GEMSCAB INDUSTRIES LIMITED STANDARD PLAN FOR HT XLPE CABLES AS PER IS:7098(PART-II)

Similar documents
MANUFACTURER'S QUALITY ASSURANCE PLAN (QAP - Instrumentation cables)

SPECIFICATION FOR FRLS POWER CABLES

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

TECHNICAL SPECIFICATIONS

4x270 MW TSGENCO BHADRADRI TPS

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

We manufacture the following Products :

Accreditation No: LAB 041. Electrical Measurement & Test Laboratory (EMTL), PCSIR Labs. Complex, Lahore Pakistan.

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

Construction guideline

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

MATERIAL STANDARD FOR CABLES AND WIRES

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

DOC No. CMD-III/IS 1554(Pt 2)/1 Date :

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

MSME Testing Centre, 65/1, G. S. T. Road, Guindy, Chennai, Tamil Nadu. Discipline Electrical Testing Issue Date

11-SDMS-01 REV. 03 ( )

Termco Heatshrink.

XLPE MATERIAL NATIONAL CABLES INDUSTRY XLPE INSULATED MEDIUM VOLTAGE CABLES

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

2.2 Copies of any records and other connected papers that may be required by the Bureau shall be made available at any time on request.

EHV XLPE CABLES CDCC LINE

1. All Members of Power Cables Sectional Committee, ET 09; 2. All Members of Electrotechnical Division Council; and 3. All other Interested.

XLPE CABLE (11KV - Aluminium)

TECHNICAL SPECIFICATION FOR. FOUR CORE AND TWO CORE XLPE CABLES of Various SIZES 16mm 2, 10mm 2 & 6mm 2 INSULATED & XLPE SHEATHED ARMORED LT CABLES

Comparison of BS 5308, PAS 5308 and BS EN

TECHNICAL SPECIFICATION FOR. L.T.XLPE POWER CABLE (armoured) FOR DISTRIBUTION NETWORK

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

U.V resistance UL Sunlight Resistance. Flame retardant IEC

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

SPECIFICATION: MOTOR

Underground Electrical Cabling works at Gandhidham-Adipur under NCRMP-II (Project Funded By the World Bank)

TI 20 PVC TI 20 INSULATED TELEPHONE WIRE

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

40/69 kv to 127/220 kv XLPE

SafeX110 Single Core Flexible Tinned Copper Cable

SPECIFICATION SS-20 / 4 STEEL STRUCTURES FOR SUBSTATION AND SWITCHING STATION MATERIAL

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

CERTIFICATE OF ACCREDITATION

Technical Specification for Insulated Low Voltage Single Core Copper Cable

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

Specification No. CSC-70/DH/UH/P&D/

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

INTERNATIONAL STANDARD

26/35kV Copper XLPE Insulation Electric Cable

Type 1 Machine Cable. Oxygen free tinned annealed copper wire interwoven with high tensile poly-yarn

INTERNATIONAL STANDARD

6A V CVQ cable (C rank)

Separator, suitable tape between the braid and outer sheath

3M Cold Shrink Joint, SC145-II/SS145-II

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

ISO 6722 INTERNATIONAL STANDARD. Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

This document is a preview generated by EVS

P.V.C. INSULATED UNARMOURED COPPER CABLES

AN ISO 9001 : 2008 COMPANY

WIRES, CABLES AND CORDS

FEDERAL STANDARD TEST METHODS FOR CABLES AND WIRE, INSULATED

FEDERAL STANDARD TEST METHODS FOR CABLES AND WIRE, INSULATED

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

THE PATHWAY TO POWER HIGH AND EXTRA HIGH VOLTAGE CABLES

Rayfit The advanced heat-shrinkable joint sleeve for medium voltage joints up to 36 kv NEW ENERGY DIVISION

DOC: STI/8783(Part 4/Sec1)/1 August 1998

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

Protection of A/C connection using a heat shrinkable jacket

Heat-Shrinkable Tubing

Test Report No.: Page 2 of 35

TECHNICAL SPECIFICATION FOR OPTICAL FIBER CABLE

TECHNICAL SPECIFICATION FOR OPTICAL FIBER CABLE

AMENDMENT OF MALAYSIAN STANDARD MALAYSIAN STANDARD MS :2009

DATA SHEET Single Core 2HR Fire Rated Cable

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

ACSR CONDUCTOR. March 2015 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

KEMA INSPECTION REPORT

List of plant, machinery and list of test equipments available in house.

