calibrated gas flows from the room burner.

Fire Testing Laboratory TEST REPORT

Fire Testing Laboratory TEST REPORT FOR THERMORY USA, LLC Wilmette Avenue, Suite 208 Wilmette, IL 60091

REPORT NUMBER: SAT-001A_Rev.2 ORIGINAL ISSUE DATE: April 7, 2015 REVISED DATE: July 21, 2015

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A

Test Summaries: AWP 1818 & 3030

Impact of NFPA 285 on Air Barrier Specification and Design

3.0 DESCRIPTION. Division: Thermal and Moisture Protection Section: Thermal Insulation

UL 1715 TESTING FOR DURABLIS ON JETBOARD WITH ELFOAM P200 AND MAGNUM BOARD WITH ELFORM P200 VTEC # TESTED: MARCH 11, 2015

BXUV.V481. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

ASTM E Fire Tests of Building Construction and Materials* Protective Structures, Ltd. Bullet-Resistant FRP Panel

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

NFPA 285 Assemblies. Table of Contents

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: TAKTL, LLC

TEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No:

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

Exterior Wall Systems NFPA 285

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Guardian Fire Testing Laboratories, Inc. Phone: ; Fax: Wenonah Terr. (Office) Lab Phone & Fax:

Engineering Analysis of NFPA 285 Tested Assemblies

Title: WF Report No: Prepared for: Alstrong Enterprises India (PVT) Limited E-40/3, Okhla Industrial Area, New Delhi, India Date: 15 th June 2015

NFPA 285 Assemblies. Table of Contents

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

BRE Global Test Report

THE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB)

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6

Burtin Polymer Laboratories 2 SwRI Project No e[1]

UL Design System HW-D-1012 continued

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

SECTION GYPSUM BOARD ASSEMBLIES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

SECTION GYPSUM BOARD SYSTEM

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

WFCi Report # Conducted For: Supress Products LLC. 5/8 Supress Sound-Engineered Drywall SED58410C; U305 Design

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018

Deer Ridge Consulting, Inc.

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SECTION GYPSUM BOARD SYSTEM

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

Originally Issued: 03/28/2014 Revised: 05/25/2017 Valid Through: 03/31/2018

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY

Duct Wrap Flexible Wraps

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018

ICC-ES Evaluation Report Reissued February 1, 2011 This report is subject to re-examination in one year.

NATIONAL GYPSUM COMPANY 2-Hour Area Separation Wall System

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

ICC-ES Evaluation Report Reissued February 1, 2012 This report is subject to renewal February 1, 2013.

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PRODEMA USA INC. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE

Gold Bond BRAND Gypsum Sheathing

Trusted ICC ES DIVISION: 07 SECTION: 07 (VFS) Evaluation. report, or as to any. ICC-ES Evaluation

Originally Issued: 02/01/2019 Valid Through: 02/28/2020

BXUV.U435. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

GA APPLICATION OF GYPSUM SHEATHING

SECTION GYPSUM BOARD ASSEMBLIES

OBJECTIVE TEST ASSEMBLY

SECTION COLD-FORMED METAL FRAMING

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

SECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications.

Originally Issued: 03/28/2014 Revised: 05/19/2017 Valid Through: 03/31/ General

Originally Issued: 03/28/2014 Revised: 05/19/2017 Valid Through: 03/31/ General

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

CommercialComplete Wall System

R-Matte Plus-3: Insulation for the Building Envelope

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016.

