Computational Fluid Dynamics on Performance of Earth Tube Heat Exchanger with Constant velocity for Heating

Similar documents
ANALYSIS OF VARIOUS DESIGNING PARAMETERS FOR EARTH AIR TUNNEL HEAT EXCHANGER SYSTEM

Design and development of an Earth Air Tube Heat Exchanger

CFD Analysis of Earth-Air Heat Exchanger to Evaluate the Effect of Parameters on Its Performance

CFD ANALYSIS OF THERMAL INFLUENCE ZONE OF EARTH AIR TUNNEL HEAT EXCHANGER UNDER TRANSIENT CONDITIONS

CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural Air Conditioning

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

Dynamic thermal simulation of horizontal ground heat exchangers for renewable heating and ventilation of buildings

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Working parameters affecting earth-air heat exchanger (EAHE) system performance for passive cooling: A review

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Łukasz Amanowicz 1, Janusz Wojtkowiak 2 ABSTRACT KEYWORDS

The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria

CFD ANALYSIS OF MINI CHANNEL HEAT EXCHANGER USING WATER AS A WORKING FLUID

Available online at ScienceDirect. Energy Procedia 61 (2014 )

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Introduction to Geothermal Comfort Systems in INDIA

[Dubey*et al., 5(7): July, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

Study on the heat transfer model and the application of the underground pipe system

CFD ANALYSIS OF SOLAR HEATER WATER PIPE WITH DIFFERENT INCLINATION

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

CFD Modelling and Analysis of Different Plate Heat Exchangers

Parametric Study for Evaluation of Design Parameters of Standing Column Well

Modeling a Novel Shallow Ground Heat Exchanger

Simulation of Melting Process of a Phase Change Material (PCM) using ANSYS (Fluent)

MULTI-YEAR OPERATION EFFECT OF GEOTHERMAL HEAT EXCHANGER ON SOIL TEMPERATURE FOR UNT ZERO ENERGY LAB. Vinayak P. Walikar

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Horizontal systems - Theory, tools and Design

CFD Simulation Studies for Vertical Temperature Profile, Pitch Optimisation and Parametric Study of Borehole Heat Exchanger

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

Analysis of working parameters affecting the performance of Earth-air tube heat exchanger (EATHE): A review

DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER

ISSN (ONLINE): , ISSN (PRINT):

Numerical Simulations of Particle Deposition in Metal Foam Heat Exchangers

Volume 2, Issue 2 (2014) ISSN International Journal of Advance Research and Innovation

EXPERIMENTAL AND NUMERICAL STUDY OF AN EARTH-TO-AIR HEAT EXCHANGER FOR BUILDINGS AIR REFRESHMENT IN MARRAKECH. Ayyad University, Marrakech.

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Introduction to Geothermal Comfort Systems in INDIA

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches

Food Dryer Design and Analysis of Velocity and Temperature Profiles

Design, CFD Analysis and Fabrication of Solar Flat Plate Collector

Performance Analysis of a Proposed Water Tube Heat Exchanger Space Cooling System in Kerala

Heat Exchanger Design Modification for Performance Optimization Using CFD Tools

ADVANCES in NATURAL and APPLIED SCIENCES

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

Project Background (long term goals)

CFD SIMULATION AND EXPERIMENTAL VALIDATION OF FLUID FLOW IN LIQUID DISTRIBUTORS

Computational Analysis of Blast Furnace Pulverized Coal Injection For Iron Making

Welcome Everyone. Not Quite this kind! Geothermal Heat Pumps are a indirect solar heating system! Introduction to Geothermal

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

DESIGN OF LIQUID COOLING FOR HIGH HEAT DISSIPATION ELECTRONIC BOARDS USING CFD

EasyChair Preprint. Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant

Computational Modeling of Counter Flow Heat Exchanger for LMTD Analysis

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Improvement of a Two-Dimensional Borehole Heat Exchanger Model

REGRESSION ANALYSIS ON INFLUENCE OF VARIOUS FACTORS ON HEAT TRANSFER OF VERTICAL GROUND HEAT EXCHANGER

ADVANCES in NATURAL and APPLIED SCIENCES

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

CFD Simulation Methodology for Ground-Coupled Ventilation System

A numerical investigation of the influence of wind on multiple short natural draft dry cooling towers

