Test 1 Non Cyclonic Testing of 0.42mm BMT KlipLok Classic 700 (Lysaght) Roof Sheeting with 75mm Spacer and 100mm Insulation

Similar documents
ROOFING & SHEET METAL MANUFACTURERS

Nutex Coatings. Nuclad Cladding System Grade-M EPS Foam Board Structural Test Report AS1562.1:1992 Region N2 Non-Cyclonic

IAN BENNIE AND ASSOCIATES TEST REPORT NO R1 EVERBRIGHT E610 CLEAR POLYCARBONATE CLADDING SYSTEM. IMPACT TESTS to AS

CEILING DIAPHRAGM ACTIONS IN COLD FORMED STEEL- FRAMED DOMESTIC STRUCTURES

Stramit Patio Roofing Cyclonic Span Tables

DANPALON POLYCARBONATE ROOF AND WALL SHEETING SYSTEMS

TECHNICAL NOTE No.5 Cyclic Testing of Solar Panels

Cyclonic Area. Design Manual. Using TOPSPAN profiles and LYSAGHT roofing and walling claddings in cyclonic areas

SECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.

XIAMEN MIBET NEW ENERGY CO., LTD. SOLAR PANEL SUPPORT FRAME ADJUSTABLE TRIPOD MOUNTING SYSTEM FOR CONCRETE AND METAL ROOF

ROOFING & SHEET METAL MANUFACTURERS

The development of generic span tables for cold formed steel studs in residential and low-rise construction

Pull-Through Failure Tests of Thin Steel Roof Battens under Wind Uplift Loads

Klip-lok Classic 700. Concealed-fixed steel cladding

TOPSPAN 61 / 120 LYSAGHT TOPSPAN 61 / 120. Light steel sections.

steel stud drywall ceiling systems

Insuliner. Insulation REFLECTIVE INSULATION FOR USE WHERE

Australian Standard. The design and installation of corrugated fibre-reinforced cement roofing and wall cladding AS

METLOK 700 DESIGN & INSTALLATION GUIDE CONCEALED FIX ROOF SYSTEM. A Met-TECH GUIDE

METLOK 700 DESIGN & INSTALLATION GUIDE CONCEALED FIX ROOF SYSTEM. A Met-TECH GUIDE

KLIP-LOK 406 DESIGN AND INSTALLATION GUIDE

Cyclone Testing Station

Guideline for the erection of Supaloc Steel Trusses Pre- Delivery preparation by the supplier Installing Supaloc Steel roof trusses...

N1 to N3. DuraGalPlus Domestic Construction Manual. Volume 3: DuraGalPlus RHS as floor beams (bearers)

Buckling Experiments on Hollow Flange Beams with Web Stiffeners

SAFEBRIDGE HIGH PERFORMANCE ROOF INSULATION SYSTEM

DIMOND STYLELINE, HI FIVE AND VEEDEK PROFILE PERFORMANCE

UL Design System HW-D-1012 continued

ML200 Panel Technical Data Guide

Stone and Masonry Veneer

EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS

SL175 Panel Technical Data Guide

National Construction Code Series (NCC 2012) Building Code of Australia (BCA)

FIRMLOK FLOORING SYSTEM DESIGN AND INSTALLATION MANUAL

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne

QUALITY CONTROL TESTING OF PLASTERBOARD FOR BRACING APPLICATIONS. Y L Liew Vicroads Victoria, Australia

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

STRUCTURAL DESIGN CERTIFICATE No: CSM SC Job No: 14S 391

Lysaght Klip-lok Maxima Concealed-fixed deck with extra wide coverage. Klip-lok Maxima Available in WA only.