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

WALL ASSEMBLIES. PHILLIPS MANUFACTURING CO. - Omaha, NE USA DESIGN NO. PMC/WA DESIGN NO. PMC/WA 60-01

BRE Global Client Report

BXUV.U415 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

REPORT NUMBER: SAT-004A ORIGINAL ISSUE DATE: April 13, 2017 REVISED DATE:

TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS

SECTION COLD-FORMED METAL FRAMING

Gold Bond BRAND Kal-Kore Plaster Base

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

138 H-STUD AREA SEPARATION WALL SYSTEM

Transcription:

Fire Testing Laboratory Page 1 of 39 TEST REPORT for 2148 S. 41st Street Lousiville, KY 40211 Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing Wall Assemblies Containing Combustible Components NFPA 285 Test Report No: Assignment No: K-1239 Subject Material: Exterior Non-Loadbearing SILBONIT Panel Ventilated Wall System Test Date: March 12, 2019 Report Date: Prepared by: Michael J. Rizzo Senior Test Engineer Reviewed by: Robert J. Menchetti Director, Laboratory Facilities and Testing Services The results reported in this document apply to specific samples submitted for measurement. No responsibility is assumed for the performance of any other specimen. The laboratory s test report in no way constitutes or implies product certification, approval or endorsement by this laboratory. This report may not be reproduced, except in full, without the written approval of the laboratory. 1650 Military Road Buffalo, NY 14217-1198 (716) 873-9750 Fax (716) 873-9753 www.ngctestingservices.com

Page 2 of 39 Revision Summary DATE SUMMARY Original issue date. Original NGCTS report.

Page 3 of 39 Table of Contents Introduction.. 4 Test Assembly Description... 4 Testing and Evaluation Methods.6 Test Results.. 8 Conclusion 11 Appendix A: Thermocouple Location Diagrams....12 Appendix B: Thermocouple Graphical Data.......16 Appendix C: Construction Photographs....26 Appendix D: Test Photographs........32

Page 4 of 39 Introduction The NFPA 285 test apparatus is used to evaluate the fire propagation characteristics of exterior non-load-bearing wall assemblies and panels used as components of curtain wall assemblies that are constructed using combustible materials or that incorporate combustible components within the wall assemblies as specified in the following: A. The ability of the wall assembly to resist flame propagation over the exterior face of the wall assembly. B. The ability of the wall assembly to resist vertical flame propagation within the combustible core or within other combustible components from one story to the next. C. The ability of the wall assembly to resist vertical flame propagation over the interior surface of the wall assembly from one story to the next. D. The ability of the wall assembly to resist lateral flame propagation from the compartment of fire origin to adjacent compartments or spaces. This report contains a description of the material evaluated, procedures used, and the test results. Note that the results listed apply only to specimens tested, in the manner tested, and not to the entire production of this or similar specimens. Test Assembly Description The test assembly was installed on a moveable frame constructed of steel I-beams and steel angles as specified per the NFPA 285 test standard. CORE WALL The core wall assembly consisted of 6 in. deep, 20-gauge galvanized steel studs fastened to 14 ft. length, 20-gauge galvanized steel track, every 24 in. on center. Two additional studs were installed in the wall to accommodate the prescribed window opening. All studs were connected to the track with #6 x 1/2 in. long self-drilling screws. Roxul AFB mineral wool insulation, 6 in. thick by 24 in. wide, was friction fit into the stud cavities of the core wall. INTERIOR WALL CLADDING The interior wall was clad with National Gypsum 5/8 in. thick Type X gypsum board fastened to the core wall with #10 x 1-1/4 in. long bugle head self-drilling drywall screws with a nominal spacing of 8 in. on center on the perimeter and 12 in. on center in the field. The gypsum board was installed, on both the first and second story floors, with the long dimension running perpendicular with the steel studs. All joints were treated with paper joint tape and joint compound. All screw heads were covered with joint compound.

