COOLING LOAD ANALYSIS IN CLASSROOMS: A CASE STUDY IN FEDERAL UNIVERSITY OF SAN FRANCISCO VALLEY, BRAZIL

Similar documents
DETERMINATION OF ENERGY INDEX FOR SHOPPING CENTERS IN BRAZIL

The use of Simulation Software to Evaluate the Thermal Performance of Buildings in Brazil

COOLING LOAD ESTIMATION OF A ROOM

Application of the adaptive model proposed by ASHRAE 55 in the Brazilian climate context: raising some issues

The Impact Of Climate Change On The São Francisco River s Hydroelectric Production

Dynamic Simulation of an Office Building in Two Different Softwares

Simulation Before Design? A New Software Program for Introductory Design Studios

THERMAL COMFORT ANALYSIS OF BUILDINGS USING THEORETICAL AND ADAPTIVE MODELS Hélder Silva Almeida

447 - Thermal Performance of Residential Buildings in Lisbon with Large Glazing Areas

Dynamic Simulation of Thermal Behaviour of Sheraton Lisboa Hotel & SPA

Chapter 6. Space heating load

Simplified methods to evaluate energy use for space cooling in the energy certification

IMPACT ANALYSIS OF WINDOWS IN BUILDING THERMAL PERFORMANCE Jorge Filipe da Cruz Sirgado Lisbon, October 2010

ECONOMIC VIABILITY AND SELECTION OF IRRIGATION SYSTEMS USING SIMULATION AND STOCHASTIC DOMINANCE 1 SUMMARY

COMPARISON OF DIFFERENT MECHANICAL SYSTEMS MODELS FOR A PASSIVE SOLAR GREENHOUSE WITH TWO THERMAL ZONES

S. LONGO. The paper shows analysis of the impact on thermal comfort of natural ventilation in a nonresidential Mediterranean case-study.

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

Influence of Glazed Façades on Energy Consumption for Air Conditioning of Office Buildings in Brazilian Climates

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Practitioner Modeling Competition

Evaluation methods for indoor environmental quality assessment according to EN15251

Free trade area United States of America/ European Union

USE OF SIMULATION TOOLS FOR MANAGING BUILDINGS ENERGY DEMAND. Alberto Hernandez Neto, Flávio Augusto Sanzovo Fiorelli

Practitioner Modeling Competition

STUDY OF THE THERMAL COMFORT, OF THE ENERGY CONSUMPTION AND OF THE INDOOR ENVIRONMENT CONTROL IN SURGERY ROOMS

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

Nota Científica / Short Communication

Measurement of the production performance through the comparison between the budgeted and the actually achieved time: a Case Study

Student Modeling Competition

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento

* Submitted 09/11/2017 Accepted 15/11/2017 DOI: /holos

A Case Study of Energy Demand in Housing Units

COMPUTATIONAL ANALYSIS - Evaluation of the impact of the user expertise on the results of simulation tools

HVAC Equipment Sizing Strategies: Taking Advantage of High-Performance Buildings. EEBA Excellence in Building Conference. Building Science Corporation

THEORETICAL ANALYSIS OF THERMAL PERFORMANCE OF CLAY AND CONCRETE MASONRY STRUCTURAL UNDER VARIOUS CONDITIONS

Student Modeling Competition

A Software for Performance Simulation of Solar Water Heating Systems

Automation of building construction teams using mobile communications

ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.

UC Berkeley Indoor Environmental Quality (IEQ)

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Sample Reports. for. HAP v4.80 Example Problem

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

A Parallel between the Brazilian Energy Labelling System and the Passivhaus Standard for Housing

Influence of Foundation Settlements in Load Redistribution on Columns in a Monitoring Construction Case Study

CAE 331/513 Building Science Fall 2017

Thermal Performance of Toplighting Systems in a Hot and Humid Climate: Thailand

Management System of Distribution Transformer Loading

Economic Feasibility Analysis of Sustainable Construction Measures

Analysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method

CHARACTERIZATION OF INSULATION CORKBOARD OBTAINED FROM DEMOLITIONS

HVAC SYSTEM ENERGY OPTIMIZATION IN INDOOR SWIMMING POOLS

Facades Modules for Eco-Efficient Refurbishment of Buildings: Glazing Thermal Performance Analyses to Coimbra and Faro

