CROSS CONNECTION CONTROL PROGRAM

Similar documents
QUONSET DEVELOPMENT CORPORATION QUONSET & LADD WATER SYSTEMS CROSS CONNECTION CONTROL & BACKFLOW PREVENTION POLICY

Elmira Water Board Cross Connection Control Program

PORTLAND WATER DISTRICT CROSS-CONNECTION CONTROL PROGRAM 1989 REVISED MAY, 2006 REVISED SEPTEMBER, 2009 REVISED JUNE, 2017

CROSS CONNECTION CONTROL PROGRAM

CITY OF GLENVILLE 20 North Court Street Glenville WV

JACKSON COUNTY WATER AND SEWERAGE AUTHORITY. Cross-Connection Control Program

ARTICLE IV CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

CROSS - CONNECTION CONTROL PROGRAM BELFAST WATER DISTRICT

ROCHESTER PUBLIC UTILITIES PUBLIC WATER SYSTEM CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM FOR ROCHESTER, MINNESOTA

ORDINANCE NO. 80. WHEREAS: The Program provides for regular inspections of Cross-Connections and Backflow Preventer devices; and

Chapter 82 UTILITIES [1]

Premises having a repeated history of cross-connections being established or reestablished.

Ordinances of the Plainview Water District Town of Oyster Bay, Nassau County, New York ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS

PROVIDENCE WATER SUPPLY BOARD CROSS-CONNECTION CONTROL PROGRAM RULES AND REGULATIONS

Cross Connection Control Rules

WEST JACKSON COUNTY UTILITY DISTRICT

CROSS-CONNECTION CONTROL PROGRAM OLD TOWN WATER DISTRICT OLD TOWN, MAINE

CROSS CONNECTION CONTROL PROGRAM PLAN CCCPP 8/13/2012 THE TOWN OF WRENTHAM WATER DIVISION

Newport Water District CROSS CONNECTION CONTROL PROGRAM

Missouri American Water Cross Connection Control Program

Cross-Connection Control and Backflow Prevention Program

ARTICLE VI. The Town of Trappe Cross Connection and Backflow Prevention Program is contained in

DIVISION 3. CROSS CONNECTION CONTROL* Sec Definitions.

ATTORNEYS AT LAW. 600 Quarrier Street Charleston, West Virginia Post Office Box 1386 Charleston, West Virginia (304)

HOLLEY NAVARRE WATER SYSTEM, INC. BACKFLOW PREVENTION & CROSS CONNECTION CONTROL POLICIES & REGULATIONS

Effective Date: November 2, 2010 Reaffirmed Date: June 19, 2012 Reaffirmed Date: July 21, 2015

City of Weiser Cross Connection ordinance 1217

DIVISION 2: BACKFLOW PREVENTION PROGRAM

Backflow Prevention:The Forefront of Responsible Irrigation

Milk Pre-Cooler Plumbing Considerations. ATCP 65, Wisconsin Administrative Code and the 2015 PMO

Cross-Connection Control Program

The following words and terms, when used in this article, shall have the following definitions, unless the context clearly indicates otherwise:

CHAPTER 6 SECTION 6.19 AN ORDINANCE OF THE TOWN OF MAYODAN TO PROTECT THE QUALITY OF THE PUBLIC POTABLE WATER SUPPLY

December Illinois American Water Cross Connection Control Program

CITY OF HAMILTON Codified Ordinance CHAPTER 941

CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM THE ISLAND WATER ASSOCIATION, INC. SANIBEL, FLORIDA

THE CONSOLIDATED MUTUAL WATER COMPANY CROSS CONNECTION CONTROL PROGRAM GENERALLY

MODEL ORDINANCE FOR CROSS CONNECTION CONTROL BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF, STATE OF WYOMING:

AN ORDINANCE TO REQUIRE CROSS CONNECTION CONTROL AND BACK FLOW PREVENTION IN THE WATER SYSTEM OF THE TOWN OF LUMBERPORT

ORDINANCE NO. 519 AN ORDINANCE ADOPTING THE RULES AND REGULATIONS RELATING TO WATER SUPPLY CROSS-CONNECTIONS AND REPEALING ORDINANCE NO. 459.