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

A quasi-two-dimensional standing column well model for ground source heat pump systems

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

A SIMULATION OF AN UNDERGROUND HEAT STORAGE SYSTEM USING MIDNIGHT ELECTRIC POWER AT PARK DOME KUMAMOTO

Derivation of Global Parametric Performance of Mixed Flow Hydraulic Turbine Using CFD. Ruchi Khare, Vishnu Prasad and Sushil Kumar

A PILOT PROJECT OF THE CLOSED-LOOP GROUND SOURCE HEAT PUMP SYSTEM IN CHINA

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse

Thermal Analysis of Solar Flat Plate Collector

Thermal Performance of an Integrated Earth-Air Tunnel System with Building s External Wall in UAE

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

THERMAL ANALYSIS OF CPU WITH VARIABLE BASEPLATE HEAT- SINK USING CFD

Thermal analysis of recent crude oil transportation technologies in China

Study on Heat Exchange Characteristics for PHC Energy Piles

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Commissioning of a Coupled Earth Tube and Natural Ventilation System at the Post-Acceptance Step

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Experimental and theoretic investigations of thermal behavior of a seasonal water pit heat storage

CFD-BASED INVESTIGATION OF HEAT TRANSFER CHARACTERISTICS OF FLUE GAS-WATER HEAT EXCHANGER PANELS PRODUCED WITH A NOVEL MANUFACTURING PROCESS

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Thermal Management of Densely-packed EV Battery Set

Transcription:

Computational Fluid Dynamics on Performance of Earth Tube Heat Exchanger with Constant velocity for Heating Piyush Pandey 1, Rajneesh Kumar 2 1 Research Scholar, RKDF College of Technology, RGPV, Bhopal 2 Assistant Professor, RKDF College of Technology, RGPV, Bhopal Abstract- The consumption of high-grade energy has increased considerably with growing needs to achieve thermal comfort conditions inside buildings, residential, greenhouses, livestock buildings, etc. Numerous alternative techniques are being currently explored to achieve thermal comfort conditions inside buildings. The earth air heat exchanger (EAHE) is a promising technique which can effectively be used to reduce the heating/cooling load of a building by preheating the air in winter and vice versa in summer. With the help of ETHE we can reduce the energy consumption required for space. Research of ETHE was carried out at beginning as a field investigation. For the CFD simulation analysis the pipe of 30 m length, 0.005m thickness and 0.195 m diameter, The temperature value considered for inlet is days in month of January from 5 Jan 2018 to 11Jan 2018 at hourly according the climate of Bhopal, M.P. has been taken to observed for the outlet blow with different velocities. Using the CFD analysis it is observed at low air velocity that rate of heat transfer and performance increases in winter. Index Terms- Earth Tube Heat Exchanger (ETHE), Computational Fluid Dynamics (CFD), Heating, Different Velocities. 1 INTRODUCTION Earth air heat exchanger exchanges heat with underground soil. It uses earth s constant underground soil temperature and it is used to heat or cool air or other fluids for commercial or residential purposes. It comprises of long tubes that are buried into the ground, through which air is passed. Because of high thermal inertia of the ground, the temperatures of underground soil remain almost unchanged as compared to ground surface. Time lag also occurs between the temperature fluctuations in the underground soil and at the surface. So at certain depth from upper ground surface, underground soil temperature is lower than outside air temperature in summer and higher in winter. The fresh air can be cooled by passing through the earth air heat exchanger and can be supplied to air conditioning unit to reduce energy consumption. The effectiveness of earth air heat exchanger depends upon material of tube, air inlet temperature, soil temperature, depth, arrangement of pipe etc. An earth-to-air heat exchanger draws air through covered pipes. As temperature of the ground below 2.5 m to 4 m is practically constant, it considerably reduces ambient air temperature variation. It therefore provides space conditioning during the year, with the incoming air being heated in the winter and cooled in the summer by means of earth coupling. Temperature remains in the comfort level range (15-27 ºC). In recent years, ground heat source heat pump systems have become increasingly popular for use in residential and commercial buildings. These systems include several different variations, all of which reject heat and/or extract heat from ground: (1) ground-coupled heat pump (GCHP) systems; (2) Surface water heat pump (SWHP) systems; (3) ground-water heat pump (GWHP) systems: a. Standing column well (SCW) systems; b. Open loop groundwater systems. The material of a pipe can be anything from plastic, metal or concrete. However concrete should be avoided in order not to be dependent on carbon filtration UV sterilization for the stuffy air coming out of concrete earth tubes. 1.2 WORKING PRINCIPLE OF EARTH AIR HEAT EXCHANGER Earth air heat exchanger exchanges heat between air and ground by the process of convection and by conduction it transfers heat to the tube wall. IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 233