Composite with Recyclable Loads for the Manufacture of Blocks to Build Popular Houses

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Selection of Industrial Transport Systems for Surface Mining Project: Ore Pipeline, Trucks, Belt Conveyors

Power Engineering Review - IEEE

A SENSITIVITY STUDY OF BUILDING PERFORMANCE USING 30-YEAR ACTUAL WEATHER DATA

FUEL ETHANOL FROM BRAZILIAN BIOMASS: ECONOMIC RISK ANALYSIS BASED ON MONTE CARLO SIMULATION TECHNIQUES

Circulating load calculation in grinding circuits

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

PG&E Residential New Construction Program Impact Evaluation

INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015

AN OVERVIEW OF THE MAIN TOPICS ON NO-TILLAGE RESEARCHES

MODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING

DETERMINATION OF HYDRAULIC CONDUCTIVITY BY THE AUGER- HOLE METHOD

Passive systems for energy savings of buildings in tropical climate

The Effects of Residential Energy Efficiency on Electric Demand Response Programs

Understanding "Heat Load & Psychometric. by Djunaidi HS

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

ESTIMATING THE IMPACTS OF CLIMATE CHANGE AND URBANIZATION ON BUILDING PERFORMANCE. Drury B. Crawley

VE-Toolkits User Guide <VE> 6.0

Mechanic and Energy. Morro do Cruzeiro UFOP Campus evaluation of indoors climatic conditions. Mecânica e Energia. Abstract. 1.

Sample Reports. for. HAP v4.90 Example Problem

Techno-economic Analysis of Solar Photovoltaic Cooling System: an analysis in four different climates in India

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

A comparison between four dynamic energy modeling tools for simulation of space heating demand of buildings

A COMPARATIVE STUDY TO BENCHMARK ENERGY PERFORMANCE USING BUILDING SIMULATION TOOLS

Metalurgia e materiais

An Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings in Brazil

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Energy Consumption Measurement of Energy-saving Buildings and Analysis of Simulation Example

Therma-Fuser Energy Analysis Report 2016

Keywords: Composite Beam, Friction contribution to horizontal shear connection, flexible connectors.

Acquisition control and health monitoring of creep in concrete specimens

RCCTE was published in February 1990, and have been in force since January It applies to buildings of both residential and tertiary sectors.

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

Opportunities and Limitations of Building Precooling

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Thermal performance of single family residential building according to the methodology of RCCTE calculation

Strength and deformability of hollow concrete blocks: correlation of block and cylindrical sample test results

Use of a Global Building-HVAC System model for Audit

Estimating Industrial Building Energy Savings using Inverse Simulation

Modeling of slab-on-grade heat transfer in EnergyPlus simulation program

Lajes lisas nervuradas bidirecionais com furos

Feasibility Study to Substitute the EER with the SEER Case Study Chiang Mai, Thailand

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

ScienceDirect. Simulation based mixed mode building design

Transcription:

