Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station

Similar documents
DETERMINATION OF CLEARANCE DISTANCES FOR VENTING OF HYDROGEN STORAGE

International Energy Agency Hydrogen Implementing Agreement. Task 19 Hydrogen Safety. KNOWLEDGE GAPS IN HYDROGEN SAFETY A White Paper.

American Society of Safety Engineers Middle East Chapter 11th Professional Development Conference & Exhibition Kingdom of Bahrain, March 16-20, 2014

Previous Relevant Experience

ABS TECHNICAL PAPERS 2007

A Risk Informed Assessment of Hydrogen Dispensing in Warehouses

NUTC R203. Safety Risks of Hydrogen Fuel for Applications in Transportation Vehicles. Shravan K. Vudumu

Hydrogen behavior in a large-dry pressurized water reactor containment building during a severe accident

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Hydrogen behaviour when released in confined atmospheres: experimental study and numerical simulations

Numerical analysis of hydrogen and methane propagation during testing of combustion engines

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

Factors Impacting Atmospheric Discharges and Selection of Pressure Protection Disposal Systems

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics

PERFORMANCE BASED EVALUATION OF FIRE SCENARIOS USING FLUENT

COMPRESSED AIR SYSTEM DESIGNS BEGIN WITH THE DEMANDS

PERFORMANCE BASED EVALUATION OF FIRE SCENARIOS USING FLUENT

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT

Computational Fluid Dynamics Modelling: Example Output

LNG dispersion over the sea

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

Large Scale Outdoor Flammable & Toxic Gas Dispersion Modelling in Industrial Environments.

Live Transportation Research and Improvement Initiatives

UTC R170. Hydrogen Flammability Limits and Implications on Fire Safety of Transportation Vehicles. Umit O. Koylu

Spray Booth Guideline

Volume 2, Issue 2 (2014) ISSN International Journal of Advance Research and Innovation

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

Numerical and Experimental Modeling of Producer Gas Carburettor

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Vipac Engineers & Scientists Ltd

Estimation of the Air-Demand, Flame Height, and Radiation Load from Low-Profile Flare using ISIS-3D

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

CONSEQUENCE ASSESSMENT OF THE BBC HYDROGEN REFUELING STATION, USING THE ADREA-HF CODE

Improving Steel Plant Work Environment

Japan-Norway Hydrogen seminar Collaboration within hydrogen future market and value chain. Petter Ellingsen 28th February 2017.

Guide to Permitting Hydrogen Motor Fuel Dispensing Facilities

EXHAUST SYSTEMS CHAPTER 5

CFD SIMULATION OF HEAVY GAS DISPERSION IN VENTILATED ROOMS AND VALIDATION BY TRACING EXPERIMENTS

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

SIMULATION OF THE EFFICIENCY OF HYDROGEN RECOMBINERS AS SAFETY DEVICES

Numerical analysis of CO concentration distribution on extraction ventilation type tunnel Tao Guo 1,a, Jun Zhou 2,b, Xiaonan Liu 3,c and Bo Shang 4

Propane Tests at Chesapeake Building

Transient and Succession-of-Steady-States Pipeline Flow Models

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

Consequence Modeling and PSM Wilbert Lee Senior Staff Process Risk Engineer Chevron Energy Technology Company

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Experimental Evaluation of LPG Release and Dispersion in the Enclosed Car Parks

CFD Analysis of a Mixture Flow in a Producer Gas Carburetor for optimizing the design configuration

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Strategies and Intervention tactics - FC stationary installations

ADVANCES in NATURAL and APPLIED SCIENCES

Source Characterization of Ammonia Accidental Releases for Various Storage and Process Conditions

BASICS OF HYDROGEN SAFETY FOR FIRST RESPONDERS. Lecture. Hazards of hydrogen use indoors

Pipe Flow Hydraulics

SITING STUDY FOR THE GRASSY POINT LNG TRANSSHIPMENT AND STORAGE TERMINAL

PLUME ANALYSIS AND CFD MODELING FOR EFFECTIVE EAF MELTSHOP ENVIRONMENT CONTROL

Use of CFD in the Performance-Based Design for Fire Safety in the Oil and Gas Sector