Backflow Prevention by Containment & Cross-Connection Control Program Easton Suburban Water Authority

Town of Chocowinity Backflow and Cross Connection Ordinance

Cross-Connection Control and Backflow Prevention for Public Water Systems

CROSS CONNECTION AND BACKFLOW PREVENTION BY-LAW BY-LAW #

THE CONSOLIDATED MUTUAL WATER COMPANY CROSS CONNECTION CONTROL PROGRAM GENERALLY

Premises Isolation Cross-Connection Control Program

(Contaminant) Backsiphonage or Backpressure Backsiphonage or Backpressure

The purpose of the cross connection and backflow prevention program is:

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM

Milk Pre-Cooler Plumbing Considerations. ATCP 65, Wisconsin Administrative Code and the 2015 PMO

DIVISION 5. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL

ORDINANCE NO AN ORDINANCE OF THE COASTSIDE COUNTY WATER DISTRICT

EL DORADO IRRIGATION DISTRICT

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

Town of Princeton. Cross Connection Control Program Policy

Cross-Connection Control Program and Plan of Operation

Florida Administrative Codes and

Water Supply System. Plumbing and Cross Connection Control. Cross-Connection. Connection. Plumbing Overview 9/24/

The rules and regulations, as part of this document, shall apply to all premises serviced by the public water system of the Northeast Water System.

Backflow Device Inspections & Cross Connections Policy

CROSS-CONNECTION CONTROL PROGRAM HARVEST-MONROVIA WATER, SEWER AND FIRE PROTECTION AUTHORITY

Sec Backflow prevention and cross-connection control.

Shannon Water and Sanitation District Backflow Prevention and Cross-Connection Control Program

ORDINANCE NO. 124 SECTION 1 - GENERAL POLICY. 1.0 PURPOSE- The purpose of this ordinance is:

Chapter 13 WATER UTILITY

Henry County Water Authority. Cross Connection Control Program

CROSS-CONNECTION CONTROL PROGRAM

TITLE 17. (b) Auxiliary Water Supply is any water supply other than that received from a public water system.

Cross Connection Control And Backflow Prevention Program. City of Rifle, Colorado Utility Department

Dillon Valley District

1.2. RESPONSIBILITY OF THE DRINKING WATER PURVEYOR (LDWA).

BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS

KING COUNTY WATER DISTRICT NO. 125 KING COUNTY, WASHINGTON. RESOLUTION NO. ~ S D * \k: - dj (j

SECTION 3 CROSS CONNECTION CONTROL

CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION

CITY UTILITIES DESIGN STANDARDS MANUAL

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM

Riviera Beach DIVISION 2. CROSS CONNECTION CONTROL

CROSS CONNECTION CONTROL PROGRAM of UTAH

Backflow explained About backflow prevention containment. Backflow explained. About backflow prevention containment. Page 1

Cross Connection Control

HIGHLANDS WATER COMPANY Lakeshore Drive Clearlake, California {707}

Advanced Backflow Prevention Internet Course 1 Hour

Sec Cross connection control, backflow prevention assemblies required, program established.

310 CMR Cross Connection Distribution System Protection - Effective Date: 01/05/2001 Page 1 of 15

ARTICLE 11 - Backflow Prevention and Cross Connection Control

ORDINANCE NO. 17. Series 2016 AN ORDINANCE AMENDING TITLE 12 OF THE BRECKENRIDGE TOWN CODE CONCERNING THE TOWN S MUNICIPAL WATER SYSTEM

100 Lyn Avenue / PO Box 4610 Pagosa Springs CO (970)

POLICY GOVERNING CROSS CONNECTIONS, AUXILARY INTAKES, BYPASSES, AND INTERCONNECTIONS

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

REGULATIONS. of the WATER COMMISSIONERS. of the TOWN OF BELLINGHAM

SECTION XIV: BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL Backflow Prevention & Cross-Connection Control Program Purpose

A BRIEF LOOK AT BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL LES O BRIEN

THE CORPORATION OF THE TOWN OF NEW TECUMSETH BY-LAW. Number

ARTICLE X. CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION ORDINANCE*

TOWN OF PAONIA RESOLUTION

DUPLIN COUNTY BACKFLOW PREVENTION ORDINANCE This ordinance shall be known as the Duplin County Backflow Prevention Ordinance.