NON-CYCLONIC ENGINEERING SPAN TABLES FOR THERM-LOC AND THERM-FLAM INSULATED PANELS

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

CBUCK Engineering. Evaluation Report Zee-Lock Panel With Continous Zee-Rib Clip Metal Roof Assembly

AS/NZS 4505:1998 AS/NZS

TRIMDEK Subtle Square Fluted Steel Cladding

PARTITION PERFORMANCE AUTOCLAVED LIGHTWEIGHT CONCRETE (ALC) WALL PANEL

KLIP-LOK 770. Profile. Figure 1. Clip

TECHNICAL NOTE No.4 Simulated Windborne Debris Impact Testing of Building Envelope Components (Version 4 Published 10 January 2017)

Superwall / Hydrowall System

1 Introduction Structural Concept Recommended Clip Spacing & Fastener Data... 5

Likely fire performance of a loadbearing framed wall system lined with FireCrunch MBE-10 boards with cavity insulation

KLIP-LOK 700. roof to the eave, but also helps to make it a leak-proof structure with better control over quality installation.

Carter Fabricating Inc. 326 Deerhurst Drive Brampton, Ontario L6T 5H9. Mr. Mike Libreiro

ever before. The smaller number of clips for a given area provides extra economy.

rondo accessories CONTENTS:

MetecnoPanel Information Guide

EVALUATION OF DIZAL INC

range of colours in COLORBOND factory pre-painted steel and in unpainted

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

inspirational architectural façades

SMALL-SCALE FIRE RESISTANCE PROPERTIES SANS : ZINCAL COATED COLORPLUS

TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS

At last! Construction bracing made easy...

ARCADIA ZEST SUN BLADE SYSTEM 2017 ARCADIA GLOBAL PTY. LTD.

klip-lok 700 HI-STRENGTH

Pull-through Failures of Crest-fixed Steel Claddings Initiated by Transverse Splitting

Shear tests of hollow flange channel beams with stiffened web openings

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

Scope. resistance expressed as a moment

Australian Standard. Design and installation of sheet roof and wall cladding. Part 3: Plastic AS AS

LABORATORY TEST REPORT

TOP HATS > REVEAL BEADS > ANGLES > SPEEDPANEL > TOOLS

CBUCK Engineering. Evaluation Report FW-1025 Panel with Optional Seamlock Metal Roof Assembly

130mm CROATIA BOARD 180mm V-GROOVE

GA GYPSUM BOARD TYPICAL MECHANICAL AND PHYSICAL PROPERTIES

Peer Industries Façade System

Dynamic Time-history Analysis on Wind-induced Response of Light-weight Roof System

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

E-Beam HD. Cold-Formed Insulated Composite Structural Elements. Engineering/Analysis Report

BOXSPAN RESIDENTIAL SPAN TABLES

MetecnoSpan Standard Construction Drawings TEK SCREWS AND WASHERS TO EVERY RIB. ADDITIONAL FIIXINGS MAY BE REQUIRED, REFER ENGINEER FOR ASSESSMENT.

SECURE. UNIVERSAL. MOUNTING. Tilt Kit Installation Manual

TEST REPORT ON. TESTED FOR: Metal Roofing Systems, Inc Mikron Drive Stanley, NC Telephone: (704) FAX: (704)

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

Klip-lok 700 Hi-Strength

ASHGRID ROOF SPACER. Insulation Product Selector NOW AVAILABLE WITH PRE-LOADED SCREWS

THIS TO CERTIFY THAT. Firetek Panel. Structure - Structural Reliability

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

PRODUCT GUIDE AVAILABLE WITH PRE-LOADED SCREWS

NZS :2008. Glazing in buildings NZS :2008. Part 4: Wind, dead, snow, and live actions. New Zealand Standard

GROUND WATER DEPOSITIONAL DUST HVAS AND METEOROLOGICAL MONITORING

ES2 integrated screening system for bifold doors

Guidance document GD 20 April 2015 amended May 2017 GUIDANCE DOCUMENT ON SERVICEABILITY STATES AND DEFLECTION CRITERIA

Code Compliance Research Report CCRR-0228

Performance of Deep Leg L-headers

THIS TO CERTIFY THAT. Ritek Roof Panels. Structure - Structural Reliability

The University of Sydney School of Civil Engineering Centre for Advanced Structural Engineering NSW 2006 Australia. SupaPurlin

Self-drilling Screwed Knee-joints for Cold-formed Steel Portal Frames in Cyclonic Regions

