SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

Similar documents
3 MODIFICATIONS TO EXISTING STANDARDS

*** Supercedes: BECO E and COM , , & ***

15 kv EPR Insulated, Jacketed, URD Cable

Clark Public Utilities

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

PV Solar Wiring Solutions

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR


STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

Standard of Practice - Campus Electrical Distribution System

Glossary Of Terms M-1

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

MATERIAL STANDARD FOR CABLES AND WIRES

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution

PILC Replacement: Getting the Lead Out

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

City of Jacksonville Beach

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

Accelerated Aging Tests for MV Cables

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

11-SDMS-01 REV. 03 ( )

catalog Copper Wires

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

Tele-Fonika Cable Americas

Technical Data. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

NEMA Standards Publication No. WC ICEA Publication No. S

DISTRIBUTION TRANSFORMER SPECIFICATION #

Cables ELE E L CT E C R T R IC I C A A L L

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

SECTION INSULATED WIRE AND CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

U.V resistance UL Sunlight Resistance. Flame retardant IEC

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

26/35kV Copper XLPE Insulation Electric Cable

PO Box 1081 Monticello, MN Ph Fax

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

Engineering Data for Copper and Aluminum Conductor Electrical Cables

HDPE Conduit Specification 2011

6A V CVQ cable (C rank)

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

America s Wire Company

Test Report No.: Page 2 of 35

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9

System No. SP777 (FOR HORIZONTAL OR VERTICAL SEPARATIONS)

SECTION WIRES AND CABLES

SSC Series. Cold Shrink Splice 2017 PRODUCT GUIDE. 15/25kV Class. 35kV Class

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

Welding Accessories

ANSI/NEMA WC ICEA S Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

TI 20 PVC TI 20 INSULATED TELEPHONE WIRE

BURNDY. Accessories TABLE OF CONTENTS. Heavy Wall Heat Shrinkable End Cap... F-9. Introduction... F-2. Clear Heat Shrink Tubing...

3M Cold Shrink Joint, SC145-II/SS145-II

INTERNATIONAL STANDARD

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

EHV XLPE CABLES CDCC LINE

DETAIL SPECIFICATION CABLES, (POWER AND SPECIAL PURPOSE) AND WIRE, ELECTRICAL (300 AND 600 VOLTS)

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

40/69 kv to 127/220 kv XLPE

SPECIFICATION FOR FRLS POWER CABLES

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

Una e mpre sa Vi akab l e GLOSSARY.

BLACK EPR INSULATED MEDIUM VOLTAGE CABLES. Ronald F. Frank, Eng. Consultant

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

Technical Specification for Substation 11kV and 22kV Single Core Underground Cable

DUO-THERM 505 Specification Guide

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

System No. C-AJ-8048

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request.

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

Transcription:

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION 1.0 SCOPE 1.1 This specification covers the construction, mechanical, and electrical requirements of single conductor, 15 kv, 25 kv, and 35 kv rated underground power cables. The cable shall be suitable for installation on grounded-wye distribution systems at the applicable voltage. 1.2 Conductor sizes of 1/0 AWG through 1,000 kcmil are included. 1.3 The conductor shall be insulated with either ethylene propylene rubber (EPR) or tree retardant crosslinked polyethylene (TR-XLPE) as specified by the purchaser in Attachment A. 1.4 The neutral shall consist of concentrically wound copper wires. 1.5 Unless otherwise specified in Attachment A, the cable assembly shall include a non-conducting outer jacket. 1.6 The cable shall be suitable for direct burial in wet or dry locations. 1.7 The cable shall be designed for continuous operating temperature of 90 C, a maximum emergency temperature of at least 130 C, and a maximum allowable short circuit temperature of 250 C. 2.0 APPLICABLE SPECIFICATIONS 2.1 The cable shall meet or exceed the requirements of the latest revision of the Rural Utilities Service (RUS) Bulletin 50-70 (U-1), titled RUS Specification for 15, 25, and 35 kv Primary Underground Power Cable. This specification shall be referred to hereafter as the RUS U-1. 2.2 The cable assembly shall meet all applicable materials, constructions, and testing requirements of the latest revision of the Insulated Cable Engineers Association, Inc. (ICEA), standard number ICEA S-94-649, titled Standard for Concentric Neutral Cables Rated 5,000 46,000 Volts. This standard j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 1