SUMMER CONDITIONS Fig 1 Working of EAHE in summer condition Hot air enters into the tube Air loses heat to the ground Cool air enters into the house WINTER CONDITIONS 1.2.2 OPEN LOOP SYSTEM In open loop system, Outside air is drawn from a clean air intake. The cooling tubes are usually 30 m long straight tubes into the home. An open system joint with energy recovery ventilation can be nearly as efficient (80-95%) as a closed loop, and make sure that entering fresh air is filtered and tempered. 1.2.3 COMBINATION SYSTEM In combination system, it is constructed with dampers that allow either open or closed operation, depending on fresh air requirements. Even in closed loop mode, can draw a quantity of relish air when air pressure drop is produced by a solar clothes dryer, chimney, kitchen or bathroom exhaust ducts. It is better to suck filtered inactive cooling air than unconditioned outside air. 1.3 DESIGN PARAMETERS OF EARTH AIR HEAT EXCHANGER 1.3.1 LOCATION If the purpose of the system is to heat, then it must be located in the sunny area. If the purpose of the system is to cool, then it should be located near shaded area of a lake or river. 1.3.2 DEPTH OF PIPE Pipe should be buried as deep as possible but favourable depth can vary from 1.5 m to 3 m. A system designed for cooling requires more depth of pipe than a system designed for heating in same location. Fig 2 Working of EAHE in winter condition Cool air enters into the tube Air gains heat from the ground Hot air enters into the house 1.2 TYPES OF EARTH AIR HEAT EXCHANGER 1.2.1 CLOSED LOOP SYSTEM In closed loop system, inside air from the home or structure is blown through a U-shaped loop of normally 30 to 150 m of tube where it is moderated to near earth temperature before returning to be distributed through ductwork throughout the home or structure. The closed loop system may be more efficient than an open system, since it recoils the air again. Fig 3 Temperature v/s Depth 1.3.3 SOIL CONDUCTIVITY For conducting heat to or from the pipe, moist and compact clay is better than dry sand. 1.3.4 PIPE MATERIAL Pipe can be made of plastics, metals or concretemade with or without fins. IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 234