Page 5 of 39 WINDOW OPENING A window opening was made from 20-gauge galvanized steel track and was centered on the vertical centerline of the wall assembly with the finished sill of the opening 30 in. above the first story floor line. The steel track sections were fastened to the core wall s steel stud framing with #6 x 1/2 in. long self-drilling screws. The steel track sections of the window opening were lined with strips of 5/8 in. thick Georgia-Pacific DensGlass Sheathing. The window opening was finished with a coating of GE Elemax* 5000 Liquid Flashing, applied per manufacturers specification. The dimensions of the completed window opening were 78 in. wide x 30 in. tall, per the requirements of NFPA 285. EXTERIOR SHEATHING The exterior sheathing consisted of 5/8 in. thick Georgia-Pacific DensGlass Sheathing that was applied horizontally and fastened to the stud wall with #10 x 1-1/4 in. long bugle head self-drilling screws with a nominal spacing of 8 in. on center. AIR & WATER BARRIER GE Elemax* 2600 AWB silicone membrane was applied over the full surface of the exterior sheathing with a medium nap roller. The application rate was verified to be 19 mils wet, per manufacturer s installation instructions. Z-FURRING STRIPS A series of 18-guage Z-furring strips were applied to the exterior sheathing, first in the horizontal orientation and then in the vertical orientation. All Z-furring strips consisted of a Z profile and were nominally 1/2 in. deep by 3-1/4 in. wide. The horizontally applied strips were attached to the steel studs 24 in. on center using #14 x 2-1/4 in. long TEK screws. The vertically orientated strips were attached to the horizonal strips using #10 x 1/2 in. TEK screws. On one leg of the vertical Z-furring strips only, nominal 1-1/4 in. by 1/8 in. EPDM rubber strips were attached with spray adhesive. EXTERIOR CLADDING PANELS The exterior cladding panels consisted of 5/16 in. thick SILBONIT panels, provided in various sizes with pre-drilled holes for attachment. The SILBONIT panels were applied horizontally, over the full exterior surface of the assembly, directly to the vertical Z-furring strips using #10 x 1 in. PN-T20 screws. All vertical and horizontal panel gaps were nominally 3/8 inches. The configuration did not include a vertical joint over the window opening and in the area of the flame plume.

Page 6 of 39 Testing and Evaluation Methods Testing was performed on March 12, 2019 in accordance with test method NFPA 285, 2019 edition. The assembly was secured onto the laboratory s intermediate scale multistory test apparatus (ISMA) and any gaps were filled with ceramic fiber blanket with a density of 128 kg/m 3. CALIBRATION INFO The test apparatus was calibrated on May 24, 2018 and followed the procedure and practices outlined in NFPA 285, Chapter 7. The apparatus is under calibrated conditions when the time average heat flux readings and the time average temperatures obtained during a calibration test meet the requirements of Table 7.1.1 of NFPA 285. Table 1 shows the average heat flux and Table 2 shows the average temperature obtained during the calibration test. All values are within the allowable ranges as specified in Table 7.1.1 (±10%). Time Interval (min) Average Heat Flux @ 2 ft. (W/cm2) Average Heat Flux @ 3 ft. (W/cm2) Average Heat Flux @ 4 ft. (W/cm2) 0:00-5:00 0.81 0.86 0.67 5:00-10:00 1.65 2.20 1.48 10:00-15:00 2.67 2.36 1.79 15:00-20:00 3.08 2.95 2.02 20:00-25:00 3.92 3.11 2.48 25:00-30:00 4.41 3.72 2.73 Table 1: Average Heat Flux Output Data from Calibration Test (5/24/18) Time Interval (min) Avg. Burn Room Temp. ( F) Avg. Interior Wall Temp. ( F) Avg. 1 ft. Temp. ( F) Avg. 2 ft. Temp. ( F) Avg. 3 ft. Temp. ( F) Avg. 4 ft. Temp. ( F) Avg. 5 ft. Temp. ( F) Avg. 6 ft. Temp. ( F) 0:00-5:00 1139 1007 616 691 644 529 498 385 5:00-10:00 1333 1272 875 959 980 832 795 652 10:00-15:00 1468 1421 971 1042 1078 926 921 754 15:00-20:00 1561 1528 1049 1113 1165 990 1009 825 20:00-25:00 1590 1565 1086 1137 1199 1033 1073 875 25:00-30:00 1669 1651 1136 1190 1256 1102 1158 925 Table 2: Average Time-Temperature Values from Calibration Test (5/24/18)