301 COOLING LOAD ANALYSIS IN CLASSROOMS: A CASE STUDY IN FEDERAL UNIVERSITY OF SAN FRANCISCO VALLEY, BRAZIL GOMES, Isabella Gonçalves de Aguiar 1 CASTRO SILVA, José 2 Recebido em: 2016.11.06 Aprovado em: 2017.04.28 ISSUE DOI: 10.3738/1982.2278.2145 SUMMARY: This paper aims to calculate the cooling thermal load of 32 classrooms of Federal University of San Francisco Valley, located in Petrolina, Brazil, using the software EnergyPlus and the graphic user interface OpenStudio. OpenStudio also has a plug-in to Sketchup, which allowed the construction of a tridimensional energetic model of the considered building. EnergyPlus takes into account climatic conditions, schedules, construction materials and internal loads such as people occupancy, lightning and electric equipment, and so it calculates the cooling thermal load. Then the cooling thermal load of a single classroom was calculated by three traditional methods described in the literature, and the results were compared with the one from EnergyPlus. The results of the 32 classrooms differed according to the building story where the classrooms are located, the orientation of walls and windows in each classroom, as well as the internal loads. Regarding the single classroom analysis, the component loads of each method were compared. For some components, such as lightning and electrical equipment, the results were very similar among all the methods, what was not verified for other componentes, such as the infiltration and solar gains. The overall cooling load results from the traditional methods were similar, but too high compared with the results from EnergyPlus. Keywords: Climatization. Heat gains. EnergyPlus. OpenStudio RESUMO: Este trabalho tem por objetivo calcular a carga térmica de resfriamento de 32 salas de aula da Universidade Federal do Vale do São Francisco, em Petrolina, Brasil, utilizando o software EnergyPlus e a interface gráfica de usuário OpenStudio. O OpenStudio possui ainda um plug-in para o SketchUp, o que permitiu a construção de um modelo energético tridimensional do edifício considerado. O EnergyPlus leva em consideração as condições climáticas, horários de funcionamento, materiais de construção e cargas internas (como ocupação, iluminação e equipamentos elétricos), para em seguida calcular a carga térmica. Em seguida, a carga térmica de uma única sala de aula foi calcula por três métodos tradicionais descritos na literatura, e tais resultados foram comparados com o valor obtido pelo EnergyPlus. O resultado das 32 salas de aula variou de acordo com o andar do edifício, a orientação das paredes e janelas em cada sala, bem como com as cargas internas. Para essa sala de aula escolhida, foram comparados os components da carga térmica obtidos com cada método. Alguns components, como iluminação e equipamentos elétricos, apresentaram resultados semelhantes em todos os métodos, o que não foi observado com outros components, como infiltração e ganhos solares. O resultado de carga térmica total dos métodos tradicionais foi muito semelhante, mas elevado em comparação com os resultados do EnergyPlus. Palavras-chave: Climatização. Carga Térmica. EnergPlus. OpenStudio INTRODUCTION Petrolina is located in the Brazilian Northeast, in Pernambuco state, and is known nationally for its high temperatures and scarce rains all year round. According to Teixeira (2010), from 1965 to 2009 the average monthly temperature in Petrolina varied between 21.4ºC and 28ºC, being June and July the coolest months and October and November the hottest. The relative humidity in Petrolina oscillates between 66% and 73% in April, the wettest month and the end of the rain season, and remains under 55% in September and October. 1 Bacharel em Engenharia Mecânica. Universidade Federal do Vale do São Francisco 2 Professor de Engenharia Mecânica da Universidade Federal do Vale do São Francisco

302 Due to Petrolina s climate conditions, the climatisation of the classrooms in the Federal University of San Francisco Valley (UNIVASF) is a factor of major impact in the welfare of students, professors and servants, and has been provided since the University was founded. Currently this climatisation is guaranteed by split sytems used in all classrooms. Given the importance of the thermal comfort at UNIVASF, this paper aims to calculate the cooling thermal load of the classrooms, using the software EnergyPlus. It is really important for a climatisation project that the cooling load be estimated with a high level of precision, in order to avoid equipment under or oversizing. In this sense, the use of EnergyPlus can provide better results, due to its capability of perform complex calculations that would be nearly impossible to do without a computational tool. Although all the advantages of EnergyPlus, in the practice of engineering still remains the use of traditional calculation methods, described in the literature and based in pre-determined tables and coefficients, which always depend on the location considered in the climatisation project. Such methods have long been used by HVAC engineers, are trustworthy among professionals and have been performing reliable results. The objective of this paper is to perform the cooling load calculation with EnergyPlus for 32 classrooms and then pick a single classroom and analyze three methodologies for cooling load calculation available in the literature and compare them with the method of EnergyPlus. MATERIAL AND METHOD Computational tool The software used to calculate the cooling load was EnergyPlus, developed by the National Renewable Energy Laboratory (NREL) of USA Department of Energy (DOE). Crawley et al (2000) state that EnergyPlus combines the best characteristics and resources of its predecessors, BLAST and DOE- 2, and even presents new resources. EnergyPlus is a simulation software, and does not have a graphic user interface. Therefore, graphic user interface used was OpenStudio, which is also developed by NREL and contains a plug-in for Sketchp, turning the modelling process easier. Modelling and Simulation Each classroom corresponds to a thermal zone, in a total of 32. In OpenStudio were inserted all the data needed for the simulation: climate conditions of Petrolina (available in the EnergyPlus s website and based in the data collected by the weather station of Petrolina s Airport), the construction materials used in the building, the schedules, the occupation rate (the amount of people in each thermal zone), the heat released by these people and the power of the lamps and the electric equipment of the rooms. The infiltration rate was calculated by EnergyPlus, and was admitted a renewal rate of outdoor air according to the Brazilian National Agency of Health Surveillance s (ANVISA) resolution (RE nº9 of 16th January of 2003). Cooling load calculation methods

