SECTION SELF-ADHERING SHEET FLASHING

Similar documents
SECTION MODIFIED BITUMINOUS SHEET AIR BARRIERS

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

A. Section includes fluid applied, vapor permeable membrane air barriers.

SECTION SHEET MEMBRANE WATERPROOFING

SECTION FIRE RESIST 705 VP FULLY-ADHERED SHEET AIR & WATER RESISTIVE BARRIER

Student Services & Classroom Addition

SECTION (07100) - DAMPPROOFING AND WATERPROOFING

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION SELF-ADHERING SHEET WATERPROOFING CCW-711

GUIDE SPECIFICATION FOR MEL-ROL : ROLLED, SELF-ADHERING WATERPROOFING MEMBRANE

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

SECTION SELF-ADHERING SHEET MEMBRANE WATERPROOFING

SECTION FLUID-APPLIED MEMBRANE AIR & VAPOR BARRIERS

Section Pre-Applied Sheet Membrane Waterproofing

SECTION DAMPPROOFING AND WATERPROOFING

A. The work of this section includes, but is not limited to, the following:

SECTION FLASHING AND SEALING FRAMING WITH NON-CHEMICAL TERMITE BARRIERS

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

SECTION TW-60 Self-Adhering Sheet Waterproofing Membrane

SECTION FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER

SECTION AIR AND VAPOR BARRIERS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SECTION FLUID-APPLIED WATERPROOFING

D. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for waterproofing.

SELF-ADHERING SHEET WATERPROOFING

DIVISION 7 MARFLEX 5000 FLUID APPLIED AIR & VAPOR BARRIER - 3 PART SPEC 07262

UNIFIED FACILITIES GUIDE SPECIFICATION

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION SUPERGREEN LAM (LIQUID-APPLIED MEMBRANE AIR/VAPOR BARRIER SYSTEM)

PART 2 - AIR BARRIERS SELF-ADHESIVE

SECTION FIRE-RESISTANT FLUID-APPLIED MEMBRANE AIR BARRIERS (BARRITECH VP)

SPECIFICATION GUIDELINE

MODIFIED BITUMINOUS SHEET AIR / VAPOUR BARRIERS SELF ADHESIVE

SPECIFICATION GUIDELINE

BUILDING ENVELOPE DESIGN GUIDELINES APPENDIX 3

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.

SECTION FIRE RESIST BARRITECH VP/ VP LT BURN-RESISTANT, FLUID-APPLIED, VAPOR- PERMEABLE MEMBRANE AIR BARRIERS

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS. A. Section Includes: 1. Fluid-applied, vapor-impermeable, water-resistive membrane air barriers.

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required. A. Section Mechanical Insulation.

PERM-A-BARRIER NPS Detail Membrane

SECTION AIR / MOISTURE / VAPOR BARRIERS 1

SECTION FLUID APPLIED VAPOR PERMEABLE AIR BARRIER MEMBRANE

SRP-AirOutshield UV Issued:

SECTION SELF-ADHERING SHEET WATERPROOFING

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

Aussie Skin 550. Heavy Duty Below Grade, Blind-Side, Under-Slab Waterproofing Membrane. Delivery, Storage, and Handling

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants.

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING

SECTION ANTI-FRACTURE MEMBRANE UNDERLAYMENT

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Aussie Skin 550. Heavy Duty Below Grade, Blind-Side, Under-Slab Waterproofing Membrane. Delivery, Storage, and Handling

SECTION VAPOR PERMEABLE FLUID-APPLIED AIR BARRIER MEMBRANE

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal

University of New Hampshire Scholars' Repository

ABAA SPECIFICATION FOR MEDIUM-DENSITY CLOSED-CELL SPRAY POLYURETHANE FOAM AIR BARRIER SECTION 07263

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING

Perm-A-Barrier NPS (Non Permeable Sheet)

SECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING

RECOMMENDED DESIGN SPECIFICATION

SECTION Self-adhered sheet membrane water resistive air barriers, vapor permeable

Product Guide Specification

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION SELF-ADHERING SHEET WATERPROOFING (PRM / PROTECTED WALL SYSTEM)