Page 7 of 39 THERMOCOUPLES The test assembly/apparatus was fitted with a total of 54 Type-K thermocouples which were distributed as per Figures 6.1 of NFPA 285. Thermocouple locations diagrams are provided in Appendix A. The first story burn room ceiling was instrumented with five, 18- gauge Type K thermocouples, while the specimen was instrumented with forty-nine, 20- gauge Type K thermocouples. The specimen thermocouples included twenty-three in the cavity air space, thirteen on the exterior façade, and nine on the interior wall surface. The thermocouple data, which was recorded at approximate 3-4 second intervals by a Fluke 2680A data acquisition system. ROOM and WINDOW BURNERS The window burned was positioned in the center of the opening and 1 in. off the exterior face of the test specimen. The position of the window burner was determined during the calibration of the test apparatus on May 24, 2018. Time Interval During Calibration During Test Room Burner Window Burner Room Burner Window Burner 0:00-5:00 37.8 SCFM 0 SCFM 37.8 SCFM 0 SCFM 5:00-10:00 37.9 SCFM 7.9 SCFM 37.8 SCFM 7.9 SCFM 10:00-15:00 42.7 SCFM 10.5 SCFM 42.7 SCFM 10.5 SCFM 15:00-20:00 45.8 SCFM 14.6 SCFM 45.8 SCFM 14.6 SCFM 20:00-25:00 45.8 SCFM 17.3 SCFM 45.8 SCFM 17.3 SCFM 25:00-30:00 49.9 SCFM 20.2 SCFM 49.9 SCFM 20.2 SCFM *SCFM: Standard Cubic Feet per Minute Table 3: Room Burner and Window Burner Gas Flow Data

Page 8 of 39 Test Results Recorded ambient conditions at the start of testing were 67 F and 34% relative humidity. An anemometer was used to verify that the airflow across the test assembly was less than 4 ft./sec., as specified in the test method. The test was commenced at 11:01 am with the room and window burners turned on for 30 and 25 minutes, respectively. After the burners were turned off, the specimen was monitored for an additional 10 minutes. TEST OBSERVATONS The following observations were made during the fire test. Test Time (min:sec) Observations from Front (Exterior Face) of Test Specimen 0:00 Test start; ignition of the room burner 01:30 Light smoke from top of assembly 02:10 Initial audible cracking of exterior cladding panels 3:00 Light spalling of exterior cladding panel above window opening 4:27 Increased spalling of first panel above window opening 5:00 Ignition of window burner 5:11 Flaming of liquid flashing around window opening 5:30 Moderate-to-heavy smoke from top of assembly 6:58 Initial spalling of second panel above window opening 10:00 Continued sporadic spalling of first two panels above window opening 14:39 Initial spalling of third panel above window opening 20:00 Continued sporadic spalling of first three panels above window opening 28:01 Initial spalling of fourth panel above window opening 30:00 Test terminated and gas to burners shut off. Beginning of 10-minute observation period. 35:00 Test specimen stable. 40:00 End of the observation period; NFPA 285 testing completed.

