FXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2

Similar documents
Transcription:

- C 1 Product Detail Engineering Data Models... C2 Structural Support Models... C6 Engineering Specifications... C8

- C 2 Engineering Data Models REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice. More can be found at www.baltimoreaircoil.com. 2x - x 1. Fluid in; 2. Fluid out; 3. Make-Up ND15;. Overflow ND80; 5. Drain ND50; 6. Access door; 7. Vent ND15. Model No. Operating Shipping Heaviest Section H L W Air (m 3 /s) Fan Spray Water (l/s) Pump Coil Volume (L) Inlet/Outlet Coil Conn. 22-H 22-J 22-K 23-J 23-K 3570 3590 3600 3800 3810 2350 2370 2380 2520 2530 10 150 160 1600 1610 13,0 1,5 16,0 1,3 15,8 (1x),0 (1x) (1x) 7,5 (1x) (1x) 7,5 (1x) 226 (1x) 226 (1x) 226 (1x) 278 (1x) 278 32-K 32-L 33-L 5250 5260 5580 3390 310 360 2150 2160 2390 2775 2775 2775 23, 26,0 25,6 (2x),0 18,3 18,3 18,3 (1x) 337 (1x) 337 (1x) 18 2-K 2-L 2-M 3-L 3-M -M 660 6660 6670 7090 7100 7520 150 180 190 80 90 780 2590 2610 2620 2910 2920 3210 26,2 29,2 32, 28,8 31,9 31,7 (2x),0 (1x) 560 (1x) 560 (1x) 669 Q0-K Q0-L Q1-L 660 6660 7510 150 180 770 2590 2610 3200 26,2 29,1 28,5 (2x),0 (1x) 669 Baltimore Aircoil

- C 3 5x - 56x 1. Fluid in; 2. Fluid out; 3. Make-Up ND25;. Overflow ND80; 5. Drain ND50; 6. Access door; 7. Vent ND15. Model No. 52-L 52-M 52-N 53-M 53-O 5-O Q50-M Q50-O Q51-O 561-M 561-O 562-M 562-O Q560-L Q560-O Q561-L Q561-O Operating 7960 7970 8000 8600 8630 9260 7970 8000 9260 10650 10710 11590 11650 11580 11650 1370 13550 Shipping 960 970 5000 510 550 5890 970 5010 5890 630 690 7090 7150 7070 7150 820 890 Heaviest Section 320 3250 3270 3720 160 3250 3280 160 020 090 680 70 670 70 6010 6090 H L W Air (m 3 /s) 35,1 38,9 1,3 38,6 3,8 3,5 38,9,2 3,5 59,3 67, 58,9 66,9 53,0 66,8 52,3 65,9 Fan (2x) 9,0 (3x) (3x) Spray Water (l/s) Pump Coil Volume (L) (1x) 832 (1x) 832 (1x) 993 (1x) 993 (1x) 762 (1x) 762 (1x) 1007 (1x) 1007 (1x) 1007 (1x) 1007 (1x) 1562 (1x) 1562 Inlet/Outlet Coil Conn.... because temperature matters

- C 6x - 66x 1. Fluid in; 2. Fluid out ND 3. Make-Up ND25;. Overflow ND80; 5. Drain ND50; 6. Access door; 7. Vent ND15. Model No. Operating Shipping Heaviest Section H L W Air (m 3 /s) Fan Spray Water (l/s) Pump Coil Volume (L) Inlet/Outlet Coil Conn. 62-L 62-M 62-N 63-M 63-N 63-O 6-N 6-O 9070 9090 9110 9770 9800 9810 1070 1080 5380 500 520 5880 5900 5910 6370 6380 390 3510 3530 3990 010 020 80 90 39,9,3 7,0 3,7 6, 9,6 5,8 9,0 (2x) 9,0 (2x) 9,0 (2x) 9,0 (1x) 723 (1x) 723 (1x) 723 (1x) 896 (1x) 896 (1x) 896 (1x) 1069 (1x) 1069 661-M 661-N 661-O 662-M 662-N 662-O 12260 12300 12320 13270 13310 13330 7000 7050 7060 7710 7760 7770 360 00 20 5070 5110 5130 68,6 72,8 77,9 67,3 62,5 76,5 (3x) 9,0 (3x) 9,0 (1x) 821 (1x) 821 (1x) 821 (1x) 108 (1x) 108 (1x) 108 Q661-M Q661-N Q661-O 15310 15360 15370 9160 9210 9220 6510 6560 6570 65, 69,5 7, (3x) 9,0 (1x) 1658 (1x) 1658 (1x) 1658 General Notes 1. Operating weight is for the tower with the water level in the cold water basin at the overflow. 2. When the flow rate for units exceeds 25 l/s the quantity of the coil connections will be double. When the flow rate for -Q units exceeds 57 l/s, connections of ND200 will be used (1 x inlet; 1 x outlet). 3. Inlet and outlet connections are beveled for welding.. Standard make-up, drain and overflow connections are MPT. 5. Dimensional drawings show standard (right hand) arrangements. Left hand arrangements can be furnished by special order. 6. All -models will be shipped in two sections: upper and lower section. 7. -units have standard Low Noise Fans. For units with optional Whisper Quiet Fans, a W is added at the end of the model name. Baltimore Aircoil