Transcription:

Test 1 Non Cyclonic Testing of 0.42mm BMT KlipLok Classic 700 (Lysaght) Roof Sheeting with 75mm Spacer and 100mm Insulation THE SCHOOL OF CIVIL, ENVIRONMENTAL AND MINING ENGINEERING THE UNIVERSITY OF ADELAIDE SOUTH AUSTRALIA 5005 TELEPHONE 618 8303 5451 FACSIMILE 618 8303 4359 Operating through: Adelaide Research & Innovation Pty. Ltd ACN 008 027 085 PREPARED FOR Carey Roofing Products Pty Ltd No. OF PAGES: 15 DISTRIBUTION: CLIENT (1) SCHOOL (1) REFERENCE NUMBER: C130501-1 DATE OF ISSUE: 8 August 2013 Prepared By:... DR F. POOYA NEJAD ENGTEST Approved By:... DR TOGAY OZBAKKALOGLU ENGTEST CONSULTANT

Table of Contents 1. Introduction 3 2. Description of Test Procedures and Equipment 3 3. Test Details 3 4. Test results 6 4.1 Serviceability limit state 6 4.2 Strength limit state 8 5. References 10 Appendix A: 11 EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 2

1. Introduction EngTest was approached by Mr. Dean Stubbs of JakMax Pty Ltd on behalf of Carey Roofing to undertake a series of cyclonic and non-cyclonic tests (including serviceability and strength limit states) on Carey Roofing products in accordance with the National Construction Code (NCC) and AS4040 as appropriate. This report relates to non-cyclonic test of Carey Roofing product in accordance with AS4040. All materials (panels, purlins, spacers and screws) were provided by Carey Roofing. Test pressures were provided by Rachael Zeuner (consultant of the project). Fixing of the panels was carried out by EngTest in accordance with the drawings and instructions provided by Rachael Zeuner, which are included in Appendix A. Testing was undertaken on 12 th June 2013 by EngTest under the supervision of Mr. Brendan Scott, Dr Fereydoon Pooya Nejad, and Dr Togay Ozbakkaloglu from the School of Civil, Environmental and Mining Engineering. 2. Description of Test Procedures and Equipment The test rig conforms to the requirements of AS4040.0 1992 and consists of two fixed vertical sides and a moveable base between the sides. The base is supported on hydraulic jacks and can be moved vertically. The panel supports are fastened to the sides of the test rig and the panels under test are fastened to the supports. Loads are applied to the panels through the airbags placed between the panels and the base of the test rig. The movement of the base is controlled electronically via pressure transducers placed inside the airbags to generate the required test pressures. 3. Test Details Figures 1 to 3 show the test setup and installation arrangement of the panels on the test rig prior to testing. The side sheets and purlin connections to the loading frame were considered to be the part of the test rig, and hence were not under test. The setup of the air bag rig and the set up of the test specimens were undertaken by EngTest. Table 1 provides a summary of the test details and configurations. Both serviceability limit state and strength limit state testing were undertaken in accordance with AS 4040.2-1992, Methods of Testing Sheet Roof and Wall Cladding Method 2: Resistance to Wind Pressures for Non-Cyclone Regions. Each incremental load that was applied to the panels was maintained for a period of one minute in accordance with the EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 3

strength limit state test requirements of AS4040.2 1992. The test results are presented in Section 4. Purlin A Purlin B Purlin C Purlin D Side Sheet Test Sheet 600mm 480mm A D1 D2 D3 D4 D5 A Side Sheet 960mm 1200mm 960mm Dial gauge 75mm spacer 100mm insulation KlipLok classic 700 Purlin A Purlin B Purlin C Purlin D Section A-A Figure 1. Test setup. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 4

Figure 2. Installation of the sheet to spacers. Figure 3. Installed sheet prior to serviceability testing. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 5