Most conductive materials at the lowest cost Least air flow resistance Corrosion resistance 1.3.5 PIPE RADIUS AND LENGHT As the radius of pipe increases, inlet air temperature also increases because with the increase of pipe radius, convective heat transfer coefficient on the inner surface of pipe decreases due to which overall heat transfer coefficient of the earth tube system deceases. For better performance smaller diameter pipe should be used. 1.3.6 AIR VELOCITY With the increase in air flow rate, mass flow rate increases and inlet air temperature also increases. For a given tube diameter, increase in airflow rate results in: Increase in film coefficient, Increase in total heat transfer, Increase in outlet temperature, High flow rates desirable for closed systems. For open systems airflow rate must be selected by considering: Outlet temperature and Total cooling or heating capacity. 2.LITERATURE REVIEW Earth tubes have gained renewed attention in the recent years, mainly due to the increasingly higher requirements for energy consumption. Earth tubes utilize the fact that the ground temperature is relativity constant during the annual year. There are few models are adapted and studies to a warm climate like Southern Europe and India. Few studies have been also made for a Nordic climate. Several publications have treated an experiment on earth tubes. However, in many of them simplifying assumptions are made such as a constant temperature or that they only consider one duct or that no latent heat will exchange takes place in the earth. Muraya (1995) used a transient two-dimensional finite element model to study the thermal interference between the U-tube legs. Rottmayer et al (1997) investigated a twodimensional thermal resistance network for a single borehole. A pie-sector shaped pipe with the same perimeter as the circular U-tube is used to approximate heat transfer inside the borehole. A geometry factor is proposed to modify the variation effects from the shape change. Li and Zheng (2009) developed a three-dimensional unstructured finite volume model for a single borehole to retain the geometric structure in the borehole. Delaunay triangulation method is used to mesh the cross-section domain of the borehole. Good accuracy is shown by a comparison between the model predictions and experimental data. heat transfer inside the borehole is simplified as a onedimensional (vertical) quasi-steady state model with a time step of 4 hours. The equivalent circuit method is used to determine the constant heat flux at the borehole wall, which acts as the boundary condition for heat transfer outside the borehole. A twodimensional (vertical and radial) transient model is developed to analyze heat transfer outside the borehole. These highly coupled equations are solved by the bisection method. This numerical model is used for a building located in Chicago as a case study. The simulation results show that the load profile is very sensitive to the thermal conductivity of the ground. The net energy input to the GHE is built up after a few years operation because of the imbalance of cooling and heating load in this building. A GHE system that integrates cooling towers will be further studied in the future to deal with the imbalance of building load. Many other papers have published in which a design method is described. Most of them are based on a discrimination of the one-dimensional heat transfer problem in the tube. Three dimensional complex models, solving conduction and moisture transport in the soil are also found. These methods are of high complexity and often not ready for use by designers. In 2010, De Paepe and Janssen presented a onedimensional analytical method to analyze the influence of the design parameters of the heat exchanger on thermo-hydraulic performance. Genetic algorithms (GAs) have emerged as powerful optimization tool for analyzing the natural problem like earth-to-air heat exchanger (EAHE) and subsequently thermal performance of non-airconditioned building. Advancement in genetic algorithm (GA) optimization tools for design application, coupled with techniques if soft computing have led to new possibilities in the way computers interact with the optimization process. IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 235

In 2011, The concept of goal-oriented GA has been used by Kumar et al. Design a tool for evaluating and optimizing various aspects of earth-to-air heat exchanger behavior. The GA designed model incorporates greater accuracy than the previous models. The proposed model accounts for humidity variations of circulating air, natural thermal stratification of the ground, latent and sensible heat transfer, and ground surface conditions, etc. In 2012,Rodriguez and Diaz described and analyzed the use of low enthalpy geothermal energy that consists of converting mine galleries in underground heat exchanges. Finally using the method, the capabilities of a typical system were analyzed and its importance on technical, economic and environmental basis was proved. In 2014 Ghosal et al., investigated the potential of using the stored Thermal energy of ground for space heating with the help of two buried pipe systems, one is ground air collector and other is earth air heat exchanger, integrated with the green house located at IIT Delhi, India. The total length of pipe is kept same in both arrangements for comparatively study. With ground air collector temperature were observed to be 2-3oC higher than those with earth air heat exchanger. In 2016 Mihalakakou et al., investigated the heating potential of a single ground to air heat exchanger and also multiple parallel tube system. An accurate numerical model was used to investigate the dynamic thermal performance of the system during the winter period in Dublin. the model has been successfully validate against an extensive set of experimental data. The results showed that the heating potential of the system during winter is significantly important. To obtained results showed that that the effectiveness of the ground to air earth air heat exchanger increases with an increase in pipe length (checked rang 30-70 m). Also, there is increase in effectiveness when the pipe is buried in greater depths (3 m instead of 1.2 m). By increasing the pipe diameter from 100 to 150 mm, the heating capacity of the system was reduced. This is due to a reduction in convective heat transfer coefficient and an increase in the pipe surface, therefore, providing a lower temperature at the pipe outlet. Finally a higher velocity in the pipe (range 5-15 m/s) leads to a reduction of the system hearting capacity, mainly because of the increased mass flow rate inside the pipe. In 2017 Vikas Bansal et.al., have worked on Performance evaluation and economic analysis of integrated earth air tunnel heat exchanger evaporative cooling system by applying implicit model based on CFD. For use of ETHE system integrated with evaporative cooling to be determine for evaluating the energy saving obtained. Four base cases of existing systems, i.e. electric heater and airconditioner. Moreover, three different types of blower (i.e. standard blower, energy efficient blower and inefficient blower) are considered for evaluating the financial viability and energy saving of the proposed system. So from the literature review we found that if we reduce velocity, checking for different material and make some appropriate changes in geometry, there will be a chance to improve the performance of earth tube air heat exchanger. 3. METHODOLOGY CFD computational Tool: This section describes about the CFD tools which are required for the CFD analysis of the problem. There are the three main elements for the processing of the CFD simulations: the pre-processor, solver, and post-processor are described. Pre-processor: A pre-processor is defined to the geometry of the problem. And it is fixed to the domain for the computational analysis and then generates the mesh of the geometry. Here also set the nomenclature like inlet, outlet, and wall etc. Generally, the finer the mesh of the geometry in the CFD analysis gives more accurate solution. Fineness of the grid also determines the computer hardware and more time needed for the calculations. Solver: In the solver processor the calculations is done by using the numerical solution methods. There are the many numerical methods which are used for the calculations for example:-the finite element method, finite volume method, the finite difference method and the spectral method. Most of them in CFD codes use finite volume method. In this project the finite volume method is used. Geometry Description Material used for Parameter of ETHE is 30 m Aluminium tube length, 0.195m tube diameter, 0.005m pipe thickness. The geometry is made on design modular of Ansys 14.5. IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 236