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 )

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

VOLUME-II SECTION-I TECHNICAL SPECIFICATIONS AND REQUIREMENTS

Profile No.: 4 NIC Code: ELECTRICAL CABLES (SINGLE AND MULTICORE)

Transcription:

-1 RAW MATERIAL INSPECTION 1.1 ALUMINIUM ROD/COPPER ROD (i) Diameter 100% IS:5484 & IS:613 IS:5484 & IS:613 GIL-GIR-006 IQC (ii) Conductivity or resistivity 100% IS:5484 & IS:613 IS:5484 & IS:613 GIL-GIR-006 IQC at 20 Deg.C (iii) Tensile Strength 100% IS:5484 & IS:613 IS:5484 & IS:613 GIL-GIR-006 IQC (iv) Surface finish 100% IS:5484 & IS:613 IS:5484 & IS:613 GIL-GIR-006 IQC 1.2 XLPE COMPOUND FOR (i) Physical Properties Supplier TC IQC 1.3 SEMI CONDUCTING (i) Physical Properties 1.4 COPPER FOIL (i) Resistivity 4% (ii) Dimensions 4% Supplier TC IQC GIL-GIR-008 IQC GIL-GIR-008 IQC 1.5 PVC COMPOUND FOR (i) Density SHEATHING ` (ii) Tensile strength & Elongation Test per batch Lot GIL-GIR-003 IQC per batch IS:5831/84 & 7098(PT-II) IS:5831/84 & 7098(PT-II) GIL-GIR-003 IQC (iii) Thermal Stability per batch IS:5831/84 & 7098(PT-II) IS:5831/84 & 7098(PT-II) GIL-GIR-003 IQC FOR FRLS COMPOUND (i) Oxygen Index per batch ASTMD 2863 ASTMD 2863 GIL-GIR-003 IQC Min.29 (ii) (iii) Smoke Density Acid Gas Generation Max.250 Deg.C per batch ASTMD 2843 ASTMD 2843 GIL-GIR-003 IQC Max.SDR 60% or Min. light transmission 40% per batch IEC 754(Pt-1) Max.20% IEC 754(PT-I) GIL-GIR-003 IQC Page 1 of 8

1.6 ARMOURING (i) Surface finish 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (ii) Dimensions 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (iii) Tensile Strength 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (iv) Elongation 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (v) Torsion/Winding 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (vi) Weight of Zinc coating 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (vii) Uniformity of Zinc coating 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (viii) Resistivity 4% IS:3975/88 IS:3975/88 GIL-GIR-004 IQC (2) IN PROCESS INSPECTION 1 WIRE DRAWING (i) Diameter Start & end Plant Plant GIL-PII-001 PQC (ii) Surface finish visual Plant Visual GIL-PII-001 PQC (iii) Resistance/Resistivity every setting IS:8130/84 IS:8130/84 GIL-PII-001 PQC (iv) Tensile Strength(Al.) every setting IS:8130/84 IS:8130/84 GIL-PII-001 PQC (v) Elongation(Cu.) every setting IS:8130/84 IS:8130/84 GIL-PII-001 PQC (vi) Wrapping Test (if applicable) every setting IS:8130/84 IS:8130/84 GIL-PII-001 PQC 2 STRANDING (i) Construction(No.of strands) Each setting & IS:8130/84 IS:8130 & Visual GIL-PII-001 PQC during running of M/C. Min.two reading in each shift. (ii) Dimensions -do- Plant Measurement GIL-PII-002 PQC (iii) Surface Finish -do- Data sheet Visual GIL-PII-002 PQC 3 (A) INSULATED CORE (i) Thickness of Insulation -do- IS:7098(PT-II) IS:7098(PT-II) GIL-PII-009 PQC (ii) Surface finish -do- Visual Visual GIL-PII-009 PQC Page 2 of 8

