CERTIFICATE OF ANALYSIS REVISED REPORT

Similar documents
Transcription:

Your C.O.C. #: XXXXXXXX Attention: 23 MAIN ST, CITY, PROVIE COUNTRY POSTAL CODE Report Date: 5/09/7 Report #: XXXXXXXX Version: 2 - Revision MAXXAM JOB #: XXXXXXX Received: 5/09/03, 5:9 Sample Matrix: Water # Samples Received: CERTIFICATE OF ANALYSIS REVISED REPORT Time the sample was received at lab. Date Date Analyses Quantity Extracted Analyzed Laboratory Method Analytical Method Alkalinity - Water Anions in Water by Ion Chromatography (, 2) True Colour (Single Wavelength) () Conductance - water Hardness Total (calculated as CaCO3) Mercury (Total) by CVAF Na, K, Ca, Mg, S by CRC ICPMS (total) Elements by CRC ICPMS (total) Nitrate + Nitrite (N) (calculated) () ph Water (3) Total Dissolved Solids (Filt. Residue) () Total coliform and E. by MF (Chromocult) () Turbidity () 5/09/08 5/09/09 BBY6SOP-00026 N/A N/A N/A N/A 5/09/04 VIC SOP-000 5/09/04 VIC SOP-0000 5/09/09 BBY6SOP-00026 5/09/4 BBY7SOP-00002 5/09/09 5/09/0 BBY7SOP-0005 N/A 5/09/4 BBY7SOP-00002 N/A 5/09/3 BBY7SOP-00002 N/A 5/09/0 VIC-SOP-00005 N/A 5/09/09 BBY6SOP-00026 N/A 5/09/09 VIC SOP-00008 N/A 5/09/03 VIC SOP 002 N/A 5/09/04 VIC SOP-000 SM 22 23 B m Based on SM-40B Based on SM-2 C SM 22 250 B m EPA 60a R m BCMOE BCLM Oct3 m EPA 60A R m EPA 60A R m Based SM-4500 NO2 E SM 22 4500-H+ B m Based on SM 2540C Based on SM-9222 Based on SM - 230 * RPDs calculated using raw data. The rounding offinal results may resul n the apparent difference. () This test was performed by Maxxam Victoria (2) Anions in Water by Ion Chromatography: The samples were received and analyzed in Maxxam Victoria. The data was processed and approved in Maxxam Burnaby. (3) The BC-MOE and APHA Standard Method require ph to be analysed within 5 minutes of sampling and therefore field analysis is required for compliance. All Laboratory ph n Key This page describes the type was done and does not relate to your results. Please direct all regarding this of Analysis to your Project Manager., Project Manager Email: EXAMPLE@maxxam.ca Phone# (XXX) XXX-XXXX ==================================================================== Maxxam has procedures in place to guard against improper use of the electronic signature and have the required "signatories", as per signing the reports. For Service Group please refer to the Signature Page. 5.0.2 of ISO/IEC 7025:05(E), Total Cover Pages : Page of 8