PART 4 - SELF ADHERING WATERPROOFING

PERM-A-BARRIER VPS. Product Description. Product Data Sheets. Self-adhering vapor permeable air and water barrier membrane

BENTONITE WATERPROOFING

DIVISION 7-THERMAL AND MOISTURE PROTECTION

Guide Specification for the OSI QUAD Window and Door Flashing System

PART 1 GENERAL 1.1 SECTION INCLUDES. A. Below grade waterproofing and dampproofing 1.2 RELATED SECTIONS 1.3 REFERENCES

Air and Vapor Barrier 3015

SECTION Blown Insulation THERMAL INSULATION

SECTION VAPOR PERMEABLE FLUID-APPLIED AIR BARRIER MEMBRANE

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

SECTION FLUID-APPLIED AIR & WATER-RESISTIVE BARRIER SYSTEM FOR NEW CONSTRUCTION

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

SECTION SINGLE-PLY ROOFING SYSTEM

A. Submit product data sheets and literature verifying fire ratings and physical properties of materials.

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

Tensile ASTM D1970 MD = 939 psi / CD = 1252 psi Self Sealability / water penetration resistance around nails. ASTM D1970 Section 7.

AFM Anti-Fracture Membrane & AFM-WM Anti-Fracture Waterproofing Membrane Three-Part Specifications

SECTION SELF-ADHERING SHEET WATERPROOFING (650 MEMBRANE SYSTEM)

Delivery, Storage, and Handling

SECTION SELF-ADHERING SHEET WATERPROOFING (650 MEMBRANE SYSTEM)

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SOLAR COATING SYSTEMS ACRYLIC RENOVATION ROOF 4.5. Specification for Built-Up Roofing SUMMARY

WEIGHT PER PIECE (LBS.)

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

Perm-A-Barrier VPS (Vapor Permeable Sheet)

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

DIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories

A. Supplier Qualifications: The ACRYSHIELD SPF Roofing System, as supplied by National Coatings Corporation, is approved for use on the project.

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

A. Submit product data sheets and literature verifying physical properties of materials.

Transcription:

MANUFACTURER S GUIDE SPECIFICATIONS SECTION 076526 SELF-ADHERING SHEET FLASHING 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 604129 03.24.15 Carlisle, Flexphalt, Sure-Seal and CAV-GRIP are trademarks of Carlisle. 2015 Carlisle.

SECTION 07 65 26 PART 1 GENERAL 1.01 SECTION INCLUDES A. Self-adhering through-wall flashing and accessory products by Carlisle Coatings & Waterproofing. B. Materials and installation of self-adhering through-wall flashing assemblies as indicated on drawings. C. Through-wall flashing and accessories for installation in cavity wall construction in the following locations: 1. Wall bases 2. Window sills 3. Heads of openings 4. Shelf angles 5. Tops of walls 6. Parapets 7. Above projections such as bay windows 8. At other discontinuities in the cavity 1.02 PRODUCTS INSTALLED BUT NOT SUPPLIED UNDER THIS SECTION: Masonry cavity drainage products (weeps and mortar drip screen) provided in Section 04 05 23 Masonry Accessories. Metal drip edge provided in Section 07 62 00 Sheet Metal Flashing and Trim. 1.03 RELATED SECTIONS A. Section 03 30 00 - Cast-In-Place Concrete: Concrete back-up walls, concrete footer B. Section 04 05 23 Masonry Accessories: Weeps, mortar drip screen C. Section 04 20 00 - Unit Masonry: concrete masonry unit (CMU) back-up walls D. Section 06 16 00 Sheathing: Exterior sheathing over wall studs E. Section 07 11 00 Damp Proofing: bituminous damp proofing installed over CMU or concrete back-up walls 07 65 26-1