Table 1. Test materials and span arrangement. Spacer height Insulation thickness Purlin type Cladding Clips Cladding span Cover plate thickness Spacer to Purlin Fasteners Clips to Spacer 75 100 C1501.2 KlipLok Classic 700 (Lysaght) 0.42mm BMT KlipLok Classic 700 (Lysaght) 960/1200/960 1.6 12_14 35 Buildex Metal Teks 5_4.14 25 Bremick 4. Test results 4.1 Serviceability limit state For serviceability limit state testing, deflections were measured for each load increment using dial gauges placed at the locations requested by Rachael Zeuner as shown in Figures 1 and 3. The target pressure for serviceability was also provided by Rachael Zeuner. Table 2 shows summary of dial gauges readings during serviceability limit state testing for each load increment, and Table 3 shows the deflections measured at the dial gages locations during the testing for each load increment. The results of the serviceability load test are presented in Figure 4. Table 2. Summary of dial gauges readings in serviceability limit state testing. Airbag pressure (kpa) D1 D2 D3 D4 D5 Comments 0.0 5.79 0.96 1.13 1.96 45.00 Immediately before application of the pressure 1.44 11.00 9.10 9.60 8.90 47.01 When the pressure has been applied for 1 minute 0.0 6.89 2.60 3.13 3.46 45.79 5 minutes after completion of removal of the pressure 2.30 14.80 13.10 12.05 11.60 49.50 When the pressure has been applied for 1 minute 0.0 7.32 3.14 4.63 3.91 46.11 5 minutes after completion of removal of the pressure 2.88 15.80 15.30 14.10 13.05 0.35 When the pressure has been applied for 1 minute 0.0 7.66 3.50 4.92 4.15 46.25 5 minutes after completion of removal of the pressure EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 6

Table 3. Deflection at the dial gages locations. Airbag pressure (kpa) D1 D2 Deflection D3 D4 D5 0.0 0.00 0.00 0.00 0.00 0.00 1.44 5.21 8.14 8.47 6.94 2.01 0.0 1.10 1.64 2.00 1.50 0.79 2.30 9.01 12.14 10.92 9.64 4.50 0.0 1.53 2.18 3.50 1.95 1.11 2.88 10.01 14.34 12.97 11.09 5.35 0.0 1.87 2.54 3.79 2.19 1.25 3.50 3.00 Airbag pressure (kpa) 2.50 2.00 1.50 1.00 0.50 D1 D3 D5 D2 D4 0.00 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 Deflection Figure 4. Summary of serviceability test results. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 7

4.2 Strength limit state After the removal of the dial gauges the sheeting was loaded incrementally from 2.88kPa to failure and increments of 0.5kPa. At each loading interval the pressures were maintained for a period of one minute as highlighted in Table 4. Based on the observations reported in Table the airbag pressure at failure was 7.89kPa and, in accordance with AS4040.2, the panels passed the strength limit state for a maximum pressure of 7.68kPa. Table 4. Summary of strength limit state testing. Airbag Pressure (kpa) 2.88 3.38-7.68 7.89 Comments Pressure was maintained for a period of one minute. Increasing deflection. Pressure was maintained for a period of one minute. Increasing deflection (Figure 5). Panel failed. Centre sheet pulled out from the clips. Separation of centre test panel from side panels at overlaps (Figures 6-7). Failure occurred at 7.89kPa. Figure 5. Deflection of the sheet at airbag pressure of 7.68kPa. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 8

Figure 6. Sheeting at failure. Figure 7. Separation of centre test panel from side panels at overlaps at failure. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 9

5. References National Construction Code (NCC) Series 2012; Volume 1, Section B Structures, Specification B1.2 Design of Buildings in Cyclonic Areas; Australian Building Codes Board. AS 4040.0-1992, Methods of testing sheet roof and wall cladding Part 0: Introduction, list of methods and general requirements. Standards Australia, Homebush, NSW, Australia. AS 4040.2-1992, Methods of testing sheet roof and wall cladding Method 2: Resistance to wind pressures for non-cyclone regions. Standards Australia, Homebush, NSW, Australia. EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 10

APPENDIX A: Carey Roofing Fixing Details EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 11

EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 12

EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 13

EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 14

EngTest Report :C 130501_Carey Roofing Report for Static Testing-Test 1 Page 15