Water Service 39 BACKFLOW PROTECTION

1 of 10

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

Transcription:

Brian Tarbuck, General Manager btarbuck@greateraugustautilitydistrict.org Ken Knight, Board Chair kknight@greateraugustautilitydistrict.org Cecil Munson cmunson@greateraugustautilitydistrict.org Pat Paradis pparadis@greateraugustautilitydistrict.org Dave Bustin, Hallowell voting member, Clerk Bradley Sawyer dbustin@greateraugustautilitydistrict.org bsawyer@greateraugustautilitydistrict.org www.greateraugustautilitydistrict.org Bob Corey, Treasurer 12 Williams Street Keith Luke, Augusta ex-officio member bcorey@greateraugustautilitydistrict.org Augusta, ME 04330-5225 kluke@greateraugustautilitydistrict.org (207) 622-3701 Kirsten Hebert Charlotte Warren, Hallowell ex-officio member khebert@greateraugustautilitydistrict.org cwarren@greateraugustautilitydistrict.org CROSS CONNECTION CONTROL PROGRAM EFFECTIE DATE February 1, 2018 As approved by Division of Environmental Health Maine Center for Disease Control & Prevention A Division of the Maine Department of Health and Human Services

TABLE OF CONTENTS I II III I Purpose Authority Definitions Degree of Hazard and Approved Devices Administration A- Program Administration B- Inspection Administration C- Permits Administration D- Testing Administration E- Installation Administration F- Thermal Expansion Administration G- Exemptions Administration H- Compliance

CROSS-CONNECTION CONTROL PROGRAM I. PURPOSE Cross-connections between a potable water system and non-potable sources of contamination represent a threat to public health. This program is designed to maintain the safety and potability of the water in the supply system by preventing the introduction, by backflow, of any foreign liquids, gases or other substances into the supply system. II. AUTHORITY This program derives its enforceability from Title 22 M.R.S.A. Chapter 601, Subchapter I, 2605 and Subchapter II, 2611-2613, 2615 and Subchapter III 2628. Maine Department of Health and Human Services Cross-Connection Rules 10-144 Chapter 231 appropriation # 013-10A-2420-032. In addition authority arises from the Rules and Regulations as published by the Greater Augusta Utility District, rule number 11, and as approved by the Public Utilities Commission of the State of Maine and from provisions of the Occupational Safety and Health Act, and the Maine State 2000 Uniform Plumbing Code Chapter 6. III. DEFINITIONS A. BACKFLOW The flow of water or other foreign liquids, gases or other substances into the distribution system of a public water supply from any source other than the intended. B. BACKFLOW PREENTER A device to prevent backflow. 1. Air Gap An approved air gap is defined as the vertical distance through free atmosphere between the discharge outlets of a potable water system to the flood level rim of a non-potable system. These vertical physical separations must be at least 2 times the pipe diameter of the water supply outlet, but never less than 1 inch. 2. Atmospheric acuum Breaker A device which prevents back-siphonage by creating an atmospheric vent where there is either a negative pressure or sub-atmospheric pressure in a water system. 3. Backflow Preventer with Intermediate Atmospheric ent A device having two check valves separated by an atmospheric vent.

4. Double Check alve A device having two, spring loaded, bronze faced with soft rubber disc check valves, with shut-off valves and test cocks for periodic testing. 5. Hose Bibb acuum Breaker A device which is permanently attached to a hose Bibb and which acts as an atmospheric vacuum breaker. 6. Pressure acuum Breaker A device containing a spring-loaded check valve and a spring loaded atmospheric vent which opens which pressure approaches atmospheric. It contains valves and fittings which allow the device to be tested. 7. Reduced Pressure Zone An assembly of two check valves and a reduced pressure zone between, which spills water to the atmosphere in event of the failure of the check valves. It has valves and fittings which allow the device to be tested. C. BACK SIPHONAGE Backflow resulting from negative or less than atmospheric pressure in the water system. D. BACK-PRESSURE A condition in which the owner s system pressure is greater than the supplier s system pressure. E. CONTAINMENT The State Of Maine Drinking Water Program requires a backflow preventer, approved for the degree of hazard at the water service entrance. This assures that water passing through the device is contained in the building and not allowed to flow back into the potable water supply.