Computational Fluid Dynamics (CFD) Simulations of Dispersed Flow of Viscous Oil in Water in a Horizontal Pipe

CRYOGENIC FLUIDS CHAPTER 55

Latest Advances in Hydrogen Safety R&D

SIMULATION AND SAFETY ANALYSIS OF THE LEAKAGE OF LIQUEFIED HYDROGEN FROM HIGH-PRESSURE CONTAINER

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

Experimental Validation of a Computational Fluid Dynamics Model for IAQ applications in Ice Rink Arenas

Numerical Prediction of Thermodynamics and Heat Transfer Characteristics of Nano Fluid.

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Consequence Modeling and PSM Wilbert Lee Safety Technology Unit Chevron Energy Technology Company

NUMERICAL SIMULATION AND OPTIMIZATION OF SOLID-LIQUID TWO-PHASE FLOW IN A BACK-SWEPT AXIAL FLOW PUMP

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

NUMERICAL MODELING OF THE INFLUENCE OF ANGLE ADJUSTMENT OF A/C DIFFUSER VANES ON THERMAL COMFORT IN A COMPUTER ROOM

CFD STUDY OF THE UNIGNITED AND IGNITED HYDROGEN RELEASES FROM TRPD UNDER A FUEL CELL CAR

Paraffin Deposition Progress Report April June 2003

Assessment of Toxic Gas Dispersion using Phast and Panache

A Numerical Investigation on bubble formation in Coolant channel with various Ethylene Glycol and water compositions and change in contact angle

Ullage Temperatures in Wet Spent Fuel Transport Flasks.

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

Survey of RCS and Best Practices for Liquid Hydrogen

PVP INVESTIGATION OF A SHELL AND TUBE EXCHANGER IN LIQUEFIED NATURAL GAS VAPORIZATION SERVICE

Air Distribution and Microenvironment Evaluation of a Desktop Task. Conditioning System 1

Computer Models For Fire and Smoke

Thermal Management of Densely-packed EV Battery Set

Numerical Simulation of Core Gas Defects in Steel Castings

VALIDATION OF PRODUCER GAS CARBURETOR USING CFD

Drums, Vessels, & Storage Tanks. Design Considerations

Testing of Novel Application of GOTHIC to Modelling of Hydrogen Distribution in Intermediate Level Waste Storage Facilities 16499

Aeronex Gas Purification System HX Series

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

MODELLING & SIMULATION OF LASER MATERIAL PROCESSING: PREDICTING MELT POOL GEOMETRY AND TEMPERATURE DISTRIBUTION

Study of ventilation reversion of airflow in mining roadways and tunnels by CFD and experimental methods

putational domain contained 8 blocks surrounding the central one. All 9 blocks had the same arrangement. Each block comprised a total of 72 residentia

Calculate the Costs of Piping System Elements

Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents. Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri

Transcription:

Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station Abstract Andrei TCHOUVELEV, Gary HOWARD and Vladimir AGRANAT Stuart Energy Systems Corporation 5101 Orbitor Dr., Mississauga ON L4W 4V1 CANADA E-mail: atchouvelev@stuartenergy.com This paper presents the comparison of IEC60079-10, CSA B108:99, NFPA 52 and API Standards requirements for determining sizes of hazardous locations with simulation results obtained by computational fluid dynamics (CFD) modeling. International standard IEC60079-10 determines the size of a hazardous location by a calculation of the hypothetical combustible volume caused by a fluid leak under specific temperatures, and ventilation rates. Canadian standard CSA B108:99 and American standard NFPA 52 use a prescriptive method to assign the size of a hazardous location depending on fuel quantities contained in the equipment. Considering hydrogen high buoyancy and diffusivity, requirements of both standards are likely too conservative. The PHOENICS CFD software package was used to solve the continuity, momentum and concentration equations with the appropriate boundary conditions, buoyancy model and turbulence models. Numerical results on hydrogen concentration predictions were obtained in the real industrial environment, which is the Hydrogen Energy Station (HES) produced by Stuart Energy Systems Corporation. Keywords: Standard, hazardous location, CFD modeling, PHOENICS, hydrogen, numerical simulation. Introduction In the absence of specific regulations, codes and standards that would address installation of hydrogen systems, IEC60079-10, and CSA B108:99, as well as NFPA 52 have been extensively used for design and installation of Stuart Energy s Hydrogen Energy Stations (HES) in various jurisdictions. API 505 is also being used as a reference document. It has been long suspected by hydrogen experts that, due to hydrogen high buoyancy and diffusivity, requirements of both standards are likely too conservative and result in inaccurate combustible volumes for hydrogen and higher than necessary hazardous zones. This, in turn, results in higher than necessary use of classified components that eventually increase the overall cost of the Hydrogen Energy Station. To address this issue, Computational Fluid Dynamics (CFD) software was used to model potential releases of hydrogen under various conditions of the Hydrogen Energy Station. The obtained CFD numerical simulation results were compared with the requirements of the above standards. 1