Model Selection Solution method momentum- 2nd order, Turbulent 1st order, Solution control Standard. The special input required is pressure based solver, Viscous, K, e two equation turbulence model and solution techniques. Figure 4 Line Diagram of Earth Tube Exchanger Meshing Meshing detail ICEM CFD meshing Method: Automatic Meshing type: Trihedral No of node -166622 No of element- 823919 Fig.5 Meshing of the Model. Material Property For Air -Density- 1.225Kg/m3 Cp-1006.43 J/Kg-K Temperature - 25.4 ºC. For Aluminium- Density-2700kg/ m3 Cp-1046.7J/Kg-K Thermal conductivity- 0.19 W/m-K Boundary Condition: To perform analysis is done on the following test data available are shown in Table 1. Based on the analysis in the investigation measurements through Computational Fluid Dynamics (CFD) software employed, the uncertainties in the measurement of air mid temperature and air outlet temperature are estimated as 2 m/s in winter season for heating. Table 1: Inlet air temperature for ETHE in January 2017(οC) Date-Time 05-Jan 06-Jan 07-Jan 08-Jan 09-Jan 10-Jan 11-Jan 10:00AM 17 20 22 19 20 21.5 21.2 11:00AM 18 20 22 21 21.3 22 22.6 12:00PM 20.5 22 23.3 22.4 23 22.8 23 1:00 PM 21 25 25 23 23.5 24 24 2:00 PM 21 26 24 23.1 24 24 23 3:00 PM 20 25.5 24.1 22 23.1 23.4 23.2 4:00 PM 18.2 24.2 23 20.8 22.6 23 22 5:00 PM 16 23 22 20 20.5 22 21 4. RESULTS AND DISCUSSIONS CFD model of ETHE system has been developed and validated for winter weather conditions by taking observations on the experimental set-up for the month of January, 2018 at Bhopal (M.P, India). Comparison of simulated for air temperature in the pipe at mid and outlet sections along the length is summarized for air velocity of 2m/s as shown in Table 6.1. Inlet condition of air in CFD simulation was kept as mention above. Simulation model was carried out 30 m tube length, 0.195 m tube diameter, 5 mm pipe thickness. Investigation data gathered on 30 m length tunnel was in agreement with the simulated values. IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 237

Figure 6 Pressure Contour for inlet temperature of 21ºC on 5th Jan. 2018 at 01:00 PM. Figure 9 Temperature Contour for inlet temperature of 26ºC on 6th Jan. 2018 at 02:00 PM. Figure 7 Temperature Contour for inlet temperature of 21ºC on 5th Jan. 2018 at 01:00 PM. Figure 10 Pressure Contour for inlet temperature of 24ºC on 11th Jan. 2018 at 01:00 PM. Figure 8 Pressure Contour for inlet temperature of 26ºC on 6th Jan. 2018 at 02:00 PM. Figure 11 Temperature Contour for inlet temperature of 24ºC on 11th Jan. 2018 at 01:00 PM. Table 2: ETHE outlet temperature in ºC at constant velocity of 2 m/s 10:00 11:00 12:00 AM AM PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM Inlet 17 18 20.5 21 21 20 18.2 16 Outlet 24.36 24.4719 24.789 25.33 25.33 24.7036 24.5942 24.1723 IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 238