(iii) Colour of cores/core -do- IS:7098(PT-II) IS:7098(PT-2) GIL-PII-009 PQC identification (iv) Hot Set Test -do- IS:7098(PT-II) IS:7098(PT-II) GIL-PII-009 PQC (B) COPPER TAPE SHEILDING Number & dimension of tape -do- IS:7098(PT-II)&Plant Std IS:7098(PT-II)&Plant Std GIL-PII-010 PQC 4 LAYING UP (i) Lay length Each setting & IS:7098(PT-II)&Plant Std IS:7098(PT-II)&Plant Std GIL-PII-005 PQC during running (ii) Laying sequence & direction of M/C. Min.two IS:7098(PT-II)&Plant Std IS:7098(PT-II)&Plant Std GIL-PII-005 PQC reading in each (iii) Diameter(laid up) shift. IS:7098(PT-II)&Plant Std IS:7098(PT-II)&Plant Std GIL-PII-005 PQC 5 INNER SHEATH (i) Thickness of Inner sheath -do- IS:7098(PT-2) IS:7098(PT-2) GIL-PII-006 PQC (ii) Dia over Inner sheath -do- Plant Standard Measurement GIL-PII-006 PQC (iii) Surface finish -do- Plant Standard Visual GIL-PII-006 PQC 6 ARMOURING (i) No.of wires/strips -do- Plant Standard Counting GIL-PII-007 PQC (ii) Lay Direction & Sequence -do- IS:7098(PT-2) IS:7098(PT-2) GIL-PII-007 PQC (iii) Dimensions of wire/strip -do- IS:7098(PT-2)&3975/88 IS:7098(PT-2)&3975/88 GIL-PII-007 PQC (iv) Gap between two wires/ -do- Plant Standard Plant Standard GIL-PII-007 PQC strips (v) Surface finish -do- Plant Standard Visual GIL-PII-007 PQC (vi) Dia over Armour -do- Plant Standard Measurement GIL-PII-007 PQC 7 OUTER SHEATHING (i) Thickness of sheath -do- IS:7098(PT-2) IS:7098(PT-2) GIL-PII-008 PQC (ii) Surface Finish -do- Plant Standard Visual GIL-PII-008 PQC (iii) Embossing Details -do- IS:7098(PT-2) Visual GIL-PII-008 PQC (iv) Overall dia -do- Plant Standard &data sheet Plant Standard &data shee GIL-PII-008 PQC (v) Progressive Sequential -do- Plant Standard &data sheet Visual GIL-PII-008 PQC Marking Page 3 of 8

-3 FINAL TESTING 1 ROUTINE TEST (i) Conductor Resistance 100% IS:7098(PT-2) IS:7098(PT-2) GIL-FIR-006 FQC (ii) H.V.Test 100% IS:7098(PT-2) IS:7098(PT-2) -do- FQC To be reviewed by client / Conslt. 2 TYPE TEST (iii) Partial Discharge Test 100% IS:7098(PT-2) IS:7098(PT-2) -do- FQC (A) Test on Conductor (i) Conductor resistance test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) GIL-FIR-002 FQC (ii) Annealing Test(Cu.) 1 sample / size IS:8130/84 IS:8130/84 -do- FQC (iii) Tensile Strength(Al.) 1 sample / size IS:8130/84 IS:8130/84 -do- FQC (iv) Wrapping Test(Al.) 1 sample / size IS:8130/84 IS:8130/84 -do- FQC (B) TEST FOR THICKNESS OF INSULATION & SHEATH (i) Thickness of insulation 1 sample / size IS:7098(PT-2) IS:7098(PT-2) GIL-FIR-002 FQC (ii) Thickness of inner sheath 1 sample / size IS:7098(PT-2) IS:7098(PT-2) FQC (iii) Thickness of outer sheath 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (C) PHYSICAL TEST ON INSULATION : To be reviewed by client / Conslt. (i) Hot set Test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) GIL-FIR-002 FQC (ii) (iii) Tensile strength & Elongation before ageing 1 sample / size IS:7098(PT-2) IS:7098(PT-2) Tensile strength & Elongation after ageing 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (iv) Shrinkage Test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (v) Water Absorption Test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (Gravimetric) Page 5 of 8