has been certified by the American National Standards Institute (ANSI) and will be referred to as ANSI/ICEA hereafter. 2.3 Where provisions of the RUS U-1 specification or the ANSI/ICEA standard conflict with this specification, or each other, the provisions of this specification shall apply. 3.0 CONDUCTOR CHARACTERISTICS 3.1 The central conductor shall be concentric lay Class B stranded, compressed aluminum as per the ANSI/ICEA and RUS U-1. 3.2 The conductor shall consist of round wire strands in ¾ or full hard, 1350 alloy, meeting the requirements of the RUS U-1 and ANSI/ICEA. 3.3 The interstices between the strands of the conductor shall be filled with a sealant designed to prevent the longitudinal migration of moisture that might enter the conductor. This material must meet the requirements of RUS U-1 and ANSI/ICEA. The presence of the compound in conductor interstices shall not degrade the performance of compression connectors. 3.4 The center strand of the conductor shall be indented with the manufacturer s name and year of manufacture as per ANSI/ICEA. 4.0 CONDUCTOR SHIELD 4.1 The conductor shall be covered with an extruded, smooth, extra clean, conductor shield material (stress control layer). The conductor shield shall meet the requirements of the RUS U-1 and ANSI/ICEA, except as specified herein. 4.2 The conductor shield shall be semi-conducting for discharge-free EPR insulated cables, non-conducting for discharge-resistant EPR insulated cables, and semi-conducting for TR-XLPE insulated cables. For TR-XLPE insulated cables, the conductor shield shall be a supersmooth compound. 4.3 The contact surface between the conductor shield and the insulation shall have no protrusions into the insulation greater than 5 mils (0.127 mm) for EPR insulated cables and 3 mils (.076 mm) for TR-XLPE insulated cables. 4.4 The purchaser reserves the right to specify the acceptable compound(s) to be used in the conductor shield; please refer to Attachment A. j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 2

5.0 INSULATION 5.1 The insulation shall be ethylene propylene rubber (EPR) or tree retardant crosslinked polyethylene (TR-XLPE) as specified by the purchaser in Attachment A. The insulation shall meet the requirements of the RUS U-1 and ANSI/ICEA, except as specified herein. 5.2 Unless otherwise specified in Attachment A, the thickness of the insulation shall meet the following requirements, in mils, for the rated voltages: Voltage Minimum Nominal Maximum 15 kv 210 220 250 25 kv 245 260 290 35 kv 330 345 375 5.3 The minimum and maximum diameter over the insulation shall meet the requirements of the ANSI/ICEA for the entire length of the cable. To insure conformance, measurements shall be made as per the ANSI/ICEA. 5.4 The purchaser reserves the right to specify the acceptable compound(s) to be used in the insulation; please refer to Attachment A. 6.0 INSULATION SHIELD 6.1 A smooth, extra clean, semi-conducting, thermosetting, polymer material shall be tightly extruded over the insulation to serve as an electrostatic shield and protective covering. The insulation shield shall meet the requirements of the RUS U-1 and the ANSI/ICEA, except as specified herein. 6.2 The insulation shield shall be compatible with all materials with which it is in contact, readily distinguishable from the insulation, and plainly identified as semi-conducting. For TR-XLPE insulated cables, the insulation shield shall be extruded over the insulation by a true 3-IN-1 triple extrusion process. 6.3 The minimum and maximum diameter over the insulation shield shall meet the requirements of the ANSI/ICEA for the entire length of the cable. To insure conformance, measurements shall be made as per the ANSI/ICEA. j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 3