303 Three methods for calculating the cooling load were choose in the literature to be compared with EnergyPlus : Springer Carrier s Air Conditioner Guide (1999), Helio Creder s method (2009) and Ennio Cruz da Costa s method (1991). All these methods are largely used in Brazil, and all of them estimate the cooling thermal load counting the heat gains due to conductivity (sensible heat), solar incidence (sensible heat), people (sensible and latent heat), lightning (sensible heat), electric equipment (sensible and latent heat), infiltration (sensible and latent heat) and ventilation (sensible and latent heat) RESULT AND DISCUSSION Cooling load results from EnergyPlus For each thermal zone, EnergyPlus found the peak cooling load, which occurs in 21th February. The following figures show the peak cooling load of each thermal zone, as well as the time of the day in which it occurs. The building s total cooling load was 86,41 TR. In Figure 1 (which represents the classrooms in the first story), the blue arrow indicates the thermal zone 2, the one chosen to compare the literature methods and EnergyPlus s method. Figure 2 represents the classrooms in the second story of the building. Figure 1: Peak cooling load results for the first story classrooms Figure 2: Peak cooling load results for the second story classrooms

304 From the figures above, it is possible to notice that the classrooms in the second story presented a higher peak cooling load than the classrooms in the first story. It happened because the classrooms in the second story have contact with the roof, what increases the conduction and solar gains. The bigger thermal zones (indicated by the yellow arrows), that are classrooms dedicated to research groups and the E-learning Department (SEaD), presented a higher peak cooling load when compared to the others due to the larger wall surfaces (which increase the conduction gains), the larger window surfaces (which increase the solar gains) and the higher number of occupants and lightning (which increases the internal gains). The following table shows the total room area, the wall and window area, the number of occupants and the lightning of the ordinary classrooms, the research groups classrooms and SEaD. Table 1: Thermal zones characteristics Space Ordinary Research groups' SEaD classrooms classrooms Area [m²] 67,12 116,8 116,8 Volume [m³] 235,29 409,37 409,37 Gross wall area [m²] 26,29 111,64 111,64 Glass window area 9,62 26,26 26,26 [m²] Lightning [W] 7200,03 12528,18 12528,18 Number of occupants 51 88 20

305 In the ordinary classrooms, which have the same area, number of occupants and lightning, the differences occurred in the thermal zones indicated by the red arrows in Figures 1 and 2. In these cases, the differences in the peak cooling load were verified because the indicated classrooms have a northwestoriented wall (that the other classroom do not have), which increases the solar gains during the afternoon Comparison between EnergyPlus and three literature methods To compare EnergyPlus s results with other three methods from the literature, the thermal zone 2 was choose. The three methods considered were Creder s (2009), Costa s (1991) and Carrier s (1999). In the comparison, have been analyzed the heat gains due to conduction, solar incidence, peope, lightning, electric equipment and infiltration. It is important to notice that EnergyPlus s algorithms calculate the total cooling load, and gives an estimation of each sensible heat gain component (not included the latent heat gains). Table 2 shows the comparison among all methods for the conduction heat gains. Creder (2009), Carrier (1999) and Costa (1991) present the same equation for conductive heat gains, varying only the heat transmission coefficient of the materials, which are defined by each method. It is important to notice that Carrier (1999) is the only method that has not presented the thermal conductivity of glass. On the other hand, EnergyPlus uses the conduction transfer functions (CTF), which are a much more sophisticated method for calculating the conductive heat gains. Table 2: Comparison of the heat gains due to conduction Method Heat gain due to conduction (kcal/h) Carrier 1641,26 Creder 1733,18 Costa 2208,76 EnergyPlus 1249,67 Table 03 compares the heat gains due to solar incidence. Carrier (1999) did not present any methodology to calculate the heat gains due to solar incidence. Table 3: Comparison of the heat gains due to solar incidence Method Heat gain due to solar incidence (kcal/h) Carrier 0,00 Creder 4025,99