Modeling Scenario Description This paper discusses one of the potential failure scenarios hydrogen release into the Generator Room of the Hydrogen Energy Station from the electrolytic hydrogen generator CF450 during self-purging start-up procedure. At start-up, to ensure only high purity gas is directed for compression, hydrogen is being vented for 10 min. After 10 min a regulator driven by PLC logic re-directs hydrogen flow from vent to process. The point of potential release the vent pipe at the roof of the hydrogen generator. The outlet pipe size is 2 and the constant flow rate is 0.0035 Nm3/s. This is a low- pressure release (P = 1 psig). This worst case scenario assumes, conservatively, that at the start-up the generator vent pipe comes off and all hydrogen that is generated during these 10 min is vented inside the Generator Room, and hydrogen sensors fail to detect the leak until after 10 minutes. Thus, this potential hydrogen release has maximum duration of 10 min. Modeling Approach The solid objects inside the Generator Room and on the roof were accurately represented in modeling domains as per provided engineering drawings of the Hydrogen Energy Station. Hydrogen convection, diffusion, buoyancy and transience were modeled based on the general 3-D conservation equations and the details of various scenarios were introduced via the proper initial and boundary conditions. PHOENICS software was chosen for the purpose of modeling of these scenarios. PHOENICS is a well-recognized general-purpose CFD software package that has been validated and successfully used around the world for more than 20 years [1]. One of the advantages of PHOENICS is that it contains the LVEL model, a proper turbulence model allowing for both laminar and turbulent flow conditions to be considered. The local Reynolds numbers in every cell of the computational mesh can be computed so that they accurately reflect the local effective viscosities, which include both laminar and turbulent components. This allows for accurate modeling of fluid flow conditions within the whole domain. Another important feature of the modeling approach was the use of transient conditions for computing the releases and dispersion of hydrogen clouds according to the requirements of different scenario conditions. First, the modeling was performed under steady-state conditions without any hydrogen leak. The velocity profiles obtained from the steady state were then used as the initial conditions for the during-the -release simulations, which were performed with a hydrogen leak at the specified rate and time increments. After- release simulations predicted the hydrogen dispersion in the room below 10% of the LFL. Note that both during- release and after- release simulations were transient, allowing for: (i) inclusion of the transient behavior of all calculated variables (pressure, gas density, velocity and hydrogen concentration); (ii) simulation of the movement of hydrogen clouds with time; as well as, (iii) evaluation of the hydrogen generator room safety by analyzing the iso-surfaces 2

of the hydrogen concentration. To account for the effect of hydrogen buoyancy, the gas mixture density was calculated as an inverse-linear function of the mass concentration of hydrogen, C1, with coefficients based on the physical densities of air and hydrogen under the specified conditions. The buoyancy force, acting on the fluid particles, was proportional to the difference between the transient local gas mixture density and the constant reference density of air under the specified conditions. As a result, the significance of the buoyancy force in various room locations depended on the transient 3-D hydrogen mass fraction distribution. The latter was calculated from the standard mass conservation equation of hydrogen (see [1] for more details). This modeling approach was validated by comparing Stuart Energy System Corporation s (SESC) PHOENICS CFD modeling results to the experimental and computational data of Swain et al. [2] for a case of slow hydrogen release and dispersion in a hallway. PHOENICS predictions of the transient behavior of hydrogen compared well with the experimental results [3]. Results Before Leak Simulation The existence of a louver and a exhaust fan in the Generator Room creates a steady-state airflow with 3-D fluid flow pattern. This airflow was simulated first, before trying to simulate the transient 3-D behaviour of hydrogen cloud introduced by a particular hydrogen release, since it provides initial fields of gas velocity and pressure for the release scenario considered below. Figure 1 shows ventilation velocities created by the louver and the exhaust fan. Figure 1. Ventilation velocities (X- and Y-planes) before leak. 3