- C 5 Sound Attenuation Models 1. Intake Attenuator; 2. Discharge Attenuator. Model No W = Unit Width, see general Engineering data. Dimensions Remote Sump Data Models D H t Intake Discharge 2x 135 715 100 10 3x 135 715 130 210 (Q)x 135 715 175 255 (Q)5x 1500 5525 250 270 (Q)56x 1500 5665 375 385 6x 2005 5525 250 310 (Q)66x 2005 5665 375 0 Refer to the "Technical Resources" section "Selection of Remote Sump" for Remote Sump Data.... because temperature matters

- C 6 Structural Support Models REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice. More can be found at www.baltimoreaircoil.com. The recommended support arrangement for units consists of parallel I-beams running the full length of the unit, spaced as shown in the following drawing. Besides providing adequate support, the steel also serves to raise the unit above any solid foundation to ensure access to the bottom of the unit. To support units in an alternate steel support arrangement, consult your BAC Balticare Representative. Units with and without Sound Attenuation 1. Unit Outline, 2. Air Intake, 3. Mounting Holes,. Unit Model Max. Deflection Dimensions W L A B C No of 20 mm Anchorbolts 2x 5 2325-255 3x 8 2775 2325-255 (Q)x 10 2325-255 (Q)5x 10 2925-255 6x 10 3550-255 (Q)56x 12 2925 20 270 8 (Q)66x 12 3550 20 270 8 Notes : 1. Support steel and anchor bolts to be designed and furnished by others. 2. All support steel must be level at the top. 3. Beams must be selected in accordance with accepted structural practice. Maximum deflection of beam under unit see table.. If vibration isolation rails are to be used between the unit and supporting steel, be certain to allow for the length of the vibration rails when determining the length of the supporting steel, as vibration rail length and mounting hole locations may differ from those of the unit. Baltimore Aircoil

- C 7 5. If point vibration isolation is used with multi-cell units, the isolators must be located under the support steel, not between the support steel and the towers. 6. All mounting holes have a diameter of 22mm.... because temperature matters