Report Date: 5/09/7 Maxxam ID Sampling Date COC Number CONVENTIONALS This is the time and date you took your sample as recorded on your COC. RESULTS OF CHEMICAL ANALYSES OF WATER NB2706 5/09/03 08:5 WI000354 UNITS MAC AO OG WELL WATER RDL QC Batch This is the sample ID you provided on your COC. Dissolved Nitrate (N) mg/l 0 - -.38 0.00 8028263 Dissolved Nitrite (N) mg/l - - 0.03 0.00 8028263 This column Misc. Inorganics shows the Dissolved Chloride (Cl) sensitivity of mg/l - 250-5.59 0.50 8028263 the test. Dissolved Fluoride (F) mg/l.5 - - 0.098 0.00 8028263 Dissolved Sulphate (SO4) mg/l - 500-8.6 0.50 8028263 Alkalinity (Total as CaCO3) mg/l - - - 2 0.50 80329 Alkalinity (PP as CaCO3) mg/l - - - <0.50 0.50 80329 Bicarbonate (HCO3) mg/l - - - 36 0.50 80329 Carbonate (CO3) mg/l - - - <0.50 0.50 80329 Hydroxide (OH) mg/l - - - <0.50 0.50 80329 MISCELLANEOUS True Colour Col. Unit - 5-0 5 8033368 Nutrients Nitrate plus Nitrite (N) mg/l - - -.4 0.00 8028247 Physical Properties us/cm - - - 280.0 803293 ph ph - 6.5:8.5-7.96 N/A 803292 Physical Properties Total Dissolved Solids mg/l - 500-53 0 803926 Turbidity NTU see remark see remark see remark 6.0 0. 8030597 N/A = Not Applicable These columns contain the Canadian Drinking Water Guidelines. Your results should be less or within the guideline. These are your results Page 2 of 8

Report Date: 5/09/7 MICROBIOLOGY (WATER) Maxxam ID Sampling Date COC Number NB2706 5/09/03 08:5 WI000354 UNITS MAC WELL WATER RDL QC Batch Microbiological Param. Total Coliforms CFU/00mL < *SEE NOTE () 802870 E. coli CFU/00mL < 230 802870 RDL = Reportable Detection Limit () Due to confluent growth a calculated estimate of >2800 cfu/00ml is given. MAC stands for Maximum Acceptable Concentration. MAC guidelines have health implications. In this example, both the E. Coli and Total Coliform exceed the MAC. More information about this guideline can be found on the Canadian Drinking Water Guidelines website. Page 3 of 8 Maxxam Analytics International Corporation o/a Maxxam Analytics Burnaby: 4606 Canada Way V5G K5 Telephone(604) 734-7276 Fax(604) 73-2386

Report Date: 5/09/7 TOT. METALS W/ CV HG FOR DRINKING WATER (WATER) Results that exceed the are shaded in grey. Maxxam ID Sampling Date COC Number Calculated Parameters NB2706 5/09/03 08:5 WI000354 UNITS MAC AO OG WELL WATER RDL QC Batch Total Hardness (CaCO3) mg/l - - - 7 0.50 802746 Results that Elements exceed the MAC are in bold. Total Mercury (Hg) - - <0.00 0.00 8032282 Total Metals by ICPMS Total Aluminum (Al) - - 00 268 3.0 803289 6 - - <0.50 0.50 803289 Total Arsenic (As) 0 - - 0.0 803289 Total Barium (Ba) 000 - - 3.9.0 803289 Total Beryllium (Be) - - - <0.0 0.0 803289 Total Bismuth (Bi) - - - <.0.0 803289 Total Boron (B) 5000 - - <50 50 803289 Total Cadmium (Cd) 5 - - 0.024 0.00 803289 Total Chromium (Cr) 50 - - <.0.0 803289 Total Cobalt (Co) - - - <0.50 0.50 803289 Total Copper (Cu) - 000-2.90 0. 803289 Total Iron (Fe) - 300-324 5.0 803289 Total Lead (Pb) 0 - - <0. 0. 803289 Total Manganese (Mn) - 50-47.3.0 803289 Total Molybdenum (Mo) - - - <.0.0 803289 Total Nickel (Ni) - - - 2.2.0 803289 Total Selenium (Se) 50 - - 0.3 0.0 803289 Total Silicon (Si) - - - 7950 00 803289 Total Silver (Ag) - - - <0.0 0.0 803289 - - - 306.0 803289 Total Thallium (Tl) - - - <0.050 0.050 803289 Total Tin (Sn) - - - <5.0 5.0 803289 Total Titanium (Ti) - - - 9.7 5.0 803289 Total Uranium (U) - - <0.0 0.0 803289 Total Vanadium (V) - - - <5.0 5.0 803289 Total Zinc (Zn) - 5000 - <5.0 5.0 803289 Total Zirconium (Zr) - - - <0.50 0.50 803289 Total Calcium (Ca) mg/l - - - 36.3 0.050 8028295 Total Magnesium (Mg) mg/l - - - 6.47 0.050 8028295 Total Potassium (K) mg/l - - -.23 0.050 8028295 Total Sodium (Na) mg/l - 0-3.3 0.050 8028295 Total Sulphur (S) mg/l - - - 6.3 3.0 8028295 Page 4 of 8