Leak Simulation: Release from hydrogen generator vent line The leak scenario considers the case when, for whatever reason, during the CF hydrogen generator start-up self-purging procedure the hydrogen vent line on the roof of CF comes off, thus causing all hydrogen being produced during the self-purging procedure (10 min) to leak into the Generator Room. It is also assumed that all hydrogen sensors intended to shut down the CF during the self-purging procedure are disabled. Room ventilation is provided by the louver and the exhaust fan (1 m 3 /s). CFD predictions of 3-D hydrogen concentration distribution are shown in Figures 2 and 3. Figure 2 illustrates the H 2 (4% vol.) iso-surface at the end of the release (10 min) and Figure 3 shows the H 2 (2% vol.) iso-surface at the end of the release. It is seen that the sizes of these two clouds are very different. Figure 2. End of 10-min release from the CF vent line (4% hydrogen cloud). 4

Figure 3. End of 10-min release from the CF vent line (2% hydrogen cloud). Size of flammable mixture cloud (CFD approach) The size of the flammable cloud was calculated, using the programmability of the PHOENICS CFD software. Three global quantities, DOMV, P4H and P2H were defined as the volume (in m 3 ) of the whole domain (DOMV), the volume of the hydrogen cloud with more than 4% volume concentration (P4H) and the volume of the hydrogen cloud with more than 2% volume concentration (P2H) respectively. The printout from the global calculations file is shown below Global calculations: DOMV = 229.9500 P4H = 8.0717586E-02 P2H = 6.225283 It is seen that the 4% cloud volume (P4H), which is about 0.081 m 3, is much smaller than the volume of cloud with 2% volume concentration (P2H), which is about 6.225 m 3. Both clouds are much smaller in volume than the whole domain volume (DOMV), which is about 230 m 3. 5

Requirements of IEC 60079-10 IEC 60079-10 sets out the essential criteria against which the risk of ignition can be assessed, and gives the guidance on the design and control parameters that can be used in order to reduce such a risk. The important criteria are: the LFL of the gas, leak rate, concentration and grade of release the degree and availability of ventilation and if there are any obstacles Calculation to ascertain the degree of ventilation within Container Gas Compartment The following method of ventilation calculation was taken from IEC 60079-10 2002. Characteristics of release Flammable material Hydrogen gas Source of release vent pipe Lower Explosive limit (LFL) 3.3 x 10-3 kg/m 3 (4% vol) Grade of release Secondary Safety factor, k (applied to LFL) 0.5 (secondary release) Release rate (dg/dt) = 12.6 Nm 3 /hr = (H 2 density = 0.084 kg/m 3 at 20C, = density = 0.090 at 273C) 12.6 Nm 3 /hr = 0.00305 m 3 /sec x 0.090kg/m 3 = 0.000275 kg/sec Gas concentration in release X o = 100% Ventilation Characteristics Generator room Volume = 7.3m x 7.5m x 4.2 m = 230 m 3 equipment volume = 185 m 3 Fan airflow = 1 Nm3/sec = 3600 Nm 3 /hour Number of air changes, C = 3600 m 3 /hr/185m 3 = 19.5/hr = 0.0054/sec Quality factor, f = 2 (There are few obstacles to impede airflow) Ambient temperature, T = 35C (308K) Temperature coefficient, (T/293 K) = 1.05 Minimum volumetric flow rate of fresh air: 4 ( dg / dt) max T 2.75 10 308 ( dv / dt) min = = = 0.175m 3 k LEL 293 0.5 3.3 10 293 Evaluation of hypothetical volume V z 3 /sec f ( dv / dt) C 2 0.175 0.0054 min V z = = = 64.8m 3 6