306 Costa 2796,52 EnergyPlus 539,76 Table 4 compares the heat gains due to people occupancy. As said before, EnergyPlus does not present the latent heat in the peak cooling load components. Creder (2009), Carrier (1999) and Costa (1991) present the values of the heat emitted by people, depending on the activity level. The fraction of sensible and latent heat is determined by the room temperature, and each method presents those values. In EnergyPlus, the user defines the amount of heat emitted by a single person and the software automatically calculates the sensible and the latent fraction. Table 4: Comparison of the heat gains due to people Method Heat gain due to people (kcal/h) Sensible Latent Carrier 3060,00 2040,00 Creder 3372,10 1794,00 Costa 3060,00 2040,00 EnergyPlus 2730,40 0,00 The results for the heat gains due to lighting are compared in Table 5. Table 5: Comparison of the heat gains due to lightning Method Heat gain due to lightning (kcal/h) Carrier 774,00 Creder 619,20 Costa 619,20 EnergyPlus 619,24 The heat gains due to electric equipment are shown in Table 6. The results from all methods were the same. That is because in all methods the heat emitted by the electric equipment is calculated by multiplying the total power by a factor of 0.86.

Table 6: Comparison of the heat gains due to electric equipment Method Heat gain due to electric equipment (kcal/h) 307 Carrier 215,00 Creder 215,00 Costa 215,00 EnergyPlus 215,00 Table 7 presents the heat gains due to infiltration. Carrier (1999) did not present any methodology to calculate the heat gains due to infiltration, and also did not provide the data needed to calculate the gains due to ventilation in this specific case (classrooms). In this table, EnergyPlus counts for both infiltration and ventilation heat gains, while all other methods count for infiltration heat gains only. Though Creder (2009) presented a methodology to calculate the heat gains due to ventilation, it has resulted in 44,52 TR due to ventilation only, while the summation of all other heat gains in this method has resulted in 4,42 TR. Because its result was absurdly high, the gain due to ventilation was neglected. Least, Costa (1991) did not present the data needed to calculate the heat gain due to ventilation. Table 7: Comparison of the heat gains due to infiltration Method Heat gain due to infiltration (kcal/h) Sensible Latent Carrier 0,00 0,00 Creder 653,89 946,47 Costa 653,89 946,48 EnergyPlus 5917,81 0,00 The final cooling load obtained by each method is reported in Table 8. The final cooling load for EnergyPlus is the peak cooling load presente by the software as the final result, not the summation of the sensible heat gain components. Table 8: Comparison of the cooling load results Method Cooling load (TR) Carrier 2,56 Creder 4,42 Costa 4,15

308 EnergyPlus 1,91 CONCLUSION When compared to the methods described in the literature, the results from EnergyPlus were the lowest among all. That is probably due to the fact that EnergyPlus calculates the cooling load for each hour of the year, taking into consideration transient heat exchanges and contributes from previous time steps, which is not done by the other methods. The other methods, for instance, use pre-determined coefficients and values, which are actually approximations of complex calculations. That can lead to uncertainties that affect the final results. In this sense, EnergyPlus can provide more accurate results, helping to avoid over dimensioning. A frailty of EnergyPlus is that the heat gain components are only estimated. Moreover, the latent heat gains are not present in these components. That can make harder to the designer to analyze the heat gains in particular, which could be helpful to evaluate the impact of each heat source in the final cooling load. REFERENCES COSTA, E.C.da. Física aplicada à construção: conforto térmico. 4.ed. São Paulo: Edgar Blücher, 1991. CRAWLEY, D.B.et al. EnergyPlus: Energy simulation program. ASHRAE Journal, abril de 2000. CREDER, H. Instalações de ar condicionado. 6.ed. LTC: Rio de Janeiro, 2009. MANUAL DO AR CONDICIONADO. Carrier Air Conditioning Co. Marcombo SA, 1999. TEIXEIRA, A. H. de C. Informações agrometeorológicas do polo Petrolina, PE/Juazeiro, BA 1963 a 2009. Petrolina: Embrapa Semiárido, 2010.