Page 9 of 39 CONDITIONS OF ACCEPTANCE Performance Criteria Test Observations Pass/Fail Flames emitting from the surface of the exterior face of the test specimen shall not reach a height of 10 ft. or greater above the top of the window opening Flames emitting from the surface of the exterior face of the test specimen shall not reach a horizontal distance of 5 ft. or greater from the vertical centerline of the window opening. Flames shall not occur in second-story test room. Flames did not reach 10 ft. above the window opening. Flames did not reach a lateral distance of 5 ft. from the vertical centerline. There was no visible flaming in the second-story test room. Pass Pass Pass Flames shall not occur beyond the intersection of the test specimen and the side walls of the apparatus. Temperatures shall not exceed 1000 F as measured by thermocouples TC11 and TC14 through TC17. Temperatures in the combustible components shall not exceed 750 F above their temperature at the start of the test as measured by TC28 and TC31 through TC40. Temperatures in the combustible components shall not exceed 750 F above their temperature at the start of the test as measured by TC18 and TC19. Temperatures measured 1 in. from the interior surface of the test specimen within the second-story test room shall not exceed 500 F above the ambient air temperature of the test facility at the start of the fire test as measured by TC49 through TC54. Flames did not reach beyond the intersection of the test specimen and the side walls. TC11 and TC14 through TC17 did not exceed the 1000 F limit. TC28 and TC31 through TC40 did not exceed the maximum temperature of 817 F. (750 F + 67 F = 817 F) TC18 and TC19 did not exceed the maximum temperature of 817 F. (750 F + 67 F = 817 F) TC49 through TC54 did not exceed the maximum temperature of 567 F. (500 F + 67 F = 567 F) Pass Pass Pass Pass Pass

Page 10 of 39 EXTENT OF DAMAGE Interior Wall Cladding: The interior gypsum was still intact after the test. The exposed gypsum in the first-story test room was heavily fatigued, showing signs of flame damage. The second-story interior gypsum was almost completely unblemished and showed no signs of flaming. Z-Furring Strips: The Z-furring strips located directly above the window opening were observed to have flame damage up to 5 ft. and discoloration up to the top of the assembly. The EPDM rubber strips on those Z-furring channels had melted away up to 5 ft. above the window opening. Air & Water Barrier/Exterior Sheathing: Charring of the GE Elemax* 2600 AWB and exterior sheathing was evident within the area of the flame plume up to 6 ft. above the window header. Lateral damage did not extend beyond the vertical plane of the window opening jambs. Discoloration of the AWB was evident up to the top of the assembly above the window opening header. Exterior SILBONIT Cladding Panels: Cracking and spalling of the SILBONIT cladding panels were evident up to and including the fourth panel above the window opening. Lateral damage was evident across the entire width of the first panel above the window opening, narrowing on the way up to the fourth panel. Charring of the panels was evident up to the third panel above the window header.

Page 11 of 39 Conclusion The Fire Testing Laboratory of NGC Testing Services conducted testing for Cement Board Fabricators on a SILBONIT Panel Ventilated Wall System assembly, to evaluate its fire propagation characteristics. Testing was conducted in accordance with the applicable requirements of, and following the standard methods of, NFPA 285 Standard Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components, 2019 Edition. This evaluation took place on March 12, 2019. Based on the data and associated observations from this test, the test assembly described in this report met the conditions of acceptance of NFPA 285.

Page 12 of 39 Appendix A Thermocouple Location Diagrams

Page 13 of 39 Figure 1: Thermocouple Locations on Exterior Wall Surface and in Cavity Air Space

Figure 2: Thermocouple Locations on Interior Wall Surface Page 14 of 39

Page 15 of 39 Figure 3: Thermocouple Locations Inside First Story Burn Room (Top View) Figure 4: Thermocouple Depth Specifications per Figure 6.1(b) Detail G of NFPA 285 Standard

Page 16 of 39 Appendix B Thermocouple Graphical Data

Page 17 of 39 1600 1400 1200 1000 800 600 400 200 0 NFPA 285 Exterior Surface - Assembly Centerline Temperatures 0 5 10 15 20 25 30 Time (minutes) TC01 TC02 TC03 TC04 TC05 TC06 TC07 TC08 TC09 TC10 TC11 TC12 TC13 Temperature (deg. F) Graph 1: Exterior Surface - Assembly Centerline Temperatures (TC01 TC13)

Page 18 of 39 800 700 600 500 400 300 200 100 0 NFPA 285 Exterior Surface - 10' Above Window Opening Header Temperatures 0 5 10 15 20 25 30 Time (minutes) TC11 TC14 TC15 TC16 TC17 Temperature (deg. F) Graph 2: Exterior Surface - 10' Above Window Opening Temperatures (TC11, TC14 TC17)