F. Section 07 21 00 - Thermal Insulation: Board insulation applied to exterior side of wall G. Section 07 25 00 Weather Barriers: 15# felt or building wrap installed over exterior sheathing H. Section 07 62 00 - Sheet Metal Flashing and Trim: Metal throughwall flashings, metal drip edge I. Section 07 90 00 - Joint Protection: Joint sealant materials and installation. J. Section 09 29 00 - Gypsum Sheathing: Gypsum sheathing over metal studs. K. Section [ ] Other 1.04 REFERENCES A. ASTM D 146 Standard Test Methods for Sampling and Testing Bitumen Saturated Felts and Woven Fabrics for Roofing and Waterproofing B. ASTM D 412 Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers Tension C. ASTM D 570 Standard Test Method for Water Absorption of Plastics D. ASTM D 903 Standard Test Method for Peel and Stripping Strength of Adhesive Bonds E. ASTM D 1876 Standard Test Method for Peel Resistance of Adhesive F. ASTM D 4263 Standard Test Method for Indicating Moisture Content by Plastic sheet Method G. ASTM E 96 Standard Test Methods for Water Vapor Transmission of Materials. H. ASTM E 154 Standard Test Methods for Water Vapor Retarders used in Contact with Earth under Concrete Slabs, on Walls or as Ground Cover 07 65 26-2

1.05 PERFORMANCE REQUIREMENTS A. Provide a membrane constructed to perform as a through-wall flashing durably integrated with the wall assembly s water resistive barrier and cavity drainage system. The installed through-wall flashing shall perform as a liquid water drainage plane to discharge incidental condensation or water penetration to the exterior through the cavity drainage system. B. Provide a fully-adhered, water proof membrane through-wall flashing of minimum 0.040 inch (40 mils) thickness consisting of 0.032 inch (32 mils) rubberized asphalt adhesive fully-coating 0.008 inch (8 mils) smooth surface, cross-laminated HDPE film. Membrane shall meet the following requirements: 1.06 SUBMITTALS REQUIREMENT RESULT TEST METHOD Tensile Strength Not less than 900 psi ASTM D-412 Puncture Resistance Not less than 80 lb. ASTM E 154 Low Temperature Unaffected at ASTM D 146 Flexibility minus 25 degrees F, 0.063 inch mandrel Peel Adhesion Not less than 5 lb per inch ASTM D 903 width on concrete prepared with contact adhesive Lap Adhesion Not less than 5 lb. per inch ASTM D 1876 width Water Vapor Not more than 0.05 Perm ASTM E-96, Method Permeance Water Absorption Not more than 0.12 percent by weight B ASTM D 570 A. Provide submittals in accordance with Section 01 33 00 B. At bid submission, provide evidence to the Architect of installer qualification by Manufacturer. C. Shop drawings showing locations of through-wall flashing and details of all typical conditions. D. Manufacturer's technical data sheets and material safety data sheets for Product and Accessories. E. Manufacturer's installation instructions. F. Manufacturer s documentation of volatile organic compounds (VOC) content for Product and Accessories. 07 65 26-3

G. Certification of compatibility by Manufacturer, listing all materials on the Project with which the Product and Accessories may come into contact. H. Samples of Product minimum 3 inch by 4 inch size. 1.07 QUALITY ASSURANCE A. Installer Qualifications: Installer shall be experienced in applying the same or similar materials and shall be specifically approved in writing by Manufacturer. B. Single-Source Responsibility: Obtain Product and Accessories from single manufacturer. C. Product and Accessories shall comply with all state and local regulations controlling use of volatile organic compounds (VOCs). D. Cooperate and coordinate with the Owner's inspection and testing agency. Do not cover any installed Product unless it has been inspected, tested and approved. 1.08 DELIVERY, STORAGE AND HANDLING A. Deliver materials to Project site in original packages with seals unbroken, labeled with manufacturer's name, product, lot number and directions for storage. B. Store materials in their original undamaged packages in a clean, dry, protected location and within temperature range required by Manufacturer. C. Protect stored materials from direct sunlight. Do not store cylinders of Aerosol Contact Adhesive above 110 degrees F. D. Avoid spillage. Immediately notify Owner, [Architect] [Consultant] if spillage occurs and start clean up procedures. Clean spills and leave area as it was prior to spill. 1.09 WASTE MANAGEMENT AND DISPOSAL A. Separate and recycle waste materials in accordance with Section 01 74 19 Construction Waste Management and Disposal, and with the Waste Reduction Work Plan. 07 65 26-4

