UL 1715 TESTING FOR DURABLIS ON JETBOARD WITH ELFOAM P200 AND MAGNUM BOARD WITH ELFORM P200 VTEC # TESTED: MARCH 11, 2015

Similar documents
Transcription:

UL 1715 TESTING FOR DURABLIS ON JETBOARD WITH ELFOAM P200 AND MAGNUM BOARD WITH ELFORM P200 VTEC #100-4738-3 TESTED: MARCH 11, 2015

V T E C L a b o r a t o r i e s I n c. March 13, 2015 Client: Attn: DuraBlis 39 Maple Place, Unit A Amityville, NY 11701 Jamie Hernandez Subject: UL 1715 Fire Test of Interior Finish Material Material Four 4ft x 8ft Jetboard with Elfoam p200 and Magnum board with Elform p200 Wall Panel were placed over the cement board on the left corner opposite the door of the test room, two panels on each adjacent wall. The panels were fastened to wall framing using drywall screws. 212 Manida Street, Bronx, New York 10474 Tel 718-542-8248 Fax 718-542-8759

VTEC# 100-4738-3 DURABLIS UL 1715 Ignition Source The ignition source was a 15-inch cube crib with a weight of 30 lbs built according to Section 4.1 of UL 1715. The crib was placed on four blocks to allow a height of 3 inches off the ground, and was placed 1 inch from adjacent walls. One pound of shredded, fluffed wood excelsior was used as starter material and placed around the bricks covering an area of approximately 21 inches by 21 inches. The wood excelsior was soaked with 0.12 liters of ethyl alcohol, except for a triangular area approximately 6 inches by 6 inches. A torch was used to ignite the dry wood excelsior. Fire Test Room The fire test room is 8ft wide by 8ft high by 12ft deep constructed of concrete blocks. The room is inside a draft free heated building. The doorway is located in the 8ft by 8ft wall. The interior of the block room is framed with metal studs. The wall opposite the door and 8ft of the adjacent wall was made up of ¼ thick cement board. The rest of the walls were made up of 5/8 thick gypsum board. The wall test area consisted of wall sections 8 feet square intersecting at the corner opposite the doorway. Instrumentation Thermocouples 1: Thermocouples 2: Thermocouples 3: Thermocouples 4: Thermocouples 5: Thermocouples 6: Thermocouples 7: Thermocouples 8: Thermocouples 9: 1 inch below the ceiling and 4 feet from both intersecting sample walls. 60 inches below the ceiling and 3 feet from 36 inches below the ceiling and 3 feet from 12 inches below the ceiling and 3 feet from 1 inch below the ceiling and 3 feet from both intersecting sample walls. 1 inch below the ceiling, 4 feet from the back wall and 3 feet from the side wall. 3 feet below the ceiling, 4 feet from the back wall and 3 inches from the side wall. 1 inch below the ceiling, 8 feet from the back wall and 3 inches from the side wall. Centered in the interior plane of the door opening 1 inch below the top of the opening. 3

VTEC# 100-4738-3 DURABLIS UL 1715 Performance Criteria 1. During the test the observed surface burning shall not extend to the outer extremities of the test specimen nor shall flame project through the doorway opening at any time. 2. At the conclusion of the test, observations shall show that the combustive damage, such as burning and charring, of the test materials within the assembly diminishes at increasing distance from the immediate fire exposure area. Results The measured room conditions before the test were 61ºF and 65% humidity. Excessive smoke was not emitted by the burning sample. After 15 minutes the crib was extinguished and posttest observations were made on the wall panel. During the test, there were no flames through the doorway and there was no burning to the outer extremities of the test specimen. Charring diminished from the exposure area to the outer extremities of the test specimen. The test data is contained on the following pages. Conclusions The Jetboard with Elfoam p200 and Magnum board with Elform p200 Wall Panel met the Conditions of UL 1715. Neil Schultz Executive Director Amirudin Rahim Technical Director Disclaimer This is a factual report of the results obtained from the laboratory test of sample products. The results may be applied only to the products tested and should not be construed as applicable to other similar products of the manufacturer. The report is not a recommendation or disapprobation by VTEC Laboratories Inc., of the material tested. While this report may be used for obtaining product acceptance, it may not be used in advertising. NOTICE: VTEC Laboratories Inc., will not be liable for any loss or damage resulting from the use of the data in this report, in excess of the invoice. This report pertains to the sample tested only. Such report shall not be interpreted to be a warranty, either expressed or implied as to the suitability or fitness of said sample for such uses or applications, as the party contracting for the report may apply such sample. 4

VTEC #100-4738-3 DURABLIS UL 1715 Time T/C 1 T/C 2 T/C 3 T/C 4 T/C 5 T/C 6 T/C 7 T/C 8 T/C 9 (mins.) deg C deg C deg C deg C deg C deg C deg C deg C deg C 0.0 16 17 17 17 17 16 16 16 17 0.5 21 654 317 140 163 15 16 70 56 1.0 22 739 488 269 331 17 16 134 112 1.5 27 677 67 370 428 20 17 210 187 2.0 35 650 93 391 446 24 17 243 214 2.5 38 671 119 396 342 26 17 253 217 3.0 44 546 142 382 324 28 18 235 212 3.5 48 568 161 360 186 30 18 235 206 4.0 51 564 178 382 192 31 19 231 204 4.5 53 590 193 405 177 31 19 221 201 5.0 55 617 210 463 348 31 20 216 200 5.5 56 647 225 485 357 30 20 216 201 6.0 57 698 239 509 375 30 21 222 202 6.5 61 796 254 551 413 34 21 224 213 7.0 65 883 278 566 444 41 21 233 215 7.5 69 936 299 507 468 53 22 235 207 8.0 72 967 318 523 494 69 22 238 214 8.5 74 962 336 562 741 135 23 251 221 9.0 75 964 361 576 688 180 23 245 225 9.5 75 984 385 619 571 162 24 239 217 10.0 75 998 399 566 553 242 24 249 218 10.5 75 1025 410 550 561 237 24 240 216 11.0 76 1038 411 522 547 241 25 225 201 11.5 75 1024 300 492 524 245 25 214 195 12.0 73 985 249 465 502 254 25 209 189 12.5 70 952 252 450 487 250 25 201 181 13.0 69 907 256 443 483 254 25 190 173 13.5 67 847 248 426 461 253 25 183 167 14.0 64 758 250 402 427 256 25 179 161 14.5 63 684 253 381 401 260 25 176 156 15.0 61 590 253 365 381 262 25 163 144 5