F. CROSS-CONNECTION Any connection or potential connection between a public potable water system and any non-potable source of liquid, gas, or solids through which backflow can occur. G. DEPARTMENT Division of Environmental Health Maine Center for Disease Control & Prevention A Division of the Maine Department of Health and Human Services H. DISTRICT Greater Augusta Utility District I. FIXTURE ISOLATION The installation of a backflow preventer located to correct a cross-connection at an internal fixture, to protect the potable water contained in the building. J. OWNER Any person who has legal title to, or license to operate or habitat in, a property upon which a crossconnection inspection is to be made or upon which a cross-connection is present. K. PERMIT A document issued by the Department with the approval of the District which documents the use of a backflow preventer.

L. WATER SERICE ENTRANCE That point in the owner s water system beyond the sanitary control of the supplier. This will usually be the outlet end of the meter and will always be before any unprotected branch. I. DEGREE OF HAZARD AND APPROED DEICES The District recognizes that varying degrees of hazard are caused by different cross-connections. The devices which are permitted for use in each class of hazard and a description of the classes are as follows. A list of manufactured approved devices is available at the District. American Water Works Association, Manual M-14 Chapter 4, guide to the assessment of hazard will be utilized for classifications purposes. A. CLASS I LOW DEGREE OF HAZARD If backflow were to occur, the resulting health significance would be limited to minor changes in the esthetic quality such as taste, odor or color. The foreign substance must be non-toxic and nonbacterial in nature with no significant health effects. The allowed devices are: Air gap, non-pressure type vacuum breaker, pressure type vacuum breaker, double check valve assembly and reduced pressure zone device. B. CLASS II MODERATE DEGREE OF HAZARD If backflow were to occur, the resulting effect on the water supply would be significant changes in the esthetic qualities. The foreign substances must be non-toxic to humans either in short or long term exposure. The allowed devices are: Air gap, pressure type vacuum breaker, double check valve assembly and reduced pressure zone devices. C. CLASS III HIGH DEGREE OF HAZARD If backflow were to occur the resulting effect on the water supply could cause illness or death if consumed by humans. The allowed devices are: Air gap and reduced pressure zone devices.

. ADMINISTRATION A. PROGRAM 1. Developed and maintained by the District. 2. Approved by Division of Environmental Health Maine Center for Disease Control & Prevention A Division of the Maine Department of Health and Human Services 3. Original Test Reports shall be kept on file by the District for five years. B. INSPECTION 1. Made during normal working hours unless otherwise arranged with the owner. 2. The owner shall allow his property to be inspected for possible cross-connections and for the testing of backflow prevention devices. 3. When applying for a new service the owner shall state the nature of the establishment to be served and inform the District if there are any possible cross-connections existing or proposed. Prior to activation of all new water services, compliance with this program and with the Maine State 2000 Uniform Plumbing Code shall be mandatory. 4. Whenever existing systems are modified, the District shall be informed by the owner. The District shall be informed of any malfunctioning backflow devices. 5. After inspection of plans or premises the District shall inform the owner by written notice of any cross-connections or malfunctioning devices, suggest ways of correcting the problem and set a time limit based on the degree of hazard for the correction to be made. Level 1 = 30 days, Level 2 = 15 days, Level 3 Immediately

6. If the District determines at any time that an immediate threat to the public health exists, service shall be terminated immediately. 7. Frequency The frequency of inspecting for backflow devices coincides with the Districts, meter clean and test program as approved by the Maine Public Utilities Commission. Cold water displacement meters 5/8 thru 2 = 12 Years or upon register rollover Cold water displacement meters 3 = 3 years or upon register rollover Cold water displacement meters 4 = 2 Years or upon register rollover Cold water displacement meters 6 and greater = 1 Year or upon register rollover Cold water Turbine meters 1 ½ & 2 = 4 Years or upon register rollover Cold water Turbine meters 3 = 3 Years or upon register rollover Cold water Turbine meters 4 = 2 Years or upon register rollover 8. The Department reserves the right to inspect all cross-connections. The owner and/or District shall comply with any required changes as a result of the inspections. C. PERMITS 1. No cross-connections shall be allowed unless issued a permit by the Department specifically for that cross-connection and on recommendation by the District. 2. The owner shall apply for a permit through the District on forms supplied by the Department. 3. Permits will only be issued for a protected cross-connection that is deemed necessary and cannot be eliminated. 4. The permit shall state: a. Degree of hazard b. Frequency of testing c. Type, model make and serial number of the backflow device. 5. Permits are non-transferable.