B. Place materials defined as hazardous or toxic waste in designated containers. C. Ensure emptied containers are stored safely for disposal away from children. 1.10 PROJECT CONDITIONS A. Do not apply during rain or accumulating snowfall. B. Applicator shall have full, safe access to area C. Apply Product and accessories within temperature range indicated in Manufacturer s literature. 1.11 WARRANTIES: Provide the Manufacturer s minimum five year material warranty under provisions of Section 01 78 36 Warranties. PART 2 PRODUCTS 2.01 PRODUCTS: Provide as manufactured by Carlisle Coatings & Waterproofing, Incorporated. 900 Hensley Lane, Wylie, TX 75098. Phone 1-800-527-7092. Website http://www.carlisleccw.com: A. Standard: CCW-705 TWF B. Low-Temp: CCW-705 TWF LT 2.02 ACCESSORIES: Provide as manufactured by Carlisle Coatings & Waterproofing, Incorporated. A. Contact Adhesive, select one: 1. CCW-702 or CCW-702 LV Solvent-Based 2. CCW-702 WB Water-Based 3. CAV-GRIP Aerosol Spray B. Mastic:LM 800 XL solvent-based synthetic rubber C. Fill Compound: 1. CCW-703 V Modified polyurethane, 2-part 2. LM 800 XL Solvent-based, synthetic rubber, 1-part 3. CCW-201 Polyurethane, 2-part D. Termination Bar: SURE-SEAL Termination Bar 07 65 26-5

PART 3 EXECUTION 3.01 EXAMINATION A. Examine substrates, areas, and conditions affecting installation of the through-wall flashing and accessory products for compliance with requirements. Verify that surfaces and conditions are suitable prior to commencing Work of this section. Do not proceed with installation until unsatisfactory conditions have been corrected. B. Concrete shall be cured for a minimum of seven days. C. Surfaces shall be sound, dry and free of oil, grease, dirt, excess mortar or other contaminants. D. Surfaces shall be supported and flush at joints without large voids or sharp protrusions. E. Ledge, footing, shelf angle or lintel surfaces shall be flat, or preferably sloped to provide drainage to the exterior. Surfaces shall not be oriented so that water can pond on the through-wall flashing. F. Inform Architect [Consultant] [Owner] in writing of anticipated problems applying Product over substrate. 3.02 SURFACE PREPARATION A. Fill joints and cracks greater than ¼ inch width with Fill Compound struck flush. B. Fill inside corners and angle changes with minimum ½ inch tooled bead of Fill Compound. 3.03 INSTALLATION A. Allow Fill compound used in Article 3.02 to cure fully before applying Product. B. Apply Product to sound substrate. Do not apply over mechanicallyattached water resistive barrier such as felt, paper or house wrap. C. Prepare all surfaces accepting Product with Contact Adhesive. Observe installation instructions, including coverage rates and drying times, indicated in Manufacturer s literature. 07 65 26-6

D. Apply Product over prepared surfaces according to Manufacturer s instructions and drawings. E. Apply Mastic to edges of Product at laps, cuts and penetrations. F. Secure vertical termination of Product with Termination Bar and Mastic, reglet with Mastic, or cast-in-place according to Manufacturer s instructions and drawings. G. Keep edge of product at least ½ inch away from exterior finish. 3.04 SCHEDULE A. Install through-wall flashing during or after construction of back-up wall. B. Install through-wall flashing before or during installation of brick veneer. C. Lap water resistive barrier over vertical termination of through-wall flashing on back-up wall. Lap and secure water resistive barrier according to water resistive barrier manufacturer s instructions. D. Integrate through-wall flashing with adhered membrane air barrier, damp proofing or water-resistive barrier according to Manufacturer s instructions and drawings. 3.05 REPAIR AND PROTECTION A. Protect from damage during application and remainder of construction period. B. Inspect before covering and make repairs according to Maufacturer s instructions.. Remove and replace damaged material. C. Product is not designed for permanent exposure. Cover with exterior cladding as soon as schedule allows. D. Outdoor exposure of installed Product shall not exceed 60 days. END OF SECTION 07 65 26-7