05-Jan 06-Jan 07-Jan 08-Jan 09-Jan 10-Jan 11-Jan Inlet 20 20 22 25 26 25.5 24.2 23 Outlet 25.29 25.31 25.38 26.12 26.12 25.36 25.292 25.2468 Inlet 22 22 23.3 25 24 24.1 23 22 Outlet 25.3412 25.3412 25.36 25.3932 25.38 25.381 25.3468 25.3411 Inlet 19 21 22.4 23 23.1 22 20.8 20 Outlet 25.292 25.3245 25.189 25.3472 25.369 25.3415 25.3199 25.3071 Inlet 20 21.3 23 23.5 24 23.1 22.6 20.5 Outlet 25.3068 25.334 25.3468 25.365 25.3763 25.354 25.3439 25.319 Inlet 21.5 22 22.8 24 24 23.4 23 22 Outlet 25.3326 25.3412 25.3504 25.3763 25.3763 25.355 25.3469 25.3412 Inlet 21.2 22.6 23 24 23 23.2 22 21 Outlet 25.38 25.39 25.40 25.42 25.40 25.41 25.387 25.376 5. CONCLUSIONS Figure 12 Analysis Results After going CFD analysis through the comparison charts shown in the above, we can see that the results are quite encouraging. From the CFD analysis by using properties and boundary conditions the following conclusions are made: For the pipe of 30 m length and 0.195 m diameter, temperature value considered for inlet is 7 days in month of January from 5 Jan 2018 to 11 Jan 2018 at hourly. Performance is effective in lower air velocity. Outlet maximum temperature is 26.12ºC on 6 Jan 2018 and the minimum temperature is 25.33ºC on 5 Jan 2018. REFERENCES Figure 13 Comparison Analysis [1] Girja Saran and Rattan Jadhav: Performance of Single Pass Earth-Tube Heat Exchanger: An experimental study agricultural journals 6(2002), 32-40 [2] Vikas Bansal., Rohit Misra, Ghanshyam Das Agrawal, Jyotirmay Mathur: Performance evaluation and economic analysis of integrated earth air tunnel heat exchanger evaporative cooling system, Energy and Buildings 55 (2012) 102 108. [3] Fabrizio Ascione, Laura Bellia, Francesco Minichiello-: Earth-to-air heat exchangers for IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 239

Italian climates, Renewable Energy 36 (2011) 2177-2188 [4] Salsuwanda Selamat, Akio Miyara and Keishi Kariya :Analysis of Short Time Period of Operation of Horizontal Ground Heat Exchangers,ISSN 2079-9276,Resources 2015, 4, 507-523; doi:10.3390/resources4030507. [5] Fuxin Niu, Yuebin Yu, Daihong Yu, Haorong Li : Heat and mass transfer performance an alysis and cooling capacity prediction of earth to air heat exchanger, Applied Energy 137(2015) 211-221 [6] Haorong Li,Yuebin Yu,Fuxin Niu,Michel Sha.k,Bing Chen : Performance of a coupled cooling system with earth-to-air heat exchanger and solar chimney,renewable Energy62(2014)468-477 [7] Clara Peretti, Angelo Zarrella, Michele De Carli, Roberto Zecchin : The design and environmental evaluation of earth-to-air heat exchangers (EAHE). Renewable and Sustainable Energy Reviews 28 (2013) 107 116 [8] Ashish Ku Chaturvedi& DR. V. N. Bartaria: Performance of Earth Tube Heat Exchanger Cooling of Air, (IJSPR) Volume-06, Number - 02, 2014 IJIRT 147114 INTERNATIONAL JO URNAL OF INNOVATIVE RESEARCH IN TECHNOLOGY 240