6. Any change in the degree of hazard or replacement of the device will require a new permit, but will keep the same State Identification Number. 7. Permits will be renewed every five years. Requests for renewal permits shall be reviewed by the District and if no changes have occurred, the permit shall be automatically renewed. If changes have occurred the renewal application shall be reviewed and a survey completed for a possible change to the degree of hazard. The State Identification Number shall remain the same. 8. The owner shall follow the provisions of the District s program and the Department s rules regarding cross-connections if a permit is issued. 9. Any private well or other source of supply shall not be cross-connected to the District s distribution system unless protected by an RPZ and approved by the Department and the District. D. TESTING 1. The testing, inspection and maintenance of approved devices shall be the responsibility of the owner. 2. Frequency of testing is stated on the permit, based on the degree of hazard. The State Uniform Plumbing Code section 608.3.3 requires annual testing as a minimum. 3. If a device fails a test the District must be notified immediately. 4. Malfunctioning devices must be repaired immediately. If removal is necessary, service must be shut down. It is mandatory that a spare parts kit be on the premises. 5. The device is to be retested after maintenance or repairs.

E. INSTALLATIONS 1. The owner, after being informed by written notice from the District shall, at his expense, install a backflow device listed and approved by the Department and the District, on his service entrance directly downstream of the water meter and before any branch lines. 2. The manner of installation shall be according to manufacturer s specifications and approved by the District. 3. Pit installations are strongly discouraged and must have Departmental approval before a permit is issued. 4. The Department requires that all services be protected by containment at the water meter. The owner shall install the backflow device as close as possible to the outlet of the meter and shall be responsible for the water quality beyond the outlet end of the device. 5. Whenever a backflow device is remote to the service entrance, all branches prior to the backflow device must be protected by an additional backflow prevention devices. 6. Installation of devices should allow for peak demand and fire flows. 7. If the device will be subject to hot water, a backflow prevention device that can withstand the maximum temperatures expected must be installed. Please note that some manufactured devices will accept greater temperatures than others. 8. In situations where the water supply cannot be interrupted to allow for testing or repair of the backflow preventer, the owner must supply an additional device in parallel, appropriate to the degree of hazard. A bypass is not allowed around any backflow preventer unless a backflow preventer is installed on the bypass piping. F Thermal Expansion State Uniform Plumbing Code section 608.3 require that Thermal Expansion Control be addressed in plumbing systems to avoid damage to fixtures and appliances. The installation of a backflow device creates a CLOSED system that prevents heated/expanded water from being forced back into the public distribution system. Thermal expansion, if not controlled can damage or reduce the life of plumbing fixtures and appliances. Thermal expansion may be

THERM-X-TROL evident by dripping or spurting from water faucets or intermittent discharge from the pressure relief valve on the hot water heater. Thermal Expansion can be easily controlled by use of a properly sized Thermal Expansion Tank on the cold water supply line, or a Watts Governor 80 M1 Toilet tank ball cock fill valve or equal. Customers are encouraged to have a licensed plumber inspect their plumbing system to determine if it is a CLOSED system. COLD WATER SUPPLY LINE. THERMAL EXPANSION TANK BACKFLOW PREENTER HOT WATER HEATER WATER METER BALL ALE ALL PIPING & ALES OWNED AND MAINTAINED BY THE OWNER G- EXEMPTIONS 1. Any existing backflow preventer in service at the time this program goes into effect shall be allowed to continue in service unless: a. The District or Department considers the condition of any portion of the device to be such that replacement shall be a backflow preventer of the appropriate classification and a permit shall be issued. b. The device protecting the cross-connection is inadequate for the degree of hazard.

H- COMPLIANCE 1. Failure to comply with these regulations either by neglect to complete the application, procure and install the proper device, or repair a malfunctioning device may lead to termination of service. 2. First notice shall be the letter of inspection. 3. Second notice shall inform the owner in writing of any failure to comply with the first notice and be given an additional 15 days to comply. 4. Final notice shall be a written notice of service termination to take place within 10 days. 5. Re-establishment of service before the installation of a backflow preventer may be allowed by the District after an agreement with the District, Department and owner has been made indicating the intention of the owner to comply and a schedule is set up based on the degree of hazard.