6.4 The shield material shall be readily removable as per the ANSI/ICEA, except that the tension necessary to remove the insulation at room temperature shall be as follows: 0-18 lbs. for discharge-resistant EPR cables, 3-18 lbs. for discharge-free EPR cables, and 6-18 lbs. for TR-XLPE cables. 6.5 The purchaser reserves the right to specify the acceptable compound(s) to be used in the insulation shield; please refer to Attachment A. 7.0 CONCENTRIC NEUTRAL 7.1 The concentric neutral shall be composed of round annealed, uncoated copper wires, meeting the requirements of the RUS U-1, and the ANSI/ICEA as it applies to jacketed cable. Neutral wires shall have uniform spacing between wires with no wires touching. 7.2 Cables with central conductors sized 1/0 AWG and 4/0 AWG, shall have full sized neutrals. Cables with central conductors sized 350 kcmil through 1000 kcmil, shall have 1/3 sized neutrals. The size and number of wires shall be according to the tables in the ANSI/ICEA. A reduced neutral design may be specified in Attachment A. If so, the size and number of wires shall be according to the tables in the ANSI/ICEA. For every design, the minimum acceptable wire size used shall be 16 AWG. 8.0 OUTER JACKET 8.1 Unless otherwise specified in Attachment A, a non-conducting outer jacket shall be extruded over the concentric neutral wires as per the requirements of the RUS U-1 and the ANSI/ICEA. The outer jacket shall encapsulate the concentric neutral wires. 8.2 The non-conducting outer jacket material shall be black, linear low density, polyethylene (LLDPE). If a semi-conducting material is specified in Attachment A, it shall be as per the RUS U-1. 8.3 Three red stripes shall be extruded into the outer surface of the jacket as per ANSI/ICEA; the stripes shall be spaced evenly at 120 apart. j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 4

8.4 The outer surface of the jacket shall be suitably marked throughout its length with clear, durable, indented markings, to indicate the following information: Name of manufacturer, year of manufacture, central conductor size and material, voltage rating, type of insulation, nominal thickness of insulation, jacket type, and the National Electrical Safety Code (NESC) symbol for an electric supply cable. There shall be no more than 6 inches of unmarked space between cable identification. 8.5 Sequential footage markings shall be applied to the outer surface of the jacket at regular intervals of 2 feet. 9.0 TESTING 9.1 Production tests shall be performed as per the most stringent requirements of the RUS U-1 and ANSI/ICEA specifications. The manufacturer shall provide the purchaser with a certified test report on the production testing at the time of cable delivery. The report shall clearly demonstrate the manufacturer s compliance with all requirements included in this specification. 9.2 Upon request, the manufacturer shall provided the purchaser with copies of the results of any or all qualification testing that is required by the RUS U-1 and ANSI/ICEA specifications. 10.0 SHIPPING 10.1 The cable shall be shipped on non-returnable wooden reels unless otherwise specified by the purchaser in Attachment A. A weather resistant tag or label shall be securely attached to the reel providing the following information: Cable description, beginning and ending sequential footage, total footage, gross weight and tare weight, and purchaser s name and purchase order number. 10.2 Watertight, heat shrink or cold shrink seals shall be applied to the cable ends to prevent the entrance of moisture during transit or storage. Each cable end shall be firmly secured to the reel. A weather resistant covering shall be applied over the outer layer of the cable on the reel. If specified in Attachment A, protective wood lagging shall be installed on reels containing cable with conductor sizes of 350 kcmil through 1000 kcmil. j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 5

10.3 The cable must be shipped with the reels in an upright position supported by both outside flanges. Delivery should be via a flat bed truck with provision for side unloading. 10.4 Unless otherwise specified in Attachment A, the maximum outside dimensions for all reels shall be as follows: Cable Size Width Diameter 1/0 AWG and 4/0 AWG 38 66 350 kcmil through 1000 kcmil 48 72 10.5 The total gross weight of the reel and cable shall not exceed 5,000 pounds; a tolerance of +/- 5% shall be allowed. j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 6

SOUTH CAROLINA ELECTRIC COOPERATIVES PRIMARY UNDERGROUND POWER CABLE SPECIFICATION ATTACHMENT A Cooperative Name: Contact: Phone #: Fax #: E-Mail: Conductor Size: 1/0 4/0 350 500 750 1000 Voltage Rating: 15 KV 25 KV 35 KV Conductor Shield Compound(s): Insulation Type: EPR Only TR-XLPE Only EPR or TR-XLPE Alt. Insulation Thickness: Min. Nominal Max. Insulation Compound(s): Insulation Shield Compound(s): Alt. Neutral Design: Full 1/3 1/6 1/8 1/12 Alt. Outer Jacket Type: Semi-Conducting: Yes No Alt. Reel Type: Returnable: Yes No Wood Lagging: Required: Yes No Alt. Reel Size (inches): Width Diameter Shipping Address: Signature: Date: Last Revised: 4/10/02 j:\materials Stds Comm\SCEC Primary Cable Spec - 041202 7