Page 19 of 39 1600 1400 1200 1000 800 600 400 200 0 NFPA 285 Air Cavity Space - Assembly Centerline Temperatures 0 5 10 15 20 25 30 Time (minutes) TC20 TC21 TC22 TC23 TC24 TC25 TC26 TC27 TC29 TC30 Temperature (deg. F) Graph 3: Air Cavity Space - Assembly Centerline Temperatures (TC20 TC30)

Page 20 of 39 800 700 600 500 400 300 200 100 0 NFPA 285 Air Cavity Space - 10' Above Window Opening Header Temperatures 0 5 10 15 20 25 30 Time (minutes) TC28 TC34 TC35 TC39 TC40 Temperature (deg. F) Graph 4: Air Cavity Space 10' Above Window Opening Temperatures (TC28, TC34-35, TC39 TC40)

Page 21 of 39 160 140 120 100 80 60 40 20 0 NFPA 285 Air Cavity Space - Left of Centerline Temperatures 0 5 10 15 20 25 30 Time (minutes) TC18 TC31 TC32 TC33 Temperature (deg. F) Graph 5: Air Cavity Space Left of Assembly Centerline Temperatures (TC18 and TC31 TC33)

Page 22 of 39 140 120 100 80 60 40 20 0 NFPA 285 Air Cavity Space - Right of Centerline Temperatures 0 5 10 15 20 25 30 Time (minutes) TC19 TC36 TC37 TC38 Temperature (deg. F) Graph 6: Air Cavity Space Right of Assembly Centerline Temperatures (TC19 and TC36 TC38)

Page 23 of 39 2000 1800 1600 1400 1200 1000 800 600 400 200 0 NFPA 285 First-Story Test Room Ceiling Temperatures 0 5 10 15 20 25 30 Time (minutes) TC41 TC42 TC43 TC44 TC45 Temperature (deg. F) Graph 7: First-Story Test Room Ceiling Temperatures (TC41 TC45)

Page 24 of 39 2000 1800 1600 1400 1200 1000 800 600 400 200 0 NFPA 285 First-Story Test Room Interior Wall Surface Temperatures 0 5 10 15 20 25 30 Time (minutes) TC46 TC47 TC48 Temperature (deg. F) Graph 8: First-Story Test Room Interior Wall Surface Temperatures (TC46 TC48)

Page 25 of 39 140 120 100 80 60 40 20 0 NFPA 285 Second-Story Test Room Interior Wall Surface Temperatures 0 5 10 15 20 25 30 Time (minutes) TC49 TC50 TC51 TC52 TC53 TC54 Temperature (deg. F) Graph 8: Second-Story Test Room Interior Wall Surface Temperatures (TC49 TC54)

Page 26 of 39 Appendix C Construction Photographs

Photo 1: Core Wall Construction Page 27 of 39

Photo 2: GE Elemax* 2600 AWB Applied to Exterior Sheathing Page 28 of 39

Page 29 of 39 Photo 3: Horizontal and Vertical Z-Furring Strips and Start of SILBONIT Panel Installation

Photo 4: Complete SILBONIT Panel Installation Page 30 of 39

Page 31 of 39 Photo 5: Complete Interior First-Story Test Room Photo 6: Complete Interior Second-Story Test Room

Page 32 of 39 Appendix D Test Photographs

Photo 1: Test Specimen After Ignition of Room Burner Page 33 of 39

Photo 2: Test Specimen after Ignition of Window Burner Page 34 of 39

Photo 3: Cracking and Spalling of SILBONIT Panels Page 35 of 39

Photo 4: Test Specimen After Burners Extinguished Page 36 of 39

Photo 5: Burn Pattern of SILBONIT Panels Page 37 of 39

Photo 6: Burn Pattern of AWB After SILBONIT Panels Removed Page 38 of 39

Photo 7: Interior Second-Story Test Room Post-Test Page 39 of 39