- C 8 Engineering Specifications 1.0 Closed Circuit Cooling Tower 1.1 General: Furnish and install factory assembled closed circuit cooling tower(s) of induced draft design with single side air entry and vertical air discharge. Overall dimensions shall not exceed approximately mm long x mm wide, with an overall height not exceeding approximately mm. Operating weight shall not exceed kg. The closed circuit cooling tower(s) shall be Baltimore Aircoil Company Model(s). (Alternate 1.1) General: Furnish and install factory assembled closed circuit cooling tower(s) of induced draft design with dual side air entry and vertical air discharge. Overall dimensions shall not exceed approximately mm long x mm wide, with an overall height not exceeding approximately mm. Operating weight shall not exceed kg. The closed circuit cooling tower(s) shall be Baltimore Aircoil Company Model(s). 1.2. Thermal Capacity (water as heat transfer fluid): The closedcircuit cooling tower(s) shall be warranted by the manufacturer to cool l/s of water from C to C at C entering wet-bulb temperature. Coil pressure drop shall not exceed kpa. 2.0 Construction Details 2.1 Coil Section: The heat transfer section of the closed circuit cooling tower shall be encased with removable heavy-gauge galvanized steel panels (or corrosion resistant, fiberglass reinforced polyester (FRP) on Models -D). The coil shall be constructed of continuous serpentine all prime surface steel designed for 10 bar, and be hot-dip galvanized after fabrication. The coil shall be designed for free drainage of fluid. 2.2 Cold Water Basin: The basin shall include a depressed section with drain/clean-out connection. Standard accessories shall include 3.0 Mechanical Equipment 3.1 Fan(s): Fan(s) shall be heavy-duty, axial flow low noise, with aluminium alloy blades. Air shall discharge through a fan cylinder designed for streamlined air entry and minimum fan blade tip clearance for maximum fan efficiency. (Alternate 3.1) Fan(s) for -models: Fan(s) shall be of Whisper Quiet fan design for ultra low sound consisting of specially shaped aluminium blades with end caps and flexible hub connection. 3.2 Fan(s) and shaft(s) shall be supported by heavy-duty, selfaligning, grease-packed ball bearings with moisture-proof seals and integral slinger rings, designed for minimum L10 life of 0,000 hours. Fan(s) shall be belt driven and specifically designed for evaporative.0 Wet Deck Surface and Drift Eliminators.1. BACross Wet Deck Surface and Drift Eliminators ( models): The wet deck surface and integral drift eliminators shall be formed from plastic material and shall be impervious to rot, decay, fungus and biological attack. The surface shall be manufactured and performance tested by the closed circuit cooling tower manufacturer to provide single source responsibility and assure control of the final 5.0 Combined Inlet Shields 5.1. Combined Inlet Shields: Combined inlet shields shall be separate from the wet deck surface and removable to allow easy access for inspection of the air/water interface at the air inlet side of the equipment. Combined inlet shields shall prevent UV-light and 6.0 Spray Water System 6.1 Spray Water Pump(s): The closed circuit cooling tower shall include an appropriate number of close-coupled, bronze-fitted centrifugal pump and motor assemblies equipped with mechanical seal, mounted in the basin and piped from the suction connection to the water distribution system. The pump motor(s) shall be the totally enclosed fan cooled (TEFC) type suitable for volts, phase, (Alternate1.2.) Thermal Capacity (aqueous glycol solution as heat transfer fluid): The closed circuit cooling tower(s) shall be warranted by the manufacturer to cool l/s of % by volume ethylene/propylene glycol solution from C to C at C entering wet-bulb temperature. Coil pressure drop shall not exceed kpa. 1.3. Corrosion Resistant Construction: Unless otherwise noted in this specification, all steel panels and structural members shall be constructed of heavy-gauge Z600 metric hot-dip galvanized steel, with all sheared edges given a protective coating of zinc-rich compound. 1.. Quality Assurance: The closed circuit cooling tower manufacturer shall have a management system certified by an accredited registrar as complying with the requirements of ISO- 9001:2000 to ensure consistent quality of its products and services. 1.5. Warranty: The manufacturer s standard equipment warranty shall be for a period of not less than one year from date of startup or eighteen months from date of shipment, whichever occurs first. large area, lift-out steel strainers with perforated openings sized smaller than water distribution nozzle orifices, and integral antivortexing hood to prevent air entrainment, waste water bleed line, and brass make-up valve with large diameter plastic float arranged for easy adjustment. 2.3 Casing Panels: For models with single air inlet side the casing panels shall be constructed of steel matching the structure defined in section 1.3. cooling service. Fan and motor sheave(s) shall be fabricated from cast aluminum. 3.3 Independent motor and drives: Each fan is equipped with an independent motor and drive assembly, which allows independent operation of each fan. 3. Fan : Fan motor(s) shall be totally enclosed fan cooled (TEFC), reversible, squirrel cage, ball bearing, designed specifically for evaporative cooling duty on volts hertz phase electrical service. The motor shall be furnished with special moisture protection on windings, shafts, and bearings. Each motor shall be mounted on an easily adjusted, heavy-duty motor base. product. A separate set of drift eliminators shall be removable in easily handled sections for quick access to the coil. Eliminators shall have a minimum of three changes in air direction. debris from entering the unit, as well as prevent water splash out during fan cycling. They shall be constructed of maintenance free, corrosion and UV resistant material. and hertz electrical service. The system shall include a metering valve and bleed line to control the bleed rate from the pump discharge to the overflow connection. 6.2 Water Distribution System: Water shall be distributed evenly over the coil at a flow rate sufficient to ensure complete wetting of the Baltimore Aircoil

- C 9 coil at all times. Large diameter, non-clog, 360 plastic distribution nozzles shall utilize a two stage diffusion pattern to provide overlapping, umbrella spray patterns that create multiple intersection 7.0 Access 7.1 Plenum Access: A large, hinged access door shall be provided for access to the coil, drift eliminators and fan plenum section. The 8.0 Sound 8.1 Sound Level: To maintain the quality of the local environment, the maximum sound pressure levels (db) measured 15 m from the points with adjacent nozzles. The branches and spray nozzles shall be held in place by snap-in rubber grommets, allowing quick removal of individual nozzles or complete branches for cleaning or flushing. water make-up valve, float ball and suction strainer shall be easily accessible. cooling tower operating at full fan speed shall not exceed the sound levels detailed below. Location 63 125 250 500 1000 2000 000 8000 db(a) Discharge Air Inlet End Back... because temperature matters