Report Date: 5/09/7 GENERAL COMMENTS REVISED REPORT (Version 2): Canadian Drinking Water guideliens added for ease of report interpretation. DN3 MAC,AO,OG: The guidelines that have been included in this report have been taken from the Canadian Drinking Water Quality Summary Table, October 4. Criteria A = Maximum Acceptable Concentration (MAC) / Criteria B = Aesthetic Objectives (AO) / Criteria C = Operational Guidance Values (OG) It is recommended to consult these guidelines when interpreting your data since there are non-numerical guidelines that are not included on this report. Turbidity Guidelines:. Chemically assisted filtration: less than or equal to 0.3 NTU in 95% of the measurements or 95% of the time each month. Shall not exceed.0 NTU at any time. 2. Slow sand / diatomaceous earth filtration: less than or equal to.0 NTU in 95% of the measurements or 95% of the time each month. Shall not exceed 3.0 NTU at any time. 3. Membrane filtration: less than or equal to 0. NTU in 99% of the measurements made or at least 99% of the time each calendar month. Shall not exceed 0.3 NTU at any time. Results relate only to the items tested. Page 5 of 8 Maxxam Analytics International Corporation o/a Maxxam Analytics Burnaby: 4606 Canada Way V5G K5 Telephone(604) 734-7276 Fax(604) 73-2386

Report Date: 5/09/7 These pages do not contain your results, but show that the tests and instruments are performing within acceptable limits. QUALITY ASSURAE REPORT Matrix Spike Spiked Blank Method Blank RPD QC Batch Parameter Date % Recovery QC Limits % Recovery QC Limits Value UNITS Value (%) QC Limits 8028263 Dissolved Chloride (Cl) 5/09/04 99 <0.50 mg/l 8028263 Dissolved Fluoride (F) 5/09/04 02 <0.00 mg/l 8028263 Dissolved Nitrate (N) 5/09/04 9 <0.00 mg/l 8028263 Dissolved Nitrite (N) 5/09/04 0 <0.00 mg/l 8028263 Dissolved Sulphate (SO4) 5/09/04 00 <0.50 mg/l 802870 E. coli 5/09/03 N/A 802870 Total Coliforms 5/09/03 N/A 8030597 Turbidity 5/09/04 98 <0. NTU 0 80329 Alkalinity (PP as CaCO3) 5/09/09 <0.50 mg/l 80329 Alkalinity (Total as CaCO3) 5/09/09 93 <0.50 mg/l 0.98 80329 Bicarbonate (HCO3) 5/09/09 <0.50 mg/l 0.98 80329 Carbonate (CO3) 5/09/09 <0.50 mg/l 80329 Hydroxide (OH) 5/09/09 <0.50 mg/l 803292 ph 5/09/09 02 97-03 0.75 N/A 803293 Conductivity 5/09/09 98.7, RDL=.0 us/cm 0.5 803926 Total Dissolved Solids 5/09/0 83 <0 mg/l 9.8 803289 Total Aluminum (Al) 5/09/3 09 <3.0.0 803289 Total Antimony (Sb) 5/09/3 00 98 <0.50 803289 Total Arsenic (As) 5/09/3 02 03 <0.0 2.2 803289 Total Barium (Ba) 5/09/3 33 () 03 <.0 803289 Total Beryllium (Be) 5/09/3 06 04 <0.0 803289 Total Bismuth (Bi) 5/09/3 90 97 <.0 803289 Total Boron (B) 5/09/3 <50 803289 Total Cadmium (Cd) 5/09/3 93 97 <0.00 803289 Total Chromium (Cr) 5/09/3 95 94 <.0 803289 Total Cobalt (Co) 5/09/3 88 95 <0.50 803289 Total Copper (Cu) 5/09/3 89 94 <0. 6. 803289 Total Iron (Fe) 5/09/3 00 <5.0 0.42 803289 Total Lead (Pb) 5/09/3 90 93 <0. 803289 Total Manganese (Mn) 5/09/3 95 <.0 0.55 803289 Total Molybdenum (Mo) 5/09/3 03 <.0 803289 Total Nickel (Ni) 5/09/3 88 94 <.0 Page 6 of 8 Maxxam Analytics International Corporation o/a Maxxam Analytics Burnaby: 4606 Canada Way V5G K5 Telephone(604) 734-7276 Fax(604) 73-2386

