energianalys samt fältstudie på ett flerbostadshus och på Byggnad 22. Report TVIT-5059, in Swedish, Avd. för Installationsteknik, Lund University, (2017).