Conclusion The hypothetical volume V z of 65 m 3 is significant relative to the room volume of 230 m 3 and would likely result in a Zone 2 room classification for at least the upper third of the room. Requirements of CSA B108:99 Section 7.14 of CSA B108 states a vent shall be provided to direct any natural gas being purged or released from the piping system of a fuelling station to a safe outdoor location. Table 7.1 Electrical Classification of Space Surrounding Vents (Relief valve vents) Class I Zone I Distance from vents The distance shall be 100 vent orifice diameters, within 15 deg. of the line of discharge Class I Zone II 1.8 m (6 ft. in all directions from the opening, excluding the Zone 1 space. For a 2 inch vent the area classification is = 200 inches = 16.7 ft. = 5 m plus an additional 1.8 m around this volume for a total of volume of 33 m 3. (This requirement is for a pressure relief device which assumes a high pressure/volume leak). NFPA 52 Requirements - Table 6.4.3.8 Electrical Installations Location Discharge from relief va lves or vents Outdoors Outdoors Division or Zone 1 2 Extent of Area Classification 5 ft (1.5 m) in all directions from the point source Beyond 5 ft (1.5 m) but within 15 ft Discharge from relief valves within 15 1 15 ft (4.6 m) in all directions from point degrees of the line of discharge of discharge Dispensing equipment - indoors 2 Entire room with adequate ventilation API 505 Requirements Section 6.6.2 defines: adequate ventilation (natural or artificial) that is sufficient to prevent the accumulation of significant quantities of vapor -air or gas-air mixtures in concentration above 25 percent of LFL). Section 6.6.2.4.2 states adequate ventilation for enclosed areas is at least 1 ft 3 /min per square foot of floor but at least 6 air changes per hour. The air changes required for the 55 m 2 (589 ft 2 ) generator room would be 35340 ft 3 /hr for 8122 ft 3 room which = 4.35 per hour. As 6 air changes minimum are required, the fan capacity must be 8122 x 6/60 = 812 cfm = 23 m 3 /min = 0.38 m 3 /sec, about one third the actual fan capacity. With this fan installed, the calculated hypothetical volume from IEC 60079-10 would be 167 m 3. 7

Comparison of results Model Hazardous location volume m 3 CFD modeling of 100% LFL H 2 0.081 m 3 cloud (4% vol. H2 in air) CFD modeling of 50% LFL H 2 cloud 6.2 m 3 (2% vol. H2 in air) IEC 60079-10 65 m 3 CSA B108 15 deg. 5m high cone 6.8 m dia. at base = 33 m 3 NFPA 52 4.57 m sphere = 50 m 3 API 505 Requires a minimum fan capacity of 0.38 m 3 /sec resulting in 167 m 3 hypothetical volume NFPA 52 and CSA B108 consider the discharge from high pressure CNG. Summary The analysis performed in this paper suggests that requirements of IEC60079-10, CSA B108:99 and NFPA 52 for the size of hazardous locations could be considered too conservative. CFD numerical simulations indicate that the size of potentially flammable cloud, even in the case of all hydrogen generator production leaking into the Generator Room of the Hydrogen Energy Station, is one tenth of that prescribed by the above standards. For this situation API 505 may not require sufficient ventilation but also refers to IEC 60079-10. The prime reason for the discrepancies is that CSA, NFPA and API do not consider the actual leak rate. IEC 60079-10 gives a very conservative result. References 1. PHOENICS Hard-copy Documentation (Version 3.5). Concentration, Heat and Momentum Limited, London, UK, September 2002. 2. M.R. Swain, E.S. Grilliot and M.N. Swain, Risks Incurred By Hydrogen Escaping From Containers And Conduits, Proceedings of the 1998 U.S. DOE Hydrogen Program Review, NREL/CP-570-25315. 3. V. Agranat, Z. Cheng and A. Tchouvelev, CFD Modeling of Hydrogen and Helium Releases and Dispersion in Hydrogen Energy Station, Proceedings of WHEC 15 Yokohama, 2004. 8