Report Date: 5/09/7 QUALITY ASSURAE REPORT(CONT'D) QC Batch 803289 803289 803289 803289 803289 803289 803289 803289 803289 803289 803289 8032282 8033368 Parameter N/A = Not Applicable Total Selenium (Se) Total Silicon (Si) Total Silver (Ag) Total Strontium (Sr) Total Thallium (Tl) Total Tin (Sn) Total Titanium (Ti) Total Uranium (U) Total Vanadium (V) Total Zinc (Zn) Total Zirconium (Zr) Total Mercury (Hg) True Colour Date 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/3 5/09/0 5/09/04 % Recovery 9 94 9 97 90 03 86 Matrix Spike QC Limits Duplicate: Paired analysis of a separate portion of the same sample. Used to evaluate the variance in the measurement. % Recovery 96 96 95 95 97 Spiked Blank Matrix Spike: A sample to which a known amount of the analyte of interest has been added. Used to evaluate sample matrix interference. 97 03 90 99 93 99 QC Limits Method Blank Spiked Blank: A blank matrix sample to which a known amount of the analyte, usually from a second source, has been added. Used to evaluate method accuracy. Method Blank: A blank matrix containing all reagents used in the analytical procedure. Used to identify laboratory contamination. (Matrix Spike): The recovery in the matrix spike was not calculated. The relative difference between the concentration in the parent sample and the spiked amount was too small to permit a reliable recovery calculation (matrix spike concentration was less than 2x that of the native sample concentration). Value <0.0 <00 <0.0 <.0 <0.050 <5.0 <5.0 <0.0 <5.0 <5.0 UNITS Value (%) (Duplicate RPD): The duplicate RPD was not calculated. The concentration in the sample and/or duplicate was too low to permit a reliable RPD calculation (one or both samples < 5x RDL). () Recovery or RPD for this parameter is outside control limits. The overall quality control for this analysis meets acceptability criteria. (2) Due to confluent growth a calculated estimate of >2800 cfu/00ml is given. 04 <0.50 <0.00 <5 Col. Unit 0.5 0.022 8. RPD QC Limits 0 Page 7 of 8 Maxxam Analytics International Corporation o/a Maxxam Analytics Burnaby: 4606 Canada Way V5G K5 Telephone(604) 734-7276 Fax(604) 73-2386

Report Date: 5/09/7 VALIDATION SIGNATURE PAGE The analytical data and all QC contained in this report were reviewed and validated by the following individual(s). FIRSTNAME LAST NAME, TITLE Maxxam has procedures in place to guard against improper use of the electronic signature and have the required "signatories", as per section 5.0.2 of ISO/IEC 7025:05(E), signing the reports. For Service Group specific validation please refer to the Validation Signature Page. Page 8 of 8 Maxxam Analytics International Corporation o/a Maxxam Analytics Burnaby: 4606 Canada Way V5G K5 Telephone(604) 734-7276 Fax(604) 73-2386