(D) PHYSICAL TEST ON SHEATH (i) Tensile strength & 1 sample / size IS:5831/84 IS:5831/84 GIL-FIR-002 FQC Elongation before ageing (ii) Tensile strength & 1 sample / size IS:5831/84 IS:5831/84 -do- FQC Elongation after ageing (iii) Shrinkage Test 1 sample / size IS:5831/84 IS:5831/84 -do- FQC (iv) Hot Deformation Test 1 sample / size IS:5831/84 IS:5831/84 -do- FQC (v) Loss of Mass Test 1 sample / size IS:5831/84 IS:5831/84 -do- FQC (vi) Heat Shock Test 1 sample / size IS:5831/84 IS:5831/84 -do- FQC (vii) Thermal stability Test 1 sample / size IS:5831/84 IS:5831/84 -do- FQC To be reviewed by client / Conslt. (E) TEST ON ARMOUR WIRES/STRIPS (i) Dimensions 1 sample / size IS:3975/88 IS:3975/88 GIL-FIR-002 FQC Strips of the sample drum (ii) Tensile strength & 1 sample / size IS:3975/88 IS:3975/88 -do- FQC Elongation Test (iii) Torsion/Winding Test 1 sample / size IS:3975/88 IS:3975/88 -do- FQC (iv) Weight of zinc coating test 1 sample / size IS:3975/88 IS:3975/88 -do- FQC (v) Dip Test 1 sample / size (vi) Resistivity Test 1 sample / size IS:3975/88 IS:3975/88 -do- FQC Page 6 of 8

(F) ELECTRICAL TEST (i) Volume resistivity test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) GIL-FIR-002 FQC for insulation (ii) High voltage test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (iii) Partial Discharge test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (iv) Bending Test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (v) Dielectric power factor test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (vi) Heating Cycle Test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC To be reviewed by client / Conslt (vii) Impulse withstand test 1 sample / size IS:7098(PT-2) IS:7098(PT-2) -do- FQC (G) TEST FOR FRLS PROPERTIES (i) Oxygen Index Test 1 sample / size ASTMD 2863 Min.29% ASTMD 2863 GIL-FIR-005 FQC FQC (ii) Temp.Index Test -do- Min.250 Deg.C ASTMD 2863 -do- FQC (iii) Acid Gas Generation Test -do- IEC 754(PT-I)Max.20% IEC 754(PT-I) -do- FQC (iv) Smoke Density Test -do- ASTMD 2843 ASTMD 2843 -do- FQC Max.SDR 60% (v) Flammability Test -do- IEC 332(PT-I),IEEE 383 IEEE 383, IEC 332(PT-I) -do- FQC 4 ACCEPTANCE TEST (NO.OF SAMPLE DRUMS AS PER IS:7098(PT-II)SAMPLING PLAN FOR ACCEPTANCE TEST) (i) Conductor resistance test As per 7098 (Pt- II) IS:7098(PT-II) IS:7098(PT-II) GIL-TEMP-008 FQC (ii) Annealing Test (Cu.).do IS:8130:84 IS:8130:84 -do- FQC (iii) Tensile strength(al.).do IS:8130:84 IS:8130:84 -do- FQC To be witnessed by client /conslt. (iv) Wrapping Test (Al.).do IS:8130:84 IS:8130:84 -do- FQC Page 7 of 8

(v) Thickness of insulation.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (vi) Thickness of inner sheath.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (vii) Thickness of outer sheath.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (viii) Hot set test.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (ix) Tensile strength & Elongation(before ageing).do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (x) Volume resistivity test.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC for insulation (xi) High voltage test.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC (xii) Partial discharge Test.do IS:7098(PT-2) IS:7098(PT-2) -do- FQC To be witnessed by client /conslt. (xiii) TEST FOR FRLS PROPERTIES (ONE SAMPLE FROM ANY SIZE/LOT) (a) Oxygen Index Test On any one size /Lot ASTMD 2863 Min 29% ASTMD 2863 -do- FQC (b) Temp.Index Test " Min.250 Deg.C ASTMD 2863 -do- FQC (c) Acid gas generation test IEC 754(PT-I)Max.20% IEC 754(PT-I) -do- FQC (d) Smoke density test " ASTMD 2843 ASTMD 2843 -do- FQC Max.SDR 60% (e) Flammability Test " IEC 332(PT-I) IEC 332(PT-I),IEEE 383 -do- FQC IEEE 383, Page 8 of 8